AS168X-CB2G270N
更新时间:2024-09-18 12:10:26
品牌:SCHURTER
描述:MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
AS168X-CB2G270N 概述
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR 手动电机控制器和补充保护器
AS168X-CB2G270N 数据手册
通过下载AS168X-CB2G270N数据手册来全面了解它。这个PDF文档包含了所有必要的细节,如产品概述、功能特性、引脚定义、引脚排列图等信息。
PDF下载MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
MOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Product description
Produktebeschreibung
The AS168X is a thermal magnetic high performance CBE to IEC 934
and a «supplementary protector» to UL 1077. It is capable of drasti-
cally limiting the «let-through energy» in case of short circuit interrup-
tions. The series is available in units from one to four poles for use in
AC and DC circuits. Multipole devices are connected internally and at
the handle for simultaneous operation. This applies also to combina-
tions with the switched neutral pole. Well designed screw type term-
inals at line and load side are provided for safe and easy connection
to line and load. They accept #16 to 4 AWG / 1,5 to 25 mm2.
Der AS168X ist ein thermisch magnetischer Hochleistungs CBE, der
in der Lage ist, bei Kurzschluss-Abschaltungen den Durchlass-Strom
drastisch zu reduzieren. Die Serie ist erhältlich in Ausführungen mit
einem bis vier geschützten Polen, die in Wechselstrom- oder Gleich-
stromnetzen eingesetzt werden können. Mehrpolige CBE sind intern
und beim Kipphebel mechanisch verbunden, um gleichzeitiges Schal-
ten zu gewährleisten. Dies gilt auch für eine Kombination mit dem
schaltbaren Null-Leiter Pol. Raffiniert konstruierte Liftklemmen auf der
Eingangs- und Abgangsseite ermöglichen einen bequemen Netz- und
Lastanschluss. Die Klemmen sind zum Anschluss von Leitern mit 1,5
bis 25 mm2 Querschnitt geeignet, (AWG #16...4).
The AS168X is suitable as supplementary protector under
UL 1077 / EN 60934 or as Manual Motor Controller according
UL 508 / CSA 22.2 14. Thus the Breaker has a high versatility
and is suitable for many functions:
• Motor overload protection (thermal and magnetic)
• Motor starting across-the-line (direct-on-line)
• Motor starting with motor disconnect (cos phi 0,4 – 0,5)
• Motor group installation (short capacity 5 kA)
• Control circuits
Der AS168X ist einsetzbar als Geräteschutzschalter nach UL 1077 /
EN 60934 oder als Motorschutzschalter nach UL 508 bzw.
CSA 22.2 14. Der Schalter ist somit vielseitig einsetzbar und eignet
sich für folgende Funktionen:
• Motor overload protection (thermisch und magnetisch)
• Motor starting across-the-line (direct-on-line)
• Motor starting with motor disconnect (cos phi 0,4 – 0,5)
• Motor group installation (short capacity 5 kA)
• Control circuits
Accessories
•
Auxiliary contact module
Zubehör
Each auxiliary contact module contains one contact,
either normally open or normally closed.
•
Hilfskontakte
Jedes Modul ist mit einem Öffnungs- oder Schliesskontakt
ausgerüstet.
•
Signal contact module
Signal contact modules are linked internally with the protected
poles but not linked at the handles.
•
Signalkontakt-Modul
Contacts are actuated by a fault condition at the protected poles,
not by the manual operation of the CBE.
Signalkontakt Module sind intern mit dem benachbarten Pol
verbunden, weisen aber keine Verbindung der Kipphebel auf.
Daher schaltet dieses Modul nur beim automatischen Auslösen
der benachbarten Pole, aber nicht bei manueller Betätigung.
•
•
Relay trip module
The relay trip module can be used for remote tripping of the
adjacent poles by applying a voltage to the module’s terminal.
•
•
Fremdauslösung
Dieses Modul kann für die Fernauslösung der benachbarten Pole
mittels eines Spannungspulses verwendet werden.
Switched neutral pole (factory assembled)
This module allows to automatically open the neutral line when
the protected poles have been tripped.
Schaltbarer Neutralleiter Pol
Dieses Modul erlaubt ein automatisches Öffnen des Neutralleiters
wenn die geschützten Pole auslösen.
