• 160W baseplate-cooled, fan-less operation  
• 230W peak power or forced air rating  
• Universal AC input range (80~264VAC)  
• Standby power consumption <0.5W  
Features  
AC/DC Converter  
Regulated  
Converter  
• Wide operating temperature range (-40°C to +80°C)  
• Household, ITE and medically 2MOPP certified  
• Operating altitude up to 5000m  
RACM230-G  
230 Watt  
4” x 2”  
Open Frame or  
Enclosed  
Description  
3
The RACM230-G Series is designed to support up to 160 watts continuous output power without fan  
cooling. The compact 4”x2” baseplate design enables direct heat dissipation through metal housings in  
the application. Up to 230 watts are available to drive dynamic loads for several seconds of peak power  
or with forced air for even longer time frames. A smart fan output is on board as standard. A wide input  
range of 80 to 264VAC, up to 5000m operating altitude, 4kVAC isolation and international safety agency  
certifications make the series worldwide compliant for medical 2 MOPP, household and industrial ITE  
applications.  
Single Output  
Selection Guide  
Part  
Number  
Input  
Voltage Range  
[VAC]  
Nom. Output  
Voltage  
Max. Output  
Current (1)  
[A]  
Efficiency  
typ. (3)  
[%]  
[VDC]  
RACM230-12SG(4)  
RACM230-24SG(4)  
RACM230-36SG(4)  
RACM230-48SG(4)  
RACM230-54SG(4)  
80-264  
80-264  
80-264  
80-264  
80-264  
12  
24  
36  
48  
54  
19.17 (2)  
91  
92  
92  
92  
92  
9.58  
6.39  
4.80  
4.26  
Notes:  
Note1: With forced air cooling (2.5m/s) + conduction cooling + refer to “Derating Graph”  
Note2: Refer to “Peak Load Capability” graph  
Note3: Efficiency is tested at nominal input and full load at +25°C ambient  
C
RoHS2  
+
ERP  
REACH  
compliant  
compliant  
compliant  
10 from 10  
LOT6  
I
Model Numbering  
CERTIFIED  
EN-60335-1  
E314885  
RACM230-__ SG/ENC  
(4)  
“Case Option  
max. Output Power  
2MOPP  
250VAC  
Single  
nom. Output Voltage  
ANSI/AAMI ES60601-1 (ed 3.1) (“/OF” version)  
CSA/CAN 22.2 60601-1-14 (ed 3.1) certified  
IEC/EN60601-1 (ed 3.1) (“/OF” version) certified  
IEC/EN62368-1 certified  
Notes:  
Note4: without suffix standard open frame version  
add suffix “/ENC” for enclosed version (MOQ: 1000pcs)  
EN60335-1 certified  
EN62233 certified  
IEC/EN61558-1 certified  
IEC/EN61558-2-16 certified  
EN55032 compliant  
Ordering Examples:  
RACM230-24SG  
24Vout  
Single  
Single  
open frame  
enclosed  
RACM230-48SG/ENC 24Vout  
EN55035 compliant  
CB Report  
www.recom-power.com  
REV.: 3/2021  
MED-1  
RACM230-G  
AC/DC Converter  
Specifications (measured @ Ta= 25°C, 230VAC rated load unless otherwise stated)  
Series  
BASIC CHARACTERISTICS  
Parameter  
Condition  
Min.  
Typ.  
Max.  
Nom. Input Voltage  
100VAC  
240VAC  
80VAC  
120VDC  
230VAC  
264VAC  
370VDC  
Input Voltage Range (5)  
115VAC  
230VAC  
3A  
1.1A  
Input Current  
115VAC  
230VAC  
40A  
60A  
Inrush Current  
No load Power Consumption  
