• Up to 1000 Watt fan-less power / 1200W boost
• Designed and made in Europe
Features
AC/DC Converter
• Efficiency exceeding 90% from 15% load
• Wide Operating temperature range -40…+80°C
• Certified to Industrial, and medical standards
• Analogue control & monitor function
Regulated
Converter
RACM1200-V
1200 Watt
Description
The RACM1200-V series is setting a new benchmark for compactness in the class of AC power
supplies for reliable fan-less operation supporting long term system availability. A special baseplate
cooled design supports heat transfer to allow up to 1000W continuous output power. Up to 1200 Watt
output power is available for up to 10 seconds and in boost mode operation or for extended time with
sufficient system airflow through the unit. A wide output voltage adjustment range and a combination
of constant current limitation and hiccup mode settings makes the product multipurpose. The various
analogue control and monitoring functions are accessible via connector. Optional firmware settings
available on project base. The RACM1200-V Series can be limited to inherently fail-safe settings on
request, using smart, controlled, fault-limiting functions. An adjustable 12V system fan output and
a 1.5kVAC isolated auxiliary stand by output of 5VSB/1A are available to power the application’s
housekeeping functions. Peak efficiency reaches up to 95% and in standby mode, the unit is
compliant to ecodesign requirements.The product holds worldwide safety files to medical, industrial and
ITE standards along with electromagnetic compatibility compliance with class A immunity and class B
emissions. All these features make the product one of the easiest to integrate modular power solutions
in the industry.
3
9” x 3.8”
Enclosed
Single Output
ERP
compliant
Selection Guide
LOT6
Part
Number
Input
Voltage Range
[VAC]
Output Voltage Output Voltage Max. Output Efficiency
Factory Set
[VDC]
Range
[VDC]
Current
[A]
typ. (1)
[%]
RACM1200-24SAV/ENC
RACM1200-48SAV/ENC
85-264
85-264
24
48
24-28
48-56
50A
25A
95
95
Notes:
Note1: Efficiency is tested at nominal input and 40-60% load at +25°C ambient temperature
E224736
2MOPP
250VAC
IEC/EN62368-1 certified
UL62368-1 certified
CAN/CSA-C22.2 No. 62368-1 certified
IEC/EN60601-1 certified
ANSI/AAMI ES60601-1 (pending)
IEC/EN61558-1/2 compliant (9)
IEC61010-1/-2-201 compliant (10)
IEC/EN60601-1-2 compliant
EN55032 compliant
Model Numbering
RACM1200-__ S AV/ENC
Peak Output Power
Enclosed Case Style
EN55035 compliant
EN55024 compliant
CB Report
Nom. Output Voltage
VSB Auxiliary Output Voltage (5VDC)
Single
www.recom-power.com
REV.: 0/2021
PA-1
RACM1200-SAV
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
BASIC CHARACTERISTICS
Parameter
Condition
60/50Hz
Min.
100VAC
85VAC
Typ.
Max.
240VAC
264VAC
14A
Nominal Input Voltage
Operating Range
Input Current
47-63Hz
according to CB report
cold start at +25°C, 230VAC
main output REMOTE ON
main output REMOTE OFF
11.5A
Inrush Current
25A
No load Power Consumption
Standby Power
2W
1W
Minimum Load
0%
refer to”Power Factor”
Power Factor
5VSB Aux.
900ms
1.5s
FAN
main, 800W, 85-264VAC (-25°C to +70°C)
800W
750ms
750ms
Start-up Time
refer to “SIGNALS”
1.5s
Hold-up Time
20ms
Output Ripple and Noise (2)
20MHz BW, valid for MAIN, 5VSB, FAN
1% of nom. Vout
Notes:
Note2: Measurements are made with a 0.1μF MLCC & 10μF E-cap in parallel across output. (low ESR)
RACM1200-24SAV/ENC and RACM1200-48SAV/ENC
Efficiency vs. Load
Power Factor
100
90
80
70
60
50
40
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
115VAC
240VAC
115VAC
240VAC
30
20
10
0
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
Output Load [W]
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
Output Load [W]
Power Dissipation
100
90
80
70
60
50
40
30
20
10
0
115VAC
240VAC
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
Output Load [W]
www.recom-power.com
REV.: 0/2021
PA-2
RACM1200-SAV
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
REGULATIONS
Parameter
Condition
Value
1.0% max.
