CBJ11A07 [REDLION]

MODEL ITMS - INTELLIGENT TEMPERATURE TO MODBUS CONDITIONER W/ ALARMS;
CBJ11A07
型号: CBJ11A07
厂家: Red Lion Controls. Inc    Red Lion Controls. Inc
描述:

MODEL ITMS - INTELLIGENT TEMPERATURE TO MODBUS CONDITIONER W/ ALARMS

文件: 总28页 (文件大小:1397K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Bulletin No. DLC-J  
Drawing No. LP0495  
Released 09/16  
Tel +1 (717) 767-6511  
Fax +1 (717) 764-0839  
www.redlion.net  
DUAL LOOP CONTROLLER  
MODULAR BUILDING BLOCK FOR MULTI-ZONE PROCESS CONTROL  
TWO INDEPENDENT PID CONTROL LOOPS  
PID CONTROL WITH REDUCED OVERSHOOT  
UNIVERSAL INPUTS ACCEPT TC, RTD, 0-10 V AND 0/4-20 mA SIGNALS  
TWO DC ANALOG OUTPUTS (OPTIONAL)  
WINDOWS® CONFIGURATION SOFTWARE  
RS485 MODBUS™ PROTOCOL  
CHANNEL B CAN BE ASSIGNED AS A SECOND ANALOG INPUT TO  
CHANNEL A FOR REMOTE SETPOINT OPERATION  
SETPOINT CONTROLLER OPTION FOR TIME VS. TEMP./PROCESS  
(RAMP/SOAK) AND SPECIAL BATCH/RECIPE APPLICATIONS  
U
R
C L US LISTED  
3RSD  
SQUARE ROOT EXTRACTION FOR FLOW SENSOR APPLICATIONS  
PROCESS CONTROL EQUIPMENT  
GENERAL DESCRIPTION  
SAFETY SUMMARY  
All safety related regulations, local codes and instructions that appear in the  
manual or on equipment must be observed to ensure personal safety and to  
prevent damage to either the instrument or equipment connected to it. If  
equipment is used in a manner not specified by the manufacturer, the protection  
provided by the equipment may be impaired.  
The Model DLC, Dual Loop Controller, is a full featured, DIN rail mounted,  
dual input PID controller. The DLC is designed as a modular building block for  
multi-zone process control applications. The controller has two independent  
“A” & “B” input channels. Each channel’s input can be configured to accept a  
wide range of thermocouple, RTD, 0-10 V, 0/4-20 mA, or resistive signals. Each  
channel can also be configured to extract the square root of the input in both  
process voltage or process current modes for applications such as flow  
measurement using a differential flow sensor.  
Do not use the controller to directly command motors, valves, or other  
actuators not equipped with safeguards. To do so can be potentially harmful to  
persons or equipment in the event of a fault to the controller. An independent  
and redundant temperature limit indicator with alarm outputs is strongly  
recommended.  
Channel B can be assigned as a Remote Setpoint for Channel A. The two  
time-proportioning or DC Analog outputs can be programmed to control two  
independent processes. The two alarms per channel can be configured for  
various alarm modes, or provide a secondary control output for heat/cool  
applications.  
CAUTION: Risk of Danger.  
Read complete instructions prior to  
installation and operation of the unit.  
The control and alarm outputs are N channel open drain MOSFETs capable  
of switching up to 1 Amp DC. For applications requiring larger loads or A/C  
loads, several DIN rail mount relays are available.  
ALARMS  
The DLC’s two solid-state alarms can be configured independently for  
absolute high or low acting with balanced or unbalanced hysteresis. They can  
also be configured for deviation and band alarm. In these modes, the alarm  
trigger values track the setpoint value. Adjustable alarm trip delays can be used  
for delaying output response. The alarms can be programmed for Automatic or  
Latching operation. Latched alarms must be reset with a serial command. A  
standby feature suppresses the alarm during power-up until the temperature  
stabilizes outside the alarm region. The outputs can also be manually controlled  
with Modbus register or coil commands.  
The controller operates in the PID Control Mode for both heating and  
cooling, with on-demand auto-tune, that establishes the tuning constants. The  
PID tuning constants may be fine-tuned through the serial interface. The  
controller employs a unique overshoot suppression feature, which allows the  
quickest response without excessive overshoot. The controller can be transferred  
to operate in the Manual Mode, providing the operator with direct control of the  
output, or the On/Off Control Mode with adjustable hysteresis.  
The controller’s high density packaging and DIN rail mounting saves time  
and panel space. The controller snaps easily onto standard top hat (T) profile  
DIN rails.  
SETPOINT CONTROLLER OPTION  
The Setpoint Controller option is suitable for time vs. temperature/process  
control applications. The controller allows a profile of up to 20 ramp/soak  
segments. Profile conformity is assured by using the Error Band Mode and  
Error Band parameter. The Profile Cycle Count allows the profile to run  
continuously or a fixed number of cycles. Power-on options automatically stop,  
abort, start, resume, or pause a running profile.  
DIMENSIONS In inches (mm)  
1
2
3
4
5
6
7
8
9
10  
RED LION CONTROLS  
MODEL DLC  
PWR/COMM.  
CH  
CH  
A
OP  
CH  
OUTPUTS  
A
CH  
OUTPUTS  
B
BOTH FLASHING  
=
INPUT ERROR  
ORDERING INFORMATION  
A
ALM  
MODEL NO. DESCRIPTION  
PART NUMBERS  
DLC00001  
DLC01001  
DLC11001  
SFDLC  
FACTORY  
JUMPER  
SETTINGS  
AUTOTUNE  
4.02  
(102)  
Dual Loop Controller  
CH  
B
OP  
BOTH FLASHING  
=
INPUT ERROR  
DLC  
Dual Loop Controller w/ 2 Analog Outputs  
Dual Setpoint Controller w/ 2 Analog Outputs  
PC Configuration Software for Windows  
Programming Interface Cable  
CH  
INPUTS  
B
CH  
INPUTS  
A
CH  
B
ALM  
SF  
CBPRO  
CBJ  
RS485  
MODBUS  
PROTOCOL  
CBPRO007  
CBJ11BD5  
DRRJ11T6  
CBLRLC00  
1
2
3
4
5
6
7
8
9
10 11  
Cable RJ11 to RJ11 (6 inch jumper)  
RJ11 to Terminal Adapter  
DRR  
RS485 to RJ11 Cable  
1.97  
(50)  
4.47 (114)  
See our RSRLYB, RLY6, and RLY7 literature for details on DIN rail  
mountable relays.  
1
7. TEMPERATURE INDICATION ACCURACY: ± (0.3% of span, +1°C).  
Includes NIST conformity, cold junction effect, A/D conversion errors,  
temperature coefficient and linearization conformity at 23 °C after 20 minute  
warm up.  
COMMUNICATIONS  
The RS485 serial communications allows the DLC to be multi-dropped, with  
Baud rates up to 38400. The CBPRO007 programming cable converts the  
RS232 port of a PC to RS485 and is terminated with an RJ11 connector. The  
bi-directional capability of the CBPRO007 allows it to be used as a permanent  
interface cable as well as a programming cable.  
8. PROCESS INPUT:  
ACCURACY *  
(18 to 28°C)  
(10 to 75% RH)  
MAX  
INPUT RANGE  
IMPEDANCE  
CONTINUOUS RESOLUTION  
OVERLOAD  
SOFTWARE  
0.10% of  
reading  
+0.02 V  
0.10% of  
reading  
The DLC is programmed with Windows® based SFDLC software. The  
software allows configuration and storage of DLC program files, as well as  
calibration. Additionally, all setup and control parameters can be interrogated  
and modified through MODBUSregister and coil commands.  
10 VDC  
(-1 to 11)  
1 M  
50 V  
1 mV  
1 µA  
20 mA DC  
(-2 to 22)  
10 Ω  
100 mA  
+0.03 mA  
ANALOG OUTPUT OPTION  
* Accuracies are expressed as ± percentages after 20 minute warm-up.  
9. ISOLATION LEVEL: 500 VAC @ 50/60 Hz, for one minute (50 V  
working) between the following groups:  
Ch A Input  
Ch B Input  
The optional dual DC Analog Output (10 V or 20 mA) can be independently  
configured and scaled for control or re-transmission purposes. These outputs can  
be assigned to separate channels, or both outputs can be assigned to the same  
channel. Programmable output update time reduces valve or actuator activity.  
Control and Alarm Outputs  
RS485/Analog Output 1  
Power Supply  
SPECIFICATIONS  
1. POWER:  
Note:  
18 to 36 VDC, 13 W (4 W if +24 VDC Output excitation is unused)  
24 VAC, ±10% 50/60 Hz, 15 VA(7VAif +24 VDC Output excitation is unused)  
Must use a Class 2 or SELV rated power supply.  
2. +24 VDC OUTPUT POWER: 24 VDC, +15%, -5%, 200 mA max  
3. MEMORY: Non-volatile memory retains all programmable parameters.  
4. INPUT:  
1
RS485 and Analog Outputs are not internally isolated. Their commons  
must not be connected together externally for proper unit function (i.e.,  
earth ground).  
10. SERIAL COMMUNICATIONS:  
Type: RS485; RTU and ASCII MODBUS modes  
Baud: 300, 600, 1200, 2400, 4800, 9600, 19200, and 38400  
Format: 7/8 bits, odd, even, and no parity  
Transmit Delay: Programmable: See Transmit Delay explanation.  
Transmit Enable (TXEN): (primarily for 20 mA loop converter) open  
collector VOH = 10 VDC max, VOL = 0.5 VDC @ 5 mA max current limit  
11. A/D CONVERTER: 16 bit resolution  
12. CONTROL AND ALARM OUTPUTS:  
Type: Non-isolated switched DC, N Channel open drain MOSFET  
Current Rating: 1 A max  
VDS ON: 0.3 V @ 1 A  
VDS MAX: 30 VDC  
Offstate Leakage Current: 0.5 mA max  
13. MAIN CONTROL:  
Control: PID or On/Off  
Sample Time: 100 msec (9.5 Hz)  
Failed Sensor Response: Open or shorted (RTD only) sensor coils  
indication, error code returned in Process Value  
Common Mode Rejection: >110 dB, 50/60 Hz  
Normal Mode Rejection: >40 dB, 50/60 Hz  
Temperature Coefficient: 0.013%/°C  
Overvoltage: 50 VDC max  
Step Response Time: 300 msec typ., 400 msec max  
5. THERMOCOUPLE INPUTS:  
Types: T, E, J, K, R, S, B, N, C, linear mV  
Input Impedance: 20 M  
Lead Resistance Effect: 0.25 µV/Ω  
Cold Junction Compensation: Less than ±1°C typical (±1.5°C max) over  
0 to 50°C ambient temperature range or less than ±1.5°C typical (2°C  
max) over -20 to 65°C maximum ambient temperature range.  
Resolution: 1° or 0.1° for all types except linear mV (0.1 or 0.01 mV)  
Output: Time proportioning or DC Analog  
Cycle Time: Programmable  
Auto-Tune: When selected, sets proportional band, integral time, derivative  
time values, and output dampening time  
Probe Break Action: Programmable  
WIRE COLOR  
MEASUREMENT  
RANGE  
TYPE  
ANSI  
BS 1843  
-200 to +400°C  
-328 to +752°F  
-200 to +750°C  
-328 to +1382°F  
-200 to +760°C  
-328 to +1400°F  
(+) Blue  
(-) Red  
(+) White  
(-) Blue  
14. ALARM: 1 or 2 alarms  
Modes:  
T
E
J
(+) Violet  
(-) Red  
(+) Brown  
(-) Blue  
Manual (through register/coil)  
Absolute High Acting (Balanced or Unbalanced Hysteresis)  
Absolute Low Acting (Balanced or Unbalanced Hysteresis)  
Deviation High Acting  
Deviation Low Acting  
Inside Band Acting  
(+) White  
(-) Red  
(+) Yellow  
(-) Blue  
-200 to +1250°C  
-328 to +2282°F  
0 to +1768°C  
+32 to +3214°F  
0 to +1768°C  
+32 to +3214°F  
+149 to +1820°C  
+300 to +3308°F  
-200 to +1300°C  
-328 to +2372°F  
(+) Yellow  
(-) Red  
(+) Brown  
(-) Blue  
K
R
S
B
N
(+) White  
(-) Blue  
(+) White  
(-) Blue  
No Standard  
No Standard  
No Standard  
Outside Band Acting  
Reset Action: Programmable; automatic or latched  
Standby Mode: Programmable; enable or disable  
Hysteresis: Programmable  
Sensor Fail Response: Upscale  
15. COOLING: Software selectable (overrides Alarm 2).  
Control: PID or On/Off  
No Standard  
(+) Orange  
(-) Red  
(+) Orange  
(-) Blue  
C
0 to +2315°C  
No Standard  
N/A  
No Standard  
N/A  
Output: Time proportioning or DC Analog  
Cycle Time: Programmable  
W5/W6  
+32 to +4199°F  
mV  
-5 mV to 56 mV  
Proportional Gain Adjust: Programmable  
Heat/Cool Deadband Overlap: Programmable  
16. ANALOG DC OUTPUTS: (optional)  
Control or retransmission, programmable update rate from 0.1 sec or  
1 to 250 sec  
6. RTD INPUTS:  
Type: 2 or 3 wire  
Excitation: 150 µA  
Lead Resistance: 15 max  
Resolution: 1 or 0.1° for all types  
Step Response Time: 100 msec  
TYPE  
INPUT TYPE  
RANGE  
ACCURACY *  
(18 to 28°C)  
(10 to 75% RH)  
-200 to +600°C  
-328 to +1100°F  
-200 to +600°C  
-328 to +1100°F  
-80 to +215°C  
-112 to +419°F  
0 to 320 Ω  
OUTPUT  
RANGE**  
RESOLUTION  
(TYPICAL)  
385  
100 platinum, Alpha = .00385  
COMPLIANCE  
392  
100 platinum, Alpha = .003919  
0.10% of FS  
+ 1/2 LSD  
0.10% of FS  
+ 1/2 LSD  
0 to 10 V  
10 Kmin  
500 max  
1/18000  
1/18000  
672  
120 nickel, Alpha = .00672  
0 to 20 mA  
ohms  
Linear Resistance  
2
ACCURACY *  
(18 to 28°C)  
(10 to 75% RH)  
OUTPUT  
RANGE**  
RESOLUTION  
(TYPICAL)  
COMPLIANCE  
0.10% of FS  
+ 1/2 LSD  
4 to 20 mA  
500 max  
1/14400  
* Accuracies are expressed as ± percentages after 20 minute warm-up.  
** Outputs are independently jumper selectable for either 10 V or 20 mA.  
The output range may be field calibrated to yield approximate 10%  
overrange and a small underrange (negative) signal.  
17. ENVIRONMENTAL CONDITIONS:  
Operating Temperature Range: -20 to +65°C  
Storage Temperature Range: -40 to +85°C  
Operating and Storage Humidity: 85% max relative humidity,  
noncondensing, from -20 to +65°C  
Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g  
Shock to IEC 68-2-27: Operational 30 g  
Altitude: Up to 2000 meters  
18. CERTIFICATIONS AND COMPLIANCE:  
CE Approved  
EN 61326-1 Immunity to Industrial Locations  
Emission CISPR 11 Class A  
Safety requirements for electrical equipment for measurement, control, and  
laboratory use:  
EN 61010-1: General Requirements  
EN 61010-2-030: Particular Requirements for Testing and Measuring  
Circuits  
RoHS Compliant  
UL Listed: File #E179259  
IP20 Enclosure rating  
19. CONSTRUCTION: Case body is black high impact plastic. Installation  
Category I, Pollution Degree 2.  
20. CONNECTIONS: Wire clamp screw terminals. Removable terminal blocks.  
21. MOUNTING: Snaps on to standard DIN style top hat (T) profile mounting  
rails according to EN50022 -35 x 7.5 and -35 x 15.  
22. WEIGHT: 10.5 oz. (298 g.)  
BLOCK DIAGRAM  
+24V OUT  
+5V MAIN DIG  
TBA  
TBB  
ISOLATED  
INPUT B  
COMMON  
1
+5V DIG  
+5VC DIG  
+5VC  
-3.6VC  
+5VS DIG  
+5VS  
-3.6VS  
+18V  
5VC  
1
o
C
20M  
INPUT  
POWER  
976K  
POWER  
SUPPLY  
4.99K  
4.02K  
INPUT B  
TC+ / RTD  
A/D  
CONV.  
2
3
C
5VC  
2
5VC  
+13.3V  
-0.6V  
+2.5V  
24VDC  
10 Ω  
INPUT B  
0-10V, 0-20mA  
RTD EXC  
24 VDC  
3
4
D
C
OUTPUT  
COMM.  
24V  
I
OP1  
5
ANNUNCIATORS  
2
ISOLATED  
INPUT A  
COMMON  
24V  
5VS  
4
5
6
S
E
MEMORY  
20M  
I
AL1  
AL2/OP2  
OP1  
6
7
976K  
4.99K  
4.02K  
24V  
INPUT A  
TC+ / RTD  
A/D  
CONV.  
S
5VS  
I
5VS  
24V  
PROCESS  
CIRCUITRY  
10 Ω  
INPUT A  
0-10V, 0-20mA  
RTD EXC  
S
D
I
8
24V  
DIP SWITCHES  
DEFAULT  
SERIAL  
SETTINGS  
7
I
AL1  
9
24V  
ISOLATED  
5V MAIN  
DIG  
D/A  
CONV.  
(PWM)  
V+  
I+  
V-  
I-  
I
AL2/OP2  
10  
+18V  
ANALOG OUT 1 +  
0-10V, 0-20mA  
8
9
O
O
O
I
25.5 Ω  
O
ANALOG OUT 1 -  
5V DIG  
o
5V MAIN  
DIG  
D/A  
CONV.  
(PWM)  
V+  
I+  
V-  
I-  
+18V  
ANALOG OUT 2 +  
0-10V, 0-20mA  
10  
11  
D
B-  
A+  
O
O
5V  
MAIN DIG  
O
RS485  
GND  
TXEN  
25.5 Ω  
O
ANALOG OUT 2 -  
U
U
(DO NOT CONNECT  
O
AND  
U
)
3
effective. The following EMI suppression devices (or equivalent) are  
recommended:  
Fair-Rite part number 0443167251 (Red Lion Controls #FCOR0000)  
Line Filters for input power cables:  
Schaffner # FN2010-1/07 (Red Lion Controls #LFIL0000)  
6. To protect relay contacts that control inductive loads and to minimize radiated  
and conducted noise (EMI), some type of contact protection network is  
normally installed across the load, the contacts or both. The most effective  
location is across the load.  
a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide  
varistor (MOV) across an AC inductive load is very effective at reducing  
EMI and increasing relay contact life.  
b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor  
switch, care must be taken not to exceed the breakdown voltage of the  
transistor when the load is switched. One of the most effective ways is to  
place a diode across the inductive load. Most Red Lion products with solid  
state outputs have internal zener diode protection. However external diode  
