375 and 500Watt AC-DC Converters  
Input range 85...264 V AC with PFC  
1 or 2 isolated, regulated outputs up to 96 V  
3 kV AC I/O electric strength test voltage  
LGA  
• Electrically and mechanically rugged DIN-rail  
front end  
• Outputs individually controlled with 150%  
output peak power  
• Operating ambient temperature range  
–40...60°C with convection cooling  
Selection chart for front ends  
Output 1  
Uo nom Io nom  
[V DC] [A]  
Output 2  
Uo nom Io nom  
[V DC ] [A]  
Input voltage  
Ui minUi max  
Rated power  
TA = 60°C  
Po tot [W]  
Type  
Options1  
24.7  
24.7  
15  
20  
-
-
-
-
375  
500  
LXR 1601-6  
LXN-1601-6  
R
D1D5  
37  
37  
9.9  
13.2  
-
-
-
-
85264 VAC  
(14440 Hz)3  
375  
500  
LXR 1701-6  
LXN 1701-6  
S
M2  
49.4  
49.4  
7.5  
10  
-
-
-
-
90350 VDC  
375  
500  
LXR-1801-6  
LXN-1801-6  
F, F1  
K2  
24.7  
49.4  
10  
5
24.7  
49.4  
10  
5
500  
500  
LXN-2660-6  
LXN 2880-6  
Selection chart for Battery chargers2  
Output  
Input voltage  
Rated power  
TA = 60°C  
Po tot [W]  
Type  
Options1  
Uo nom  
[V DC]  
Io nom  
[A]  
Ui minUi max  
25.7...29.3  
25.7...29.3  
12.6  
16.9  
85264 VAC  
(14440 Hz)3  
90350 VDC  
345  
460  
LXR 1240-6 M1  
LXN 1240-6 M1  
F, F1  
K2  
51.4...58.6  
51.4...58.6  
6.3  
8.4  
345  
460  
LXR 1740-6 M1  
LXN 1740-6 M1  
1 For lead times and minimum order quantities contact Power-One.  
2 For availability contact Power-One.  
3 Input frequency range certified for 14...440 Hz. For continuous operating frequency <40 Hz and >100 Hz contact  
factory.  
www.power-one.com  
Edition 5/7.2001  
1
X Series  
375 and 500Watt AC-DC Converters  
Input  
Input voltage  
world wide mains, single phase  
for derating information see application note  
wide frequency range  
85...264 V AC  
90...350 V DC  
16 2/3...440 Hz  
up to 0.99  
Input frequency  
Power factor  
active PFC  
Inrush current  
virtually no inrush current  
Output  
Efficiency  
Ui nom, Io nom  
up to 89%  
±1.3% Uo nom  
typ. 50 mV  
1.2 Vpp  
typ. 50 mV  
1.6% Uo nom  
Output voltage setting accuracy Ui nom, Io nom  
Output voltage noise  
Output voltage ripple  
Line and cross regulation  
Load regulation  
IEC/EN 61204  
sinusoidal output ripple at twice the line frequency  
Ui min...Ui max  
0...100% Io nom, Ui nom  
Minimum load  
not required  
Current limitation  
rectangular U/I characteristic  
1 s, electronically controlled  
enabled by droop current share  
Io nom, Uo decreases to 80% of Uo nom  
101...112% Io nom  
150% Io nom  
Short term peak power  
Operation in parallel  
Hold-up time  
typ. 15 ms  
Control  
Status indication  
LED output(s) OK  
Protection  
Input reverse polarity  
Input fuse  
Input undervoltage lockout  
Input overvoltage lockout  
Input transient  
bridge rectifier  
not user accessible  
10 A, fast blow  
typ. 80% Ui min  
typ. 105% Ui max  
voltage depending resistor (VDR)  
Output(s)  
Output overvoltage  
Overtemperature  
no-load, overload and short circuit proof  
second control loop, each output, 24/48 V  
reduced output power if thermally overloaded  
30/60 V SELV  
Safety  
Approvals in progress  
EN 60950, UL 1950, CSA22.2 No. 950, UL 508 listed  
Electric strength test voltage  
class I, I/case  
class I, I/O  
class I, O/case  
class I, O/O  
AC-in / DC-in  
2 kV AC  
3 kV AC  
1 kV AC  
0.35 kV AC  
3/2  
Pollution degree  
Degree of protection  
IP 20  
www.power-one.com  
Edition 5/7.2001  
2