Input Frequency Range  
300mW  
50Hz  
500mW  
63Hz  
AC input  
47Hz  
ErP Lot 6 Standby Mode Conformity  
(Output Load Capability)  
Input Power= 1W  
300mW  
12Vout  
24Vout  
36Vout  
48Vout  
54Vout  
11.4VDC  
22.8VDC  
34.2VDC  
45.6VDC  
51.3VDC  
12.6VDC  
25.2VDC  
37.8VDC  
50.4VDC  
56.0VDC  
Output Voltage Adjustability (6)  
Minimum Load  
Power Factor  
0%  
115VAC  
230VAC  
0.98  
0.95  
0.99  
0.97  
Start-up Time  
Rise Time  
115/230VAC  
0.5s  
10ms  
230W  
200W  
160W  
130W  
8ms  
10ms  
16ms  
25ms  
Hold-up Time  
115/230VAC  
Output Ripple and Noise(7)  
20MHz BW @ +25°C  
1% of Vout nom. max.  
Notes:  
Note5: The products were submitted for safety files at AC-input operation. For DC-input make sure that sufficient fuses are used  
Note6: By trimming up, decrease output current to avoid exceeding rated output power. By trimming down, do not exceed maximum  
continuous output current. If enclosed version is used, please remove cover, to use trim function.  
Note7: Measurements are made with a 12“ twisted pair-wire terminated with a 0.1µF and 10µF parallel capacitor  
Efficiency vs. Load  
24V to 54V models  
12V model  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
110VAC  
230VAC  
110VAC  
230VAC  
0
10 20 30 40 50 60 70 80 90 100  
0
10 20 30 40 50 60 70 80 90 100  
Output Load [%]  
Output Load [%]  
continued on next page  
REV.: 3/2021  
www.recom-power.com  
PA-2  
RACM230-G  
AC/DC Converter  
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)  
Series  
REGULATIONS  
Parameter  
Condition  
Value  
1.0% typ.  
0.5% typ.  
0.5% typ.  
Output Accuracy  
Line Regulation  
Load Regulation (8)  
low line to high line, full load  
10% to 100% load  
Notes:  
Note8: Operation below 10% load will not harm the converter, but specifications may not be met  
FAN OUTPUT  
Parameter  
Condition  
Min.  
Typ.  
Max.  
Output Current  
@50°C  
continuous  
500mA  
Output Voltage  
12VDC  
Ambient Temperature  
Short Circuit Protection (SCP)  
Over Current Protection (OCP)  
full load  
50°C  
none  
none  
PROTECTIONS  
Parameter  
Type  
line and neutral  
Value  
Internal Input Fuse (9)  
2x T6.3A, slow blow type  
hiccup mode, auto recovery  
105% - 150%, latch off mode  
Short Circuit Protection (SCP)  
Over Voltage Protection (OVP)  
Over Load Protection (OLP)  
Over Voltage Category (OVC)  
Isolation Voltage (safety certified)(10)  
Isolation Resistance  
105% - 200% (150% typ.); hiccup mode auto recovery  
OVCII  
4kVAC  
I/P to O/P  
1 minute  
10Mmin.  
reinforced  
0.3mA max.  
2MOPP  
Insulation Grade  
Leakage Current  
Means of Protection  
250VAC working voltage  
Notes:  
Note9: Refer to local safety regulations if input over-current protection is also required. Recommended fuse: slow blow type  
Note10: For repeat Hi-Pot testing, reduce the time and/or the test voltage  
ENVIRONMENTAL  
Parameter  
Condition  
refer to derating graphs  
Value  
-40°C to +80°C  
0.05%/ꢀ  