Features
•
•
•
•
•
•
Excellent short circuit performance (up to 10 kA)
Besondere Merkmale
High limits of discrimination (due to energy limitation)
Wide choice of characteristics (Adaptability)
Availability of AC and DC in the same frame size
Compact, «finger safe» design
•
•
Exzellentes Abschaltvermögen (bis zu 10 kA)
Ermöglicht hohe Selektivitätsgrenzen durch energiebegrenzendes
Schalten
Ease installation (on DIN rail)
•
•
Grosse Auswahl von Auslösekennlinien
Anpassungsfähigkeit an die Applikations-Bedingungen
Ausführungen für Wechsel- und Gleichstrom in gleicher
Gehäusegrösse
Applications
• Industrial machines
• Automation
•
•
Kompakte «fingersichere» Bauweise
Einfache Montage (DIN-Schiene)
• Aircondition, ventilation
• Transformers
• Power supplies
• Telecom systems
• Computer systems
• Test systems
Anwendungen
• Industrieller Maschinenbau
• Automation
• Klima- und Ventilationsanlagen
• Transformatoren
• Medical equipments
• Stromversorgungen
•Telekommunikationsanlagen
• Computersysteme
• Testsysteme
• Medizinalgeräte
www.schurter.com
123
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
MOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Effect of ambient
temperature
Einfluss der
Umgebungstemperatur
AC-breakers are calibrated for an ambient
temperature of +40°C, DC-breakers for
+23°C. To determine the rated current for
a lower or higher ambient temperature, use
a correction factor from the table below:
AC-Schalter sind für eine Umgebungs-
temperatur von +40°C geeicht, DC-Schalter
für +23°C. Zur Bestimmung des Nennstromes
für eine tiefere oder höhere Umgebungs-
temperatur ist ein Korrekturfaktor gemäss
untenstehender Tabelle zu verwenden:
Ambient
Correction factor
Umgebungs-
Korrekturfaktor
temperature [°C] AC version DC version
temperatur [°C]
AC-Version DC-Version
–20
–5
0,78
0,82
0,83
0,87
0,91
0,95
1,00
1,05
1,11
0,80
0,87
0,90
0,95
1,00
1,05
1,10
1,20
1,30
–20
–5
0,78
0,82
0,83
0,87
0,91
0,95
1,00
1,05
1,11
0,80
0,87
0,90
0,95
1,00
1,05
1,10
1,20
1,30
0
0
+10
+23
+30
+40
+50
+60
+10
+23
+30
+40
+50
+60
Example DC version:
Rated current at +23°C
Ambient temperature
Correction factor
Beispiel DC-Version:
Nennstrom bei +23°C
Umgebungstemperatur
Korrekturfaktor
10 A
+50°C
1,2
10 A
+50°C
1,2
Chosen rated current at
+50°C ambient temperature
10 A x 1,2 = 12 A
Gewählter Nennstrom bei
+50°C Umgebungstemperatur
10 A x 1,2 = 12 A
Tripping characteristic F
Auslösekennlinie F
Tripping characteristic G
Auslösekennlinie G
Tripping characteristic H
Auslösekennlinie H
1hr
1hr
1hr
1000s
1000s
1000s
100s
10s
1s
100s
10s
1s
100s
10s
1s
0,1s
10ms
1ms
0,1s
10ms
1ms
0,1s
10ms
1ms
0,1ms
0,1ms
0,1ms
1
10
100
1000 x I
1
10
100
1000 x I
1
10
Multiple of rated current (x I )
n
100
1000 x I
n
n
n
Multiple of rated current (x I
Nennstrom-Vielfaches (x I
)
Multiple of rated current (x I
Nennstrom-Vielfaches (x I
)
n
)
n
)
Nennstrom-Vielfaches (x I )
n
n
n
www.schurter.com
124
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
MOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Tripping characteristic DF
Auslösekennlinie DF
Tripping characteristic DG
Auslösekennlinie DG
Tripping characteristic DH
Auslösekennlinie DH
1hr
1hr
1hr
1000s
1000s
1000s
100s
10s
1s
100s
10s
1s
100s
10s
1s
0,1s
10ms
1ms
0,1s
10ms
1ms
0,1s
10ms
1ms
0,1ms
0,1ms
0,1ms
1
10
100
1000 x I
1
10
100
1000 x I
1
10
Multiple of rated current (x I )
n
100
1000 x I
n
n
n
Multiple of rated current (x I
Nennstrom-Vielfaches (x I
)
Multiple of rated current (x I
Nennstrom-Vielfaches (x I
)
n
)
n
)
Nennstrom-Vielfaches (x I )
n
n
n
Technical data / Technische Daten
Pole / Pole:
Rated voltage U
Nennspannung U
AC versions / AC Versionen F; G; H
AC 480/277 V; DC 65 V
DC 180 V 1 pole / 1polig
e
e
DC versions / DC Versionen DF; DG; DH
DC 360 V 2 – 3 pole / 2 – 3polig
Note: The connection polarity must be strictly
observed. An application with a DC Type AS168X
in an AC network is not allowed.
