FAL12020 [SCHNEIDER]
Thermal Magnetic Circuit Breaker,;![FAL12020](http://pdffile.icpdf.com/pdf2/p00233/img/icpdf/FAL12020_1367822_icpdf.jpg)
型号: | FAL12020 |
厂家: | ![]() |
描述: | Thermal Magnetic Circuit Breaker, 电路保护 |
文件: | 总2页 (文件大小:63K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
Product data sheet
FAL12020
Characteristics
FA/LA MOLDED CASE CIRCUIT BREAKER
240V, 20A, 1P
Product availability : Stock - Normally stocked in distribution facility
Price* : 356.40 USD
Main
Product or component type
Range of product
Trip Unit Type
Rating Code
Circuit breaker
I-Line
Thermal-magnetic
A
Complementary
Line Rated Current
Number of Poles
Interrupt Rating
20 A
1P
5 kA at 125 V DC
10 kA at 120 V AC
System Voltage
Mounting mode
120 V AC
Unit mount
Electrical connection
Lugs load
Lugs line
Wire Gauge
AWG 14...AWG 4 (copper) 1 cable(s)
AWG 12...AWG 4 (aluminium) 1 cable(s)
Terminal Type
Magnetic hold current
Magnetic tripping current
Phase connection
Height
AL50FA
275 A
600 A
ABC
6.4 in
1.5 in
4.13 in
Width
Depth
Environment
Product certifications
CSA
UL listed
May 3, 2019
1
Ordering and shipping details
Category
00901 - FAL 240V BREAKERS & SWITCH
Discount Schedule
GTIN
DE2
00785901342465
Nbr. of units in pkg.
Package weight(Lbs)
Returnability
1
1.97
N
Country of origin
MX
Offer Sustainability
Sustainable offer status
RoHS (date code: YYWW)
Green Premium product
Compliant - since 1304 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile
Product end of life instructions
California proposition 65
- - - - - - - Substance 1
Available
Need no specific recycling operations
WARNING: This product can expose you to chemicals including:
DINP, which is known to the State of California to cause cancer, and
DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
For more information go to www.p65warnings.ca.gov
- - - - - - - Substance 2
- - - - - - - More information
Contractual warranty
Warranty period
18 months
FAL12020 is replaced by:
Unit Mount BDL16020
PowerPact-circuit breaker-20A 1P AC 18kA at 480/440V(UL/IEC)-TMD-EverLink lug
Qty 1
Reason for Substitution: End of life | Substitution date: 30 June 2019 | (Ref #) is replaced by (New Ref #)
2
相关型号: