RACM230-48SG [RECOM]
230 Watt 4â x 2â Open Frame or Enclosed Single Output;型号: | RACM230-48SG |
厂家: | RECOM INTERNATIONAL POWER |
描述: | 230 Watt 4â x 2â Open Frame or Enclosed Single Output |
文件: | 总9页 (文件大小:1675K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
• 160W baseplate-cooled, fan-less operation
• 230W peak power or forced air rating
• Universal AC input range (80~264VAC)
• Standby power consumption <0.5W
Features
AC/DC Converter
Regulated
Converter
• Wide operating temperature range (-40°C to +80°C)
• Household, ITE and medically 2MOPP certified
• Operating altitude up to 5000m
RACM230-G
230 Watt
4” x 2”
Open Frame or
Enclosed
Description
3
The RACM230-G Series is designed to support up to 160 watts continuous output power without fan
cooling. The compact 4”x2” baseplate design enables direct heat dissipation through metal housings in
the application. Up to 230 watts are available to drive dynamic loads for several seconds of peak power
or with forced air for even longer time frames. A smart fan output is on board as standard. A wide input
range of 80 to 264VAC, up to 5000m operating altitude, 4kVAC isolation and international safety agency
certifications make the series worldwide compliant for medical 2 MOPP, household and industrial ITE
applications.
Single Output
Selection Guide
Part
Number
Input
Voltage Range
[VAC]
Nom. Output
Voltage
Max. Output
Current (1)
[A]
Efficiency
typ. (3)
[%]
[VDC]
RACM230-12SG(4)
RACM230-24SG(4)
RACM230-36SG(4)
RACM230-48SG(4)
RACM230-54SG(4)
80-264
80-264
80-264
80-264
80-264
12
24
36
48
54
19.17 (2)
91
92
92
92
92
9.58
6.39
4.80
4.26
Notes:
Note1: With forced air cooling (2.5m/s) + conduction cooling + refer to “Derating Graph”
Note2: Refer to “Peak Load Capability” graph
Note3: Efficiency is tested at nominal input and full load at +25°C ambient
C
RoHS2
+
ERP
REACH
compliant
compliant
compliant
10 from 10
LOT6
I
Model Numbering
CERTIFIED
EN-60335-1
E314885
RACM230-__ SG/ENC
(4)
“Case Option
”
max. Output Power
2MOPP
250VAC
Single
nom. Output Voltage
ANSI/AAMI ES60601-1 (ed 3.1) (“/OF” version)
CSA/CAN 22.2 60601-1-14 (ed 3.1) certified
IEC/EN60601-1 (ed 3.1) (“/OF” version) certified
IEC/EN62368-1 certified
Notes:
Note4: without suffix standard open frame version
add suffix “/ENC” for enclosed version (MOQ: 1000pcs)
EN60335-1 certified
EN62233 certified
IEC/EN61558-1 certified
IEC/EN61558-2-16 certified
EN55032 compliant
Ordering Examples:
RACM230-24SG
24Vout
Single
Single
open frame
enclosed
RACM230-48SG/ENC 24Vout
EN55035 compliant
CB Report
www.recom-power.com
REV.: 3/2021
MED-1
RACM230-G
AC/DC Converter
Specifications (measured @ Ta= 25°C, 230VAC rated load unless otherwise stated)
Series
BASIC CHARACTERISTICS
Parameter
Condition
Min.
Typ.
Max.
Nom. Input Voltage
100VAC
240VAC
80VAC
120VDC
230VAC
264VAC
370VDC
Input Voltage Range (5)
115VAC
230VAC
3A
1.1A
Input Current
115VAC
230VAC
40A
60A
Inrush Current
No load Power Consumption
Input Frequency Range
300mW
50Hz
500mW
63Hz
AC input
47Hz
ErP Lot 6 Standby Mode Conformity
(Output Load Capability)
Input Power= 1W
300mW
12Vout
24Vout
36Vout
48Vout
54Vout
11.4VDC
22.8VDC
34.2VDC
45.6VDC
51.3VDC
12.6VDC
25.2VDC
37.8VDC
50.4VDC
56.0VDC
Output Voltage Adjustability (6)
Minimum Load
Power Factor
0%
115VAC
230VAC
0.98
0.95
0.99
0.97
Start-up Time
Rise Time
115/230VAC
0.5s
10ms
230W
200W
160W
130W
8ms
10ms
16ms
25ms
Hold-up Time
115/230VAC
Output Ripple and Noise(7)
20MHz BW @ +25°C
1% of Vout nom. max.