Hinweis: Die Anschlusspolarität muss unbedingt
beachtet werden. Eine Anwendung von
DC Versionen in AC Netzen ist nicht zulässig.
Rated current I
n
See approvals, page 126
Siehe Approbationen Seite 126
AC/DC 0,5 – 52 A
AC/DC 0,5 – 52 A
Nennstrom I
n
Endurance
Lebensdauer
Number of cycles at I
n
Anzahl Schaltspiele bei I
n
6000
6000
Type of tripping
Auslöseart
• Thermal magnetic / thermisch-magnetisch
• Positively trip-free / positive Freiauslösung
TM
Type of actuation / Betätigungsart
Manual ON/OFF / Manuell EIN/AUS
S-type / S-Typ
2
Permissible wire cross section
Zulässiger Leiterquerschnitt
1,5 – 25 mm /AWG #16...4
2
1,5 – 25 mm /AWG #16...4
Switched neutral / Schaltbarer, neutraler Pol:
Rated voltage U / Nennspannung U
AC 277 V
AC/DC 65 A
e
e
Rated current I / Nennstrom I
n
n
Function
The switched neutral closes with
manual closure of the poles and opens
automatically with thermal magnetic
tripping of the poles.
www.schurter.com
125
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
MOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Technical data (continued) / Technische Daten (Fortsetzung)
Funktion
Der Neutralleitertrenner schliesst bei
manueller Einschaltung der Pole und
öffnet automatisch bei thermisch-
magnetischer Auslösung der Pole.
Add-on modules / Zusatzmodule:
Rated voltage U / Nennspannung U
e
Rated current I / Nennstrom I
n
e
n
Auxiliary contact H1 & H2 and
Signal contact S1 & S2
Hilfskontakt H1 & H2 und
Signalkontakt S1 & S2
AC 277 V
DC 125 V
DC 50 V
6 A
1 A
6 A
Functional auxiliary contact module
Funktion Hilfskontakt
Type H1 (assumes the same contact position)
Type H2 (assumes the opposite position)
Actuation of the contact is determined
by the condition of the handle position
of the adjacent poles.
Hilfskontakte schalten bei thermisch-
magnetischer Auslösung sowie
Handbetätigung synchron mit den
geschützten Polen.
Typ H1 (gleichschaltend)
Typ H2 (gegenschaltend)
Functional signal contact
Funktion Signalkontakt
Type S1 (assumes the same contact position)
Type S2 (assumes the opposite position)
The signal contact operates due to a
thermal magnetic tripping and must
be reset by hand.
Signalkontakte schalten nur bei
thermisch-magnetischer Auslösung
und sind von Hand zurückzustellen.
Typ S1 (gleichschaltend)
Typ S2 (gegenschaltend)
Relay trip module
Fremdauslösung
Type
Typ
A1
A2
A3
Voltage range AC/DC
Arbeitsbereich AC/DC
5 – 12 V
10 – 24 V
20 – 48 V
Impedance at 50 Hz
Impedanz bei 50 Hz
1.1 Ω
4.7 Ω
16 Ω
A4
40 – 110 V
63 Ω
A5
90 – 240 V
395 Ω
Function of relay trip module
Funktion Fremdauslösung
When voltage is applied across the
terminals, remote tripping takes place
by a self interrupting magnetic system.
Trip delay time 8 - 16 ms.
Beim Anlegen der Klemmenspannung
erfolgt die Auslösung durch ein
selbstunterbrechendes Magnetsystem.
Ausschaltverzögerung 8 – 16 ms.