protection at the load is always a good design practice to limit EMI.  
Although the use of a snubber or varistor could be used.  
EMC INSTALLATION GUIDELINES  
Although Red Lion Controls products are designed with a high degree of  
immunity to Electromagnetic Interference (EMI), proper installation and wiring  
methods must be followed to ensure compatibility in each application. The type  
of the electrical noise, source or coupling method into a unit may be different  
for various installations. Cable length, routing, and shield termination are very  
important and can mean the difference between a successful or troublesome  
installation. Listed are some EMI guidelines for a successful installation in an  
industrial environment.  
1. A unit should be mounted in a metal enclosure, which is properly connected  
to protective earth.  
2. Use shielded cables for all Signal and Control inputs. The shield connection  
should be made as short as possible. The connection point for the shield  
depends somewhat upon the application. Listed below are the recommended  
methods of connecting the shield, in order of their effectiveness.  
a. Connect the shield to earth ground (protective earth) at one end where the  
unit is mounted.  
b. Connect the shield to earth ground at both ends of the cable, usually when  
the noise source frequency is over 1 MHz.  
Red Lion part numbers: Snubber: SNUB0000  
3. Never run Signal or Control cables in the same conduit or raceway with AC  
power lines, conductors, feeding motors, solenoids, SCR controls, and  
heaters, etc. The cables should be run through metal conduit that is properly  
grounded. This is especially useful in applications where cable runs are long  
and portable two-way radios are used in close proximity or if the installation  
is near a commercial radio transmitter. Also, Signal or Control cables within  
an enclosure should be routed as far away as possible from contactors,  
control relays, transformers, and other noisy components.  
Varistor: ILS11500 or ILS23000  
7. Care should be taken when connecting input and output devices to the  
instrument. When a separate input and output common is provided, they  
should not be mixed. Therefore a sensor common should NOT be connected  
to an output common. This would cause EMI on the sensitive input common,  
which could affect the instrument’s operation.  
Visit http://www.redlion.net/emi for more information on EMI guidelines,  
Safety and CE issues as they relate to Red Lion products.  
4. Long cable runs are more susceptible to EMI pickup than short cable runs.  
5. In extremely high EMI environments, the use of external EMI suppression  
devices such as Ferrite Suppression Cores for signal and control cables is  
STEP 1 SETTING THE JUMPERS AND DIP SWITCHES  
The jumpers are accessible from the bottom of the controller. Needle-nose  
pliers are needed to remove the jumpers. They should be set prior to installation.  
ANALOG DC OUTPUTS (OPTIONAL)  
To insure proper operation, the jumpers must match the controller software  
configuration.  
I2-  
Analog  
Output 2  
Jumpers  
Analog Output 1 and Analog Output  
2 can be configured for voltage (V) or  
current (I), independent of each other.  
Both V/I + and V/I - jumpers of the  
V2+  
I2-  
V2+  
I1-  
Analog Output 2  
same channel must be set for the same  
Analog  
Output 1  
Jumpers  
Jumpers (current)  
type of output signal.  
V1+  
Analog Output 1  
Jumpers (current)  
I1-  
V1+  
INPUTS  
Channel A and Channel B can be  
configured independent of each other.  
Jumper position can be ignored for  
thermocouple and millivolt inputs.  
10V  
Channel A  
Input  
20mA  
RTD  
Channel A  
Input Jumpers  
10V  
20mA  
RTD  
(RTD)  
Channel B  
Input Jumpers  
Channel B  
Input  
(As set from factory)  
SERIAL DIP SWITCH SETTINGS  
The DLC Serial Communications Settings can be set via DIP Switches or  
through the serial communications port (software selectable). The software  
selectable serial settings method using the serial communications port must be  
set using “RLCPRO” or another software program to write to the DLC Modbus  
registers (40401-40407). When using the DIP switches to configure the serial  
settings, the Modbus mode is limited to “RTU” mode only.  
M 2 8 0 2 X  
X
M 2 8 0 2  
4
SWA  
SWB  
SWITCH  
POSITION  
SWITCH POSITION / (BIT WEIGHT)  
SWITCH POSITION  
DEFAULT SERIAL  
SETTINGS  
BAUD RATE  
UNIT ADDRESS  
1
2
(64)  
3
4
5
6
7
8
4
5
6
1
(128)  
(32)  
(16)  
(8)  
(4)  
(2)  
(1)  
300  
600  
DN  
DN  
DN  
DN  
UP  
UP  
UP  
UP  
DN DN  
DN UP  
UP DN  
UP UP  
DN DN  
DN UP  
UP DN  
UP UP  
Software Selectable  
Serial Settings  
Use DIP Switch or  
Software Serial Settings  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
UP  
1200  
2400  
4800  
9600  
19200  
38400  
1
2
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
DN  
UP  
DN  
DN  
DN  
UP  
UP  
UP  
UP  
DN  
DN  
UP  
UP  
DN  
DN  
UP  
UP  
DN  
UP  
DN  
UP  
DN  
UP  
DN  
UP  
DN  
Use Default Serial  
Settings  
3
4
SWITCH POSITION  
PARITY  
5
2
3
6
None  
None  
Even  
Odd  
DN  
DN  
UP  
UP  
DN  
UP  
DN  
UP  
Serial Communication Defaults:  
7
Protocol: RTU  
Address: 247  
Baud Rate:9600  
Stop Bit: 1  
8
Parity:  
none  
247*  
Start Bit  
1
UP  
UP  
UP  
UP  
DN  
UP  
UP  
UP  
*- Unit will use address 247 for binary switch settings above 247  
STEP 2 INSTALLING THE CONTROLLER  
INSTALLATION  
The controller is designed for attachment to standard DIN style top hat (T)  
profile mounting rails according to EN50022 -35 x 7.5 and -35 x 15. The  
controller should be installed in a location that does not exceed the maximum  
operating temperature and provides good air circulation. Placing the controller  
near devices that generate excessive heat should be avoided.  
T Rail Installation  
To install the DLC on a “T” style rail, angle the controller so that the top  
groove of the mounting recess is located over the lip of the top rail. Push the  
controller toward the rail until it snaps into place. To remove a controller from  
the rail, insert a screwdriver into the slot on the bottom of the controller, and  
pry upwards until it releases from the rail.  
STEP 3 IDENTIFYING THE LEDs - LED FUNCTIONALITY  
On power-up, all LEDs are turned on briefly in an alternating pattern to allow visual check of LED functionality.  
CONDITION  
PRIORITY  
PWR/COMM  
On  
CH A OP  
-------  
-------  
On  
CH A ALM  
-------  
AUTOTUNE  
-------  
CH B OP  
-------  
CH B ALM  
-------  
Power Applied  
1
1
4
4
4
4
4
4
5
5
3
3
3
3
2
1
Communicating  
Flashing  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
OP1 On (Channel A) **  
OP1 On (Channel B) **  
AL1 On (Channel A) *  
AL1 On (Channel B) *  
AL2 On (Channel A) *  
AL2 On (Channel B) *  
OP2 On [Cool](Channel A)  
OP2 On [Cool](Channel B)  
Auto-Tune On (Channel A)  
Auto-Tune On (Channel B)  
Input Error (Channel A)  
Input Error (Channel B)  
Calibration Mode  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
-------  
On  
-------  
On  
-------  
-------  
-------  
-------  
-------  
-------  
On  
Fast Flashing  
-------  
-------  
-------  
-------  
-------  
Fast Flashing  
-------  
-------  
-------  
Fast Flashing  
-------  
-------  
-------  
-------  
-------  
-------  
Fast Flashing  
-------  
-------  
-------  
-------  
On  
-------  
-------  
-------  
Fast Flashing  
-------  
-------  
-------  
Slow Flashing Slow Flashing  
-------  
-------  
-------  
On  
-------  
On  
-------  
Slow Flashing Slow Flashing  
On On  
On  
Checksum Error  
Slow Flashing Slow Flashing Slow Flashing Slow Flashing Slow Flashing  
* If AL1 & AL2 outputs are on at the same time, the ALM annunciator will alternate between On and Fast Flashing every ½ second.  
** If OP1 and AL2/OP2 (configured for cool) outputs are on at the same time, the annunciator will only show the OP1 state. The OP2 state is only shown when OP1 is off.  
5
STEP 4 WIRING THE CONTROLLER  
WIRING CONNECTIONS  
All conductors should meet voltage and current ratings for each terminal. Also, cabling should conform to appropriate standards of good installation, local codes  
and regulations. When wiring the controller, use the numbers on the label to identify the position number with the proper function. Strip the wire, leaving  
approximately 1/4" (6 mm) of bare wire exposed. Insert the wire into the terminal, and tighten the screw until the wire is clamped tightly. (Pull wire to verify  
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm), two #18 AWG (1.02 mm), or four #20 AWG (0.61 mm) wires.  
24 VAC POWER  
18 to 36 VDC POWER  
CONTROLLER POWER CONNECTIONS  
For best results, the power should be relatively “clean” and within the  
specified limits. Drawing power from heavily loaded circuits or from circuits  
that also power loads that cycle on and off should be avoided. It is recommended  
that power supplied to the controller be protected by a fuse or circuit breaker.  
(AC)  
DC-  
~
~
-
+
(AC)  
DC+  
TBA  
TBA  
INPUT CONNECTIONS  
Thermocouple and Millivolt  
0-10V, 0-20mA  
Voltage or Current  
RTD and Resistance *  
0-10V, 0-20mA  
0-10V, 0-20mA  
Exc./  
DC+  
DC-  
RTD EXC.  
RTD EXC.  
RTD EXC.  
Jumper  
Sense  
Sense  
TC+ OR RTD  
TC+ OR RTD  
TC+  
TC-  
TC+ OR RTD  
INPUT COMMON  
INPUT COMMON  
INPUT COMMON  
CH A = Terminals 4, 5 & 6  
CH B = Terminals 1, 2 & 3  
CH A = Terminals 4, 5 & 6  
CH B = Terminals 1, 2 & 3  
CH A = Terminals 4, 5 & 6  
CH B = Terminals 1, 2 & 3  
TBB  
TBB  
TBB  
3 Wire Current or Voltage Signal Requiring DLC Excitation **  
2 Wire Current Signal Requiring DLC Excitation **  
0-10V, 0-20mA  
-
0-10V, 0-20mA  
RTD EXC.  
Out  
RTD EXC.  
+
TC+ OR RTD  
Vs  
TC+ OR RTD  
Comm  
+24VDC OUT  
(200 mA max)  
+24VDC OUT  
(200 mA max)  
INPUT COMMON  
INPUT COMMON  
TBA  
TBB  
TBA  
TBB  
CH A = Terminals 4, 5 & 6  
CH B = Terminals 1, 2 & 3  
CH A = Terminals 4, 5 & 6  
CH B = Terminals 1, 2 & 3  
* For two wire RTDs, install a copper sense lead of the same gauge and length as the RTD leads. Attach one end of the wire at the probe and the other end to input  
common terminal. Complete lead wire compensation is obtained. This is the preferred method. If a sense wire is not used, then use a jumper. A temperature offset  
error will exist. The error may be compensated by programming a temperature offset.  
** +24 VDC OUT (Terminal 3) shares common with Ch A Inputs & All Control/Alarm Outputs.  
CONTROL AND ALARM OUTPUT CONNECTIONS  
Load Power from DLC  
External Controller Power  
Separate External Power  
For Load and Controller  
Combined External Power  
For Load and Controller  
+
+
+
-
+
+
+
-
+
+
+
-
Load  
Load  
Load  
AL2/OP2  
AL1  
Load  
Load  
Load  
Load  
Load  
Load  
AL2/OP2  
AL1  
AL2/OP2  
AL1  
-
-
-
-
-
-
OP1  
+
-
OP1  
OP1  
OUTPUT COMMON  
OUTPUT COMMON  
+24VDC OUT  
OUTPUT COMMON  
+24VDC OUT  
+24VDC OUT  
(200 mA max)  
DC- / (AC)  
DC- / (AC)  
DC- / (AC)  
-
+
-
+
-
+
DC+ / (AC)  
DC+ / (AC)  
DC+ / (AC)  
TBA  
TBA  
TBA  
CH A = Terminals 5, 6, & 7  
CH B = Terminals 8, 9, & 10  
CH A = Terminals 5, 6, & 7  
CH B = Terminals 8, 9, & 10  
CH A = Terminals 5, 6, & 7  
CH B = Terminals 8, 9, & 10  
6
ANALOG DC OUTPUT CONNECTIONS  
DEFAULT SERIAL SETTING CONNECTIONS  
-
OUT -  
If using software selectable serial  
TBB  
settings and the serial settings are  
unknown or forgotten, they can be  
temporarily reset to the defaults by  
connecting the “Default Serial  
DEFAULT SERIAL  
SETTING  
ANALOG OUTPUT  
0-10V, 0(4)-20mA  
Controller,  
+
Recorder  
OUT +  
OUTPUT COMMON  
Setting” terminal  
7 to “Output  
TBB  
Output 1 = Terminals 8 & 9  
Output 2 = Terminals 10 & 11  
Common” terminal 4 with a jumper.  
TBA  
Defaults:  
Protocol: RTU  
Data Bits: 8  
Note: Analog Outputs & RS485 are not internally isolated and must not  
share the same common (i.e., earth ground).  
Address: 247  
Baud Rate: 9600  
Parity:  
none  
RS485 SERIAL CONNECTIONS  
There are two modular connectors located on the front for paralleling  
communications. The CBPRO007 programming cable converts the RS232 port  
of a PC to RS485 and is terminated with an RJ11 connector. The bi-directional  
capability of the CBPRO007 allows it to be used as a permanent interface cable  
as well as a programming cable.  
STEP 5 INSTALLING SFDLC (Software for DLC)  
After downloading RLCPro for DLC Series (http://www.redlion.net/  
SFDLC) open the ZIP archive and then run dlc207.exe to install the  
software.  
STEP 6 PROGRAMMING - Getting Started  
You will be prompted to  
select the proper device,  
Run RLCPro by double-clicking the icon, or use the start menu.  
and then the model.  
Use the FILE pull-down menu  
to select a NEW file.  
7
STEP 7 PROGRAMMING THE PID SETTINGS  
Note: The register numbers correspond to (Channel A/Channel B).Channel B PID control is not functional  
when the input is assigned as a Remote Setpoint.  
The Auto-Tune procedure of the controller sets the Proportional Band, Integral Time, Derivative Time,  
Digital Filter, Control Ouput Dampening Time, and Relative Gain (Heat/Cool) values appropriate to the  
characteristics of the process.  
Proportional Band (40007/40023): Proportional band, entered as percent of full input range, is the band from  
the setpoint where the controller adjusts the percent output power based on how close the process value is  
to the setpoint. For temperature inputs, the input range is fixed per the entered thermocouple or RTD type.  
For process inputs, the input range is the difference between the entered Process Low Scaling Value and the  
Process High Scaling Value. The proportional band should be set to obtain the best response to a process  
disturbance while minimizing overshoot. A proportional band of 0.0% forces the controller into On/Off  
Control with its characteristic cycling at setpoint.  
Integral Time (40008/40024): Integral time is defined as the time, in seconds, it takes the output power due to integral action alone to equal  
the output power due to proportional action alone during a constant process error. As long as the error exists, integral action repeats the  
proportional action each integral time. Integral action shifts the center point position of the proportional band to eliminate error in the  
steady state. The higher the integral time, the slower the response. The optimal integral time is best determined during PID Tuning. If time  
is set to zero, the previous Integral output power value is maintained. Offset Power can be used to provide Manual Reset. Integral Action  
can be disabled by writing a ‘1’ to the Disable Intergral Action register (40044/40052).  
Derivative Time (40009/40025): Derivative time, entered as seconds per repeat, is the time that the controller looks ahead at the ramping  
error to see what the proportional contribution will be and it matches that value every Derivative time. As long as the ramping error exists,  
the Derivative action is repeated by Proportional action every derivative time. Increasing the derivative time helps to stabilize the response,  
but too high of a derivative time, coupled with noisy signal processes, may cause the output to fluctuate too greatly, yielding poor control.  
Setting the time to zero disables Derivative Action.  
Control Mode (40041/40049): In Automatic Mode, the percentage of Output Power is automatically determined by PID or On/Off Control.  
In Manual Mode, the percentage of Output Power is entered manually. For more information, see Control Mode Explanations Section.  
Output Power (40005/40021): This parameter can only be changed by direct entry in Manual Mode. For more details on this parameter, see  