5.0% max.
MAIN
5VSB / FAN
Set Point Accuracy
MAIN & FAN
5VSB Aux.
2.0% max.
5.0% max.
Total Regulation
line, load and temperature drift
ADDITIONAL FEATURES
Parameter
Condition
Min.
Typ.
Max.
5VSB Stand By Output Voltage
5VSB Stand By Output Current
5VDC
1A
always on
24Vout type (100mV steps)
48Vout type (200mV steps)
24VDC
48VDC
28VDC
56VDC
Output Voltage Adjustability
Remote ON/OFF
tactile button push up/down
maximum allowed voltage referenced to SIGNAL RTN
5VDC
OFF
FAN Output Voltage adjustment
via FAN ADJ Pin #6 @ TTL levels
CTRL= 2.5VDC
CTRL= 2.2VDC...0VDC or open
5VDC
12VDC
1A
0.9A
24Vout
ON/OFF with main channel
48Vout
FAN Output Current
“Remote Sense”
differential mode, cable loss compensation
500mV
Green continuously
Blue intermittent (30% on)
Green intermittent (50% on)
Green / Red alternatively (50%:50%)
Red intermittent (50% on)
Red / Blue alternatively (50%:50%)
Red continuously
PSU-Good: PSU in standard operation mode
STBY: Standby mode; Main Output OFF via REMOTE signal
DC-LOW: Signal: {75%<VOUT<95%} drives nonlinear loads
OTW: Over temperature warning; Output normal operation
OTP: Over temperature, Output OFF, self-recovering after cooling
OLP: Over load protection: Output OFF, auto-recovery
LED Signals
(Single RGB LED)
DC-Fail: Output latch-OFF, permanent fault until AC-reset
Remote Sense
RW1
+Vout
+Vout
VACIN (L)
VACin(L)
VACin(N)
+Sense
PE
-Sense
-Vout
-Vout
VACIN (N)
RW2
BLOCK DIAGRAM
Feedback
LLC
+Vout
+Remote Sense
-Remote Sense
-Vout
Output
Filter
L
N
Fuse, Inrush
EMI Filter
Inrush Lim.
MAIN
Control &
Protection
LLC
Control
Rectifier
Transformer
PE
FAN
Control &
Protection
+Fan
PFC
Converter
Buck
Converter
Output
Filter
Rectifier
Fan ADJ
Fan RTN
Primary
Control
Protection
5V AUX
Control &
Protection
+5VSB
Flyback
Control
Flyback
Transformer
Output
Filter
Rectifier
5VSB RTN
Feedback
PSU_GOOD
AC_OK
Remote Sense
Remote ON/OFF
Signal RTN
Secondary
Control
Protection
Communication
Output
Filter
www.recom-power.com
REV.: 0/2021
PA-3
RACM1200-SAV
AC/DC Converter
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
Series
SIGNALS
POWER ON
REMOTE OFF
AC FAIL
floating
REMOTE
ON/OFF
<2ms
GNDVSB
lead dependent (min. 3.8s - max 8s)
AC INPUT
AC_OK 0VDC
8ms
-5VDC
max. 1.3s
max.
200ms
5VSB
MAIN
max 100ms
400ms
90%
90%
10%
max. 1.5s
90%
10%
90%
FAN
lead dependent
(800W~30ms)
1000W~18ms
1200W~13ms
PSU_GOOD(3)
200ms
typ.
0VDC
200ms typ.
-5VDC
Notes:
Note3: The outputs are open-drain and require an external pull-up resistor to keep the output in a defined logic state
www.recom-power.com
REV.: 0/2021
PA-4
RACM1200-SAV
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
Signal Description
Remote ON/OFF
Pin position - #17 (CON3 connector). Pin type – input pin, referenced to ‘SIGNAL RTN’ ground. Max. allowed voltage level: 5VDC. Leave this signal ‘open’ (not
connected) for always-ON operation. Connect to ‘SIGNAL RTN’ for ‘always-OFF’ operation.
NOTE: Typically, use external mechanical switch between pins #17 and #18 of CON3 connector to control the unit’s on/off functionality.
