4404.0028 [SCHURTER]

Thermal Circuit Breaker, ROHS COMPLIANT;
4404.0028
型号: 4404.0028
厂家: SCHURTER INC.    SCHURTER INC.
描述:

Thermal Circuit Breaker, ROHS COMPLIANT

电路保护
文件: 总4页 (文件大小:334K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Thermal (T- and TA-Line)  
T9-311  
https://www.schurter.com /PG17_18_19  
Circuit Breaker for Equipment thermal, Threaded-neck type, 1 pole  
T9-311: Threaded neck type with nut nickel-  
plated  
See below:  
Approvals and Compliances  
Description  
Applications  
- Threaded neck type  
- Power supplies  
- Uninterruptible power supply  
- Power tools  
- Thermal circuit breaker  
- 1-pole  
- On request available with elevaled glow-wire ratings  
- Quick connect terminal 6.3 x 0.8 mm  
- Industrial appliances  
- HVAC  
- Household appliances  
Unique Selling Proposition  
- Reset type  
- Cycling trip-free release  
- Compact design  
Weblinks  
pdf datasheet, html-datasheet, General Product Information, Distributor-  
Stock-Check, Detailed request for product, Product News  
- Different mounting possibilities  
Technical Data  
Rated Voltage AC  
Rated Voltage DC  
Rated current  
Conditional short circuit ca-  
pacity  
240 V, 50 / 60 Hz  
Ambient temperature  
Weight  
3 A: -5 °C to 60 °C  
4 A: -5°C to 50 °C  
5-16 A: -5 °C to 60 °C  
9 - 13 g  
48 / 32 V, see approvals  
3-16 A, see approbations  
IEC: Inc, PC1, AC 240 V: 2 kA  
UL / CSA: SC, AC 240 V DC 48 / 32 V:  
2 kA, C1  
Degree of protection front side IP 40  
Endurance minimum  
IEC: 200% Ir, cos φ 0.6: min. 50 swit-  
ching cycles  
Endurance typical  
3-8 A: 150% Ir, cos φ 0.9:  
2500switching cycles  
10-16 A: 150% Ir, cos φ 0.9:  
6000switching cycles  
1500VAC  
Dielectric Strength  
Insulation Resistance  
500 VDC > 1000 MΩ  
Approvals and Compliances  
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about  
Approvals  
Approvals  
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.  
Approval Reference Type: T9  
Approval Logo  
Certificates  
Certification Body  
Description  
VDE Approvals  
VDE  
VDE Certificate Number: 40038016  
UL Approvals  
UL  
UL File Number: E71572  
CQC Approvals  
CQC  
CCC Certificate Number: 2013010307617688  
1
Circuit Breakers  
 