the Control Mode Explanations Section.  
Offset Power (Manual Reset) (40010/40026): If the Integral Time is set to zero (Automatic Reset is off), it may be necessary to modify the  
output power to eliminate errors in the steady state. The offset power is used to shift the proportional band to compensate for errors in the  
steady state. If Integral Action is later invoked, the controller will re-calculate the internal integral value to provide “bumpless” transfer.  
Auto-Tune Code (40013/40029): Prior to starting Auto-Tune, this code should be set to achieve the necessary dampening level under PID  
Control. When set to zero, it yields the fastest process response with possible overshoot. A setting of 2 yields the slowest response with  
the least amount of overshoot. If the Auto-Tune Code is changed, Auto-Tune needs to be reinitiated for the changes to affect the PID  
settings. Auto-tune is initiated by writing a ‘1’ to the Auto-Tune start register (40011/40027). The Auto-Tune phase will be shown in  
register (40012/40028). For more information, see PID Tuning Explanations Section.  
STEP 8 PROGRAMMING THE INPUT SETUP  
Input Type (40101/40201): Select the proper input type from the pull down menu. Make sure the input  
jumpers are set to match the input signal selection.  
Scale (40102/40202): Select either degrees Fahrenheit or Celsius. For mV, resistance, voltage or current types,  
this has no effect. If changed, check all temperature related values, as the DLC does not automatically  
convert these values.  
Resolution (40103/40203): For all temperature and ohms Input Types low (x1) resolution selects whole units  
of measure. In these same modes, high (x10) resolution selects tenth of units of measure. For mV mode, low  
selects tenths of mV and high selects hundredths of mV. If changed, be sure to check all parameters because  
the controller does not automatically convert related parameter values. For voltage or current types, this has  
no effect.  
Rounding (40104/40204): Rounding selections other than 1 cause the process value to round to the nearest  
rounding increment selected. (For example, rounding of 5 causes 122 to round to 120 and 123 to round to  
125.) Rounding starts at the least significant digit of the process value. If the signal is inherently jittery, the  
process value may be rounded to a value higher than 1. If the range of the signal exceeds the required  
resolution (for example, 0-1000 psi, but only 10 psi resolution is required), a rounding increment of 10 will  
effectively make the reading more stable.  
Digital Filtering (40105/40205): The filter is an adaptive digital filter that discriminates between measurement  
noise and actual process changes. If the signal is varying too greatly due to measurement noise, increase the  
filter value. If the fastest controller response is needed, decrease the filter value.  
Span Correction (40106/40206): This value is the correction slope. A span of 1.0000 applies no correction.  
Span only applies to temperature sensor, millivolt, and ohms inputs.  
Offset Correction (40107/40207): This value offsets the temperature value by the entered amount. Offset only  
applies to temperature sensor, millivolt, and ohms inputs  
Channel B Assignment (40198): This is used to configure Channel B to operate as a Remote Setpoint to  
Channel A. Channel B PID control is not functional when the input is assigned as a Remote Setpoint.  
8
Local/Remote Setpoint Transfer Mode (40199): When cycling from/to Local or Remote Setpoint (register 40046), the response of the controller can be  
programmed to act in a variety of ways. The table summarizes the responses for Setpoint transfer options.  
LOCAL/REMOTE SETPOINT  
TRANSFER MODE  
LOCAL TO REMOTE  
REMOTE TO LOCAL  
0 - Normal  
1 - Auto  
Output may bump.  
No output bump. Process error eliminated  
Output may bump.  
No output bump. Process error  
at rate of integral action. Ramping disabled eliminated at rate of integral action.  
during transfer.  
Ramping disabled during transfer.  
2 - Track  
Output may bump.  
Local Setpoint (40002) assumes value  
of Remote Setpoint (tracks). No  
output bump.  
Note: In situations where an output bump may occur, the Setpoint ramp function can be used to reduce or eliminate bumping when switching Setpoint modes.  
The setpoint ramp feature ramps the setpoint from the old setpoint to the new Setpoint.  
Remote Setpoint Ratio Multiplier (40206): This value is used for channel B when it is assigned as a Remote Setpoint Input. The Ratio Multiplier applies to  
all input types (0-15).  
Remote Setpoint Bias Offset (40207): This value is used for channel B when it is assigned as a Remote Setpoint Input.  
Scaling Points (40111-40114/40211-40214): Low and high scaling points are necessary to scale the controller for process voltage and current inputs. Each scaling  
point has a coordinate pair of input and process value entries. The process value will be linear between and continue past the entries up to the limit of the input  
range. Reverse acting measurement can be accomplished by reversing the Input or Process entries, but not both. (Do not reverse the input wires to change the  
action.) To scale a 4-20 mA Input signal to provide process values of 0 to 100.00 (% in hundredths), the Input Low (40113/40213) and Input High (40114/40214)  
values would be 4000 and 20000 (0.001 mA resolution), and the Process Low (40111/40211) and Process High (40112/40212) values would be 0 and 10000.  
Process Decimal Point (Dec Pt) (40115/40215): The decimal point position is used to enable SFDLC display in desired engineering units for voltage and current  
Process values. It is not used internally by the DLC.  
STEP 9 PROGRAMMING THE SETPOINTS  
Setpoint (40002/40018): Enter the setpoint value. Deviation of Process Value (40001/40017) from  
setpoint value can be viewed in the Setpoint Deviation register (40006/40022).  
Low Limit (40108/40208); High Limit (40109/40209): The controller has programmable high and low  
setpoint limit values to restrict the setting range of the setpoint. Set the limits so that the setpoint value  
cannot be set outside the safe operating area of the process.  
Ramp Rate (40110/40210): The setpoint ramp rate can reduce sudden shock to the process and reduce  
overshoot on startup or after setpoint changes, by ramping the setpoint at a controlled rate. The ramp  
rate is 0.1° for input types 0-11, 0.1 for input type 12, 0.01 for input type 13, and 0.1 unit for input  
types 14-15 per minute. Writing a ‘0’ disables setpoint ramping. The Disable Setpoint Ramping register  
(40042/40050) can also be used to disable ramping. The Setpoint Ramping In-Process register  
(40043/40051) will be a ‘1’ during setpoint ramping. While ramping is enabled, the Ramping Setpoint  
can be viewed in register (40045/40053). The Ramp Rate for CHB is not functional when it is assigned  
as a Remote Setpoint Input.  
Once the ramping setpoint reaches the target setpoint, the setpoint ramp rate disengages until the setpoint is changed again. If the ramp value is changed  
during ramping, the new ramp rate takes effect. If the setpoint is ramping prior to starting Auto-Tune, the ramping is suspended during Auto-Tune and then  
resumed afterward using the present Process value as a starting value. Deviation and band alarms are relative to the target setpoint, not the ramping setpoint. A  
slow process may not track the programmed setpoint rate. At power-up, the ramping setpoint is initialized to the starting process value.  
Remote/Local Setpoint Select (40046): Channel A setpoint mode can be switched between Local Setpoint operation and Remote Setpoint operation. The  
Channel B input must be assigned as a remote setpoint (register 40198).  
STEP 10 PROGRAMMING PROFILE SETUP (Optional)  
Profile Power Cycle Mode (40321/40421): Upon controller power-on several profile operating modes  
exist.  
Stop: If the Profile was running when powered down, upon power-up, "Stop" places the profile into the  
stop or off mode, regardless of the mode prior to the power-down. The active Setpoint is the setpoint  
of the last segment that ran before power-down.  
Abort: If the Profile status was running, paused, or in Error Delay when powered down, upon power-up,  
"Abort" will place the controller in manual mode at 0% Output Power. The Setpoint and Ramp Rate  
are the values they were prior to running the profile. If the Setpoint Controller was 'paused,' they will  
be set to the values that they were at power-down.  
Start: The Start power cycle mode causes the controller to automatically start the profile at Power-up.  
This will occur if the unit was in manual or automatic control mode. During maintenance or at other  
times when this action is not desired, the Profile Power Cycle mode should be changed appropriately.  
Resume: At Power-up, Resume causes the profile to continue from the point and phase when power was  
removed. If the unit was in ramp phase, the ramping setpoint will start ramping from the initial  
process value at power-up.  
Pause: Upon Power-up, the controller pauses and maintains control at the initial process value (on  
power-up), at the phase where the controller was powered down. The user can then determine how to  
proceed based on the process that is being controlled.  
9
Profile Error Band Mode (Guaranteed Soak) (40322/40422): Profile conformity can be assured by using the profile Error Band Mode and Error Band  
parameter. If the process value deviates outside the error band value while a profile is running, the controller enters the delay mode. In the delay mode,  
the profile phase timer is held (delayed) until the process value is within the deviation error band value - the Error band hysteresis value. At this time, the  
profile continues running unless the process value again deviates. These actions assure that the actual process value conforms to the profile.  
Disable Error Band: Error band operation is disabled.  
Ramp Phase Only Error Band: The Profile Error Band only applies to the ramp phases of the running profile.  
Hold Phase Only Error Band: The Profile Error Band only applies to hold phases of the running profile.  
Ramp & Hold Phase Error Band: The Profile Error Band applies to both ramp and hold phases of the running profile.  
Profile Error Band (40323/40423): During a hold phase, the profile is paused when the process error is >= the Profile Error Band. The profile will remain  
paused until the process error (deviation) is within the Profile Error Band (Error Band-Error Band Hysteresis).  
Profile Error Band Hysteresis (40324/40424): Controls the process value at which the profile will come out of an error band delay. If in error band delay,  
the profile phase timer is held (delayed) until the process value is within the deviation error band value - the Error band hysteresis value.  
Profile End Segment (40325/40425): The Profile End Segment indicates the last segment (i.e., the number of segments to be used in a profile) that is to be  
ran in the profile before it stops or re-starts (dependent on Profile Cycle Count/Profile Cycle Count remaining).  
Profile Cycle Count (40326/40426): Once a profile is started, it runs the number of cycles programmed in this register and then automatically defaults to  
the Profile End Control Mode. If this parameter is changed while the profile is active, the new value (if less than 250) will not take effect until the profile  
is stopped and re-started. If the Profile Cycle Count is set to 250 (continuous profile cycling), the change will take affect immediately.  
Profile End Control Mode (40327/40427): This parameter sets the type of control action that will be used when the number of profile cycles as programmed  
in the Profile Cycle Count parameter has run to completion.  
Control Outputs Off : Control is turned off by putting the controller in manual mode at 0% Power. Control can be resumed by changing the Control  
Mode (40041/40049) to Automatic.  
Automatic: When configured for Automatic the controller will continue controlling at the last setpoint value.  
Setpoint Controller Setpoint Segment Registers 1-20 (40601-40620[ChA]/40701-  
40720[ChB]): The setpoints for the profile are written in these registers. The values are limited  
by the Setpoint Lo and Setpoint Hi limits registers. Register (40601/40701) is the Setpoint for  
the 1st segment of the profile.  
Setpoint Controller Ramp Rate Segment Registers 1-20 (40621-40640[ChA]/40721-  
40740[ChB]): The Ramp Rates for the profile are written in these registers. Register  
(40621/40721) is the Ramp Rate for the 1st segment of the profile. A ramp rate of 0 disables  
setpoint ramping.  
Setpoint Controller Hold Time Segment Registers 1-20 (40641-40660[ChA]/40741-  
40760[ChB]): The Hold Times for the profile are written in these registers. Register  
(40641/40741) is the Hold Time for the 1st segment of the profile. Segment Hold times of 0  
can be used to achieve a ramp with multiple slopes.  
STEP 11 MONITORING PROFILE OPERATION (Optional)  
Profile Operating Status/Mode (40065/40073)  
Stop/Off: The Stop/Off status indicates the profile is dormant or off. A profile can be stopped by setting this register to 0, by allowing a profile to run to  
completion, or by removing and re-applying power when the Power Cycle Mode is configured for stop. If the profile was terminated during a ramp  
phase, the unit will continue to ramp to the active setpoint.  
Abort: Abort is a command action that can be used quickly to stop the profile and turn off the control outputs. The controller is placed into manual mode  
at 0% output power. Following the abort command the Profile Operating Status will go to 0 (Stop/Off).  
Run/Start: The profile is in the run mode when it is executing. While running, the profile can be stopped (0), paused (3), or advanced to the next phase.  
A profile can be started and placed into the Run mode automatically when the controller is powered-up (see Profile Power Cycle Mode). If the profile  
was previously stopped, when it is placed in to the Run/Start mode (2), the controller will be put into automatic control (if it was in manual) and start  
the profile at the first segment. If the controller was in manual mode prior to starting the profile, the controller will start ramping from the current  
process value. If the profile was "paused," it will resume operation. The advancement of the profile can be viewed in the Profile Phase (40066/40074)  
and Profile Segment register (40067/40075).  
10  
Pause: Pause signifies that a profile is active but the time base (Profile Phase Timer) is paused. The pause mode can only be invoked by writing a  
3 in the Profile Operating Status register. Pausing a profile during a ramp phase pauses the ramp and the controller maintains control at the  
ramping setpoint value (40045/40053) at the instant of the pause action. The use of pause, effectively lengthens the total run time of a profile.  
The unit will remain in pause mode until it is placed back in the run mode by writing a 2 (Run/Start) into the Profile Operating Status Register.  
Error Delay (Guaranteed Soak): The Error Delay Setting is used only as a status indication. It indicates that a profile is active but the phase timer  
or profile advancement has stopped. This is caused by automatic action of the controller when the process deviates more than a specified amount  
from the active profile segment. The Error Delay is similar to pause, except the error delay status can only be invoked automatically. See "Profile  