General data / Allgemeine Daten:
Dielectric strength
Spannungsfestigkeit
AC 2000 V
AC 2000 V
Vibration resistance
Schwingungsfestigkeit
IEC 60068-2-6, Test Fc
IEC 60068-2-27, Test Ea
0,75 mm amplitude, 10 – 57 Hz
0,75 mm Amplitude, 10 – 57 Hz
Shock resistance / Stossfestigkeit
25 g / 10 ms Halfsinus
Protection against electric shock
Berührungsschutz
Finger safe per IEC 529
Fingerschutz nach IEC 529
IP20
IP20
Permissible ambient temperature
Zul. Umgebungstemperatur
-20°C to +60°C
-20°C bis +60°C
Weight / Gewichte
1 pole / 1-Pol
ca. 130 g
ca. 130 g
ca. 100 g
ca. 100 g
ca. 120 g
Switched neutral / Schaltbarer neutraler Pol
Auxiliary contact / Hilfskontakt
Signal contact / Signalkontakt
Relay trip module / Fremdauslösung
www.schurter.com
126
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
MOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Approvals / Approbationen
AC versions / AC-Versionen
V
D E
VDE
EN 60934 *
UL
UL 1077
CSA 22.2 235
Volt DC
UL
UL 508 **
CSA 22.2 14
Poles
Characteristic/
Nennstrom [A]
Volt AC
Volt
DC
Icn [A]
4500
Volt AC
277
277
Icn [A]
5000
Volt AC
Icn [A]
1
F / G / H
45 - 52
F / G
420/240
420/240
420/240
420/240
420
65
65
65
65
65
65
65
65
65
65
65
65
65
65
277
277
277
277
480
480
480
480
480
480
480
480
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
4500
4500
4500
4500
4500
4500
4500
5000
10000
5000
0.5 - 25
240
277
65
65
H
0.5 - 40
F / G
277
240
480
5000
10000
5000
27 - 40
F / G / H
45 - 52
F / G
65
65
2
3
4
420
480
480
480
65
65
65
65
65
65
65
65
10000
5000
0.5 - 25
H
420
0.5 - 40
F / G
27 - 40
F / G / H
45 - 52
F / G
420
10000
5000
420
4500 480Y/277
4500 480Y/277
4500 480Y/277
4500 480Y/277
4500 480Y/277
420
10000
5000
0.5 - 25
H
420
0.5 - 40
F / G
27 - 40
F / G / H
0.5 - 52
420
10000
420/240
5000 480Y/277
DC versions / DC-Versionen
V
D E
VDE *
EN 60934
UL
UL 1077
CSA 22.2 235
Volt DC Icn [A]
Poles
Characteristic/
Nennstrom [A]
Volt DC
120
Icn [A]
1
DF / DG
0.5 - 50
DH
4500
4500
4500
4500
4500
4500
4500
4500
4500
4500
180
180
360
360
360
360
360
360
360
360
2000
2000
2000
2000
10000
5000
5000
10000
5000
5000
120
240
240
360
360
360
360
360
360
6 - 50
2
3
DF / DG
0.5 - 50
DH
6 - 50
DF / DG
0.5 - 40
DF / DG
45 - 50
DH
6 - 50
4
DF / DG
0.5 - 40
DF / DG
45 - 50
DH
6 - 50
* VDE approval pending / VDE Zulassung pendent
** Rated currents 32 –52 A available approx. March 2003 / Nennwerte 32 –52 A ca. ab März 2003 lieferbar
www.schurter.com
127
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
MOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Conversion table Ampere rating – Horsepower rating / Umrechnungstabelle Ampère – Horsepower
Voltage Rating:
One pole:
Two pole:
Three pole:
AC 277 V, 1 phase
AC 480Y/277 V, 1 phase
AC 480Y/277 V, 3 phase
HP-Rating: 1 phase (1 pole & 2 pole):
HORSEPOWER
(FLA & LRC RATINGS APPLY WHERE NO HP RATING IS GIVEN)
NOMINAL CIRCUIT VOLTAGE, Vac
AS168X-CB
MOTOR NAMEPLATE
110-
120
220-
240
380-
415
440-
480
200
208
265
277
Rated Current
