ETD-BL-1T-230-PT [PHOENIX]
Multifunctional time relay with various functions and adjustable times;型号: | ETD-BL-1T-230-PT |
厂家: | PHOENIX CONTACT |
描述: | Multifunctional time relay with various functions and adjustable times |
文件: | 总7页 (文件大小:143K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
ETD-BL-1T-230(-PT)
Multifunctional time relay with various functions and
adjustable times
Data sheet
106395_en_03
© PHOENIX CONTACT 2016-05-03
1
Description
Requirements pertaining to safety and system availability
increase constantly – regardless of the industry. Processes
are becoming more and more complex, not only in the
mechanical engineering and chemical industry but also in
plant and automation technology. Demands on power
engineering are also constantly on the rise.
Features
–
–
–
–
–
–
Adjustable time
Time range from 50 ms to 1 h
Non-floating control input
Delay functions
Wiper functions
1 floating PDT
Timer relays of the ETD series are available for controlling
the time sequences in production and process engineering.
WARNING: Risk of electric shock
Never carry out work when voltage is present.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This document is valid for the products listed in the “Ordering data”.
ETD-BL-1T-230(-PT)
2
Table of contents
1
Description .............................................................................................................................. 1
Table of contents..................................................................................................................... 2
Ordering data .......................................................................................................................... 3
Technical data ......................................................................................................................... 3
Safety notes............................................................................................................................. 4
Basic circuit diagram ............................................................................................................... 5
Structure.................................................................................................................................. 5
Installation ............................................................................................................................... 5
Time setting............................................................................................................................. 5
Diagnostics.............................................................................................................................. 5
Connection examples.............................................................................................................. 6
Function................................................................................................................................... 7
2
3
4
5
6
7
8
9
10
11
12
106395_en_03
PHOENIX CONTACT 2 / 7
ETD-BL-1T-230(-PT)
3
Ordering data
Description
Type
Order No.
Pcs./Pkt.
Compact multi-functional timer relay with 4 functions and an adjustable
ETD-BL-1T-230
2905813
1
time range (50 ms - 1 h), with screw connection, 1 PDT
Compact multi-functional timer relay with 4 functions and an adjustable
time range (50 ms - 1 h), with push-in connection, 1 PDT
ETD-BL-1T-230-PT
2905814
1
4
Technical data
Input data
Input voltage range
Nominal frequency
Temperature coefficient, typical
Recovery time
24 V AC/DC ... 240 V AC/DC -15 % ... +10 %
48 Hz ... 63 Hz
≤ 0.01 %/K
100 ms
Time setting range
Function
50 ms ... 1 h (5 time end ranges)
E: With switch-on delay
R: With release delay and control contact
Es: With switch-on delay and control contact
Ws: With single shot leading edge and control contact
Basic accuracy
Setting accuracy
Repeat accuracy
± 1 % (of scale end value)
≤ 5 % (of scale end value)
≤ 0.5 % ±5 ms
Output data
Contact type
1 floating PDT
Maximum switching voltage
Interrupting rating (ohmic load) max.
Output fuse
250 V AC (in acc. with IEC 60664-1)
1250 VA (5 A/250 V AC)
5 A (fast-blow)
Control contact
Control contact
Non-floating, terminals A1-B1
Control pulse length
≥ 50 ms (DC)
General data
Mechanical service life
Service life, electrical
Operating mode
Degree of protection
Degree of pollution
Overvoltage category
Flammability rating according to UL 94
Mounting
6
15 x 10 cycles
5
1 x 10 cycles
100% operating factor
IP40 (housing) / IP20 (connection terminal blocks)
2 (according to EN 50178)
III, basic insulation (as per EN 50178)
V0
on standard DIN rail NS 35 in accordance with EN 60715
Mounting position
Width
any
17.5 mm
88 mm
65.5 mm
gray
Height
Depth
Color
106395_en_03
PHOENIX CONTACT 3 / 7
ETD-BL-1T-230(-PT)
Connection data
Conductor cross section, solid
Conductor cross section, flexible
AWG
Screw connection
0.14 mm² ... 2.5 mm²
0.14 mm² ... 2.5 mm²
20 ... 14
Push-in connection
0.5 mm² ... 2.5 mm²
0.5 mm² ... 2.5 mm²
26 ... 14
Stripping length
8 mm
8 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
-25 °C ... 55 °C
-25 °C ... 70 °C
15 % ... 85 %
Conformance / approvals
Conformance
CE-compliant
UL, USA / Canada
UL, USA / Canada
UL 508 Listed
Conformance with EMC Directive 2014/30/EU
Noise immunity according to
EN 61000-6-2
EN 61000-6-3
Noise emission according to
Conformance with Low Voltage Directive 2006/95/EC (valid until 2016-04-19) / 2014/35/EU (valid from 2016-04-20)
5
Safety notes
WARNING: Risk of electric shock
Never carry out work when voltage is present.