Error Band Mode (40322/40422)." Do not write a "4 - Error Delay," to the Profile Operating Status Register. Doing so will instead put the  
controller in pause mode (3).  
Profile Phase (40066/40074): When the profile is active, this register indicates whether the controller is in a ramp (0) or hold (1) phase.  
Profile Segment (40067/40075): Indicates the current active segment while the profile is running. A zero indicates that the profile is stopped or off.  
Profile Phase Timer (40068/40076): This register shows the remaining segment phase time in 10ths of minutes. The remaining phase time can be  
changed "on the fly" to accelerate or decelerate the phase time. The change in phase time will only affect the running profile and not the stored  
parameters. If the phase time is changed during the ramp phase, a new ramp rate will be calculated which will achieve the desired phase time. The  
Profile Phase Timer will stop while the unit is paused or during an error delay caused by Profile Error Band operation (guaranteed soak).  
Profile Cycle Count Remaining (40069/40077): Indicates the number of profile cycles that are yet to be run. If the Profile Cycle Count register  
(40326/40426) is set to 250, the Profile Cycle Count Remaining Register will run continuously, resetting to "250" when reaching "0". This register  
value can be changed, however, it will only affect the current run cycle. When the profile is stopped and re-started, the Profile Cycle Count  
Remaining Register will be reloaded based on the "Profile Cycle Count (40326/40426)" value.  
Advance Profile Phase (40070/40078): Writing a "1" to this register while the profile is running will cause the controller to advance immediately to  
the beginning of the next ramp or hold phase. Using the advance operation shortens the total run time of the profile. If the profile is "paused," the  
profile will advance but the profile will remain paused. The Profile can also be advanced while in the error delay mode.  
STEP 12 PROGRAMMING THE OUTPUTS  
Cycle Time (40116/40216): The cycle time, entered in seconds, is the combined time of an on and off  
cycle of a time proportioning control output OP1/OP2. With time proportional output, the percentage  
of control power is converted into output on time of the cycle time value. (If the controller calculates  
that 65% power is required and has a cycle time of 10 seconds, the output will be on for 6.5 seconds  
and off for 3.5 seconds.) For best control, a cycle time equal to one-tenth of the process time constant,  
or less, is recommended. When using the DC Analog output signal for control, a setting of zero will  
keep output OP1 off. The status of OP1 can be read through registers 40014/40030.  
Control Action (40117/40217): This determines the control action for the PID loop. Programmed for  
direct action (cooling), the DLC output power will increase if the Process value is above the Setpoint  
value. Programmed for reverse action (heating), the output power decreases when the Process Value is  
above the Setpoint Value. For heat and cool applications, this is typically set to reverse. This allows  
OP1 to be used for heating, and AL2/OP2 to be used for cooling.  
Power Low Limit (40118/40218); High Limit (40119/40219): These parameters may be used to limit controller power due to process disturbances  
or setpoint changes. Enter the safe output power limits for the process. If Alarm 2 is selected for cooling, the range is from -100 to +100%. At 0%,  
both OP1 and OP2 are off; at 100%, OP1 is on; and at -100%, OP2 is on. When the controller is in Manual Control Mode, these limits do not apply.  
Sensor Fail Power Preset (40120/40220): This parameter sets the power level for the control outputs in the event of a sensor failure or extreme  
overdriven/underdriven input. If Alarm 2 is not selected for cooling, the range is from 0% (OP1 output full off) to 100% (OP1 output full on). If  
AL2 is selected for cooling, the range is from -100 to +100%. At 0%, both OP1 and OP2 are off; at 100%, OP1 is on; and at -100%, OP2 is on. The  
alarm outputs are upscale drive with an open sensor, and downscale drive with a shorted sensor (RTD only), independent of this setting. Manual  
Control overrides the sensor fail preset.  
Dampening Time (40121/40221): The dampening time, entered as a time constant in seconds, dampens (filters) the calculated output power.  
Increasing the value increases the dampening effect. Generally, dampening times in the range of one-twentieth to one-fiftieth of the controller’s  
integral time (or process time constant) is effective. Dampening times longer than these may cause controller instability due to the added lag effect.  
On/Off Control Hysteresis (40122/40222): The controller can be placed in the On/Off Control Mode by setting the Proportional Band to 0.0%. The  
On/Off Control Hysteresis (balanced around the setpoint) eliminates output chatter. In heat/cool applications, the control hysteresis value affects  
both Output OP1 and Output OP2 control. It is suggested to set the hysteresis band to 2 (Factory Setting) prior to starting Auto-Tune. After Auto-  
Tune, the hysteresis band has no effect on PID Control. On/Off Control Hysteresis is illustrated in the the On/Off Control Mode section.  
11  
STEP 13 PROGRAMMING THE ALARMS  
Alarm 1 and 2: The controller is equipped with two alarms for each channel. The status of these alarms  
can be read through AL1 registers 40015/40031 and AL2 registers 40016/40032.  
Action (40131/40231), (40136/40236): Select the action for the alarms. See Alarm Action Figures for a  
visual explanation.  
Manual: In Manual mode, the alarms are forced on and off by writing ‘0’ or ‘1’ to the appropriate  
alarm output register. In this mode, the alarms will not respond to Alarm and Hysteresis Values.  
Absolute HI (balanced or unbalanced hysteresis): The alarm energizes when the Process Value exceeds  
the alarm.  
Absolute LO (balanced or unbalanced hysteresis): The alarm energizes when the Process Value falls  
below the alarm.  
Deviation HI, Deviation LO, Band Acting: In these actions, Alarm 1 and 2 value tracks the Setpoint  
value.  
Cooling (OP2): For heat/cool applications, select Cool for Alarm 2. The controller then utilizes the  
Alarm 2 output as the Cooling Output (OP2). If cooling is selected, the remaining Alarm 2  
parameters are not available.  
ALARM ACTION FIGURES  
AL + ½Hys  
SP  
AL + Hys  
AL  
Hys  
Hys  
SP + (-AL)  
Hys  
AL - ½Hys  
AL  
ALARM  
STATE  
OFF  
OFF  
ON  
ALARM  
STATE  
ON  
OFF  
ON  
ALARM  
STATE  
OFF  
ON  
OFF  
TRIGGER POINTS  
TRIGGER POINTS  
TRIGGER POINTS  
Absolute High Acting (Balanced Hys)  
Deviation High Acting (AL< 0)  
SP + AL  
Hys  
AL + ½Hys  
SP + AL  
Hys  
AL  
SP  
Hys  
SP  
AL - ½Hys  
Hys  
SP - AL  
OFF  
ON  
OFF  
ALARM  
STATE  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
ON  
OFF  
ALARM  
STATE  
ALARM  
STATE  
TRIGGER POINTS  
TRIGGER POINTS  
TRIGGER POINTS  
Band Outside Acting  
Absolute Low Acting (Balanced Hys)  
Deviation High Acting (AL > 0)  
Hys  
Hys  
SP  
AL  
SP + AL  
Hys  
SP  
Hys  
SP - AL  
AL - Hys  
SP - AL  
ALARM  
STATE  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
ALARM  
STATE  
ALARM  
STATE  
TRIGGER POINTS  
TRIGGER POINTS  
TRIGGER POINTS  
Band Inside Acting  
Absolute High Acting (Unbalanced Hys)  
Deviation Low Acting (AL > 0)  
Note: Hys in the above figures refers to the Alarm Hysteresis.  
Value (40003/40019), (40004/40020): The alarm values are entered as process units or degrees.  
Hysteresis (40134/40234), (40139/40239): The Hysteresis Value is either added to or subtracted from the alarm value, depending on the alarm action selected.  
See the Alarm Action Figures for a visual explanation of how alarm actions are affected by the hysteresis.  
Trigger Points: Trigger points are the Process Values where the alarm state changes. Their values cannot be entered directly, but are shown as a reference in the  
SFDLC software. The alarm value, hysteresis value, and setpoint alarm type determine the trigger points. With Deviation or Band actions, the alarm value and  
setpoint value are combined to determine the trigger points. Trigger points must not be greater than +32000 or less than -32000. If these limits are exceeded,  
the alarm may not function properly.  
Reset (40132/40232), (40137/40237): The alarms can be programmed for Automatic or Latched. In Automatic mode, an energized alarm turns off automatically  
once the Process Value leaves the alarm region. In Latched mode, an energized alarm requires a manual reset. This is done by writing ‘0’ to the appropriate  
output status register. After writing ‘0’, the Automatic or Latched alarm will not turn on again until after the Process Value first returns to the alarm off region.  
Only alarms configured for Manual action can be energized by writing a ‘1’ to its’ alarm output status register.  
On Delay (40135/40235), (40140/40240): The time, in seconds, required for the Process Value to be in the alarm region before the alarm will activate. It is used  
to allow temporary or short excursions into the alarm region without tripping the alarm.  
Enable Standby Delay (40133/40233), (40138/40238): Standby prevents nuisance (typically low level) alarms after a power up or setpoint change. After  
powering up the controller or changing the setpoint, the process must leave the alarm region. Once this has occurred, the standby is disabled and the alarm  
responds normally until the next controller power up or setpoint change.  
12  
STEP 14 PROGRAMMING THE COOLING  
To enable Cooling in Heat/Cool applications, the Alarm 2 Action must first be set for Cooling. When  
set to cooling, the output no longer operates as an alarm but operates as an independent cooling output.  
The OP2 terminals are the same as AL2. Cooling output power ranges from -100% (full cooling) to 0%  
(no cooling, unless a heat/cool deadband overlap is used). The Power Limits in the Output category also  
limits the cooling power.  
Cycle Time (40141/40241): This cycle time functions like the OP1 Output Cycle Time but allows  
independent cycle time for cooling. A setting of zero will keep output OP2 off. The status of OP2 can  
be read through registers (40016/40032).  
Relative Gain (40142/40242): This defines the gain of the cooling relative to the heating. It is generally  
set to balance the effects of cooling to that of heating. This is illustrated in the Heat/Cool Relative Gain  
Figures. A value of 0.0 places the cooling output into On/Off Control. This may be done independent  
of the OP1 Output PID or On/Off Control Modes.  
Deadband (40143/40243): This defines the area in which both heating and cooling are active (negative  
value) or the deadband area between the bands (positive value). If a heat/cool overlap is specified, the  
percent output power is the sum of the heat power (OP1) and the cool power (OP2). If Relative Gain  
is zero, the cooling output operates in the On/Off Control Mode, with the Deadband value becoming  
the cooling output hysteresis (positive value only). This is illustrated in the On/Off Control Mode  
section. For most applications, set this parameter to 0.0 prior to starting Auto-Tune. After the  
completion of Auto-Tune, this parameter may be changed.  
HEAT/COOL RELATIVE GAIN FIGURES  
2X PROPORTIONAL  
BAND  
DEADBAND  
POSITIVE VALUE  
O1  
+100%  
O2  
-100%  
RELATIVE GAIN  
O1  
+100%  
O2  
-100%  
2
1
.5  
%
%
OUTPUT  
POWER  
OUTPUT  
POWER  
TEMPERATURE  
TEMPERATURE  
HEAT  
COOL  
RELATIVE GAIN = .5  
COOL  
HEAT  
SETPOINT  
SETPOINT  
Heat/Cool Deadband = 0  
Heat/Cool Deadband > 0  
DEADBAND  
NEGATIVE VALUE  
RELATIVE GAIN  
1
O1  
+100%  
O2  
-100%  
2
.5  
%
OUTPUT  
POWER  
TEMPERATURE  
RELATIVE GAIN = .5  
COOL  
HEAT  
SETPOINT  
Heat/Cool Deadband < 0  
13  
STEP 15 PROGRAMMING THE ANALOG OUTPUT (Optional)  
Note: The register numbers correspond to (Analog Output 1/Output 2).  
Assignment (40301/40309): This setting selects the value that the Analog Output will retransmit, or track.  
The Analog output can be assigned for the following:  
SELECTION  
DESCRIPTION  
Output Power A  
Process Value A  
Setpoint A  
Transmits the Output Power demand of Channel A. Used if linear control is desired.  
Retransmits Process Value Channel A  
Retransmits Setpoint Value Channel A  
Ramping Setpoint A  
Deviation A  
Retransmits Ramping Setpoint Channel A  
Retransmits Deviation (difference of Setpoint Value - Process Value) Channel A  
Retransmits Direct Entry Value 1 (Manual Analog Control)  
Transmits the Output Power demand of Channel B. Used if linear control is desired.  
Retransmits Process Value Channel B  
Direct Entry Value 1  
Output Power B  
Process Value B  
Setpoint B  
Retransmits Setpoint Value Channel B  
Ramping Setpoint B  
Deviation B  
Retransmits Ramping Setpoint Channel B  
Retransmits Deviation (difference of Setpoint Value - Process Value) Channel B  
Retransmits Direct Entry Value 2 (Manual Analog Control)  
Direct Entry Value 2  
Mode (40302/40310): Select the type of output and range. The Analog output jumpers must be set to match the  
output type and range selected. The Analog output can be calibrated to provide up to 5% of over range operation.  
Output Scaling Values: The Scaling Low value (40303/40311) corresponds to 0 V, 0 mA or 4 mA, depending on  
the range selected. The Scaling High value (40304/40312) corresponds to 10 V or 20 mA depending on the range  
selected. An inverse acting output can be achieved by reversing the Scaling Low and Scaling High points.  
Deadband (40305/40313): The output power change must be greater than the deadband value in order for the  
Analog output to update. This only applies when the Analog Output is assigned to Output Power. This setting  
can be used to reduce actuator activity.  
Update Time (40306/40314): To reduce excess valve actuator or pen recorder activity, the update time of the  
analog output can be set in seconds. A value of zero seconds results in an update time of 0.1 second.  
Direct Entry Value (40307/40315): If the analog output is programmed for Direct Entry, it retransmits this value.  
This value may be controlled by the host.  
Filter (40308-40316): Entering a 1 will apply averaging when the Update Time >=1.  
STEP 16 PROGRAMMING THE DLC COMMS PORT  
Note: If the software selectable communication settings are changed and then a download is performed, the  
controller will immediately respond to the new settings. Any further attempts to communicate to the controller  
must target the new address, with the new settings.  
MINIMUM TRANSMIT DELAY  
SERIAL SETTINGS  
MODBUS Protocol (40405): RTU or ASCII  
Unit Address (40401): 1-247  
Baud Rate (40402): 300 to 38400  
Data Bits (40404): 7 or 8  
Parity (40403): odd, even, or none  
Transmit Delay (40406): Programmable from 2-250 milliseconds.  
The Transmit Delay is the time the DLC waits to respond to a serial  
command, UNLESS the values in the table are larger.  
Note: Changing the above parameters by writing to their registers  
directly will not update the DLC until Load Serial Settings register  
40407 is a ‘1’. After a write, this register will return to ‘0’.  
DIP Switch Serial Settings: The DIP switches can be used to select the  
baud rate, parity, and unit address. When using the DIP switches to  
BAUD  
38400  
19200  
9600  
4800  
2400  
1200  
600  
RTU  
ASCII  
2 msec  
3 msec  
5 msec  
9 msec  
17 msec  
33 msec  
65 msec  
129 msec  
2 msec  
2 msec  
2.3 msec  
4.6 msec  
9.2 msec  
18.4 msec  
36.7 msec  