Notes:
Note5: The products were submitted for safety files at AC-input operation. For DC-input make sure that sufficient fuses are used
Note6: By trimming up, decrease output current to avoid exceeding rated output power. By trimming down, do not exceed maximum
continuous output current. If enclosed version is used, please remove cover, to use trim function.
Note7: Measurements are made with a 12“ twisted pair-wire terminated with a 0.1µF and 10µF parallel capacitor
Efficiency vs. Load
24V to 54V models
12V model
100
90
80
70
60
50
40
30
20
10
0
100
90
80
70
60
50
40
30
20
10
0
110VAC
230VAC
110VAC
230VAC
0
10 20 30 40 50 60 70 80 90 100
0
10 20 30 40 50 60 70 80 90 100
Output Load [%]
Output Load [%]
continued on next page
REV.: 3/2021
www.recom-power.com
PA-2
RACM230-G
AC/DC Converter
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)
Series
REGULATIONS
Parameter
Condition
Value
1.0% typ.
0.5% typ.
0.5% typ.
Output Accuracy
Line Regulation
Load Regulation (8)
low line to high line, full load
10% to 100% load
Notes:
Note8: Operation below 10% load will not harm the converter, but specifications may not be met
FAN OUTPUT
Parameter
Condition
Min.
Typ.
Max.
Output Current
@50°C
continuous
500mA
Output Voltage
12VDC
Ambient Temperature
Short Circuit Protection (SCP)
Over Current Protection (OCP)
full load
50°C
none
none
PROTECTIONS
Parameter
Type
line and neutral
Value
Internal Input Fuse (9)
2x T6.3A, slow blow type
hiccup mode, auto recovery
105% - 150%, latch off mode
Short Circuit Protection (SCP)
Over Voltage Protection (OVP)
Over Load Protection (OLP)
Over Voltage Category (OVC)
Isolation Voltage (safety certified)(10)
Isolation Resistance
105% - 200% (150% typ.); hiccup mode auto recovery
OVCII
4kVAC
I/P to O/P
1 minute
10MΩ min.
reinforced
0.3mA max.
2MOPP
Insulation Grade
Leakage Current
Means of Protection
250VAC working voltage
Notes:
Note9: Refer to local safety regulations if input over-current protection is also required. Recommended fuse: slow blow type
Note10: For repeat Hi-Pot testing, reduce the time and/or the test voltage
ENVIRONMENTAL
Parameter
Condition
refer to derating graphs
Value
-40°C to +80°C
0.05%/ꢀ
Operating Temperature Range
Temperature Coefficient
Operating Altitude (11)
Operating Humidity
Pollution Degree
5000m
non-condensing
5% - 90% RH max.
PD2
+25°C (forced air cooling)
+50°C (forced air cooling)
200 x 103 hours
60 x 103 hours
according to
MIL-HDBꢀ-217F, G.B.
MTBF
Notes:
Note11: Recognized by safety agency for safe operation up to 5000m. High altitude operation may impact the performance and lifetime.