Operating Temperature Range  
Temperature Coefficient  
Operating Altitude (11)  
Operating Humidity  
Pollution Degree  
5000m  
non-condensing  
5% - 90% RH max.  
PD2  
+25°C (forced air cooling)  
+50°C (forced air cooling)  
200 x 103 hours  
60 x 103 hours  
according to  
MIL-HDBꢀ-217F, G.B.  
MTBF  
Notes:  
Note11: Recognized by safety agency for safe operation up to 5000m. High altitude operation may impact the performance and lifetime.  
Please contact RECOM tech support for advice.  
continued on next page  
www.recom-power.com  
REV.: 3/2021  
MED-3  
RACM230-G  
AC/DC Converter  
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)  
Series  
Derating Graph  
(@ 2.5m/s airflow + conduction cooling)  
12V model  
others  
240  
220  
200  
240  
220  
200  
180  
160  
140  
120  
100  
80  
230  
207  
186  
180  
167  
160  
150  
140  
120  
100  
80  
60  
60  
100VAC  
115VAC  
240VAC  
100VAC  
115VAC  
240VAC  
50  
45  
40  
20  
0
40  
25  
20  
0
-40 -30 -20 -10  
0
10 20 30 40 50 60 70 80 90  
-40 -30 -20 -10  
0
10 20 30 40 50 60 70 80 90  
45  
Ambient Temperature [°C]  
Ambient Temperature [°C]  
Derating Graph  
(@ natural convection + conduction cooling)  
12V model  
others  
170  
160  
150  
140  
130  
120  
110  
100  
90  
170  
160  
150  
140  
130  
120  
110  
100  
90  
144  
144  
80  
80  
70  
70  
60  
60  
50  
50  
40  
30  
20  
10  
40  
30  
20  
10  
100VAC  
115VAC  
240VAC  
100VAC  
115VAC  
240VAC  
35  
0
0
-40 -30 -20 -10  
0
10 20 30 40 50 60 70 80 90  
25  
-40 -30 -20 -10  
0
10 20 30 40 50 60 70 80 90  
Ambient Temperature [°C]  
Ambient Temperature [°C]  
Derating Graph  
(@ natural convection)  
12V model  
others  
140  
130  
140  
130  
120  
110  
100  
90  
120  
117  
117  
105  
110  
105  
100  
90  
80  
70  
60  
50  
40  
30  
80  
70  
60  
50  
40  
100VAC  
115VAC  
240VAC  
100VAC  
115VAC  
240VAC  
30  
25  
20  
15  
20  
10  
10  
0
0
-40 -30 -20 -10  
0
10 20 30 40 50 60 70 80 90  
-40 -30 -20 -10  
0
10 20 30 40 50 60 70 80 90  
Ambient Temperature [°C]  
Ambient Temperature [°C]  
Convection Cooling:  
<0.1m/s = still air  
0.1 - 0.2m/s = natural convection  
Conduction Cooling:  
ground plane ref.: 2mm alloy; size A4  
www.recom-power.com  
REV.: 3/2021  
MED-4  
RACM230-G  
AC/DC Converter  
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)  
Series  
Peak Load Capability  
Calculation  
Pout [W]  
Pnom = nom. output power  
[W]  
PP = peak output power (230W) [W]  
Pnom x (t1 + t2) - (PP x t1)  
t2 x k  
Pr = recovery output power  
t1 = peak time set (10s max.)  
t2 = recovery time (min. 4 x t1)  
[W]  
[s]  
[s]  
[ ]  
Pp  
Pr =  
k
= safety factor 1.7  
Pnom  
Pr  
Practical Example (RACM230-12SG):  
Take the RACM230-12SG at 230VAC input Voltage and full load at TAMB= 25°C (160W) with  
conduction cooling.  
0
Time [s]  
t1  
t2  
Pnom. = refer to derating graphs (160W)  
PP = 230W  
160 x (1 + 40) - (230 x 1)  
t1 = 1s  