73.4 msec  
300  
configure the serial settings, the Modbus communications mode will be RTU only. There is also a "Default Serial  
Settings" switch to quickly configure the DLC for use with the "RLCPRO" Programming Software.  
Software Selectable Serial Settings: Setting all of the DIP switches to the "off" position and having the "Default  
Serial Setting" terminal un-connected, enables Software Selectable Serial settings. When leaving the factory the  
Software Selectable serial settings are set to the Serial Communication Defaults. Software Selectable Serial  
Settings allows set-up of all serial settings including the choice of RTU or ACSII communications modes and the  
number of data bits. If the Software Selectable Serial Settings are changed, the load serial register must be used  
or power to the DLC must be removed and re-applied in order for the settings to take effect. The use of RLCPRO  
Programming software or another software program supporting Modbus protocol is required to write to the DLC  
serial settings registers (40401-40407).  
14  
Default Serial Settings: The DLC serial port can be temporarily set to the factory defaults by setting the Default serial communications DIP switch to  
the “up” position OR by placing a jumper from the “Default Serial Setting” terminal 7 (TBB) to Output common terminal 4 (TBA). Both of these  
have precedence over the DIP switch serial settings and the software selectable serial settings. Once the serial default DIP switch is set to the “off”  
position or the jumper is removed, the DLC serial settings will immediately change as programmed by the DIP switches or the software selectable  
serial settings if all of the DIP switches are in the “off” position. The Default Serial Settings are NOT loaded into the software selectable serial  
registers when the serial default setting switch/terminal is active, they must be explicitly changed.  
Serial Communication Defaults: 9600 baud, 1 start bit, no Parity, 1 stop bit, address 247, and RTU mode.  
Communications Diagnostics: The Communications Diagnostics function (MODBUS Function Code 08) can be used to troubleshoot systems that are  
experiencing communication errors. Press the Read button to retrieve the diagnostics information. The Commands Received and the Commands  
Processed values are automatically reset when the values are read, at each controller power-up, and when the Commands Received reaches 65536.  
Commands Received: The total number of messages received that started with the controller’s own address since the last reset or power up.  
Commands Processed: The number of “good” messages received. A “good” message is considered one that contained the correct unit address,  
parity, and checksum (CRC or LRC).  
STEP 17 PC PORT CONFIGURATION  
Go to the SETTINGS pull-down menu, and select PC PORT SETTINGS.  
The Communications Settings window allows you to set up the software properly to perform a download.  
Connection: Select the computer port (COMM 1-4) that the DLC is connected to.  
Note: The following settings must match the DLC. If you do not know or cannot recall the DLC settings, they can  
be temporarily set to factory defaults. Simply jumper the Default Serial Setting terminal 7 to Input Common  
terminal 4 or put the Default Serial Settings DIP switch in the “UP” position. The serial settings will default  
to RTU mode, 9600 baud, 8 data bits, no parity, with an address of 247.  
Protocol: RTU or ASCII  
Unit Address: 1-247  
Baud Rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400  
Data Bits: 7 or 8  
Parity: odd, even, or none  
Connect the DLC to the computer with the CBPRO007 interface cable (or any suitable RS232/RS485 converter).  
Apply power to the supply terminals of the DLC.  
RED LION CONTROLS  
MODEL DLC  
PWR/COMM.  
CH  
CH  
A
OP  
BOTH FLASHING  
=
INPUT ERROR  
A
ALM  
AUTOTUNE  
Note: The CBPRO007 download cable DOES NOT  
typically require power. In most cases it will derive  
its power from the PC. If communications can not be  
established, follow the troubleshooting guide. If it is  
determined that the converter requires power, attach  
a 12 VDC power supply to the VDC and common  
terminals of the cable.  
CH  
CH  
B
OP  
BOTH FLASHING  
=
INPUT ERROR  
B
ALM  
RS485  
MODBUS  
PROTOCOL  
DLC  
CBPRO  
STEP 18 DOWNLOADING  
Go to the FILE pull-down menu, and select DOWNLOAD.  
The following screen prompts you to  
ensure that the proper file is downloaded  
to the correct controller. Click “OK” to  
continue.  
15  
STEP 19 SCRATCH PAD MEMORY  
The Scratch Pad category can be used to read or write to the Scratch Pad memory locations (41101-  
41116). The Scratch Pad locations can be used to store user information.  
Data Format: Allows registers to be viewed in decimal or hexadecimal format.  
Upload: The Upload button causes SFDLC software to read the Scratch Pad registers from the controller.  
Download: The Download button causes SFDLC software to write to the Scratch Pad registers in the  
controller.  
Note: Downloading new values to the controller Scratch Pad locations overwrites the information that is  
currently stored in those registers.  
Defaults: For this category, there are no controller factory defaults. The defaults for this category are only  
SFDLC software basic default values.  
STEP 20 VIEW REGISTERS  
The View Registers category can be used as a method of diagnostics. Use the DLC Register Table as a  
reference of register assignments and data.  
First Register: This specifies the first register to be read in a block.  
# of Registers: This is the length of the block to be read. The controller supports block read and write  
commands up to 32 registers in length. The SFDLC software only allows 16 to be read in a block.  
Data Format: Allows registers to be viewed in decimal or hexadecimal format.  
Read: Clicking the Read button causes SFDLC software to read the selected registers from the controller.  
Write: Clicking the Write button causes SFDLC software to write the selected registers to the controller.  
Note: The Write button overwrites the existing register values, and may change the module setup and  
operation.  
Defaults: For this category, there are no controller factory defaults. By clicking Defaults, the present  
entries from the other SFDLC software category screens will be displayed.  
STEP 21 CALIBRATION  
The DLC is fully calibrated from the factory. Recalibration is recommended every two years. Each channel is calibrated separately. All calibration settings  
are stored in the non-volatile memory. Calibration may be performed by using SFDLC software or MODBUS commands. When using SFDLC for calibration,  
connect the signal or measuring source to the proper DLC terminals, verify the input or output jumper positions, select the type of calibration to be performed,  
and click the Calibrate button. Follow the calibration procedures in the software.  
Note: Allow the DLC to warm up for 30 minutes minimum and follow the manufacturers warm-up recommendations for the calibration source.  
INPUT CALIBRATION  
When calibrating the input, the millivolt calibration must be performed first. All other input types use the  
millivolt points. Each input range (non-thermocouple) also has its own internal references that are recalled  
when the range is selected. Non-used types need not be calibrated.  
Calibration Type: This specifies the type of calibration to be performed.  
Millivolt: Millivolt calibration requires a precision voltage source with an accuracy of 0.03% or better.  
It is used for thermocouple inputs and as a basis for all other input calibration types.  
RTD: RTD calibration requires a 0.1% (or better) precision 277.0 ohm resistor.  
Process Voltage: Process calibration requires a precision signal source with an accuracy of 0.03% (or  
better) that is capable of generating 10.00 V.  
Process Current: Process current calibration requires a precision signal source with an accuracy of  
0.03% (or better) that is capable of generating 20.00 mA.  
Cold Junction: Cold Junction calibration requires a thermocouple of known accuracy of types T, E, J, K, C or N only and a calibrated external reference  
thermocouple probe.  
TC Type: This selects the type of TC that is being used to calibrate the cold junction.  
Scale: This selects the scale in which the Thermometer temperature is entered and the controller temperature is displayed.  
Thermometer: Enter the reference thermometer temperature here.  
DLC: This displays the DLC process temperature value after a cold junction calibration is completed to verify the accuracy.  
Calibrate: The Calibrate button initiates the calibration process after the appropriate settings are selected.  
16  
ANALOG OUTPUT CALIBRATION  
Calibration Type: This specifies the Analog Output point to be calibrated.  
Volts: Analog Output Voltage calibration requires a precision meter with an accuracy of 0.05% (or better)  
that is capable of measuring 10.00 V.  
mA: Analog Output Current calibration requires a precision meter with an accuracy of 0.05% (or better)  
that is capable of measuring 20.00 mA.  
Meter Value: After pressing the Calibrate button, this shows the value the DLC is outputting. Measure the  
actual output with an external meter and enter that value here. Press the Calibrate button again and follow  
the prompts.  
Calibrate: The Calibrate button initiates the calibration process after the appropriate settings are selected.  
APPLICATION  
A plastic extrusion company was building a four-zone extruder, and wanted a centrally located,  
multi-zone interface. The interface needed to display the temperature and setpoint values, as well as  
the screw RPM and barrel pressure. The customer provided a speed proportional 0-10 Volt signal  
from a motor drive, and installed a 4-20 mA output pressure sensor in the extruder barrel. Each of  
the four heat/cool zones were equipped with a thermocouple.  
Three DLC-Dual Loop Controllers, with a G3 HMI, allowed the customer to build his own control  
system. Only three DLCs were required; two were needed to control the four temperature zones, and  
one was needed to monitor the two process signals.  
POWER  
18-36VDC/  
24VAC  
RED LION CONTROLS  
MODEL DLC  
RED LION CONTROLS  
MODEL DLC  
RED LION CONTROLS  
MODEL DLC  
All three units were  
connected to the RS485  
RS485  
MODBUS  
PROTOCOL  
RS485  
MODBUS  
PROTOCOL  
RS485  
MODBUS  
PROTOCOL  
port of the G3 display. The  
customer created his own  
displays on the HMI,  
which allowed him to  
monitor and control the  
setpoints and alarms  
4-20mA SIG.  
(FROM PRESSURE  
SENSOR)  
within the DLCs. The G3’s  
multi-protocol capability  
allowed it to tie the DLCs  
to his PLC, creating a true  
centralized interface.  
+
+
+
+
ZONE 1  
ZONE 2  
ZONE 3  
ZONE 4  
0-10V SIG.  
(FROM MOTOR DRIVE)  
FOUR-ZONE EXTRUDER  
HMI UNIT  
CONTROL MODE EXPLANATIONS  
MANUAL CONTROL MODE  
MODE TRANSFER  
In Manual Control Mode, the controller operates as an open loop system  
(does not use the setpoint and process feedback). The user enters a percentage  
of power through the Output Power register (40005/40021) to control the heat  
(reverse) or cool (direct) for Output OP1. When Alarm 2 is configured for  
Cooling (OP2), Manual operation provides 0 to 100% power to OP1 (heating)  
and -100 to 0% power to OP2 (Cooling). The Low and High Power limits are  
ignored when the controller is in Manual.  
When transferring the controller mode from or to Automatic, the controlling  
outputs remain constant, exercising true bumpless transfer. When transferring  
from Manual to Automatic, the power initially remains steady, but Integral  
Action corrects (if necessary) the closed loop power demand at a rate  
proportional to the Integral Time. The Control Mode can be changed through  
the Control Mode register (40041/40049).  
For time proportional outputs, the output power is converted into output On  
time using the Cycle Time. For example, with a four second cycle time and 75%  
power, the output will be on (4 × 0.75) for three seconds and off for one second.  
For Analog Outputs (0-10 VDC or 0/4-20 mA), the percent output power is  
converted into a linear value according to the Percent Low and High scaling set  
for the analog output. For example, with 0 VDC (scaled 0.0%) to 10 VDC  
(scaled 100%) and 75% power, the analog output will be 7.5 VDC.  
AUTOMATIC CONTROL MODE  
In Automatic Control Mode, the percentage of output power is automatically  
determined by PID or On/Off calculations based on the setpoint and process  
feedback. For this reason, PID Control and On/Off Control always imply  
Automatic Control Mode.  
17  
ON/OFF CONTROL - HEAT/COOL OUTPUT FIGURES  
ON/OFF CONTROL  
The controller operates in On/Off Control when the Proportional Band is set  
to 0.0%. In this control, the process will constantly oscillate around the setpoint  
value. The On/Off Control Hysteresis (balanced around the setpoint) can be  
used to eliminate output chatter. Output OP1 Control Action can be set to  
reverse for heating (output on when below the setpoint) or direct for cooling  
(output on when above the setpoint) applications.  
INPUT  
HEAT/COOL DEADBAND VALUE (db) = 0  
SP + 1/2 HYS  
HYS  
SP  
SP - 1/2 HYS  
ON/OFF CONTROL - REVERSE OR DIRECT ACTING FIGURES  
INPUT  
REVERSE ACTING  
OFF  
ON  
ON  
OFF  
ON  
Output 1 (OP1) :  
SP+1/2 HYS  
SP  
OFF  
Output 2 (OP2) :  
INPUT  
HEAT/COOL DEADBAND VALUE (db) > 0  
SP-1/2 HYS  
SP + 1/2 (db) + 1/2 HYS  
HYS  
SP + 1/2 (db)  
SP + 1/2 (db) - 1/2 HYS  
db  
OFF  
ON  
OFF  
Output 1 (OP1) :  
SP  
INPUT  
SP - 1/2 (db) + 1/2 HYS  
SP - 1/2 (db)  
DIRECT ACTING  
HYS  
SP - 1/2 (db) - 1/2 HYS  
SP+1/2 HYS  
SP  
OFF  
ON  
OFF  
Output 1 (OP1) :  
Output 2 (OP2) :  
OFF  
ON  
OFF  
HYS  
SP-1/2 HYS  
INPUT  
HEAT/COOL DEADBAND VALUE (db) < 0  
OFF  
ON  
OFF  
Output 1 (OP1) :  
SP + 1/2 (db) + 1/2 HYS  
SP + 1/2 (db)  
SP + 1/2 (db) - 1/2 HYS  
For heat and cool systems, OP1 Control Action is set to reverse (heat) and the  
Alarm 2 Action is set to cooling (OP2). The Proportional Band is set to 0.0 and  
the Relative Gain in Cooling to 0.0. The Deadband in Cooling sets the amount  
of operational deadband or overlap between the outputs. The setpoint and the  
On/Off Control Hysteresis applies to both OP1 and OP2 outputs. The hysteresis  
is balanced in relationship to the setpoint and deadband value.  
db  
SP  
SP - 1/2 (db) + 1/2 HYS  
SP - 1/2 (db)  
SP - 1/2 (db) - 1/2 HYS  
HYS  
ON  
OFF  
ON  
Note: HYS in the On/Off Control Figures refers to the On/Off Control Hysteresis.  
Output 1 (OP1) :  
Output 2 (OP2) :  
ON  
OFF  
ON  
TYPICAL PID RESPONSE CURVE  
P & I  
PID CONTROL  
In PID Control, the controller processes the input and then calculates a  
control output power value by use of a modified Proportional Band, Integral  
Time, and Derivative Time control algorithm. The system is controlled with the  
new output power value to keep the process at the setpoint. The Control Action  
for PID Control can be set to reverse for heating (output on when below the  
setpoint) or direct for cooling (output on when above the setpoint) applications.  
For heat and cool systems, the heat (OP1) and cool (OP2) outputs can be used  
together in the PID Control. The PID parameters can be Auto-Tune or Manual  
Tune to the process.  
P & I & D  
INPUT  
SP  
P & D  
P only  
TIME  
REMOTE SETPOINT  
Channel B can operate as a Remote Setpoint Input to Channel A. Channel B  
PID control is not functional when the input is assigned as a Remote Setpoint.  