Remote Sense Activation
Pin position - #15 (CON3 connector). Pin type – input pin, referenced to ‘SIGNAL RTN’ ground. Max. allowed voltage level: 5VDC. Leave this signal ‘open’ (not
connected) for internal output sensing functionality. Connect to ‘SIGNAL RTN’ for activating the remote main-output voltage sensing. When this functionality
is set active, the pins ‘Remote Sense +’ (pin #10) and ‘Remote Sense RTN’ (pin #9) must be connected to the load points where customer wants to remotely
monitor the main output amplitude. When this functionality shall be left inactive (default state), the remote sensing lines ‘Remote Sense+’ and ‘Remote Sense
RTN’ must stay unconnected.
NOTE: Typically, activating this feature comes together with an external wired sense line connections to the load point, which is expected to be done at process
of installing the unit within a system.
AC_OK
Pin position - #13 (CON3 connector). Pin type – open-collector output pin, referenced to ‘SIGNAL RTN’ ground. Minimal pull-up resistor: 5kOhm. Maximal pull-up
rail voltage: 5VDC. Maximal output current (+25°C): 1mAmp. Active status: low. Output voltage at active-low state (+25°C): max. 0.4V. Recommended usage:
pull-up resistor of 10kOhm to +5VSB voltage rail.The ‘AC_OK’ signal is set active-low state, when input AC line is more than typ.80VACrms.The ‘AC_OK’ signal
is set inactive-high state, when input AC line is less than typ.70VACrms.
PSU_GOOD
Pin position - #14 (CON3 connector). Pin type – open-collector output pin, referenced to ‘SIGNAL RTN’ ground. Minimal pull-up resistor: 5kOhm. Maximal pull-up
rail voltage: 5VDC. Maximal output current (+25°C): 1mAmp. Active status: low. Output voltage at active-low state (+25°C): max. 0.4V. Recommended usage:
use pull-up resistor of 10kOhm to +5VSB voltage. The ‘PSU_OK’ signal is set active-low state, when 3 conditions are met: outputs are present, temperature is
within limits (less than warning temperature) and no internal failure is activated (e.g. OTP, OCP, OLP, etc.) The ‘PSU_OK’ signal is set inactive-high state, when
at least one of the above 3 conditions is not met.
PROTECTIONS
Parameter
Type
Value
Internal Input Fuse
L and N (dual fusing)
2x T12A/250VAC
IEC62368-1; IEC61010-1 (10)
IEC62477-1; up to 2000m
OVCII
OVCIII
Over Voltage Category (OVC)
Over Temperature Protection (OTP)
Over Temperature Warning
Class of Equipment
detected on internal sensors
auto recovery after cooling down to 70°C ( 5°C)
LED= green/red alternatively , DC low
with PE
Class I
4kVAC
I/P to O/P (unit)
I/P and O/P to chassis
1.5kVAC
Isolation Voltage (4)
1 minute
O/P to 5VSB & signals; 5VSB & signals to chassis
(when factory bridge #7 to #16 is removed)
1.5kVAC
Insulation Grade
I/P to O/P
reinforced
NC: 300μA max.; SFC: 1mA
Earth Leakage Current
Patient Leakage
NC: 100μA max.; SFC: 500μA
Means of Protection
Medical Device Classification
2MOPP
built-in, suitable for Type BF rated medical applications
Notes:
Note4: For repeat Hi-Pot testing, reduce the time and/or the test voltage
continued on next page
REV.: 0/2021
www.recom-power.com
PA-5
RACM1200-SAV
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
PROTECTIONS MAIN OUTPUT
Parameter
Type
Value
Short Circuit Protection (SCP)
auto recovery, hiccup mode
24Vout
48Vout
29.5VDC typ., Latch OFF
59VDC typ., Latch OFF
Over Voltage Protection (OVP)
no reverse overvoltage protection
Over Current Protection (OCP)
refer to “Over Current Protection”
power limiting (>75% Vout), Hiccup Mode
Over Current Protection
max. Vout
nom. Vout
constant current
75% Vout
Over Current Protection
(Hiccup Mode)
Iout
85%
100%
PROTECTIONS FAN
Parameter
Short Circuit Protection (SCP)
Over Voltage Protection (OVP)
Over Current Protection (OCP)
Type
Value
auto recovery
if OVP is activated, all outputs will shut off
auto recovery, hiccup mode
auto recovery, power limitation
PROTECTIONS 5VSB
Parameter
Short Circuit Protection (SCP)
Over Voltage Protection (OVP)
Over Current Protection (OCP)
Type
Value
auto recovery, hiccup mode
auto recovery, hiccup mode
auto recovery, hiccup mode
if any protection is activated, all outputs will shut off
ENVIRONMENTAL
Parameter
Condition
Value
refer to “Main Output Nominal Power
Rating vs. Ambient Temperature”
T
AMB and TBASE temperature
-40°C to +80°C
+70°C typ.
