Characteristics  
TeSys GV2 - Circuit breaker - thermal-magnetic -  
17...23 A - spring terminals  
Price* : 69.90 GBP  
Main  
Range  
TeSys  
Product name  
Device short name  
Device application  
Trip unit technology  
TeSys GV2  
GV2ME  
Motor  
Thermal-magnetic  
Complementary  
Poles description  
Network type  
3P  
AC  
Utilisation category  
AC-3 conforming to IEC 60947-4-1  
Category A conforming to IEC 60947-2  
Network frequency  
Fixing mode  
50/60 Hz conforming to IEC 60947-4-1  
Clipped on 35 mm symmetrical DIN rail  
Screwed on panel (with adaptor plate)  
Operating position  
Motor power kW  
Any position  
11 kW at 400/415 V AC 50/60 Hz  
11 kW at 500 V AC 50/60 Hz  
9 kW at 400/415 V AC 50/60 Hz  
Breaking capacity  
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2  
15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2  
50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2  
6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2  
4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2  
[Ics] rated service short-circuit  
breaking capacity  
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2  
40 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2  
50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2  
75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2  
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2  
Control type  
Push-button  
23 A  
[In] rated current  
May 24, 2019  
1
Thermal protection adjustment range  
Magnetic tripping current  
17...23 A  
327 A  
[Ue] rated operational voltage  
[Ui] rated insulation voltage  
690 V AC 50/60 Hz conforming to IEC 60947-2  
690 V AC 50/60 Hz conforming to IEC 60947-2  
23 A conforming to IEC 60947-4-1  
[Ith] conventional free air thermal  
current  
[Uimp] rated impulse withstand voltage  
Power dissipation per pole  
Mechanical durability  
Electrical durability  
6 kV conforming to IEC 60947-2  
2.5 W  
100000 cycles  
100000 cycles for AC-3 at 440 V  
25 cyc/h  
Operating rate  
Rated duty  
Continuous conforming to IEC 60947-4-1  
Connections - terminals  
Spring terminals 2 cable(s) 1...6 mm² solid  
Spring terminals 2 cable(s) 1.5...4 mm² flexible without cable end  
Suitability for isolation  
Phase failure sensitivity  
Height  
Yes conforming to IEC 60947-1  
Yes conforming to IEC 60947-4-1  
101 mm  
45 mm  
Width  
Depth  
78.2 mm  
0.28 kg  
Product weight  
Environment  
Standards  
EN 60204  
IEC 60947-1  
IEC 60947-2  
IEC 60947-4-1  
NF C 63-120  
NF C 63-650  
NF C 79-130  
UL 508  
VDE 0113  
VDE 0660  
CSA C22.2  
Product certifications  
ATEX  
BV  
CCC  
CEBEC  
CSA  
DNV  
EZU  
GL  
LROS (Lloyds register of shipping)  
RINA  
SETI  
TSE  
UL  
EAC  
Protective treatment  
TH  
IP degree of protection  
IK degree of protection  
Ambient air temperature for operation  
Ambient air temperature for storage  
Fire resistance  
IP20 conforming to IEC 60529  
IK04  
-20...60 °C  
-40...80 °C  
960 °C conforming to IEC 60695-2-1  
2000 m  
Operating altitude  
Offer Sustainability  
Sustainable offer status  
RoHS (date code: YYWW)  
Green Premium product  
Compliant - since 0631 - Schneider Electric declaration of conformity  
Schneider Electric declaration of conformity  
REACh  
2
Reference contains SVHC above the threshold - Go to CaP for more details  
Go to CaP for more details  
Available  
Product environmental profile  
Product end of life instructions  
Product Environmental Profile  
Need no specific recycling operations  
Contractual warranty  
Warranty period  
18 months  
3
Product datasheet  
GV2ME213  
Performance Curves  
Thermal-Magnetic Tripping Curves for GV2ME and GV2P  
Average Operating Times at 20 °C Related to Multiples of the Setting Current  
1
2
3
3 poles from cold state  
2 poles from cold state  
3 poles from hot state  
Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))  
Dynamic Stress  
I peak = f (prospective Isc) at 1.05 Ue = 435 V  
4
1
Maximum peak current  
2
24-32 A  
3
20-25 A  
4
17-23 A  
5
13-18 A  
6
9-14 A  
7
6-10 A  
8
4-6.3 A  
9
2.5-4 A  
10  
11  
12  
1.6-2.5 A  
1-1.6 A  
Limit of rated ultimate breaking capacity on short-circuit of GV2ME (14, 18, 23, and 25 A ratings).  
Thermal Limit on Short-Circuit for GV2ME  
Thermal Limit in kA2s in the Magnetic Operating Zone  
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V  
5
1
2
3
4
5
6
7
8
9
10  
24-32 A  
20-25 A  
17-23 A  
13-18 A  
9-14 A  
6-10 A  
4-6.3 A  
2.5-4 A  
1.6-2.5 A  
1-1.6 A  
6
Product datasheet  
GV2ME213  
Dimensions Drawings  
Dimension  
GV2ME  
(1)  
Maximum  
X1 Electrical clearance = 40 mm for Ue ≤ 690 V  
b
GV2ME●●  
GV2ME●●  
89  
101  
3
Mounting  
GV2ME  
On 35 mm rail  
c = 78.5 on AM1 DP200 (35 x 7.5)  
c = 86 on AM1 DE200, ED200 (35 x 15)  
On panel with adapter plate GV2AF02  
On pre-slotted plate AM1 PA  
On rails DZ5 MB201  
7
GV2AF01  
Combination GV2ME + TeSys k contactor  
GV2AF3  
Combination GV2ME + TeSys d contactor  
GV2ME +  
LC1D09…D18  
176.4  
LC1D25 and D32  
186.8  
b
c1  
c
94.1  
100.4  
99.6  
105.9  
GV2AF4 + LAD311  
Combination GV2ME + TeSys d contactor  
GV2ME +  
LC1D09…D18  
176.4  
LC1D25 and D32  
186.8  
b
c1  
c
103.1  
136.4  
135.6  
141.9  
d1  
d
107  
107  
112.5  
112.5  
GV2ME + GV1L3 (Current Limiter)  
8
X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue ≤ 690 V  
9
Product datasheet  
GV2ME213  
Connections and Schema  
GV2ME•• and GV2RT  
Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only  
10  

相关型号:

GV2ME21TQ

Thermal Magnetic Circuit Breaker,
SCHNEIDER

GV2ME226

Thermal Magnetic Circuit Breaker,
SCHNEIDER

GV2ME22TQ

Thermal Magnetic Circuit Breaker,
SCHNEIDER

GV2ME32

Thermal Magnetic Circuit Breaker, 3 Pole(s), 32A, 690VAC, Panel Mount
SCHNEIDER

GV2ME326

Thermal Magnetic Circuit Breaker,
SCHNEIDER

GV2ME32TQ

Thermal Magnetic Circuit Breaker,
SCHNEIDER

GV2MP01

Manual Motor Starters, Controllers, and Protectors
ETC

GV2MP02

Manual Motor Starters, Controllers, and Protectors
ETC

GV2MP03

Manual Motor Starters, Controllers, and Protectors
ETC

GV2MP04

Manual Motor Starters, Controllers, and Protectors
ETC

GV2N01

Manual Motor Starters, Controllers, and Protectors
ETC

GV2P07

Accurate and reliable control of motors
ETC