This mode of operation enables Cascade control (external), Ratio control, and  
Temperature Setpoint Slave control, among others.  
The Ratio Multiplier and Bias Offset parameters offer on-line scaling of the  
Remote Setpoint to adjust control ratios or biases among related processes.  
The Remote Setpoint is restricted to the setpoint low and high limit values for  
channel B. These parameters may be used to limit the range of the Remote  
Setpoint to a safe or more stable control range. For Remote Setpoint signal  
sources that change wildly or are too sensitive to process upsets, the CHA  
Setpoint Ramp Rate parameter (40110) can be used to ramp (rate limit) the  
Remote Setpoint reading. This can subsequently reduce the fluctuations of the  
secondary control loop.  
The Remote Setpoint value used internally by the controller is:  
Remote Setpoint = (Scaled CHB Input * Remote Setpoint Ratio Multiplier)  
+ Remote Setpoint Bias Offset  
where Ratio Multiplier  
Bias Offset  
= 0.0001 to 3.2000  
= -32000 to 32000  
18  
PID TUNING EXPLANATIONS  
AUTO-TUNE  
AUTO-TUNE CODE FIGURE  
INPUT  
Auto-Tune is a user-initiated function where the controller automatically determines the  
Proportional Band, Integral Time, Derivative Time, Digital Filter, Control Ouput Dampening  
Time, and Relative Gain (Heat/Cool) values based upon the process characteristics. The  
Auto-Tune operation cycles the controlling output(s) at a control point three-quarters of the  
distance between the present process value and the setpoint. The nature of these oscillations  
determines the settings for the controller’s parameters.  
SP  
2
Prior to initiating Auto-Tune, it is important that the controller and system be first tested.  
(This can be accomplished in On/Off Control or Manual Control Mode.) If there is a wiring,  
system or controller problem, Auto-Tune may give incorrect tuning or may never finish.  
Auto-Tune may be initiated at start-up, from setpoint or at any other process point. However,  
insure normal process conditions (example: minimize unusual external load disturbances) as  
they will have an effect on the PID calculations. Auto-Tune cannot be initiated while running  
a profile.  
TYPICAL RESPONSE CURVES WITH  
AUTO-TUNE CODES 0 TO 2.  
1
0
TIME  
Start Auto-Tune  
1. Enter the On/Off Control Hysteresis value.  
(For most applications, 10 is a suggested value.)  
2. Enter the Deadband value, if using OP2.  
(For most applications, 0 is a suggested value.)  
3. Enter the Setpoint value.  
AUTO-TUNE OPERATION  
(REVERSE ACTING)  
INPUT  
SETPOINT  
(If Auto-Tune overshoot is unacceptable, then lower the value and restart.)  
½ HYS *  
AUTO-TUNE  
CONTROL  
POINT  
4. Enter the Auto-Tune Code. (See Figure for details)  
5. Enter ‘1’ in the Auto-Tune Start register . (Channel A 40011/Channel B 40027).  
6. The Auto-Tune LED will come on.  
½ HYS *  
AUTO-TUNE COMPLETE, PID  
SETTINGS ARE CALCULATED  
AND LOADED INTO MEMORY  
Auto-Tune Progress  
AUTO-TUNE  
START  
The controller will oscillate the controlling output(s) for four cycles. The cycling  
phase can be monitored from the Auto-Tune Phase Register (Channel A 40012/  
Channel B 40028). The time to complete the Auto-Tune cycles is process dependent.  
The controller should automatically stop Auto-Tune and store the calculated values  
when the four cycles are complete. If the controller remains in Auto-Tune unusually  
long, there may be a process problem. Auto-Tune may be stopped by entering ‘0’ in  
Auto-Tune Start Register (Channel A 40011/Channel B 40027).  
TIME  
PHASE  
1
2
3
4
OFF  
OFF  
Output 1 (OP1) :  
ON  
ON  
* - On/Off Control Hysteresis  
PID Adjustments  
starting value and allow the process sufficient time to stabilize before evaluating  
the effects of the new parameter settings.  
In some unusual cases, the Auto-Tune function may not yield acceptable  
control results or induced oscillations may cause system problems. In these  
applications, Manual Tuning is an alternative.  
In some applications, it may be necessary to fine tune the Auto-Tune  
calculated PID parameters. To do this, a chart recorder or data logging device is  
needed to provide a visual means of analyzing the process. Compare the actual  
process response to the PID response figures with a step change to the process.  
Make changes to the PID parameters in no more than 20% increments from the  
PROCESS RESPONSE EXTREMES  
OVERSHOOT AND OSCILLATIONS  
SLOW RESPONSE  
INPUT  
INPUT  
SP  
SP  
TIME  
TIME  
TO DAMPEN RESPONSE:  
TO QUICKEN RESPONSE:  
- INCREASE PROPORTIONAL BAND.  
- INCREASE INTEGRAL TIME.  
- USE SETPOINT RAMPING.  
- USE OUTPUT POWER LIMITS.  
- RE-INVOKE AUTO-TUNE WITH A  
HIGHER AUTO-TUNE CODE.  
- DECREASE PROPORTIONAL BAND.  
- DECREASE INTEGRAL TIME.  
- INCREASE OR DEFEAT SETPOINT RAMPING.  
- EXTEND OUTPUT POWER LIMITS.  
- RE-INVOKE AUTO-TUNE WITH A  
LOWER AUTO-TUNE CODE.  
- INCREASE DERIVATIVE TIME.  
- CHECK CYCLE TIME.  
- DECREASE DERIVATIVE TIME.  
19  
Output Power (40005/40021) to drive the process value to the Setpoint value.  
Allow the process to stabilize after setting the Output Power.  
6. Place the controller in Automatic Control Mode (40041/40049). If the process  
will not stabilize and starts to oscillate, set the Proportional Band two times  
higher and go back to Step 5.  
7. If the process is stable, decrease Proportional Band setting by two times and  
change the setpoint value a small amount to excite the process. Continue with  
this step until the process oscillates in a continuous nature.  
8. Fix the Proportional Band to three times the setting that caused the oscillation  
in Step 7.  
MANUAL TUNING  
A chart recorder or data logging device is necessary to measure the time  
between process cycles. This procedure is an alternative to the controller’s  
Auto-Tune function. It will not provide acceptable results if system problems  
exist. This procedure should be performed by directly accessing the controller’s  
registers. The register numbers correspond to (Channel A/Channel B).  
1. Set the Proportional Band (40007/40023) to 10.0% for temperature inputs  
and 100.0% for process inputs.  
2. Set both the Integral Time (40008/40024) and Derivative Time (40009/40025)  
to 0 seconds.  
3. Set the Output Dampening Time (40121/40221) to 0 seconds.  
4. Set the Output Cycle Time (40116/40216) to no higher than one-tenth of the  
process time constant (when applicable).  
9. Set the Integral Time to two times the period of the oscillation.  
10. Set the Derivative Time to one-eighth (0.125) of the Integral Time.  
11. Set the Output Dampening Time to one-fortieth (0.025) the period of the  
oscillation.  
5. Place the controller in Manual Control Mode (40041/40049) and adjust the  
MODBUS INFORMATION  
The remaining sections of this bulletin list information for MODBUS conformity with DLC registers and coils data.  
MODBUS SUPPORTED FUNCTION CODES  
FC01: Read Coils  
1. Valid coil addresses are 1-33.  
2. All coils can be requested.  
FC16: Preset Multiple Registers  
1. Valid write (preset) register addresses are are 40002-40005, 40007-40011,  
40013, 40015-40016, 40018-40021, 40023-40027, 40029, 40031-40032,  
40041-40042, 40044, 40046, 40049-40050, 40052-40053, 40065, 40068-  
40070, 40073, 40076-40078, 40100-40122, 40131-40143, 40198-40222,  
40231-40243, 40301-40316, 40321-40327, 40401-40407, 40421-40427,  
40501-40505, 40601-40660, 40701-40760, 41101-41116.  
2. No response is given with an attempt to write to more than 32 registers at a  
time.  
3. Block starting point can not exceed coil 33.  
FC05: Force Single Coil  
1. Valid write (force) coil addresses are 1-4, 10-13, 15-16, 22-25, 27-33.  
2. HEX <8001> is echoed back for a request to write to a read only coil, to  
indicate that the coil did not change.  
3. Block starting point can not exceed the read and write boundaries.  
4. If a multiple write includes read only registers, then only the write registers  
will change.  
5. If the write value exceeds the register limit (see Register Table), then that  
register value changes to its high or low limit.  
FC15: Force Multiple Coils  
1. Valid write (force) coil addresses are 1-4, 10-13, 15-16, 22-25, 27-33.  
2. Block starting point can not exceed coil 33.  
3. If a multiple write includes read only coils, then only the write coils will  
change.  
FC04: Read Input Registers  
1. Valid register addresses are 30001-30032, 30041-30046, 30049-30053,  
30065-30070, 30073-30078, 30100-30122, 30131-30143, 30198-30222,  
30231-30243, 30301-30308, 30309-30316, 30321-30327, 30401-30407,  
30421-30427, 30501-30505, 30601-30660, 30701-30760, 31001-31010,  
31101-31116.  
FC03: Read Holding Registers  
1. Valid register addresses are 40001-40032, 40041-40046, 40049-40053,  
40065-40070, 40073-40078, 40100-40122, 40131-40143, 40198-40222,  
40231-40243, 40301-40308, 40309-40316, 40321-40327, 40401-40407,  
40421-40427, 40501-40505, 40601-40660, 40701-40760, 41001-41010,  
41101-41116.  
2. Up to 32 registers can be requested at one time.  
3. Block starting point can not exceed register boundaries.  
4. HEX <8000> is returned in registers beyond the boundaries.  
5. Input registers are a mirror of Holding registers.  
2. Up to 32 registers can be requested at one time.  
3. Block starting point can not exceed the register boundaries.  
4. HEX <8000> is returned in registers beyond the boundaries.  
5. Holding registers are a mirror of Input registers.  
FC08: Diagnostics  
The following is sent upon FC08 request:  
FC06: Preset Single Register  
Module Address, 08 (FC code), 04 (byte count), “Total Comms” count,  
“Total Good Comms” count, checksum of the string  
“Total Comms” is the total number of messages received that were addressed to  
the DLC. “Total Good Comms” is the total messages received by the DLC  
with good address, parity and checksum. Both counters are reset to 0 upon  
response to FC08, on power-up, and when Total Comms register rolls over.  
1. Valid write (preset) register addresses are 40002-40005, 40007-40011, 40013,  
40015-40016, 40018-40021, 40023-40027, 40029, 40031-40032, 40041-  
40042, 40044, 40046, 40049-40050, 40052-40053, 40065, 40068-40070,  
40073, 40076-40078, 40100-40122, 40131-40143, 40198-40222, 40231-  
40243, 40301-40316, 40321-40327, 40401-40407, 40421-40427, 40501-  
40505, 40601-40660, 40701-40760, 41101-41116.  
2. HEX <8001> is echoed back that the register did not change during the  
request to write to a read only register.  
FC17: Report Slave ID  
The following is sent upon FC17 request:  
3. If the write value exceeds the register limit (see Register Table), then that  
register value changes to its high or low limit. It is also returned in the  
response.  
Unit Address, 17 (FC code), RLC-DLCxx000 (model number), 0200 (for code  
version 2.00), 32 (number of read supported registers), 32 (number of writes  
supported registers), 16 (number of registers available for GUID/Scratch pad  
memory), checksum of the string.  
20  
SUPPORTED EXCEPTION CODES  
Cold Junction Calibration *  
01: Illegal Function  
Cold Junction calibration requires a thermocouple of known accuracy of  
types T, E, J, K, C or N only and a calibrated external reference thermocouple  
probe.  
Issued whenever the requested function is not implemented in the controller.  
02: Illegal Data Address  
1. Connect the thermocouple probe source to the proper DLC terminals.  
2. Enter the connected thermocouple type into register 40101 (Ch A) or 40201  
(Ch B).  
Issued whenever an attempt is made to access a single register or coil that  
does not exist (outside the implemented space) or to access a block of registers  
or coils that falls completely outside the implemented space.  
3. Enter the scale (F or C) that matches the thermometer and the controller  
temperature, preferrably °C into register 40102 (Ch A) or 40202 (Ch B).  
4. Enter 1 for high resolution into register 40103 (Ch A) or 40203 (Ch B).  
5. Place an external reference thermometer probe at the end of the DLC probe.  
The two probes should be shielded from air movement and allowed sufficient  
time to equalize in temperature. (As an alternative, the DLC probe may be  
placed in a calibration bath of known temperature.)  
6. To open calibration mode, enter 48 into register 40501.  
7. To start CJ calibration, enter 10 (Ch A) or 110 (Ch B) into register 40501.  
8. Read the Process Value register 40001 (Ch A) or 40017 (Ch B).  
9. Subtract the external reference reading from the Process Value register  
reading. Adjust the results to tenths position, drop decimal point, and  
maintain the results sign. (If the difference is -2 degrees, then adjust to -2.0  
and remove decimal point yielding a value of -20.)  
10. Add the value from step 9 (maintain the sign) to the value existing in register  
40502.  
11. If necessary, continue to adjust the register 40502 value until the Process  
Value register 40001 (Ch A) or 40017 (Ch B) matches the external reference  
reading.  
12. To exit CJ calibration, enter 11 (Ch A) or 111 (Ch B) into register 40501.  
13. To save the calibration results and close calibration mode, enter 0 into  
register 40501.  
03: Illegal Data Value  
Issued when an attempt is made to read or write more registers or coils than  
the controller can handle in one request.  
07: Negative Acknowledge  
Issued when a write to coil or register is attempted with an invalid string  
length.  
CHECKSUM ERRORS  
1. Calibration checksum covers the area that contains calibration values for all  
ranges. When a calibration checksum error occurs, coil 1 becomes a “1”.  
2. Parameter checksum covers the area that contains the stored Holding register  
settings. When this checksum error occurs, coil 2 becomes a “1”.  
3. Integral and Offset/Manual Power checksum covers the area that contains the  
stored Integral register settings. When this checksum error occurs, coil 3  
becomes a “1”.  
4. Setpoint Controller Segment Memory checksum covers the memory area that  
contains the profile segments for channel A and B. When this checksum error  
occurs, coil 29 becomes a "1".  
5. Setpoint Controller Status Memory checksum covers the memory area that  
contains the profile operating status. When this checksum error occurs, coil  
30 becomes a "1" and aborts the profile putting channel in manual control at  
0% power.  
6. All LEDs except PWR/COMMS will flash as long as one of the errors exist.  
7. The control and alarm outputs are disabled as long as one of the errors exist.  
8. These errors can be cleared or activated manually by writing to the  
appropriate coil. (This does not correct the reason for the error. It may be  
necessary to reconfigure or calibrate.)  
RTD Calibration *  
RTD calibration requires a 0.1% (or better) precision 277.0 ohm resistor.  
1. Connect a precision 277.0 ohm resistor, and a short, to terminals 1 & 2 (Ch  
B) or 4 & 5 (Ch A). During the complete procedure, short terminals 2 & 3  
(Ch B) or 5 & 6 (Ch A).  
9. The checksums are verified at power up.  
2. Verify the input jumper is in the RTD position.  
3. Enter 12 (ohms mode) into register 40101 (Ch A) or 40201 (Ch B).  
4. To open calibration mode, enter 48 into register 40501.  
5. To start RTD calibration, enter 20 (Ch A) or 120 (Ch B) into register 40501.  
6. Leave 0 ohms (short) on terminals 1 & 2 (Ch B) or 4 & 5 (Ch A) for 10  
seconds.  
7. To store 0 ohm results, enter 21 (Ch A) or 121 (Ch B) into register 40501.  
8. Apply 277 ohms by removing the short from terminal 1 & 2 (Ch B) or 4 & 5  
(Ch A) for 10 seconds.  
CALIBRATION USING MODBUS COMMANDS  
The DLC is fully calibrated from the factory. Recalibration is recommended  