(See Note #1)
0.5A
1A
FLA
Rating
0.5A
1A
1.5A
2A
3A
4A
5A
6A
Starting/
LRC Rating
3°
1
2 pole
pole
6°
9°
12A
18A
24A
30A
36A
42A
48A
54A
60A
72A
78A
90A
96A
1/10
1/6
1/4
1/3
1/2
3/4
1
1 1/2
2
2
2
3
3
3
3
5
5
5
1.5A
2A
3A
4A
5A
6A
7A
8A
9A
10A
12A
13A
15A
16A
18A
20A
23A
25A
27A
30A
1/10
1/8
1/4
1/3
1/2
1/2
3/4
1
1
1 1/2
2
2
2
2
3
3
3
3
3
5
1/10
1/6
1/4
1/3
1/2
3/4
1
1/10
1/6
1/3
1/3
1/2
3/4
1
1
1 1/2
2
2
2
3
3
3
3
3
5
5
5
1/10
1/8
1/6
1/4
1/4
1/3
1/3
1/2
1/2
1/2
3/4
1
1/6
1/4
1/3
1/2
1/2
3/4
3/4
1
1 1/2
1 1/2
2
2
2
1/6
1/3
1/3
1/2
1/2
3/4
1
1/2
1
1 1/2
2
2
2
3
3
3
3
5
5
5
5
7 1/2
7 1/2
10
10
7A
8A
9A
1
1 _
1 1/2
2
2
3
3
3
3
3
10A
12A
13A
15A
16A
18A
20A
23A
25A
27A
30A
1
1 1/2
1 1/2
2
2
2
3
3
3
3
108A
120A
138A
150A
162A
180A
1
1 1/2
1 1/2
2
2
2
3
3
3
3
5
5
5
5
7 1/2
7 1/2
3
3
HP-Rating: 3 phase (3 pole):
HORSEPOWER
MOTOR
NAMEPLATE
AS168X-CB
(FLA & LRC RATINGS APPLY WHERE NO HP RATING IS GIVEN)
NOMINAL CIRCUIT VOLTAGE, VAC
110-120
200
208
220-240
380-415
440-480
3 pole
Rated Current
FLA
Rating
0.5A
1A
Starting/
LRC Rating
(See Note #1)
0.5A
1A
1.5A
2A
3A
4A
5A
6A
7A
8A
1.5A
2A
3A
4A
5A
6A
7A
8A
9A
10A
12A
13A
15A
16A
18A
20A
23A
25A
27A
30A
10A
12.5A
20A
25A
32A
32A
32A
46A
46A
1/2
3/4
1
1 1/2
2
2
3
3
3
1/2
3/4
1 1/2
2
3
3
3
5
5
5
7 1/2
7 1/2
10
10
10
10
15
15
20
20
1/2
3/4
1
1
1 1/2
2
2
2
3
3
3
3
5
5
5
5
7 1/2
7 1/2
1/2
3/4
1
1
1 1/2
2
2
2
3
3
3
3
5
1/2
3/4
1
1 1/2
2
2
2
3
3
3
3
5
5
1/2
1/2
3/4
3/4
1
9A
10A
12A
13A
15A
16A
18A
20A
23A
25A
27A
30A
46A
1
5
5
5
63.5A
63.5A
81A
81A
81A
1 1/2
1 1/2
2
2
2
3
3
3
3
7 1/2
7 1/2
10
10
10
10
15
15
81A
5
5
5
116A
116A
145A
145A
7 1/2
7 1/2
7 1/2
10
7 1/2
7 1/2
7 1/2
3
Note #1: For AC motor circuit nameplate FLA loads, AC general-use loads, AC resistance loads
www.schurter.com
128
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
MOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Order code / Bestellcode
Basic type / Grundtyp
Thermal magnetic high performance circuit breaker
Thermisch-magnetischer Hochleistungs-Geräteschutzschalter
Number of poles / Polzahl
1
2
3
4
Tripping characteristics / Auslösekennlinien
Thermal
Magnetic
Deliverable currents
Thermisch
Magnetisch
Lieferbare Nennströme
F
G
H
1.0 –1.25 xI
3 – 5 xI
n
0,5 – 52 A
0,5 – 52 A
0,5 – 52 A
0,5 – 50 A
0,5 – 50 A
6,0 – 50 A
n
1.0 –1.25 xI
6 – 10 xI
n
n
n
1.0 –1.25 xI
12 – 20 xI
n
DF 1.05 –1.35 xI
DG 1.05 –1.35 xI
DH 1.05 –1.35 xI
4,5 – 8 xI
n
n
n
n
9 – 16 xI
n
18 – 32 xI
n
Rated current / Nennstrom
Code
I
(A)
Code
I
(A)
Code
I
(A)
Code
I (A)
n
n
n
n
005
010
015
020
030
040
050
0.5
060
070
080
090
100
120
150
6.0
160
180
200
230
250
270
300
16.0
18.0
20.0
23.0
25.0
27.0
30.0
320
350
400
450
500
520
32.0
35.0
40.0
45.0
50.0
52.0 *
1.0
1.5
2.0
3.0
4.0
5.0
7.0
8.0
9.0
10.0
12.0
15.0
* AC version only /
Nur AC-Version
Switched neutral pole / Schaltbarer neutraler Pol
N
Maximum
combination
Maximale
AS168X – CB 2 DG 200 N
AS168X – ACB S2
Kombinationen
1 Add-on module + 4 poles
1 Zusatzmodul + 4 Pole