Pr =  
= 93W  
40 x 1.7  
40s  
=
t2  
k
= 1.7  
SAFETY AND CERTIFICATIONS  
Certificate Type (Safety)  
Report Number  
Standard  
Audio/video, information and communication technology equipment - Safety requirements  
Audio/video, information and communication technology equipment - Safety requirements (LVD)  
Audio/video, information and communication technology equipment - Safety requirements (CB)  
Audio/video, information and communication technology equipment - Safety requirements  
Household and similar electrical appliances - Safety - Part 1: General requirements  
IEC62368-1:2014 2nd Edition  
EN62368-1:2014 + A11:2017  
IEC62368-1:2014, 2nd Edition  
EN62368-1:2014 + A11:2017  
EN60335-1:2012 + A13:2017  
SA1903063L01001  
211-700882-000  
SA1903063L01001  
SA0903063L02001  
Measurement methods for electromagnetic fields of household appliances and similar  
apparatus with regard to human exposure  
EN62233:2008  
ANSI/AAMI ES60601-1:2005 + A2:2010/  
(R)2012  
CAN/CSA-C22.2 No. 6060-1:14, 3rd Edition  
IEC60601-1:2005, 3rd Edition + AM1:2012  
EN60601-1:2006 + A1:2013  
E314885  
(“/OF” Version)  
Medical Electric Equipment, General Requirements for Safety and Essential Performance  
Medical Electric Equipment, General Requirements for Safety and Essential Performance (CB)  
Medical Electric Equipment, General Requirements for Safety and Essential Performance  
E314885  
IEC61558-1:2005, 2nd Edition + A1:2009  
EN61558-1:2005 + A1:2009  
Safety of power transformers, power supplies, reactors and similar products -  
Part 1: General requirements and tests  
211-700883-000  
Safety of transformers, reactors, power supply units and similar products for supply  
voltages up to 1100 V - Part 2-16: Particular requirements and tests for switch mode  
power supply units and transformers for switch mode power supply units (CB)  
211-700883-000  
211-700883-000  
IEC61558-2-16:2009, 1st Edition + A1:2013  
Safety of transformers, reactors, power supply units and similar products for supply  
voltages up to 1100 V - Part 2-16: Particular requirements and tests for switch mode  
power supply units and transformers for switch mode power supply units (LVD)  
EN61558-2-16:2009 + A1:2013  
RoHS 2011/65/EU + AM2015/863  
RoHS2  
continued on next page  
REV.: 3/2021  
www.recom-power.com  
MED-5  
RACM230-G  
AC/DC Converter  
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)  
Series  
EMC Compliance  
Electromagnetic compatibility of multimedia equipment - Emission requirements  
Condition  
without external filter  
Standard / Criterion  
EN55032:2015, Class B  
EN55035:2017  
Electromagnetic compatibility of multimedia equipment - Immunity requirements  
Information technology equipment - Immunity characteristics - Limits and methods of  
measurement  
EN55024:2010 + A1:2015  
IEC61000-4-2:2008, Criteria A  
EN61000-4-2:2009, Criteria A  
ESD Electrostatic discharge immunity test  
Air: 8kV; Contact 4kV  