every two years. Each channel is calibrated separately. All calibration settings  
are stored in the non-volatile memory. The DLC may be calibrated using  
MODBUS. However, the preferred method of calibrating the controller is  
through the SFDLC software.  
When calibrating the input, a successful millivolt calibration must be  
performed first. All other input types use the millivolt points. Each input range  
(non-thermocouple) also has its own internal references that are recalled when  
the range is selected. Non-used types need not be calibrated.  
9. To store 277 ohm results, enter 22 (Ch A) or 122 (Ch B) into register 40501.  
10. To save the calibration results and close calibration mode, enter 0 into  
register 40501.  
Each of the procedures below show the calibration steps/register numbers for  
both channels A & B, however, only one channel can be calibrated at a time.  
Note: Allow the DLC to warm up for 30 minutes minimum and follow the  
manufacturers warm-up recommendations for the calibration or measuring  
source.  
Process Voltage Calibration *  
Process calibration requires a precision signal source with an accuracy of  
0.03% (or better) that is capable of generating 10.00 V.  
1. Connect the signal source to the proper DLC terminals.  
2. Verify the input jumper is in the 10 V position.  
3. Enter 14 (for voltage input) into register 40101 (Ch A) or 40201 (Ch B).  
4. To open calibration mode, enter 48 into register 40501.  
5. To start voltage calibration, enter 12 (Ch A) or 112 (Ch B) into register 40501.  
6. Apply 0.00 V for a minimum of 10 seconds.  
7. To store 0.00 V reading, enter 13 (Ch A) or 113 (Ch B) into register 40501.  
8. Apply 10.00 V for a minimum of 10 seconds.  
9. To store 10.00 V reading, enter 14 (Ch A) or 114 (Ch B) into register 40501.  
10. To save the calibration results and close calibration mode, enter 0 into  
register 40501.  
mV Calibration  
Millivolt calibration requires a precision signal source with an accuracy of  
0.03% (or better) that is capable of generating the range to be calibrated. It is  
used for thermocouple inputs and as a basis for all other input calibration types.  
1. Connect the signal source to the proper DLC terminals.  
2. Enter 13 (for mV input) into register 40101 (Ch A) or 40201 (Ch B).  
3. To open calibration mode, enter 48 into register 40501.  
4. To start mV calibration, enter 1 (Ch A) or 101 (Ch B) into register 40501.  
5. Apply the appropriate calibration voltage for a minimum of 10 seconds.  
6. To store the mV calibration reading, enter the corresponding range number  
into register 40501:  
RANGE  
0 mV  
14 mV  
28 mV  
42 mV  
56 mV  
Ch A  
Ch B  
102  
103  
104  
105  
106  
2
3
4
5
6
7. Repeat steps 5 and 6 for each range to be calibrated for that channel.  
8. To save the calibration results and end calibration, enter 0 into register  
40501.  
* - Dependent on successful mV calibration.  
21  
Process Current Calibration *  
Restore Factory Settings  
Process current calibration requires a precision signal source with an  
accuracy of 0.03% (or better) that is capable of generating 20.00 mA.  
1. Connect the signal source to the proper DLC terminals.  
2. Verify the input jumper is in the 20 mA position.  
The Factory Settings are listed in the DLC Register Table. This restore does  
not affect the calibration or communication settings of the DLC but may change  
all other settings for the channel.  
1. To open calibration mode, enter 48 into register 40501.  
2. To restore Factory Settings, enter 66 (Input Ch A and Analog Out 1) or 166  
(Input Ch B and Analog Out 2) into register 40501.  
3. To save the restore results and close calibration mode, enter 0 into register  
40501.  
3. Enter 15 (for current input) into register 40101 (Ch A) or 40201 (Ch B).  
4. To open calibration mode, enter 48 into register 40501.  
5. To start current calibration, enter 15 (Ch A) or 115 (Ch B) into register 40501.  
6. Apply 0.00 mA for a minimum of 10 seconds.  
7. To store 0.00 mA reading, enter 16 (Ch A) or 116 (Ch B) into register 40501.  
8. Apply 20.00 mA for a minimum of 10 seconds.  
9. To store 20.00 mA reading, enter 17 (Ch A) or 117 (Ch B) into register 40501.  
10. To save the calibration results and close calibration mode, enter 0 into  
register 40501.  
Clear Setpoint Controller Segment Memory  
1. To open calibration mode, enter 48 into register 40501.  
2. To clear Setpoint Controller Segment memory, enter 67 (CHA Segment  
memory) or 167 (CHB Segment Memory) into register 40501.  
3. To save the Clear results and close calibration mode, enter 0 into register  
40501.  
Analog Output Voltage Calibration  
Analog Output Voltage calibration requires a precision meter with an  
accuracy of 0.05% (or better) that is capable of measuring 10.00 V.  
Nominal Calibration Settings  
Nominal Calibration Settings does not require any calibration signals nor  
meters. This calibration should not be performed under normal circumstances.  
Caution: This procedure results in up to ±10% reading error and the DLC will  
no longer be within factory specifications.  
1. Connect the meter to the proper DLC terminals.  
2. Verify the output jumpers are in the V positions.  
3. To open calibration mode, enter 48 into register 40501.  
4. To start 0 volt calibration, enter 30 (Out 1) or 130 (Out 2) into register 40501.  
5. Adjust register 40502 value until the external meter displays 0.00 V.  
6. To start 10 volt calibration, enter 31 (Out 1) or 131 (Out 2) into register 40501.  
7. Adjust register 40502 value until the external meter displays 10.00 V.  
8. To save the calibration results and close calibration mode, enter 0 into register  
40501.  
1. To open calibration mode, enter 48 into register 40501.  
2. To enter Nominal Calibration Settings, enter 77 (Input Ch A and Analog Out  
1) or 177 (Input Ch B and Analog Out 2) into register 40501.  
3. To save the Nominal Calibration Settings and close calibration mode, enter 0  
into register 40501.  
Analog Output Current Calibration  
Analog Output Current calibration requires a precision meter with an  
accuracy of 0.05% (or better) that is capable of measuring 20.00 mA.  
1. Connect the meter to the proper DLC terminals  
2. Verify the output jumpers are in the I position.  
3. To open calibration mode, enter 48 into register 40501.  
4. To start 0 mA calibration, enter 32 (Out 1) or 132 (Out 2) into register 40501.  
5. Adjust register 40502 value until the external meter displays 0.00 mA.  
6. To start 20 mA calibration, enter 33 (Out 1) or 133 (Out 2) into register 40501.  
7. Adjust register 40502 value until the external meter displays 20.00 mA.  
8. To save the calibration results and close calibration mode, enter 0 into register  
40501.  
* - Dependent on successful mV calibration.  
22  
DLC REGISTER TABLE  
The below limits are shown as Integers or HEX < > values. Read and write functions can be performed in either Integers or Hex as long as the conversion was done  
correctly. Negative numbers are represented by two’s complement.  
Note 1: The DLC should not be powered down while parameters are being changed. Doing so may corrupt the non-volatile memory resulting in checksum errors.  
REGISTER  
ADDRESS 1  
FACTORY  
SETTING 3  
REGISTER NAME  
LOW LIMIT 2  
HIGH LIMIT 2  
ACCESS  
COMMENTS  
CH A  
CH B  
CONTROLLING VALUES  
Process value of present input level. This value is  
affected by Input Type, Resolution, & Scaling. In  
Square Root Extraction Modes, the Process Value will  
read zero for inputs below 0.1% of full scale.  
40001  
40017 Process Value  
N/A  
N/A  
N/A  
Read Only  
40002  
40003  
40004  
40018 Setpoint Value  
40019 Alarm 1 Value  
40020 Alarm 2 Value  
PID PARAMETERS  
-32000  
-32000  
-32000  
32000  
32000  
32000  
0
0
0
Read/Write Limited by Setpoint Limit Low and Setpoint Limit High.  
Read/Write  
Read/Write  
1 = 0.1%, 0.0 = Off; Limited by Power Low Limit and  
Power High Limit in Automatic Control Mode. Negative  
percent is cooling (direct) available when AL2 is  
Cooling. Write only possible during Manual mode.  
40005  
40006  
40021 Output Power  
0 or -1000  
N/A  
1000  
N/A  
0
Read/Write  
Deviation = Process Value - Setpoint Value; During  
Read Only  
40022 Setpoint Deviation  
N/A  
Auto-Tune: Process Value - Auto-Tune Setpoint Value  
40007  
40008  
40009  
40010  
40011  
40012  
40013  
40023 Proportional Band  
40024 Integral Time  
40025 Derivative Time  
40026 Offset Power  
40027 Auto-Tune Start  
40028 Auto-Tune Phase  
40029 Auto-Tune Code  
OUTPUT STATUS  
0
0
9999  
9999  
9999  
1000  
1
40  
120  
30  
0
Read/Write 0 = On/Off Control, 1 = 0.1%  
Read/Write 0 = Off, 1= 1 second  
0
Read/Write 0 = Off, 1= 1 second  
-1000  
0
Read/Write 1 = 0.1%; Applied when Integral Time is 0.  
Read/Write 0 = Stop, 1 = Start; Mirror of Coil 16/28.  
0
N/A  
0
N/A  
2
N/A  
0
Read Only  
0 = Off, 4 = Last phase during Auto-Tune  
Read/Write 0 = Fastest response, 2 = Slowest response  
40014  
40015  
40030 Control Output OP1  
N/A  
0
N/A  
1
N/A  
0
Read Only  
Read/Write  
0 = Off, 1 = On; Mirror of Coil 9/21.  
0 = Off, 1 = On; A write of 1 is only possible when  
alarm is set for Manual. Mirror of Coil 10/22.  
40031 Alarm Output AL1  
0 = Off, 1 = On; A write of 1 is only possible when  
alarm is set for Manual. Mirror of Coil 11/23.  
40016  
40032 Alarm Output AL2 / OP2  
0
1
0
Read/Write  
CONTROL STATUS  
40041  
40042  
40043  
40044  
40049 Control Mode  
0
0
1
1
0
0
Read/Write 0 = Automatic, 1 = Manual; Mirror of Coil 12/24.  
Read/Write 0 = Enabled, 1 = Disabled; Mirror of Coil 13/25.  
40050 Disable Setpoint Ramping  
40051 Setpoint Ramping In Process  
40052 Disable Integral Action  
N/A  
0
N/A  
1
N/A  
0
Read Only  
0 = No, 1 = Yes; Mirror of Coil 14/26.  
Read/Write 0 = Enabled, 1 = Disabled; Mirror of Coil 15/27  
Actual Setpoint Value used for control (ramps when  
Read/Write ramping enabled.) Limited by Setpoint Limit Low and  
Setpoint Limit High.  
40045  
40046  
40053 Ramping Setpoint Value  
N/A  
0
N/A  
1
N/A  
0
Remote / Local Setpoint Select  
Read/Write 0 = Local Setpoint, 1= Remote Setpoint  
PROFILE OPERATION  
SETPOINT CONTROLLER MODEL ONLY  
0 = Off; 1 = Abort; 2 = Run/Start, 3 = Pause, 4 = Error  
Delay (status only - writing a “4” will revert unit to mode  
“3” Pause)  
Read/Write  
(0-3 only)  
40065  
40073 Profile Operating Status  
0
3
0
40066  
40067  
40074 Profile Phase  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Read Only  
Read Only  
0 = Ramp; 1 = Hold  
40075 Profile Segment  
(0 = Stop, 1-20 = Current Segment)  
1= 0.1 Minute; Can make temporary change on the fly  
40068  
40076 Profile Phase Time Remaining  
1
9999  
N/A  
Read/Write Value Over-range = 32003 (may occur on extremely  
slow ramp; Ramp will function properly)  
0-250; If Cycle Count (40326/40426) is 250  
Read/Write  
40069  
40070  
40077 Profile Cycle Count Remaining  
40078 Advance Profile Phase  
1
0
250  
1
0
0
(Continuous operation), value will reset to 250 at 0.  
1 = Advances “running” Profile to next ramp or hold  
Read/Write  
phase  
INPUT PARAMETERS  
40198 Ch B Assignment  
0
0
1
2
0
0
Read/Write 0 = PID, 1 = Remote Setpoint  
0 = Normal (Output may bump)  
Local / Remote Setpoint  
40199  
1 = Auto (Output may bump)  
Read/Write  
Transfer Mode  
2 = Track (Local Setpoint assumes value of Remote SP  
for Remote to Local Transfer)  
40101  
40102  
40201 Input Type  
0
0
17  
1
2
0
Read/Write See Input Listing  
40202 Temperature Scale  
Read/Write 0 = °F, 1 = °C, For Input Types 0-11.  
Input Types 0-12 0=Low (x1) whole input units, 1  
Read/Write = High (x10) tenth of input units, Input Type 13 0 = 0.1  
mV, 1 = 0.01 mV, Input Types 14-15, N/A  
40103  
40203 Resolution  
0
1
0
1
2
3
For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.  
An attempt to exceed a limit will set the register to its high or low limit value.  
See MODBUS Calibration for procedure on restoring Factory Settings.  
23  
DLC REGISTER TABLE Continued  
REGISTER  
ADDRESS 1  
FACTORY  
SETTING 3  
REGISTER NAME  
LOW LIMIT 2  
HIGH LIMIT 2  
ACCESS  
COMMENTS  
CH A  
CH B  
INPUT PARAMETERS  
Greater than 1 causes rounding starting at least  
significant digit.  
40104  
40105  
40204 Rounding  
1
0
100  
4
1
1
Read/Write  
40205 Digital Input Filter  
Read/Write 0 = Least, 4 = Highest  
10000 = 1.0000 (applies no correction), 1 = 0.0001, For  
Read/Write Input Types 0-11. Applies to all inputs (0-15) for ChB  
when ChB is configured for Remote Setpoint (40198).  
Span Correction / Remote  
Setpoint Ratio Multiplier  
40106  
40107  
40206  
40207  
1
32000  
32000  
10000  
0
Offset Correction / Remote  
Setpoint Bias Offset  
For Input Types 0-13/ Applies to all inputs (0-15) for ChB  
when ChB is configured for Remote Setpoint (40198).  
-32000  
Read/Write  
SETPOINT PARAMETERS  
40108  
40109  
40208 Low Limit  
40209 High Limit  
-32000  
-32000  
32000  
32000  
0
Read/Write ChB value also applies to Remote Setpoint  
Read/Write ChB value also applies to Remote Setpoint  
1 = 0.1° per minute for input types 0-11, 0.1 ohms for  
32000  
input type 12, 0.01 mV for input type 13, 0.1 process units  
for input types 14-15, 0 = off (ChB Ramp Rate is Non-  
40110  
40210 Ramp Rate  
0
32000  
0
Read/Write  
functional in remote setpoint mode)  
SCALING POINTS PARAMETERS  
40111  
40112  
40113  
40114  
40211 Process Low  
40212 Process High  
40213 Input Low  
40214 Input High  
-32000  
-32000  
-32000  
-32000  
32000  
32000  
32000  
32000  
0
Read/Write For Input Types 14-15  
1000  
4000  
20000  
Read/Write For Input Types 14-15  
Read/Write 1 = 0.001 V or 0.001 mA, For Input Types 14-15.  
Read/Write 1 = 0.001 V or 0.001 mA For Input Types 14-15.  
Can be used by host to determine resolution of input. For  
Input Types 14-15.  
40115  
40215 Process Decimal Point  
0
5
3
Read/Write  
CONTROL (OP1) PARAMETERS  
NON-FUNCTIONAL IN REMOTE SETPOINT MODE (SEE 40198)  
CH A  
40116  
40117  
CH B  
40216 Cycle Time  
0
0
2500  
1
20  
0
Read/Write 1 = 0.1 second  
40217 Control Action  
Read/Write 0 = Reverse Acting, 1 = Direct Acting  
1 = 1%; Negative percent is only available to OP2 when  
AL2 is set for Cooling.  
40118  
40119  
40120  
40218 Power Low Limit  
0 or -100  
0 or -100  
0 or -100  
100  
100  
100  
0
100  
0
Read/Write  
1 = 1%; Negative percent is only available to OP2 when  
AL2 is set for Cooling.  
40219 Power High Limit  
Read/Write  
1 = 1%; Negative percent is only available to OP2 when  
AL2 is set for Cooling.  
40220 Sensor Failure Power Preset  
Read/Write  
40121  
40122  
40221 Dampening Time  
0
1
250  
250  
3
2
Read/Write 1 = 1 second  
Read/Write  
40222 On/Off Control Hysteresis  
ALARM 1 (AL1) OUTPUT PARAMETERS  
40131  
40132  
40133  
40134  
40135  
40231 Action  
0
0
0
1
0
8
1
3
0
0
1
0
Read/Write See Alarm Action Register Table.  
Read/Write 0 = Automatic, 1 = Latched  
Read/Write 0 = Disable, 1 = Enable  
Read/Write  
40232 Reset  
40233 Enable Standby Delay  
40234 Hysteresis  
40235 On Delay  
1
250  
32000  
Read/Write 1 = 1 second  
ALARM 2 (AL2) OUTPUT PARAMETERS  
40136  
40137  
40138  
40139  
40140  
40236 Action  
0
0
0
1
0
9
1
3
0
0
1
0
Read/Write See Alarm Action Register Table.  
Read/Write 0 = Automatic, 1 = Latched; Not for Cooling Action.  
Read/Write 0 = Disable, 1 = Enable; Not for Cooling Action.  
Read/Write Not for Cooling Action.  
40237 Reset  
40238 Enable Standby  
40239 Hysteresis  
40240 On Delay  
1
250  
32000  
Read/Write 1 = 1 second; Not for Cooling Action.  
NON-FUNCTIONAL IN REMOTE SETPOINT MODE (SEE 40198)  