Please contact RECOM tech support for advice.
continued on next page
www.recom-power.com
REV.: 3/2021
MED-3
RACM230-G
AC/DC Converter
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)
Series
Derating Graph
(@ 2.5m/s airflow + conduction cooling)
12V model
others
240
220
200
240
220
200
180
160
140
120
100
80
230
207
186
180
167
160
150
140
120
100
80
60
60
100VAC
115VAC
240VAC
100VAC
115VAC
240VAC
50
45
40
20
0
40
25
20
0
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80 90
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80 90
45
Ambient Temperature [°C]
Ambient Temperature [°C]
Derating Graph
(@ natural convection + conduction cooling)
12V model
others
170
160
150
140
130
120
110
100
90
170
160
150
140
130
120
110
100
90
144
144
80
80
70
70
60
60
50
50
40
30
20
10
40
30
20
10
100VAC
115VAC
240VAC
100VAC
115VAC
240VAC
35
0
0
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80 90
25
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80 90
Ambient Temperature [°C]
Ambient Temperature [°C]
Derating Graph
(@ natural convection)
12V model
others
140
130
140
130
120
110
100
90
120
117
117
105
110
105
100
90
80
70
60
50
40
30
80
70
60
50
40
100VAC
115VAC
240VAC
100VAC
115VAC
240VAC
30
25
20
15
20
10
10
0
0
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80 90
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80 90
Ambient Temperature [°C]
Ambient Temperature [°C]
Convection Cooling:
<0.1m/s = still air
0.1 - 0.2m/s = natural convection
Conduction Cooling:
ground plane ref.: 2mm alloy; size A4
www.recom-power.com
REV.: 3/2021
MED-4
RACM230-G
AC/DC Converter
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)
Series
Peak Load Capability
Calculation
Pout [W]
Pnom = nom. output power
[W]
PP = peak output power (≤230W) [W]
Pnom x (t1 + t2) - (PP x t1)
t2 x k
Pr = recovery output power
t1 = peak time set (10s max.)
t2 = recovery time (min. 4 x t1)
[W]
[s]
[s]
[ ]
Pp
Pr =
k
= safety factor 1.7
Pnom
Pr
Practical Example (RACM230-12SG):
Take the RACM230-12SG at 230VAC input Voltage and full load at TAMB= 25°C (160W) with
conduction cooling.
0
Time [s]
t1
t2
Pnom. = refer to derating graphs (160W)
PP = 230W
160 x (1 + 40) - (230 x 1)
t1 = 1s
Pr =
= 93W
40 x 1.7
40s
=
t2
k
= 1.7
SAFETY AND CERTIFICATIONS
Certificate Type (Safety)
Report Number
Standard
Audio/video, information and communication technology equipment - Safety requirements
Audio/video, information and communication technology equipment - Safety requirements (LVD)
Audio/video, information and communication technology equipment - Safety requirements (CB)
Audio/video, information and communication technology equipment - Safety requirements
Household and similar electrical appliances - Safety - Part 1: General requirements
IEC62368-1:2014 2nd Edition
EN62368-1:2014 + A11:2017
IEC62368-1:2014, 2nd Edition
EN62368-1:2014 + A11:2017
EN60335-1:2012 + A13:2017
SA1903063L01001
211-700882-000
SA1903063L01001
SA0903063L02001
Measurement methods for electromagnetic fields of household appliances and similar
apparatus with regard to human exposure
EN62233:2008
ANSI/AAMI ES60601-1:2005 + A2:2010/
(R)2012
CAN/CSA-C22.2 No. 6060-1:14, 3rd Edition
