LC1D50A6P7 [SCHNEIDER]
TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 50 A - 230 V AC 50/60 Hz coil;型号: | LC1D50A6P7 |
厂家: | SCHNEIDER ELECTRIC |
描述: | TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 50 A - 230 V AC 50/60 Hz coil |
文件: | 总4页 (文件大小:144K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Product data sheet
LC1D50A6P7
Characteristics
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V
50 A - 230 V AC 50/60 Hz coil
Product availability : Non-Stock - Not normally stocked in distribution facility
Price* : 246.00 USD
Main
Range
TeSys
Product name
TeSys D
Contactor
LC1D
Product or component type
Device short name
Contactor application
Resistive load
Motor control
Utilisation category
AC-3
AC-1
AC-4
Poles description
3P
Power pole contact composition
[Ue] rated operational voltage
3 NO
Power circuit: <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current
Motor power kW
50 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
80 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
15 kW 220...230 V AC 50/60 Hz AC-3)
22 kW 380...400 V AC 50/60 Hz AC-3)
30 kW 500 V AC 50/60 Hz AC-3)
33 kW 660...690 V AC 50/60 Hz AC-3)
25 kW 415 V AC 50/60 Hz AC-3)
30 kW 440 V AC 50/60 Hz AC-3)
11 kW 400 V AC 50/60 Hz AC-4)
Motor power HP (UL / CSA)
3 hp 115 V AC 50/60 Hz 1 phase
7.5 hp 230/240 V AC 50/60 Hz 1 phase
15 hp 200/208 V AC 50/60 Hz 3 phase
15 hp 230/240 V AC 50/60 Hz 3 phase
40 hp 460/480 V AC 50/60 Hz 3 phase
40 hp 575/600 V AC 50/60 Hz 3 phase
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
230 V AC 50/60 Hz
* Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
Jan 4, 2021
1
Auxiliary contact composition
[Uimp] rated impulse withstand voltage
Overvoltage category
1 NO + 1 NC
6 kV conforming to IEC 60947
III
[Ith] conventional free air thermal
current
10 A 140 °F (60 °C) signalling circuit
80 A 140 °F (60 °C) power circuit
Irms rated making capacity
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
900 A 440 V power circuit IEC 60947
Rated breaking capacity
900 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current
400 A 40 °C - 10 s for power circuit
810 A 40 °C - 1 s for power circuit
84 A 40 °C - 10 min for power circuit
208 A 40 °C - 1 min for power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
Associated fuse rating
10 A gG signalling circuit IEC 60947-5-1
100 A gG <= 690 V type 1 power circuit
100 A gG <= 690 V type 2 power circuit
Average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
[Ui] rated insulation voltage
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Power circuit 690 V IEC 60947-4-1
Electrical durability
1.45 Mcycles 50 A AC-3 <= 440 V
1.1 Mcycles 80 A AC-1 <= 440 V
Power dissipation per pole
3.7 W AC-3
9.6 W AC-1
Front cover
With
Mounting support
Rail
Plate
Standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product certifications
DNV
LROS (Lloyds register of shipping)
CCC
GL
RINA
BV
GOST
CSA
UL
Connections - terminals
Tightening torque
Control circuit: lugs-ring terminals (external diameter: 8 mm)
Power circuit: lugs-ring terminals (external diameter: 16.5 mm)
Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5
Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5
Power circuit: 6 N.m - on lugs-ring terminals hexagonal screw head 10 mm M6
Operating time
4...19 ms opening
12...26 ms closing
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6 Mcycles
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Complementary
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
2
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA
140 VA 60 Hz cos phi 0.75 (at 20 °C)
160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA
13 VA 60 Hz 0.3 68 °F (20 °C))
15 VA 50 Hz 0.3 68 °F (20 °C))
Heat dissipation
4…5 W at 50/60 Hz
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency
Minimum switching current
Minimum switching voltage
Non-overlap time
25...400 Hz
5 mA signalling circuit
17 V signalling circuit
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Insulation resistance
Contact compatibility
Compatibility code
> 10 MOhm signalling circuit
M2
LC1D
Environment
IP degree of protection
IP20 front face IEC 60529
Protective treatment
TH IEC 60068-2-30
3
Pollution degree
Ambient air temperature for operation
-40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating
Ambient air temperature for storage
Operating altitude
-76…176 °F (-60…80 °C)
0...9842.52 ft (0...3000 m)
1562 °F (850 °C) IEC 60695-2-1
V1 UL 94
Fire resistance
Flame retardance
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz
Vibrations contactor closed4 Gn, 5...300 Hz
Shocks contactor closed15 Gn for 11 ms
Shocks contactor open10 Gn for 11 ms
Height
4.80 in (122 mm)
2.17 in (55 mm)
Width
Depth
4.72 in (120 mm)
1.88 lb(US) (0.855 kg)
Net Weight
Ordering and shipping details
Category
22357 - CTR,TESYS D,OPEN,40-65A AC
Discount Schedule
GTIN
I12
00785901606666
Nbr. of units in pkg.
Package weight(Lbs)
Returnability
1
1.87 lb(US) (0.85 kg)
No
FR
Country of origin
Packing Units
Unit Type of Package 1
Package 1 Height
Package 1 width
PCE
2.36 in (6 cm)
5.51 in (14 cm)
5.91 in (15 cm)
Package 1 Length
Offer Sustainability
Sustainable offer status
Green Premium product
3
California proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony
trioxide, which is known to the State of California to cause cancer. For more information go to
www.P65Warnings.ca.gov
REACh Regulation
REACh free of SVHC
EU RoHS Directive
REACh Declaration
Yes
Compliant
EU RoHS Declaration
Toxic heavy metal free
Mercury free
Yes
Yes
Yes
RoHS exemption information
China RoHS Regulation
China RoHS declaration
Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure
Circularity Profile
WEEE
Product Environmental Profile
End of Life Information
The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins.
PVC free
Yes
Contractual warranty
Warranty
18 months
4