Read/Write 1 = 0.1 second; 0 = OP2 Off  
Read/Write 1 = 0.1; 0 = On/Off Control  
Read/Write  
COOLING (OP2) PARAMETERS  
40141  
40142  
40143  
OUT 1  
40241 Cycle Time  
40242 Relative Gain  
40243 Deadband  
0
0
2500  
100  
20  
10  
0
-32000  
32000  
OUT 2  
ANALOG OUTPUT PARAMETERS  
ANALOG MODEL ONLY  
0(Out 1)  
6(Out 2)  
40301  
40309 Assignment  
0
11  
Read/Write See Analog Output Assignment Register Table.  
40302  
40303  
40304  
40305  
40306  
40307  
40308  
40310 Mode  
1
-32000  
-32000  
0
3
3
Read/Write 1 = 0-10 V, 2 = 0-20 mA, 3 = 4-20 mA  
40311 Scaling Value Low  
40312 Scaling Value High  
40313 Deadband  
32000  
32000  
250  
0
Read/Write Corresponds with 0 V, 0 mA or 4 mA output.  
Read/Write Corresponds with 10 V or 20 mA output.  
Read/Write 1 = 0.1%; Applies when Assignment is Output Power.  
Read/Write 0 = scan rate (10 updates/ sec) 1 = 1 second  
Read/Write Applies when Assignment is Direct Entry Value.  
Read/Write 1 = Applies averaging when Update Time is >=1  
1000  
0
0
0
0
40314 Update Time  
40315 Direct Entry Value  
40316 Filter  
0
250  
-32000  
0
32000  
1
1
2
3
For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.  
An attempt to exceed a limit will set the register to its high or low limit value.  
See MODBUS Calibration for procedure on restoring Factory Settings.  
24  
DLC REGISTER TABLE Continued  
REGISTER  
ADDRESS 1  
FACTORY  
ACCESS  
REGISTER NAME  
LOW LIMIT 2  
HIGH LIMIT 2  
COMMENTS  
SETTING 3  
CH A  
CH B  
SETPOINT CONTROLLER PROFILE PARAMETERS  
SETPOINT CONTROLLER MODEL ONLY  
0 = Stop (control at current active SP); 1 = Abort  
Read/Write (manual control, 0% power); 2 = Start; 3 = Resume; 4 =  
Pause  
40321  
40322  
40421 Profile Power Cycle Mode  
40422 Profile Error Band Mode  
0
0
4
3
1
0
0 = Disable Error Band, 1 = Error Band applies to  
Read/Write Ramp Phase 2 = Error Band applies to Hold Phase  
3 = Error Band applies to Both Ramp and Hold Phase  
1 = 1 process unit; During Hold phase, profile is paused  
when process error >= error band until process error  
(deviation) is within the Error band (Error Band - Error  
40323  
40423 Profile Error Band  
1
32000  
10  
Read/Write  
Band Hysteresis)  
40324  
40325  
40424 Profile Error Band Hysteresis  
40425 Profile End Segment  
0
1
250  
20  
2
1
Read/Write 1 = 1 Process Unit  
Read/Write Segment that ends the profile  
1 - 249 = Number of times to run profile  
Read/Write  
40326  
40327  
40426 Profile Cycle Count  
1
0
250  
1
1
0
250 = Run Profile continuously  
0 = Manual Mode, 0% power; 1 = Automatic Control at  
40427 Profile End Control Mode  
Read/Write  
last Setpoint  
SERIAL COMMUNICATION SETTINGS  
40401  
40402  
Unit (Node) Address  
Baud Rate  
1
0
1
0
0
2
247  
7
247  
5
Read/Write Node serial DLC address.  
Read/Write See Serial Baud Rate Register Table.  
Read/Write 1 = None, 2 = Even, 3 = Odd  
Read/Write 0 = 7 bits, 1 = 8 bits  
40403  
40404  
40405  
40406  
Parity  
3
1
Data Bits  
1
1
MODBUS Protocol  
Transmit Delay  
1
1
Read/Write 0 = ASCII Mode, 1 = RTU Mode  
Read/Write 2 = 2 msec; See Transmit Delay explanation.  
Changing 40401-40406 will not update the DLC until  
250  
2
40407 is 1. After a write, the communicating device  
must be changed to the new DLC settings and 40407  
40407  
Load Serial Settings  
0
1
0
Read/Write  
returns to 0.  
CALIBRATION  
40501  
40502  
Unit Calibration  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Read/Write See MODBUS Calibration explanation.  
Read/Write See MODBUS Calibration explanation.  
Calibration Data Register  
Non-Volatile Memory Write  
Disable  
0 = Enable writes, 1 = Disable writes; Returns to 0 at  
power cycle. Mirror of Coil 4.  
40503  
0
1
0
Read/Write  
40504  
40505  
Input Error Status Register  
N/A  
0
N/A  
N/A  
N/A  
0
Read Only  
Bits 0-7 are mirror of Coils 5-8/17-20, See Coils Table.  
Checksum Error Status Register  
Read/Write Bits 0-3 are mirror of Coils 1-3, See Coils Table.  
CHA  
CHB  
SETPOINT CONTROLLER PROFILE SEGMENTS  
SETPOINT CONTROLLER MODEL ONLY  
40601  
to  
40620  
40701  
to  
40720  
Setpoint Value Segment 1 - 20  
Ramp Rate Segment 1 - 20  
Hold Time Segment 1 - 20  
-32000  
32000  
32000  
9999  
Read/Write Limited by Setpoint Limit Low and Setpoint Limit High.  
40621  
to  
40640  
40721  
to  
40740  
1 = 0.1° per minute for input types 0-11, 0.1 ohms for  
Read/Write input type 12, 0.01 mV for input type 13, 0.1 process  
units for input types 14-15, 0 = Off  
0
0
40641  
to  
40741  
to  
Read/Write 1 = 0.1 minute  
40660  
40760  
RLC-DLC1xx00 (model) 2.00 version (maybe higher)  
Read Only  
41001-41010  
Slave ID  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
32 reads, 32 writes 16 scratch. See FC17 explanation.  
This area is for the user to store any related  
Read/Write information. This register area does not affect DLC  
operations.  
41101-41116  
GUID/Scratch Pad  
1
2
3
For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.  
An attempt to exceed a limit will set the register to its high or low limit value.  
See MODBUS Calibration for procedure on restoring Factory Settings.  
25  
COILS TABLE  
COIL ADDRESS  
COIL NAME  
MIRROR REGISTER  
ACCESS  
COMMENTS  
1 = Error; Causes Process Value to be 32100, Disables control and alarm outputs,  
causes flashing LEDs. Writing a zero clears the error.  
1
Calibration Checksum Error  
40505 (bit 0)  
Read/Write  
Read/Write  
Read/Write  
Read/Write  
1 = Error; Causes Process Value to be 32100, Disables control and alarm outputs,  
causes flashing LEDs. Writing a zero clears the error.  
2
3
4
Parameter Checksum Error  
40505 (bit 1)  
40505 (bit 2)  
40503  
Integral and Offset/Manual  
Power Checksum Error  
1 = Error; Causes Process Value to be 32100, Disables control and alarm outputs,  
causes flashing LEDs. Writing a zero clears the error.  
Non-Volatile Memory Write  
Disable  
1 = Disables writes to the non-volatile memory; Returns to 0(writes are enabled) at  
power cycle.  
CH A  
CH B  
1 = Shorted RTD; Causes process value to be -32002, disables alarms, sets control  
output(s) to sensor failure power preset level, causes flashing LEDs.  
5
17  
Shorted RTD Input Error  
40504  
40504  
40504  
40504  
40504  
40504  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Read Only  
Open Thermocouple, RTD, or  
Extreme Process Input Over/  
Under Range Input Error  
1 = Input Error; Causes process value to be 32002, disables alarms, sets control  
output(s) to sensor failure power preset level, causes flashing LEDs.  
6
7
18  
19  
Signal or Sensor Under  
Range Input Error  
1 = Under Range Error; Causes process value to be -32001, maintains control  
output at present level, causes flashing LEDs.  
1 = Under Range Error; Causes process value to be -32003, maintains control  
output at present level until input causes Sensor FailurePower Preset Level, causes  
flashing LEDs.  
Process Value (<-32000)  
Under Range Input Error  
Signal or Sensor Over  
Range Input Error  
1 = Over Range Error; Causes process value to be 32001, maintains control output  
at present level, causes flashing LEDs.  
8
20  
1 = Over Range Error; Causes process value to be 32003, maintains control output  
at present level until input causes Sensor FailurePower Preset Level, causes  
flashing LEDs.  
Process Value (>32000)  
Over Range Input Error  
9
21  
22  
23  
24  
25  
26  
27  
28  
Control Output OP1 State  
Alarm 1 Output AL1 State  
Alarm 2 Output AL2/OP2 State  
Control Mode  
40014/40030  
40015/40031  
40016/40032  
40041/40049  
40042/40050  
40043/40051  
40044/40052  
40011/40027  
Read Only  
Read/Write  
Read/Write  
Read/Write  
Read/Write  
Read Only  
Read/Write  
Read/Write  
0 = Off, 1 = On  
10  
11  
12  
13  
14  
15  
16  
0 = Off, 1 = On; A write of 1 is only possible when alarm is set for Manual.  
0 = Off, 1 = On; A write of 1 is only possible when alarm is set for Manual.  
0 = Automatic Mode, 1 = Manual Mode  
0 = Enabled, 1 = Disabled  
Disable Setpoint Ramping  
Setpoint Ramping In Process  
Disable Integral Action  
Auto-Tune Start  
0 = No, 1 = Yes  
0 = Enabled, 1 = Disabled  
0 = Stop, 1 = Start  
SETPOINT CONTROLLER MODEL ONLY  
1 = Checksum Error in A or B Setpoint Controller Segment memory (40601-40760),  
causes process value to be 32100 disables control and alarm outputs, causes  
flashing LEDs.  
1 = Checksum Error in A or B Setpoint Controller Operating Status memory, disables  
control and alarm outputs, causes flashing LEDs, and aborts profile putting channel  
in manual control at 0% power.  
Setpoint Controller Segment  
Memory Checksum Errror  
29  
30  
40505 (bit 4)  
Read/Write  
Read/Write  
Setpoint Controller Status  
Memory Checksum Error  
40505 (bit 5)  
31  
32  
Advance Profile Phase  
40070/40078  
40046  
Read/Write  
Read/Write  
1 = Advance running Profile to next phase  
0 = Local Setpoint; 1 = Remote Setpoint  
33  
Local/Remote Setpoint Select  
ALARM 1 (40131/40231) AND ALARM 2  
(40136/40236) ACTION REGISTER TABLE  
INPUT TYPE REGISTER (40101/40201) TABLE  
MODE  
9
10  
11  
12  
13  
14  
15  
16  
17  
TYPE  
MODE  
TYPE  
RTD platinum 385  
RTD platinum 392  
RTD nickel 672  
0
1
2
3
4
5
6
7
8
Thermocouple - T  
Thermocouple - E  
Thermocouple - J  
Thermocouple - K  
Thermocouple - R  
Thermocouple - S  
Thermocouple - B  
Thermocouple - N  
Thermocouple - C  
MODE  
ACTION  
0
1
2
3
4
5
6
7
8
9
Manual  
Absolute HI (Balanced)  
Absolute LO (Balanced)  
Absolute HI (Unbalanced)  
Absolute LO (Unbalanced)  
Deviation HI  
Deviation LO  
Band Inside Acting  
Band Outside Acting  
Cooling (Alarm 2 only)  
Linear Ohms  
Linear mV (1 = 10mV)  
Process Voltage  
Process Current  
Process Voltage, Square Root Ext.  
Process Current, Square Root Ext.  
ANALOG OUTPUT ASSIGNMENT REGISTER  
(400301/40309) TABLE  
MODE  
ASSIGNMENT  
Output Power A  
Process Value A  
Setpoint A  
0
1
2
SERIAL BAUD RATE REGISTER (40402) TABLE  
3
4
5
6
7
8
9
10  
11  
Ramping Setpoint A  
Deviation A  
Direct Entry Value 1  
Output Power B  
Process Value B  
Setpoint B  
Ramping Setpoint B  
Deviation B  
Direct Entry Value 2  
MODE  
BAUD  
300  
600  
1200  
2400  
4800  
9600  
19200  
38400  
0
1
2
3
4
5
6
7
26  
TROUBLESHOOTING  
PROBLEM  
CAUSE  
REMEDIES  
Power LED will not light  
Controller power  
Check controller power connections and voltage level  
Process Value not changing or incorrect  
Input signal  
Incorrect channel  
Incorrect programming  
Check input signal connections and signal level  
Check proper channel setup, reading and connections  
Check input setup, scaling values, and re-download  
Alarms not functioning properly  
Calculated trigger points are over +32000 or below -32000  
Input Signal (sensor) under-range or over-range *  
Shorted RTD sensor *  
Adjust alarm value, alarm hysteresis, and setpoint  
value to ensure valid trigger points  
Process Value stays at -32001 or +32001  
Process Value stays at -32002  
Check input type, level, channel, jumpers and  
re-download. Replace sensor. Perform calibration.  
Check input sensor, level, channel, jumpers and  
re-download. Replace probe.  
Process Value stays at +32002  
Open TC or RTD sensor *  
Check input sensor, level, channel, jumpers and  
re-download. Replace probe.  
Process Value stays at -32003 or +32003  
Process Value underrange (<-32000) or overrange (>+32000) Check input level, scaling, jumpers and re-download  
Process Value stays at +32100, All LEDs  
Flashing, Alarms disabled  
Parameter checksum error †  
Calibration checksum error †  
Re-download SFDLC file  
Perform calibration procedure  
Integral and Offset/Manual Power checksum error †  
Setpoint Controller Segment Memory checksum error †  
Consult Factory  
Check A & B Setpoint Ramp Rate and Hold Time  
Segments. Change minimum of 1 segment register for  
each channel to cause a new checksum to be written  
Consult Factory  
Setpoint Controller Status Memory checksum error †  
Will not communicate (Comm. LED not flashing) Incorrect serial settings (DLC port)  
Incorrect serial settings (computer port)  
Verify DLC communications setup  
Go to pull down menu SETTINGS,PC PORT SETTING  
Try switching A+ and B- lines  
Incorrect wiring  
Note: The DLC serial settings must match the device that it is communicating with. If you do not know or cannot recall  
the DLC settings, they can be reset back to factory defaults. Simply jumper the Default Serial terminal to Input  
Common or by putting the Default Serial setting DIP switch in the “UP” position.  
* Can also be monitored by accessing coils 5-8 and 17-20, or register 40504.  
Can also be monitored by accessing coils 1-3, 29-30 or register 40505.  
For further technical assistance, contact technical support.  
27  
LIMITED WARRANTY  
(a) Red Lion Controls Inc., Sixnet Inc., N-Tron Corporation, or Blue Tree Wireless Data, Inc. (the “Company”) warrants that all  
Products shall be free from defects in material and workmanship under normal use for the period of time provided in “Statement  
of Warranty Periods” (available at www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”).  
EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH  
RESPECT TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF  
FITNESS FOR A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL  
PROPERTY RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEALING,  
COURSE OF PERFORMANCE, USAGE OF TRADE OR OTHERWISE. Customer shall be responsible for determining that  
a Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law.  
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a result of Customer’s  
failure to store, install, commission or maintain the Product according to specifications; (ii) Customer alters or repairs such  
Product without the prior written consent of Company.  
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its sole discretion,  
either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that, if Company so requests, Customer  
shall, at Company’s expense, return such Product to Company.  
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE  
REMEDY AND COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET  
FORTH IN PARAGRAPH (a).  
Red Lion Controls  
China  
Red Lion Controls  
Headquarters  
20 Willow Springs Circle  
York PA 17406  
Tel +1 (717) 767-6511  
Fax +1 (717) 764-0839  
Red Lion Controls  
Europe  
Softwareweg 9  
Red Lion Controls  
India  
201-B, 2nd Floor, Park Centra  
Opp 32 Mile Stone, Sector-30  
Gurgaon-122002 Haryana, India  
Tel +91 984 487 0503  
Unit 1102, XinMao Plaza  
Building 9, No.99 Tianzhou Road  
ShangHai, P.R. China 200223  
Tel +86 21 6113 3688  
Fax +86 21 6113 3683  
NL - 3821 BN Amersfoort  
Tel +31 (0) 334 723 225  
Fax +31 (0) 334 893 793  

相关型号:

CBJ11BD5

DUAL LOOP CONTROLLER
REDLION

CBJ157

Triaxial Connector, 1 Contact(s), Female, Board Mount, Solder Terminal, Locking, Jack,
BEL

CBJ3157

Triaxial Connector, 1 Contact(s), Board Mount, Solder Terminal, Locking, Jack,
BEL

CBJE130-2

RF Connector, 1 Contact(s), Female, Board Mount, Surface Mount Terminal, Jack
BEL

CBJR157

Triaxial Connector, 1 Contact(s), Female, Locking, Jack,
BEL

CBJR3157

Triaxial Connector, 1 Contact(s), Female, Locking, Jack,
BEL

CBJR70

Triaxial Connector, 1 Contact(s), Female, Board Mount, Solder Terminal, Locking,
BEL

CBJR70A

Triaxial Connector, 1 Contact(s), Female, Board Mount, Solder Terminal, Locking,
BEL

CBK-0505SF

DC-DC Regulated Power Supply Module, 1 Output
TDK

CBK-0512DF

DC-DC Regulated Power Supply Module, 2 Output
TDK

CBK-0515DF

DC-DC Regulated Power Supply Module, 2 Output
TDK

CBK-0515SF

暂无描述
TDK