4404.0003 [SCHURTER]
Thermal Circuit Breaker, ROHS COMPLIANT;型号: | 4404.0003 |
厂家: | SCHURTER INC. |
描述: | Thermal Circuit Breaker, ROHS COMPLIANT 电路保护 |
文件: | 总4页 (文件大小:342K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Thermal (T- and TA-Line)
T9-611
https://www.schurter.com /PG17_18_19
Circuit Breaker for Equipment thermal, Snap-in type, Fuseholder style, 1 pole
See below:
Approvals and Compliances
Description
Applications
- Snap-in type from front side (0.8...2.0mm)
- Thermal circuit breaker
- Power supplies
- Uninterruptible power supply
- Power tools
- 1-pole
- On request available with elevaled glow-wire ratings
- Quick connect terminals 6.3 x 0.8 mm
- Industrial appliances
- HVAC
- Household appliances
Unique Selling Proposition
- Reset type
- Cycling trip-free release
- Compact design
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News
- Different mounting possibilities
Technical Data
Rated Voltage AC
Rated Voltage DC
Rated current
Conditional short circuit ca-
pacity
240 V, 50 / 60 Hz
Ambient temperature
Weight
3 A: -5 °C to 60 °C
4 A: -5°C to 50 °C
5-16 A: -5 °C to 60 °C
9 - 13 g
48 / 32 V, see approvals
3-16 A, see approbations
IEC: Inc, PC1, AC 240 V: 2 kA
UL / CSA: SC, AC 240 V DC 48 / 32 V:
2 kA, C1
Degree of protection front side IP 40
Endurance minimum
IEC: 200% Ir, cos φ 0.6: min. 50 swit-
ching cycles
Endurance typical
3-8 A: 150% Ir, cos φ 0.9:
2500switching cycles
10-16 A: 150% Ir, cos φ 0.9:
6000switching cycles
1500VAC
Dielectric Strength
Insulation Resistance
500 VDC > 1000 MΩ
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: T9
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
VDE Certificate Number: 40038016
UL Approvals
UL
UL File Number: E71572
CQC Approvals
CQC
CCC Certificate Number: 2013010307617688
1
Circuit Breakers
Thermal (T- and TA-Line)
T9-611
https://www.schurter.com /PG17_18_19
Product standards
Product standards that are referenced
Organization
Design
Standard
Description
Designed according to
IEC 60934
Circuit-breakers for equipment (CBE)
Designed according to
Designed according to
Designed according to
UL 1077
Standard for Supplementary Protectors for Use in Electrical Equipment
Supplementary Protectors
CSA C22.2 No. 235
GB 17701
Circuit-breaker for equipment
Application standards
Application standards where the product can be used
Organization
Design
Standard
Description
Designed for applications acc.
IEC/UL 60950
IEC 60950-1 includes the basic requirements for the safety of information
technologyequipment.
Compliances
The product complies with following Guide Lines
Identification
Details
Initiator
Description
CE declaration of conformity
SCHURTER AG
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
RoHS
SCHURTER AG
SCHURTER AG
SCHURTER AG
EU Directive RoHS 2011/65/EU
China RoHS
REACH
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
Dimension [mm]
T9-611
0.3
0.5
0.3
3.4
34
10
14+0.15
0
10A
0.3
0.ꢀ
13.6
5
19
6.3x0.8mm
Pannel thickness s = 0.8 - 2.0 mm
Approval
Rated current
Rated voltage AC
Rated voltage DC
UL 1077
3 - 12 A
14 - 16 A
240 V
240 V
48 V
32 V
CSA 22.2 235
3 - 12 A
14 - 16 A
240 V
240 V
48 V
32 V
IEC 60934
GB 17701
3 - 12 A
240 V
240 V
48 V
32 V
14 - 16 A
3 - 12 A
14 - 16 A
240 V
240 V
48 V
32 V
2
Circuit Breakers
Thermal (T- and TA-Line)
T9-611
https://www.schurter.com /PG17_18_19
Typical internal resistance
Rated Current [A]
Internal Resistance [mΩ]
3
4
65.0
21.6
23.6
16.3
15.3
12.9
7.3
5
6
7
8
10
12
14
15
16
7.0
4.8
4.3
3.9
Time-Current-Curves
[min]
[sec]
[min]
60
[sec]
10'000
10'000
T9
T9
5 A -16 A (TC-1)
4 A (TC-2)
3
A
(TC-2)
60
30
20
30
20
1'000
1'000
10
10
5
3
5
3
100
100
1
1
10
10
1
1
0.1
1
0.1
1
2
3
4
5
6
7
8
10
2
3
4
5
6
7
8
10
Multiple of Rated Current In
Reference Temperature +23°
Multiple of Rated Current In
Reference Temperature +23°
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-
rent for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient temperature [°C]
Correction factor
-5
0,85
0,95
1,00
1,08
1,21
+10
+23
+40
+60
Example: Rated current = 10 A; Environmental temperature = 60 °C; --> Correction factor
= 1.21; Resulting current = 12.1 A --> Fount to next higher rated current: 13 A
3
Circuit Breakers
Thermal (T- and TA-Line)
T9-611
https://www.schurter.com /PG17_18_19
Accessory
Part Number
4404.0039
Type
Resources / Description
Protection cover for IP 65
Knurled nut nickel-plated
Knurled nut black
TZZ31
TZZ11
TZZ11-414
TZZ12
TZZ51
4400.0420
4400.0559
4400.0425
Additional hexagonal nut nickel-plated
Additional hexagonal nut PA 66
4404.0072
Variants
Mounting
Front printing
Rated current
Order Number
Snap-in mounting from front side
Rated current printed on front
3.0 A
4404.0018
█
█
█
█
█
█
█
█
█
█
█
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Rated current printed on front
Rated current printed on front
Rated current printed on front
Rated current printed on front
Rated current printed on front
Rated current printed on front
Rated current printed on front
Rated current printed on front
Rated current printed on front
Rated current printed on front
Rated current printed on front 90° shifted
Rated current printed on front 90° shifted
4.0 A
5.0 A
6.0
4404.0001
4404.0007
4404.0002
4404.0009
4404.0003
4404.0004
4404.0005
4404.0008
4404.0010
4404.0006
4404.0066
4404.0067
7.0 A
8.0 A
10.0 A
12.0 A
14.0 A
15.0 A
16.0 A
4.0 A
5.0 A
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Snap-in mounting from front side
Rated current printed on front 90° shifted
Rated current printed on front 90° shifted
Rated current printed on front 90° shifted
Rated current not printed on front
Rated current not printed on front
Rated current not printed on front
Rated current not printed on front
Rated current not printed on front
Rated current not printed on front
Rated current not printed on front
Rated current not printed on front
Rated current not printed on front
Rated current not printed on front
Rated current not printed on front
6.0
4404.0068
4404.0069
4404.0071
4404.0088
4404.0089
4404.0090
4404.0091
4404.0065
4404.0092
4404.0093
4404.0063
4404.0094
4404.0095
4404.0087
8.0 A
15.0 A
3.0 A
4.0 A
5.0 A
6.0
7.0 A
8.0 A
10.0 A
12.0 A
14.0 A
15.0 A
16.0 A
█ Most Popular.
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
100 Pcs
Packaging Unit
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
4
Circuit Breakers
相关型号:
4404.0021
Thermal Circuit Breaker, 1 Pole(s), 8A, 240VAC, 48VDC, Panel Mount, ROHS COMPLIANT
SCHURTER