IEC60601-1:2005, 3rd Edition + AM1:2012
EN60601-1:2006 + A1:2013
E314885
(“/OF” Version)
Medical Electric Equipment, General Requirements for Safety and Essential Performance
Medical Electric Equipment, General Requirements for Safety and Essential Performance (CB)
Medical Electric Equipment, General Requirements for Safety and Essential Performance
E314885
IEC61558-1:2005, 2nd Edition + A1:2009
EN61558-1:2005 + A1:2009
Safety of power transformers, power supplies, reactors and similar products -
Part 1: General requirements and tests
211-700883-000
Safety of transformers, reactors, power supply units and similar products for supply
voltages up to 1100 V - Part 2-16: Particular requirements and tests for switch mode
power supply units and transformers for switch mode power supply units (CB)
211-700883-000
211-700883-000
IEC61558-2-16:2009, 1st Edition + A1:2013
Safety of transformers, reactors, power supply units and similar products for supply
voltages up to 1100 V - Part 2-16: Particular requirements and tests for switch mode
power supply units and transformers for switch mode power supply units (LVD)
EN61558-2-16:2009 + A1:2013
RoHS 2011/65/EU + AM2015/863
RoHS2
continued on next page
REV.: 3/2021
www.recom-power.com
MED-5
RACM230-G
AC/DC Converter
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)
Series
EMC Compliance
Electromagnetic compatibility of multimedia equipment - Emission requirements
Condition
without external filter
Standard / Criterion
EN55032:2015, Class B
EN55035:2017
Electromagnetic compatibility of multimedia equipment - Immunity requirements
Information technology equipment - Immunity characteristics - Limits and methods of
measurement
EN55024:2010 + A1:2015
IEC61000-4-2:2008, Criteria A
EN61000-4-2:2009, Criteria A
ESD Electrostatic discharge immunity test
Air: 8kV; Contact 4kV
3V/m (80-1000, 1800MHz,
2600MHz, 3500MHz,
5000MHz)
Radiated, radio-frequency, electromagnetic field immunity test
IEC/EN61000-4-3:2006+A2:2010, Criteria A
Fast Transient and Burst Immunity
Surge Immunity
AC Power Port: L, N 1kV
IEC/EN61000-4-4:2012, Criteria A
IEC/EN61000-4-5:2014, Criteria B
AC Power Port: L-N 1kV
AC Power Port: 3V (0.15-
10MHz)
3V to 1V (10-30MHz)
1V (30-80MHz)
IEC61000-4-6:2013. Criteria A
EN61000-4-6:2014, Criteria A
Immunity to conducted disturbances, induced by radio-frequency fields
Power Magnetic Field Immunity
IEC61000-4-8:2009, Criteria A
EN61000-4-8:2010, Criteria A
50Hz/60Hz, 1A/m
Voltage Dips 100% at
50/60Hz
IEC/EN61000-4-11:2004, Criteria A
Voltage Dips 30% at 50Hz
IEC/EN61000-4-11:2004, Criteria A
IEC/EN61000-4-11:2004, Criteria B
Voltage Dips 30% at 60Hz
Voltage Interruptions > 95%
at 50Hz
Voltage Interruptions > 95%
at 60Hz
Voltage Dips and Interruptions
IEC/EN61000-4-11:2004, Criteria C
IEC/EN61000-4-11:2004, Criteria B
Limits of Harmonic Current Emissions
Limits of Voltage Fluctuations & Flicker
EN61000-3-2:2014
EN61000-3-3:2013
DIMENSION AND PHYSICAL CHARACTERISTICS
Parameter
Type
Value
PCB
FR4, (UL94 V-0)
aluminium
Material
baseplate / case (“/ENC”)
open frame version
enclosed version
101.6 x 50.8 x 32.0mm
105.0 x 62.0 x 35.0mm
Dimension (LxWxH)
Weight
open frame version
enclosed version
220g typ.
290g typ.