3V/m (80-1000, 1800MHz,  
2600MHz, 3500MHz,  
5000MHz)  
Radiated, radio-frequency, electromagnetic field immunity test  
IEC/EN61000-4-3:2006+A2:2010, Criteria A  
Fast Transient and Burst Immunity  
Surge Immunity  
AC Power Port: L, N 1kV  
IEC/EN61000-4-4:2012, Criteria A  
IEC/EN61000-4-5:2014, Criteria B  
AC Power Port: L-N 1kV  
AC Power Port: 3V (0.15-  
10MHz)  
3V to 1V (10-30MHz)  
1V (30-80MHz)  
IEC61000-4-6:2013. Criteria A  
EN61000-4-6:2014, Criteria A  
Immunity to conducted disturbances, induced by radio-frequency fields  
Power Magnetic Field Immunity  
IEC61000-4-8:2009, Criteria A  
EN61000-4-8:2010, Criteria A  
50Hz/60Hz, 1A/m  
Voltage Dips 100% at  
50/60Hz  
IEC/EN61000-4-11:2004, Criteria A  
Voltage Dips 30% at 50Hz  
IEC/EN61000-4-11:2004, Criteria A  
IEC/EN61000-4-11:2004, Criteria B  
Voltage Dips 30% at 60Hz  
Voltage Interruptions > 95%  
at 50Hz  
Voltage Interruptions > 95%  
at 60Hz  
Voltage Dips and Interruptions  
IEC/EN61000-4-11:2004, Criteria C  
IEC/EN61000-4-11:2004, Criteria B  
Limits of Harmonic Current Emissions  
Limits of Voltage Fluctuations & Flicker  
EN61000-3-2:2014  
EN61000-3-3:2013  
DIMENSION AND PHYSICAL CHARACTERISTICS  
Parameter  
Type  
Value  
PCB  
FR4, (UL94 V-0)  
aluminium  
Material  
baseplate / case (“/ENC”)  
open frame version  
enclosed version  
101.6 x 50.8 x 32.0mm  
105.0 x 62.0 x 35.0mm  
Dimension (LxWxH)  
Weight  
open frame version  
enclosed version  
220g typ.  
290g typ.  
continued on next page  
REV.: 3/2021  
www.recom-power.com  
MED-6  
RACM230-G  
AC/DC Converter  
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)  
Series  
Dimension Drawing Open Frame (mm)  
101.6  
1
2
ꢀꢁꢂꢅ  
9
Top View  
8
7
6
5
4
1
3
Aꢀꢁ  
5.0  
91.6  
Side View  
4 x Ø3.5  
FC 95.25  
FC 3.2  
ꢀeneꢁaꢂ toꢂeꢁanceꢃ accoꢁding to ꢄꢅꢆ ꢇꢈꢉꢊꢋꢌ  
ꢍtaꢎꢂe ꢏoꢁ ꢁeꢏeꢁence onꢂꢐꢑ  
Bottom View  
ꢀiꢁenꢂion ꢃange  
0.5 - 6 ꢁꢁ  
Toleꢃanceꢂ  
0.1 ꢁꢁ  
0.2 ꢁꢁ  
0.3 ꢁꢁ  
0.5 ꢁꢁ  
6 - 30 ꢁꢁ  
30 - 120 ꢁꢁ  
120 - ꢄ00 ꢁꢁ  
AC side  
DC side  
11.62  
5x 3.96  
2x 3.96  
17.45  
Spꢁing Waꢀheꢁ (0.ꢂꢃꢃ)  
Standoff (2.0ꢃꢃ)  
Baꢀeplate  
Application  
ꢀꢁꢂꢅ  
ꢀꢁꢂꢃ  
ꢀꢁꢂꢄ  
Tꢄp. tightening toꢁꢅue= 0.6ꢆꢃ  
Compatible Connector (valid for open frame and enclosed version)  
AC Input (CON1)  
Function Connector  
DC Output Connector (CON2)  
FAN Connector (CON3)  
#
#
Function  
Connector  
#
Function  
Connector  
1
3
AC/N  
AC/L  
Molex 09-50-3031 7,8,9  
or similar 4,5,6  
+Vout  
-Vout  
Molex 09-50-1061  
or similar  
1
2
-FAN  
+FAN  
Molex 22-01-1022  
or similiar  
Maximum tightening torque for mounting without standoffs: 0.3Nm  
FC= fixing centers  
continued on next page  
www.recom-power.com  
REV.: 3/2021  
MED-7  
RACM230-G  
AC/DC Converter  
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)  
Series  
Dimension Drawing Enclosed Version (mm)  
105.0  
9
8
7
6
5
4
1
Top View  
3
Aꢀꢁ  
Side View  
embossed logo  
FC 4.87  
FC 95.25  
2 x Ø3.5  
Bottom View  
Notes:  
