M9U21125 [SCHNEIDER]
Multi 9 - C60H-DC - MCB - 1P - 25 A - C Curve - 250 V DC - 10 kA;型号: | M9U21125 |
厂家: | SCHNEIDER ELECTRIC |
描述: | Multi 9 - C60H-DC - MCB - 1P - 25 A - C Curve - 250 V DC - 10 kA |
文件: | 总3页 (文件大小:87K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Product data sheet
M9U21116
Characteristics
Multi 9 - C60H-DC - MCB - 1P - 16 A - C Curve -
250 V DC - 10 kA
Product availability : Non-Stock - Not normally stocked in distribution facility
Price** : 182.00 USD
Main
Range
Multi 9
Product name
Multi 9 C60H-DC
Product or component type
Device short name
Device application
Poles description
Number of protected poles
Line Rated Current
Network type
Miniature circuit-breaker
C60H-DC
Distribution
1P
1
16 A 77 °F (25 °C) EN/IEC 60947-2
DC
Trip unit technology
Curve code
Thermal-magnetic
C
Breaking capacity
10 kA Icu 220 V DC EN/IEC 60947-2
6 kA Icu 250 V DC EN/IEC 60947-2
20 kA Icu 110 V DC EN/IEC 60947-2
5 kA AIR 12...250 V DC UL 1077
10 kA Icu 220 V DC GB 14048.2
6 kA Icu 250 V DC GB 14048.2
20 kA Icu 110 V DC GB 14048.2
Utilisation category
Suitability for isolation
Standards
Category A EN/IEC 60947-2
Yes EN/IEC 60947-2
EN/IEC 60947-2
GB 14048.2
UL 1077
Product certifications
IEC
CCC
UR
Complementary
[Ue] rated operational voltage
250 V DC
110 V DC
220 V DC
Magnetic tripping limit
7...10 x In DC
[Ics] rated service breaking capacity
7.5 kA 75 % EN/IEC 60947-2 - 220 V DC
4.5 kA 75 % EN/IEC 60947-2 - 250 V DC
Mar 10, 2020
1
15 kA 75 % EN/IEC 60947-2 - 110 V DC
7.5 kA 75 % GB 14048.2 - 220 V DC
4.5 kA 75 % GB 14048.2 - 250 V DC
15 kA 75 % GB 14048.2 - 110 V DC
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
Contact position indicator
Control type
500 V DC EN/IEC 60947-2
6 kVEN/IEC 60947-2
Yes
Toggle
Local signalling
Mounting mode
Mounting support
9 mm pitches
ON/OFF indication
Clip-on
DIN rail
2
Height
3.19 in (81 mm)
0.71 in (18 mm)
2.87 in (73 mm)
0.28 lb(US) (0.128 kg)
Grey
Width
Depth
Net weight
Color
Mechanical durability
Electrical durability
20000 cycles
3000 cycles 250 V DC L/R = 2 ms
6000 cycles 250 V DC
Provision for padlocking
Connections - terminals
Padlockable
Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) AWG 18...AWG 4) - rigid stranded
Tunnel type terminal top or bottom) 0.00…0.02 in² (1…16 mm²) AWG 18...AWG 6) - flexible
Tunnel type terminal top or bottom) 0.00…0.02 in² (1…16 mm²) AWG 18...AWG 6) - flexible with
ferrule
Tunnel type terminal top or bottom) - 2 0.00…0.02 in² (1…10 mm²) AWG 18...AWG 8) - rigid stranded
Tunnel type terminal top or bottom) - 2 0.00…0.02 in² (1…10 mm²) AWG 18...AWG 8) - flexible
Tunnel type terminal top or bottom) - 2 0.00…0.02 in² (1…10 mm²) AWG 18...AWG 8) - flexible with
ferrule
Tunnel type terminal top or bottom) - 3 0.00 in² (1 mm²) AWG 18) - flexible stranded
Wire stripping length
Tightening torque
0.55 in (14 mm) top or bottom
22.13 lbf.in (2.5 N.m) top or bottom
Without
Earth-leakage protection
Environment
Heat dissipation
2.5 W 220 V - 16 A
IP degree of protection
IP20IEC 60529
IP40 modular enclosure)IEC 60529
Pollution degree
Tropicalisation
3 EN/IEC 60947-2
2 IEC 60068-2
2 GB 14048.2
Relative humidity
95 % 131 °F (55 °C)
Ambient air temperature for operation
Ambient air temperature for storage
-13…158 °F (-25…70 °C)
-40…185 °F (-40…85 °C)
Ordering and shipping details
Category
00948 - M9 GEN 2 CB UL1077 / IEC
Discount Schedule
GTIN
DE2
00785901774792
Returnability
No
Country of origin
CN
Offer Sustainability
REACh Regulation
REACh free of SVHC
EU RoHS Directive
REACh Declaration
Yes
Compliant
EU RoHS Declaration
2
Toxic heavy metal free
Mercury free
Yes
Yes
Yes
RoHS exemption information
China RoHS Regulation
China RoHS declaration
Pro-active China RoHS declaration (out of China RoHS legal scope)
WEEE
The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins.
3