Operating Temperature Range
Operating Altitude (5)
max. start-up temperature
IEC/EN62368-1
ANSI/AAMI/EN60601-1 (pending)
5000m
4000m
Operating Humidity
IP Rating
non-condensing
95% RH max.
IP20
Pollution Degree
Design Lifetime
PD2
88 x 103 hours
+40°C (reference point)
Notes:
Note5: Recognized by safety agency for safe operation up to 5000m. High altitude operation above 2000m may impact the performance
and lifetime. Please contact RECOM tech support for advice.
continued on next page
www.recom-power.com
REV.: 0/2021
PA-6
RACM1200-SAV
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
Suggested Power Rating for main Output
Conduction cooled operation (still air / non stired)
Provided airflow trough the unit
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
NOM AMB
BASE
P
P
P
P
, T =50°C; T = <80°C
NOM AMB
P
P
P
P
, T =50°C; 1.25m/s
NOM AMB
, T =40°C; T = <70°C
PEAK PEAK
, t <4sec
PEAK PEAK
, t <10sec
BASE
NOM AMB
, T =40°C; 2.5m/s
PEAK PEAK
, t <4sec
PEAK PEAK
, t <10sec
85 100 120 140 160 180 200 220 240 264
85 100 120 140 160 180 200 220 240 264
90 103
172
90 103
172
Input Voltage [VAC]
Input Voltage [VAC]
The units were evaluated to safety files for nominal input voltages 100-240VAC; including a tolerance band of 10%, with a specified maximum TBASE of
80°C for full load rating with 50°C TAMB and up to 80°C TAMB. at reduced output power. TBASE at reference point (see ”thermal reference point”) shall not
exceed 70°C, 80°C or 90°C depending on the condition as per derating graph.
Peak power was evaluated at 60s duty cycle period for safety files. Without externally provided forced airflow, continuous output power needs to be limited to
1000W at high input voltage range and TAMB <40°C with a TBASE <70°C. With forced airflow of 2.5m/s 1200W continuous boost power at high input voltage
range (>172V) is available.
Main Output Nominal Power Rating vs. Ambient Temperature
100
90
80
70
60
50
40
30
(7)
20
10
0
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80(8) 90
Ambient Temperature [°C]
-25(6)
Notes:
Note6: Below TAMB -25°C some specifications may not be met
Note7: Output Power at TAMB= -40°C cold start ≤250W.
Note8: At TAMB +80°C and 30% load, the maximum allowed baseplate temperature TBASE ≤90°C measured on
thermal reference point. Refer to “thermal reference point”
www.recom-power.com
REV.: 0/2021
PA-7
RACM1200-SAV
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
PEAK LOAD CAPABILITY
PEAK POWER IS NOT AVAILABLE DURING START UP PHASE!
Exceeding power ratings, may reduce the lifetime and lead to OLP power limitation or OTP temperature shut off. Inherently safe unit set up for more strict automatic
power limitation is available on request per firmware setting option. Peak Power duty cycle plus recovery period shall not exceed 90% of the average nominal
power for repetitive load conditions.