AC side  
DC side  
Note12: Please remove cover, to use trim function  
2x 3.96  
23.0  
17.2  
5x 3.96  
Maximum tightening torque for mounting: 0.6Nm  
FC= fixing centers  
ꢀeneꢁaꢂ toꢂeꢁanceꢃ accoꢁding to ꢄꢅꢆ ꢇꢈꢉꢊꢋꢌ  
ꢍtaꢎꢂe ꢏoꢁ ꢁeꢏeꢁence onꢂꢐꢑ  
ꢀiꢁenꢂion ꢃange  
0.5 - 6 ꢁꢁ  
6 - 30 ꢁꢁ  
30 - 120 ꢁꢁ  
120 - ꢄ00 ꢁꢁ  
Toleꢃanceꢂ  
0.1 ꢁꢁ  
0.2 ꢁꢁ  
0.3 ꢁꢁ  
0.5 ꢁꢁ  
ꢀꢁꢂꢅ  
ꢀꢁꢂꢃ  
ꢀꢁꢂꢄ  
www.recom-power.com  
REV.: 3/2021  
MED-8  
RACM230-G  
AC/DC Converter  
Specifications (measured @ Ta= 25°C, rated input, rated load unless otherwise stated)  
Series  
INSTALLATION AND APPLICATION  
Mounting  
vertical  
side 1  
side 2  
horizontal (standard)  
DC  
AC  
airflow  
upside-down  
airflow  
AC  
DC  
Notes:  
Note13: If module is side mounted, vertically or upside-down with natural convection cooling, the power must be derated  
down to 85% for the RACM230-12SG, for the other models 90%.  
For convection cooling, ensure sufficient distance to adjacent components!  
Device should be fan cooled from DC side.  
Block Diagram  
ADJ  
PFC LLC  
Controller  
Feedback  
and Isolation  
Controller  
Rectifier  
L
Fuse, Inrush  
Current Linitation,  
Input Filter  
+Vout  
-Vout  
Rectifier +  
Bulk Cap  
Output  
Filter  
Switcher  
PFC  
Boost  
N
PE  
+Fan  
-Fan  
Rectifier  
Transformer  
PACKAGING INFORMATION  
Parameter  
Type  
Value  
Packaging Dimension (LxWxH)  
cardboard box  
112.0 x 80.0 x 50.0mm  
Packaging Quantity  
1pcs  
Storage Temperature Range  
Storage Humidity  
-55°C to +100°C  
5% - 90% RH max.  
non-condensing  
The product information and specifications may be subject to changes even without prior written notice.The product has been designed for various applications; its suitability lies in the responsibility of each customer. The  
products are not authorized for use in safety-critical applications without RECOMꢀs explicit written consent. A safety-critical application is an application where a failure may reasonably be expected to endanger or cause  
loss of life, inflict bodily harm or damage property. The applicant shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized  
use of RECOM products in such safety-critical applications.  
www.recom-power.com  
REV.: 3/2021  
MED-9  

相关型号:

RACM230-54SG

230 Watt 4” x 2” Open Frame or Enclosed Single Output
RECOM

RACM230-G

230 Watt 4” x 2” Open Frame or Enclosed Single Output
RECOM

RACM30-12SER

30 Watt Round Shape Single Output
RECOM

RACM30-24SER

30 Watt Round Shape Single Output
RECOM

RACM30-ER

30 Watt Round Shape Single Output
RECOM

RACM30-ER-W

30 Watt Wired Round Shape Single Output
RECOM

RACM40

Long 5 Year Warranty
RECOM

RACM40-05S

40 Watt Enclosed & Open Frame Case Style Single Output
RECOM

RACM40-05S-ST

CONV AC/DC 40W 85-264VIN 05VOUT
ETC

RACM40-05S/OF

CONV AC/DC 40W 85-264VIN 05VOUT
ETC

RACM40-05S/OF-ST

CONV AC/DC 40W 85-264VIN 05VOUT
ETC

RACM40-12S

40 Watt Enclosed & Open Frame Case Style Single Output
RECOM