Thermal (T- and TA-Line)  
T9-311  
https://www.schurter.com /PG17_18_19  
Product standards  
Product standards that are referenced  
Organization  
Design  
Standard  
Description  
Designed according to  
IEC 60934  
Circuit-breakers for equipment (CBE)  
Designed according to  
Designed according to  
Designed according to  
UL 1077  
Standard for Supplementary Protectors for Use in Electrical Equipment  
Supplementary Protectors  
CSA C22.2 No. 235  
GB 17701  
Circuit-breaker for equipment  
Application standards  
Application standards where the product can be used  
Organization  
Design  
Standard  
Description  
Designed for applications acc.  
IEC/UL 60950  
IEC 60950-1 includes the basic requirements for the safety of information  
technologyequipment.  
Compliances  
The product complies with following Guide Lines  
Identification  
Details  
Initiator  
Description  
CE declaration of conformity  
SCHURTER AG  
The CE marking declares that the product complies with the applicable  
requirements laid down in the harmonisation of Community legislation on  
its affixing in accordance with EU Regulation 765/2008.  
RoHS  
SCHURTER AG  
SCHURTER AG  
SCHURTER AG  
EU Directive RoHS 2011/65/EU  
China RoHS  
REACH  
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March  
2007. It is similar to the EU directive RoHS.  
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,  
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as  
"REACH") entered into force.  
Dimension [mm]  
T9-211/311  
0.2  
ø 15.4  
10.4  
36.1  
10  
19  
8
5
6.3x0.8  
3/8" -27UNS  
Pannel thickness s = 0.8 - 5.5 mm  
8.90+0.10  
0.00  
9.6  
Hexagonal nut TZZ12 / TZZ51  
Cover TZZ31für IP65 optional, see accessory  
3/8" -27UNS  
2.5  
13.6  
2
Circuit Breakers  
Thermal (T- and TA-Line)  
T9-311  
https://www.schurter.com /PG17_18_19  
Approval  
Rated current  
Rated voltage AC  
Rated voltage DC  
UL 1077  
3 - 12 A  
14 - 16 A  
240 V  
240 V  
48 V  
32 V  
CSA 22.2 235  
IEC 60934  
3 - 12 A  
240 V  
240 V  
48 V  
32 V  
14 - 16 A  
3 - 12 A  
14 - 16 A  
240 V  
240 V  
48 V  
32 V  
GB 17701  
3 - 12 A  
14 - 16 A  
240 V  
240 V  
48 V  
32 V  
Typical internal resistance  
Rated Current [A]  
Internal Resistance [m]  
3
4
65.0  
21.6  
23.6  
16.3  
15.3  
12.9  
7.3  
5
6
7
8
10  
12  
14  
15  
16  
7.0  
4.8  
4.3  
3.9  
Time-Current-Curves  
[min]  
[sec]  
[min]  
[sec]  
10'000  
10'000  
T9  
T9  
5 A -16 A (TC-1)  
4 A (TC-2)  
3
A
(TC-2)  
60  
60  
30  
20  
30  
20  
1'000  
1'000  
10  
10  
5
3
5
3
100  
100  
1
1
10  
10  
1
1
0.1  
1
0.1  
1
2
3
4
5
6
7
8
10  
2
3
4
5
6
7
8
10  
Multiple of Rated Current In  
Reference Temperature +23°  
Multiple of Rated Current In  
Reference Temperature +23°  
3
Circuit Breakers  
Thermal (T- and TA-Line)  
T9-311  
https://www.schurter.com /PG17_18_19  
Effect of ambient temperature  
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-  
rent for a lower or higher ambient temperature, use a correction factor (typical value) from  
the table below:  
Ambient temperature [°C]  
Correction factor  
-5  
0,85  
0,95  
1,00  
1,08  
1,21  
+10  
+23  
+40  
+60  
Example: Rated current = 10 A; Environmental temperature = 60 °C; --> Correction factor  
= 1.21; Resulting current = 12.1 A --> Fount to next higher rated current: 13 A  
Accessory  
Part Number  
4404.0039  
4400.0420  
4400.0559  
4400.0425  
4404.0072  
Type  
Resources / Description  
Protection cover for IP 65  
Knurled nut nickel-plated  
Knurled nut black  
TZZ31  
TZZ11  
TZZ11-414  
TZZ12  
TZZ51  
Additional hexagonal nut nickel-plated  
Additional hexagonal nut PA 66  
Variants  
Mounting  
Front printing  
Rated current  
Order Number  
Threaded-neck type  
Threaded-neck type  
Threaded-neck type  
Threaded-neck type  
Threaded-neck type  
Rated current not printed on front  
Rated current not printed on front  
Rated current not printed on front  
Rated current not printed on front  
Rated current not printed on front  
3.0 A  
4.0 A  
5.0 A  
6.0  
4404.0049  
4404.0019  
4404.0025  
4404.0020  
4404.0027  
7.0 A  
Threaded-neck type  
Threaded-neck type  
Threaded-neck type  
Threaded-neck type  
Threaded-neck type  
Threaded-neck type  
Rated current not printed on front  
Rated current not printed on front  
Rated current not printed on front  
Rated current not printed on front  
Rated current not printed on front  
Rated current not printed on front  
8.0 A  
10.0 A  
12.0 A  
14.0 A  
15.0 A  
16.0 A  
4404.0021  
4404.0022  
4404.0023  
4404.0026  
4404.0028  
4404.0024  
Most Popular.  
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER  
100 Pcs  
Packaging Unit  
The specifications, descriptions and illustrations indicated in this document are based on current  
information. All content is subject to modifications and amendments. Information furnished is believed  
to be accurate and reliable. However, users should independently evaluate the suitability and test each  
product selected for their own applications.  
4
Circuit Breakers  

相关型号:

4404.0029

Thermal Circuit Breaker, ROHS COMPLIANT
SCHURTER

4404.0030

Thermal Circuit Breaker, ROHS COMPLIANT
SCHURTER

4404.0031

Thermal Circuit Breaker, ROHS COMPLIANT
SCHURTER

4404.0032

Thermal Circuit Breaker, ROHS COMPLIANT
SCHURTER

4404.0033

Thermal Circuit Breaker, ROHS COMPLIANT
SCHURTER

4404.0034

Thermal Circuit Breaker, ROHS COMPLIANT
SCHURTER

4404.0035

Thermal Circuit Breaker, ROHS COMPLIANT
SCHURTER

4404.0036

Circuit Breaker for Equipment thermal, Snap-in rear side, 1 pole
SCHURTER

4404.0037

Circuit Breaker for Equipment thermal, Snap-in rear side, 1 pole
SCHURTER

4404.0038

Thermal Circuit Breaker, ROHS COMPLIANT
SCHURTER

4404.0039

Resettable Thermal Circuit Breaker
SCHURTER

4404.0049

Circuit Breaker for Equipment thermal, Threaded-neck type, 1 pole
SCHURTER