3-101-226 [SCHURTER]
Thermal Circuit Breaker,;型号: | 3-101-226 |
厂家: | SCHURTER INC. |
描述: | Thermal Circuit Breaker, 电路保护 |
文件: | 总4页 (文件大小:326K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Thermal (T- and TA-Line)
T9-817
https://www.schurter.com /PG17_18_19
Circuit Breaker for Equipment thermal vertical, THT terminals for PCB mounting, 1 pole
See below:
Approvals and Compliances
Description
Applications
- Thermal circuit breaker
- 1-pole
- Power supplies
- Uninterruptible power supply
- Power tools
- On request available with elevaled glow-wire ratings
- THT connectors
- Industrial appliances
- HVAC
- Household appliances
Unique Selling Proposition
- Reset type
- Cycling trip-free release
- Compact design
- Different mounting possibilities
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News, Video
Technical Data
Rated Voltage AC
Rated Voltage DC
Rated current
Conditional short circuit ca-
pacity
240 V, 50 / 60 Hz
48 V
4-12 A
Ambient temperature
5-12 A: -5 °C to 60 °C
4 A: -5°C to 50 °C
Wave
245°C / 3sec acc. to IEC 60068-2-
20 / Test Ta, method 1
Soldering Methods
Solderability
IEC: Inc, PC1, AC 240 V: 2 kA
UL / CSA: SC, AC 240 V DC 48 / 32 V:
2 kA, C1
Resistance to Soldering Heat 260°C / 10sec acc. to IEC 60068-2-
20 / Test Tb, method 1A
Degree of protection front side IP 40
Weight
approx. 12.5 g
Endurance minimum
IEC: 200% Ir, cos φ 0.6: min. 50 swit-
ching cycles
Endurance typical
4-8 A: 150% Ir, cos φ 0.9:
2500switching cycles
10-12 A: 150% Ir, cos φ 0.9:
6000switching cycles
1500VAC
Dielectric Strength
Insulation Resistance
500 VDC > 1000 MΩ
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: T9
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
VDE Certificate Number: 40038016
UL Approvals
UL
UL File Number: E71572
CQC Approvals
CQC
CCC Certificate Number: 2013010307617688
1
Circuit Breakers
Thermal (T- and TA-Line)
T9-817
https://www.schurter.com /PG17_18_19
Product standards
Product standards that are referenced
Organization
Design
Standard
Description
Designed according to
IEC 60934
Circuit-breakers for equipment (CBE)
Designed according to
Designed according to
Designed according to
UL 1077
Standard for Supplementary Protectors for Use in Electrical Equipment
Supplementary Protectors
CSA C22.2 No. 235
GB 17701
Circuit-breaker for equipment
Application standards
Application standards where the product can be used
Organization
Design
Standard
Description
Designed for applications acc.
IEC/UL 60950
IEC 60950-1 includes the basic requirements for the safety of information
technologyequipment.
Compliances
The product complies with following Guide Lines
Identification
Details
Initiator
Description
CE declaration of conformity
SCHURTER AG
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
RoHS
SCHURTER AG
SCHURTER AG
SCHURTER AG
EU Directive RoHS 2011/65/EU
China RoHS
REACH
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
Dimension [mm]
Ø9.5
Ø7.8
12.2
7.8 6.8
6.3
3.95 4.3
2.3
2
6.3
9.2
Approval
Rated current
Rated voltage AC
Rated voltage DC
UL 1077
4 - 12 A
240 V
240 V
240 V
48 V
CSA 22.2 235
IEC 60934
4 - 12 A
4 - 12 A
48 V
48 V
GB 17701
4 - 12 A
240 V
48 V
2
Circuit Breakers
Thermal (T- and TA-Line)
T9-817
https://www.schurter.com /PG17_18_19
Typical internal resistance
Rated Current [A]
Internal Resistance [mΩ]
4
5
26.3
24.1
19.0
18.0
14.8
13.0
12.7
6
7
8
10
12
Time-Current-Curves
[min]
[sec]
10'000
T9
5 A -16 A (TC-1)
4 A (TC-2)
60
30
20
1'000
10
5
3
100
1
10
1
0.1
1
2
3
4
5
6
7
8
10
Multiple of Rated Current In
Reference Temperature +23°
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-
rent for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient temperature [°C]
Correction factor
-5
0,85
0,95
1,00
1,08
1,21
+10
+23
+40
+60
Example: Rated current = 10 A; Environmental temperature = 60 °C; --> Correction factor
= 1.21; Resulting current = 12.1 A --> Fount to next higher rated current: 13 A
Variants
connection type
Rated current
Order Number
Solder, THT
Solder, THT
Solder, THT
Solder, THT
4A
5A
6A
7A
3-101-228
3-101-227
3-101-226
3-101-232
3
Circuit Breakers
Thermal (T- and TA-Line)
T9-817
https://www.schurter.com /PG17_18_19
connection type
Rated current
Order Number
Solder, THT
Solder, THT
Solder, THT
8A
3-101-231
3-101-230
3-101-229
10A
12A
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-
Check/Stock-Check-SCHURTER
100 Pcs
Packaging Unit
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
4
Circuit Breakers
相关型号:
3-101-227
Circuit Breaker for Equipment thermal vertical, THT terminals for PCB mounting, 1 pole
SCHURTER
3-101-228
Circuit Breaker for Equipment thermal vertical, THT terminals for PCB mounting, 1 pole
SCHURTER
3-101-229
Circuit Breaker for Equipment thermal vertical, THT terminals for PCB mounting, 1 pole
SCHURTER
3-101-232
Circuit Breaker for Equipment thermal vertical, THT terminals for PCB mounting, 1 pole
SCHURTER
3-102-850
IEC Appliance Inlet C14 with Filter 2-Stages, Fuseholder 1- or 2-pole, Line Switch 2-pole
SCHURTER
3-102-852
IEC Appliance Inlet C14 with Filter 2-Stages, Fuseholder 1- or 2-pole, Line Switch 2-pole
SCHURTER
3-102-854
IEC Appliance Inlet C14 with Filter 2-Stages, Fuseholder 1- or 2-pole, Line Switch 2-pole
SCHURTER
©2020 ICPDF网 联系我们和版权申明