Peak Load Calculation
Pout [W]
Pp
Pnom
Pr
... nominal power output (as per derating graph)
... applied recovery power
... applied peak power
... recovery time
[W]
[W]
[W]
[s]
Pp
tr
Pnom
Pr
tp
... peak time
[s]
VIN <172VAC = 4s
[s]
VIN ≥172VAC-264VAC = 10s
[s]
Time [s]
tp
tr
SAFETY AND CERTIFICATIONS
Certificate Type (Safety)
Report Number
Standard
Audio/video, information and communication technology equipment- Safety requirements (CB)
Audio/video, information and communication technology equipment - Safety requirements
Audio/video, information and communication technology equipment- Safety requirements (CB)
Audio/video, information and communication technology equipment - Safety requirements
IEC62368-1:2014 2nd Edition
EN62368-1:2014 + A11:2017
UL62368-1:2014
T223-0765/20
E224736-A6006-
UL
CAN/CSA-C22.2 No. 62368-1:2014
ANSI/AAMI ES60601-1:2005
CAN/CSA-C22.2 No. 60601:14
Medical Electric Equipment, General Requirements for Safety and Essential Performance
pending
Medical Electric Equipment, General Requirements for Safety and Essential Performance (CB)
Medical Electric Equipment, General Requirements for Safety and Essential Performance
IEC60601-1:2005, 3rd Edition + AM1:2012
EN60601-1:2006 + A1:2013
T223-0766/20
IEC61558-1:2005, 2nd Edition + A1:2009
EN61558-1:2005 + A1:2009
Safety of transformers, reactors, power supply units and combinations thereof - Part 1: General
requirements and tests
compliant (9)
compliant (10)
Electrical Equipment For Measurement, Control, and Laboratory Use; Part 1: General Requirements
RoHS2
IEC61010-1/-2-201
RoHS 2011/65/EU + AM2015/863
Notes:
Note9: Insulation inside transformer meets requirements for insulation and overload per IEC61558-1 (tested in T223-0765/20)
Note10: Creepage and clearance according to IEC61010-1/-2-201 (tested in T223-0766/20)
continued on next page
www.recom-power.com
REV.: 0/2021
PA-8
RACM1200-SAV
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
EMC Compliance (Medical)
Medical electrical equipment - Part 1-2: General requirements for basic safety and essential
performance - Collateral standard: Electromagnetic compatibility - Requirements and tests
IEC60601-1-2:2014, Class B
EN60601-1-2:2015, Class B
Industrial, scientific and medical equipment - Radio frequency disturbance
characteristics - Limits and methods of measurement
EN55011, Class B
Industrial, scientific and medical equipment - Radio-frequency disturbance characteristics -
Limits and methods of measurement(12)
CISPR 11, Group 1, Class B
IEC61000-4-2:2008
EN61000-4-2:2009
ESD Electrostatic discharge immunity test
Contact: 8kV
10V/m (80-1000MHz, 1.0-2.7GHz)
27V/m (385MHz)
28V/m (450, 810, 870, 930, 1720, IEC61000-4-3:2006+A2:2010
Radiated, radio-frequency, electromagnetic field immunity test
Fast Transient and Burst Immunity
1845, 1970, 2450MHz)
9V/m (710, 745, 780, 5240, 5500,
5785MHz)
EN61000-4-3:2006+A2:2010
AC Power Port: 2kV
IEC/EN61000-4-4:2012
IEC/EN61000-4-5:2014
AC Power Port: L-N 1kV
L-PE, N-PE: 2kV
Surge Immunity
3Vrms (0.15-80MHz)
6Vrms (ISM, amateur radio bands)
IEC61000-4-6:2013
EN61000-4-6:2014
Immunity to conducted disturbances, induced by radio-frequency fields
Power Magnetic Field Immunity
IEC61000-4-8:2009
EN61000-4-8:2010
30A/m, 50 Hz
Voltage Dip 100% (0.5P)
Voltage Dip 100% (1.0P)
Voltage Dip 30%
Voltage Dips and Interruptions
IEC/EN61000-4-11:2004
Voltage Interruption 100%
Limits of Harmonic Current Emissions
Limits of Voltage Fluctuations & Flicker
Class A
EN61000-3-2
EN61000-3-3
Clause 5
EMC Compliance (Industrial)
Electromagnetic compatibility of multimedia equipment - Emission requirements(9)
EN55032:2015, Class B
EN55035:2017
Electromagnetic compatibility of multimedia equipment - Immunity requirements
Information technology equipment - Immunity characteristics - Limits and methods of
measurement
EN55024:2010 + A1:2015
Limitations on the amount of electromagnetic interference allowed from digital and
electronic devices
FCC 47 CFR Part 15 Subpart B,
ANSI C63.4:2014, Class B
Notes:
Note11: The emission performance was tested with snap-on ferrite Wurth 742 712 21. The 48V versions with 2-turns of AC-line cable; the 24V
version with 2-turns of N (neutral) line only. The output cables were used twisted pair lines, with the typical configuration of grounded return lines.