106395_en_03
PHOENIX CONTACT 4 / 7
ETD-BL-1T-230(-PT)
6
Basic circuit diagram
8
Installation
B1
16 18
WARNING: Risk of electric shock
Never carry out work when voltage is present.
A1
The module can be snapped onto all 35 mm DIN rails
according to EN 60715.
t
A2
9
Time setting
15
U = 24...240 V AC/DC
2
0.5
2
U/t
4
6
Figure 1
Block diagram
8
1
1
10
1
m
s
1
10
7
Structure
1h
Es
E
2
-
R
R
-1T
Ws
ETD-BL
1
2
Specification of the time end range using a rotary
switch, e.g. 10 m (10 minutes)
Fine setting of the time using a potentiometer, e.g. 0.4
15
6
A1
B1
Set time: 0.4 x 10 minutes = 4 minutes
5
U 0.
/t
5
10 Diagnostics
The LEDs indicate the following error states:
2
8
4
6
1
s
1
1
0
4
3
1
m
10
1h
"U/t" LED (Green)
- 2 3 0 - P T
R
E
- 1 T
–
–
LED flashes: Voltage present, set time running
LED ON: Voltage present, set time has elapsed
E
s
R
E T D - B L
W
s
2
“R” LED (yellow)
1
–
–
LED ON: Output relay has picked up
LED OFF: Output relay has dropped out
1
2
3
4
5
6
"FUNCTION" rotary switch: Function selection
LED "R": output relay
Rotary switch "TIME": Time end range
"TIME" potentiometer: Preset value
"U/t" LED: Supply and adjustable time TIME
Snap-on foot for DIN rail mounting
106395_en_03
PHOENIX CONTACT 5 / 7
ETD-BL-1T-230(-PT)
11 Connection examples
NOTE:
When the control input is connected to a
parallel load, ensure that the minimum load
connected in parallel is > 1 VA.
S
15
B1
A1
15
16 18
15
B1
A1
A2
16 18
15
Figure 4
Connection with control contact and parallel
load (e.g. relay)
16 18
A2
16 18
Figure 2
Connection without control contact
S
15
B1
A1
15
16 18
A2
16 18
Figure 3
Connection with control contact
106395_en_03
PHOENIX CONTACT 6 / 7
ETD-BL-1T-230(-PT)
R: With Release Delay and Control Contact
12 Function
Supply voltage U must be applied permanently at the device
(green "U/t" LED is ON). When control contact A1-B1 is
closed, the output relay picks up (yellow "REL" LED is ON).
If control contact A1-B1 is opened, set time t starts running
(green "U/t" LED flashes). Once time t has elapsed
(green "U/t" LED is ON), the output relay drops out
(yellow "REL" LED is OFF). If the control contact is closed
again before time t has elapsed, the elapsed time is deleted
and restarted with the next cycle.
NOTE: Module can become damaged
Only set the functions when the module is
switched off.
E: With Switch-On Delay
When supply voltage U is applied, set time t starts running
(green "U/t" LED flashes). Once time t has elapsed
(green "U/t" LED is ON), the output relay picks up
(yellow "REL" LED is ON). This state is maintained until
supply voltage U is interrupted. If supply voltage U is
interrupted before time t has elapsed, the elapsed time is
deleted (relay does not pick up). The next time supply
voltage U is applied, the time is restarted.
U
LED U/t
A1 - B1
LED REL, R
t
< t
U
LED U/t
Ws: With single shot leading edge and control contact
LED REL, R
Supply voltage U must be applied permanently at the device
(green "U/t" LED is ON). When control contact A1-B1 is
closed, the output relay picks up (yellow "REL" LED is ON)
and set time t starts running (green "U/t" LED flashes). Once
time t has elapsed (green "U/t" LED is ON), the output relay
drops out (yellow "REL" LED is OFF).
t
< t
Es: With Switch-On Delay and Control Contact
The control contact can be freely switched during this time.
Another cycle cannot be started until the current cycle has
been completed.
Supply voltage U must be applied permanently at the device
(green "U/t" LED is ON). When control contact A1-B1 is
closed, set time t starts running (green "U/t" LED flashes).
Once time t has elapsed (green "U/t" LED is ON), the output
relay picks up (yellow "REL" LED is ON). This state is
maintained until the control contact is opened. If the control
contact is opened before time t has elapsed, the elapsed
time is deleted (relay does not pick up) and restarted with
the next cycle.
U
LED U/t
A1- B1
LED REL, R
t
t
U
LED U/t
A1 - B1
LED REL, R
t
< t
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
106395_en_03
7 / 7