Characteristics
TeSys K control relay - 3 NO + 1 NC - <= 690 V -
120 V AC coil
Price* : 26.33 GBP
Main
Range
TeSys
Product name
TeSys CAK
Control relay
CA2K
Product or component type
Device short name
Contactor application
Utilisation category
Control circuit
DC-13
AC-15
Pole contact composition
[Ue] rated operational voltage
Control circuit type
3 NO + 1 NC
<= 690 V <= 400 Hz
AC at 50/60 Hz
[Uc] control circuit voltage
120 V AC 50/60 Hz
Complementary
[Ith] conventional free air thermal
current
10 A (at 50 °C)
Irms rated making capacity
Associated fuse rating
110 A conforming to IEC 60947
10 A gG conforming to IEC 60947
10 A gG conforming to VDE 0660
[Ui] rated insulation voltage
690 V conforming to IEC 60947
750 V conforming to VDE 0110 group C
690 V conforming to BS 5424
600 V conforming to CSA C22.2 No 14
Mounting support
Rail
Plate
Connections - terminals
Screw clamp terminals 1 cable(s) 1.5…4 mm²solid
Screw clamp terminals 2 cable(s) 1.5…4 mm²solid
Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 0.34…1.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible without cable end
Aug 16, 2019
1
Tightening torque
1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm
Control circuit voltage limits
Operating time
Drop-out: 0.2...0.75 Uc (at <50 °C)
Operational: 0.8...1.15 Uc (at <50 °C)
10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
15...25 ms coil de-energisation and NC closing
5...15 ms coil energisation and NC opening
Mechanical durability
Maximum operating rate
Immunity to microbreaks
Inrush power in VA
Hold-in power consumption in VA
Heat dissipation
10 Mcycles
10000 cyc/h
2 ms
30 VA (at 20 °C)
4.5 VA (at 20 °C)
1.3 W
Minimum switching voltage
Minimum switching current
Non overlap distance
Insulation resistance
Height
17 V
5 mA
0.5 mm
> 10 MOhm
58 mm
Width
45 mm
Depth
57 mm
Net weight
0.18 kg
Environment
Standards
BS 5424
IEC 60947
NF C 63-140
VDE 0660
Product certifications
UL
CSA
IP degree of protection
IP2x
Protective treatment
TC conforming to IEC 60068
-25…50 °C
Ambient air temperature for operation
Ambient air temperature for storage
Operating altitude
-50…80 °C
2000 m without
Flame retardance
V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
Mechanical robustness
Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Offer Sustainability
Sustainable offer status
REACh Regulation
Green Premium product
REACh Declaration
EU RoHS Directive
Not applicable, out of EU RoHS legal scope
EU RoHS Declaration
Mercury free
Yes
Yes
RoHS exemption information
China RoHS Regulation
Download RoHS China Declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
Circularity Profile
WEEE
Product Environmental Profile
End of Life Information
The product must be disposed on European Union markets following specific waste collection and