Note12: Performance criteria A indicates operation within 10% tolerance band of nominal settings
DIMENSION AND PHYSICAL CHARACTERISTICS
Parameter
Type
Value
case/baseplate
PCB
aluminum
FR4 (UL94 V-0)
Material
Dimension (LxWxH)
Weight
228.0 x 96.2 x 40.0mm
1000g. typ.
continued on next page
REV.: 0/2021
www.recom-power.com
PA-9
RACM1200-SAV
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
Dimension Drawing (mm)
Top View
228.±
Side View
thermal reference point
7 x M3 4.ꢀmax.
82.ꢀ*
2X 6±.±
2X 36.±
27.9*
26.±
Bottom View
±
13.2
General tolerances according to ISO 2768-m
(table for reference only)
ꢀimension range
ꢁꢂꢃ ꢄ ꢅ mm
ꢅ ꢄ ꢆꢁ mm
ꢆꢁ ꢄ ꢇꢈꢁ mm
ꢇꢈꢁ ꢄ ꢉꢁꢁ mm
ꢊolerances
ꢁꢂꢇ mm
ꢁꢂꢈ mm
ꢁꢂꢆ mm
ꢁꢂꢃ mm
continued on next page
REV.: 0/2021
www.recom-power.com
PA-10
RACM1200-SAV
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
Dimension Drawing (mm)
Front View (Input)
Back View (Output/Signal)
(dip switch)
ADJ
CON1
ꢀ 2 1
2 2 1 1
CON2
LED
CON3
Connector information CON3
Cvilux CI0120P1HD0.NH Type Pin Header
Connector information
AC Input CON1
#
2
4
6
8
Function
Reserved for factory config.
Reserved for factory config.
FAN ADJ
#
1
3
5
7
9
Function
reserved for factory config.
NC
FAN+
FAN RTN *
#
1
3
Function
AC/L
AC/N
Terminal
Phoenix
TDPT 4-SP-6.35
NC
DC Output Connector CON2
Function
10 Remote Sense+
12 NC
Remote Sense RTN
11 NC
#
Terminal
14 PSU_GOOD
16 Signal RTN *
18 Signal RTN
20 5VSB RTN
13 AC_OK
1,1
2,2
+Vout
-Vout
Phoenix
TDPT 2.5-SP-5.w08
15 Remote Sense Activation
17 Remote ON/OFF
19 5VSB+
General tolerances according to ISO 2768-m
(table for reference only)
ꢀimension range
ꢁꢂꢃ ꢄ ꢅ mm
*Factory bridge from Pin7 (FAN RTN) to Pin16 (Signal RTN)
ꢊolerances
ꢁꢂꢇ mm
ꢁꢂꢈ mm
ꢁꢂꢆ mm
ꢁꢂꢃ mm
Mating connector CON3
ꢅ ꢄ ꢆꢁ mm
Housing= Cvilux CI0120SD000
Contact= Cvilux CI01TD21PE0
ꢆꢁ ꢄ ꢇꢈꢁ mm
ꢇꢈꢁ ꢄ ꢉꢁꢁ mm
Connection wire cross sections: during building in the product, installer needs to take care to use wires with appropriate cross-section for the rated voltage/currents
INSTALLATION AND APPLICATION
Mounting suggestions
horizontal
side
AC
ꢀC
upside down
AC
ꢀC
If the PSU is horizontal, upside down or side mounted, no derating is required.
With forced air cooling, mounting orientation has no impact on output power. Device should be fan cooled from AC side.
If thermal conduction cooling is suggested, use of heat sink compound is recommended for improved heat transfer via baseplate.
www.recom-power.com
REV.: 0/2021
PA-11
RACM1200-SAV
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
PACKAGING INFORMATION
Parameter
Type
Value
303.0 x164.0 x 45.0mm
1pcs
Packaging Dimension (LxWxH)
Packaging Quantity
cardboard box
Storage Temperature Range
Storage Humidity
-40°C to +85°C
90% RH max.
non-condensing
The product information and specifications may be subject to changes even without prior written notice.The product has been designed for various applications; its suitability lies in the responsibility of each customer. The
products are not authorized for use in safety-critical applications without RECOM’s explicit written consent. A safety-critical application is an application where a failure may reasonably be expected to endanger or cause
loss of life, inflict bodily harm or damage property. The applicant shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized
use of RECOM products in such safety-critical applications.
www.recom-power.com
REV.: 0/2021
PA-12