continued on next page
REV.: 3/2021
www.recom-power.com
MED-6
RACM230-G
AC/DC Converter
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)
Series
Dimension Drawing Open Frame (mm)
101.6
1
2
ꢀꢁꢂꢅ
9
Top View
8
7
6
5
4
1
3
Aꢀꢁ
5.0
91.6
Side View
4 x Ø3.5
FC 95.25
FC 3.2
ꢀeneꢁaꢂ toꢂeꢁanceꢃ accoꢁding to ꢄꢅꢆ ꢇꢈꢉꢊꢋꢌ
ꢍtaꢎꢂe ꢏoꢁ ꢁeꢏeꢁence onꢂꢐꢑ
Bottom View
ꢀiꢁenꢂion ꢃange
0.5 - 6 ꢁꢁ
Toleꢃanceꢂ
0.1 ꢁꢁ
0.2 ꢁꢁ
0.3 ꢁꢁ
0.5 ꢁꢁ
6 - 30 ꢁꢁ
30 - 120 ꢁꢁ
120 - ꢄ00 ꢁꢁ
AC side
DC side
11.62
5x 3.96
2x 3.96
17.45
Spꢁing Waꢀheꢁ (0.ꢂꢃꢃ)
Standoff (2.0ꢃꢃ)
Baꢀeplate
Application
ꢀꢁꢂꢅ
ꢀꢁꢂꢃ
ꢀꢁꢂꢄ
Tꢄp. tightening toꢁꢅue= 0.6ꢆꢃ
Compatible Connector (valid for open frame and enclosed version)
AC Input (CON1)
Function Connector
DC Output Connector (CON2)
FAN Connector (CON3)
#
#
Function
Connector
#
Function
Connector
1
3
AC/N
AC/L
Molex 09-50-3031 7,8,9
or similar 4,5,6
+Vout
-Vout
Molex 09-50-1061
or similar
1
2
-FAN
+FAN
Molex 22-01-1022
or similiar
Maximum tightening torque for mounting without standoffs: 0.3Nm
FC= fixing centers
continued on next page
www.recom-power.com
REV.: 3/2021
MED-7
RACM230-G
AC/DC Converter
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)
Series
Dimension Drawing Enclosed Version (mm)
105.0
9
8
7
6
5
4
1
Top View
3
Aꢀꢁ
Side View
embossed logo
FC 4.87
FC 95.25
2 x Ø3.5
Bottom View
Notes:
AC side
DC side
Note12: Please remove cover, to use trim function
2x 3.96
23.0
17.2
5x 3.96
Maximum tightening torque for mounting: 0.6Nm
FC= fixing centers
ꢀeneꢁaꢂ toꢂeꢁanceꢃ accoꢁding to ꢄꢅꢆ ꢇꢈꢉꢊꢋꢌ
ꢍtaꢎꢂe ꢏoꢁ ꢁeꢏeꢁence onꢂꢐꢑ
ꢀiꢁenꢂion ꢃange
0.5 - 6 ꢁꢁ
6 - 30 ꢁꢁ
30 - 120 ꢁꢁ
120 - ꢄ00 ꢁꢁ
Toleꢃanceꢂ
0.1 ꢁꢁ
0.2 ꢁꢁ
0.3 ꢁꢁ
0.5 ꢁꢁ
ꢀꢁꢂꢅ
ꢀꢁꢂꢃ
ꢀꢁꢂꢄ
www.recom-power.com
REV.: 3/2021
MED-8
RACM230-G
AC/DC Converter
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)
Series
INSTALLATION AND APPLICATION
Mounting
vertical
side 1
side 2
horizontal (standard)
DC
AC
airflow
upside-down
airflow
AC
DC
Notes:
Note13: If module is side mounted, vertically or upside-down with natural convection cooling, the power must be derated
down to 85% for the RACM230-12SG, for the other models 90%.
For convection cooling, ensure sufficient distance to adjacent components!
Device should be fan cooled from DC side.
Block Diagram
ADJ
PFC LLC
Controller
Feedback
and Isolation
Controller
Rectifier
L
Fuse, Inrush
Current Linitation,
Input Filter
+Vout
-Vout
Rectifier +
Bulk Cap
Output
Filter
Switcher
PFC
Boost
N
PE
+Fan
-Fan
Rectifier
Transformer
PACKAGING INFORMATION
Parameter
Type
Value
Packaging Dimension (LxWxH)
cardboard box
112.0 x 80.0 x 50.0mm
Packaging Quantity
1pcs
Storage Temperature Range
Storage Humidity
-55°C to +100°C
5% - 90% RH max.
non-condensing
The product information and specifications may be subject to changes even without prior written notice.The product has been designed for various applications; its suitability lies in the responsibility of each customer. The
products are not authorized for use in safety-critical applications without RECOMꢀs explicit written consent. A safety-critical application is an application where a failure may reasonably be expected to endanger or cause
loss of life, inflict bodily harm or damage property. The applicant shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized
use of RECOM products in such safety-critical applications.
www.recom-power.com
REV.: 3/2021
MED-9
相关型号:
©2020 ICPDF网 联系我们和版权申明