+
+
N
N
2 Add-on modules + 3 poles + N
2 Zusatzmodule + 3 Pole + N
Auxiliary contact / Hilfskontakt
H1 Assumes the same contact position as the protected poles
Gleiche Kontaktposition wie die geschützten Pole (gleichschaltend)
H2 Assumes the opposite contact position as the protected poles
Entgegengesetzte Kontaktposition wie die geschützten Pole (gegenschaltend)
Signal contact / Signalkontakt
S1 Assumes the same contact position as the protected poles
Gleiche Kontaktposition wie die geschützten Pole (gleichschaltend)
S2 Assumes the opposite contact position as the protected poles
Entgegengesetzte Kontaktposition wie die geschützten Pole (gegenschaltend)
Relay trip module / Fremdauslösung
A1 AC/DC 5 – 12 V
A2 AC/DC 10 – 24 V
A3 AC/DC 20 – 48 V
A4 AC/DC 40 – 110 V
A5 AC/DC 90 – 240 V
Accessories / Zubehör
Must be ordered separately / muss separat bestellt werden
www.schurter.com
129
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
MOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
DIN rail mounting / Hutschiene DIN-Befestigung
AS168X-CB1…
…N
45
17.5 +–00..05
17.5 +–00..05
35
90
1.9
35 mm DIN rail EN 50022
35 mm Hutschiene DIN-EN 50022
Max. torque
Max. zulässiges Anzugsdrehmoment
Wire crosssection
Drahtquerschnitt
1.5…10 mm2
16 …25 mm2
AWG #16...8
Max. torque
Max. Drehmoment
2.5 Nm
3.1 Nm
22 Ib–in
AWG #6...4
28 Ib–in
AS168X-ACBH.
AS168X-ACBA.
AS168X-ACBS.
17.5 +–00..05
17.5 +–00..05
17.5 +–00..05
www.schurter.com
130
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
MOTOR- UND GERÄTESCHUTZSCHALTER
AS168X
Schematic diagrams / Schaltbilder
AS168X-CB1…
AS168X-CB1…
AS168X-ACBH1
AS168X-CB1…
AS168X-ACBH2
AS168X-CB1…N
AS168X-CB1…
AS168X-ACBS1
AS168X-CB1…
AS168X-ACBS2
AS168X-CB1…
AS168X-ACBA.
Accessories / Zubehör
AS168X-ACBLOA
Lockout attachment / Abschliessverriegelung
www.schurter.com
131
AS168X-CB2G270N 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
AS168X-CB2G300N | SCHURTER | MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR | 获取价格 | |
AS168X-CB2G320N | SCHURTER | MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR | 获取价格 | |
AS168X-CB2G350N | SCHURTER | MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR | 获取价格 | |
AS168X-CB2G400N | SCHURTER | MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR | 获取价格 | |
AS168X-CB2G450N | SCHURTER | MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR | 获取价格 | |
AS168X-CB2G500N | SCHURTER | MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR | 获取价格 | |
AS168X-CB2G520N | SCHURTER | MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR | 获取价格 | |
AS168X-CB2H005N | SCHURTER | MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR | 获取价格 | |
AS168X-CB2H010N | SCHURTER | MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR | 获取价格 | |
AS168X-CB2H015N | SCHURTER | MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR | 获取价格 |
AS168X-CB2G270N 相关文章
- 2024-09-20
- 6
- 2024-09-20
- 9
- 2024-09-20
- 8
- 2024-09-20
- 6