DIN Rail Mountable  
X Series  
EMC  
Electrostatic discharge  
Electromagnetic field  
Electr. fast transients/bursts  
Surge  
IEC/EN 61000-4-2, level 4, contact/air (8/15 kV)  
IEC/EN 61000-4-3, level 3 (10 V/m)  
IEC/EN 61000-4-4, level 4, capacitive/direct (4/2 kV)  
IEC/EN 61000-4-5, level 3, in and out, line to line (2 kV) criterion B  
level >3, input, line to case (3.5 kV) criterion B  
criterion A  
criterion A  
criterion A  
level 2, output, line to case (1 kV)  
IEC/EN 61000-4-6, level 3 (10 V)  
CISPR 22/EN 55022, conducted  
criterion A  
criterion A  
class B  
Conducted disturbances  
Electromagnetic emissions  
Environmental  
Operating ambient temperature Ui nom, Io nom, convection cooled  
Operating case temperature TC Ui nom, Io nom  
40...60°C  
40...87°C  
40...100°C  
56 days  
Storage temperature  
Damp heat  
non operational  
IEC/EN 60068-2-3, 93%, 40°C  
unit wall mounted with brackets  
IEC/EN 60068-2-27, 11 ms  
IEC/EN 60068-2-29, 11 ms  
IEC/EN 60068-2-6, 10...60/60...2000 Hz  
IEC/EN 60068-2-64, 20...500 Hz  
MIL-HDBK-217E, GB, 40°C  
Shock and vibration  
Shock  
50 gn  
25 gn  
0.35 mm/5 gn  
0.05 g2/Hz  
400'000 h  
Bump  
Vibration, sinusoidal  
Vibration, random  
MTBF  
Options  
Input and output undervoltage monitoring  
D1...D5  
Output voltage adjustment  
Remote on/off  
Multi option choice  
Built-in second input fuse in the neutral  
No fuse fittet (for operation from high DC)  
System connectors with screw terminals  
10 V...110% of Uo nom  
R
S
M1...M2  
F
(D1...D5, R, S) via Sub-D connector  
F1  
K2  
www.power-one.com  
Edition 5/7.2001  
3
X Series  
375 and 500Watt AC-DC Converters  
Mechanical data  
Tolerances ±0.3 mm (0.012") unless otherwise indicated.  
European  
Projection  
204 (8.03")  
196 (7.71")  
194 (7.64")  
113.6 (4.47")  
106.6 (4.2")  
S09127  
29.4 (1.16")  
Option M  
31 (1.22")  
TA  
TA  
Wall mounting  
brackets  
(accessory)  
Measuring point for  
case temperature TC  
www.power-one.com  
Edition 5/7.2001  
4
DIN Rail Mountable  
X Series  
Terminal allocation input side  
S10066  
Pin  
1
Des.  
Determination  
Protective earth  
Input neutral  
I
2
N
P
1
2
3
n
3
S90048  
Terminal allocation output side  
Pin  
1
Des.  
Single output  
Earth to load  
Output pos.  
Output pos.  
Output neg.  
Output neg.  
Output pos.  
Output pos.  
Output neg.  
Output neg.  
Options  
Double output  
Earth to load  
Output 1 pos.  
Output 1 pos.  
Output 1 neg.  
Output 1 neg.  
Output 2 pos.  
Output 2 pos.  
Output 2 neg.  
Output 2 neg.  
Options  
9
1
2
3
4
5
6
7
8
10  
11  
12  
2
+
3
+
4
5
+
6
7
+
8
9
10  
11  
12  
Aux1  
Aux2  
Options  
Options  
Earth to load  
Earth to load  
Accessories  
Mounting brackets for vertical chassis/wall mounting  
Protective covers over input and output terminals  
www.power-one.com  
Edition 5/7.2001  
5

相关型号:

LXN-1801-6

375 and 500 Watt AC-DC Converters
POWER-ONE

LXN-2660-6

375 and 500 Watt AC-DC Converters
POWER-ONE

LXN1240-6M1

375 and 500 Watt AC-DC Converters
POWER-ONE

LXN1701-6

375 and 500 Watt AC-DC Converters
POWER-ONE

LXN1740-6M1

375 and 500 Watt AC-DC Converters
POWER-ONE

LXN2880-6

375 and 500 Watt AC-DC Converters
POWER-ONE

LXO

Low Power Crystal Oscillator
STATEK

LXO-AT

Low Power Crystal Oscillator
STATEK

LXO-AT10

Telecommunication IC
ETC

LXO-AT2

Telecommunication IC
ETC

LXO-AT2E40MHZ(A/I)

Micro Peripheral IC
STATEK

LXO-AT2E40MHZ(A/M)

Peripheral IC
ETC