LOA24.173A27 [SIEMENS]

Oil Burner Controls;
LOA24.173A27
型号: LOA24.173A27
厂家: Siemens Semiconductor Group    Siemens Semiconductor Group
描述:

Oil Burner Controls

文件: 总10页 (文件大小:529K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
118  
7
ISO 9001  
LOA2...  
LOA3...  
LOA2...  
LOA3...  
Oil Burner Controls  
Oil burner controls for the supervision, startup and control of single- or 2-stage  
forced draft oil burners in intermittent operation.  
Oil throughput up to 30 kg/h.  
The LOA2... / LOA3... and this Data Sheet are intended for use by OEMs which  
integrate the oil burner controls in their products.  
Use, features  
Use  
The LOA... are used for the startup, supervision and control of single- or 2-stage forced  
draft oil burners in intermittent operation.  
Yellow-burning flames are supervised with photoresistive detectors QRB..., blue-  
burning flames with blue-flame detectors QRC...  
-
-
Forced draft oil burners conforming to EN 267  
Oil atomization burners as monoblocks conforming to EN 230  
General features  
Specific features  
-
-
Undervoltage detection  
Bridging contact for oil preheater (not with LOA28.173A27)  
-
-
Special versions including models for incinerator plant and flash-steam generators  
LOA36... with color LED for indicating flame strength and operation  
Siemens Building Technologies  
HVAC Products  
CC1N7118en  
09.10.2002  
Warning notes  
To avoid injury to persons, damage to property or the environment, the following  
warning notes should be observed!  
Do not open, interfere with or modify the unit!  
S
S
S
S
S
Before performing any wiring changes in the connection area of the LOA..., com-  
pletely isolate the unit from the mains supply (all-polar disconnection)  
Ensure protection against electric shock hazard by providing adequate protection  
for the burner control’s connection terminals  
Check to ensure that wiring is in an orderly state and that the wires are firmly con-  
nected  
Press the lockout reset button / operating button only manually (applying a force of  
no more than 60 N), without using any tools or pointed objects  
Fall or shock can adversely affect the safety functions. Such units may not be put  
into operation, even if they do not exhibit any damage  
Mounting notes  
S
Ensure that the relevant national safety regulations are complied with  
Installation notes  
S
S
S
Installation and commissioning work must be carried out by qualified staff  
Do not mix up live and neutral conductors  
Always run high-voltage ignition cables separately while observing the greatest  
possible distance to the unit and to other cables  
Electrical connection of flame detectors  
It is important to achieve practically disturbance- and loss-free signal transmission:  
S
Never run the detector cable together with other cables  
– Line capacitance reduces the magnitude of the flame signal  
– Use a separate cable  
Observe the permissible lengths of the flame detector cables (refer to Data Sheets  
7714 (QRB...) and 7716 (QRC...))  
S
Commissioning notes  
S
S
Commissioning work must be carried out by qualified staff  
When commissioning the plant, when carrying out maintenance work, or after  
longer off periods, make the following safety checks:  
Safety check  
a) Burner startup with flame detector  
darkened  
Anticipated response  
Lockout at the end of «TSA»  
b) Burner startup with flame detector  
exposed to extraneous light  
Lockout after approx. 40 seconds  
c) Simulation of flame failure during  
operation. For that purpose, darken  
the flame detector during operation  
and maintain this state  
Repetition followed by lockout at the  
end of «TSA»  
2/10  
Siemens Building Technologies  
HVAC Products  
CC1N7118en  
09.10.2002  
Standards  
Conformity to EEC directives  
Electromagnetic compatibility EMC (immunity) 89 / 336 EEC  
Low-voltage directive  
73 / 23 EEC  
Service notes  
S
S
Maintenance work must be carried out by qualified staff  
Each time a unit has been replaced, check wiring to ensure it is in an orderly state  
and that the wires are firmly connected; make the safety checks as indicated in  
«Commissioning notes» above  
S
Use the KF... test adapters for short periods of time only  
Disposal notes  
The unit contains electrical and electronic components and may not be disposed of  
together with household waste.  
Local and currently valid legislation must be observed.  
Mechanical design  
The housing is made of impact-proof, heat-resistant and flame-retarding plastic.  
The oil burner control is of plug-in design and engages audibly in its base.  
The housing accommodates the  
-
-
-
thermal-electric sequence switch  
flame signal amplifier with the flame relay  
lockout reset button with its integrated fault indication lamp  
Type summary  
The type references given below apply to burner controls without base and without flame detector.  
Version  
Type reference  
Voltage  
(VAC)  
Under-  
voltage  
CE  
t1  
t3  
TSAmax.  
t3n  
t3n´  
t4  
Replacement  
for  
detection  
Standard version  
LOA24.171B27 ²)  
LOA24.171B17 ²)  
LOA24.173A27  
LOA24.174A27  
LOA26.171B27 ²)  
LOA36.171A27  
LOA24.571C27  
220  
110  
220  
220  
220  
220  
220  
X
X
X
X
X
X
X
x
x
x
x
x
x
x
13  
13  
13  
13  
13  
13  
6
13  
13  
13  
13  
13  
13  
6
10  
10  
10  
10  
10  
10  
10  
15  
15  
20  
35  
15  
15  
20  
---  
---  
2
15  
15  
20  
35  
15  
15  
20  
LAI2.3  
LAI2.3  
---  
---  
---  
LAI5  
2
With remote reset  
facility  
For flash-steam  
generators  
---  
---  
---  
For incinerator plant LOA25.173C27 ¹)  
LOA25.173C17 ¹)  
220  
110  
220  
X
X
X
---  
---  
---  
13  
13  
13  
13  
13  
13  
10  
10  
10  
---  
---  
---  
2
2
2
15  
15  
15  
LAB2  
---  
LOA28.173A27 ¹)  
¹)  
²)  
LOA25... and LOA28... are designed for use on incinerator plant where lockout by extraneous light is not desired. These  
types of oil burner controls are not covered by EN 230  
IRD1010 infrared flicker detectors can also be used  
Legend  
t1  
Prepurge time  
t3  
Preignition time  
t3n  
t3n´  
t4  
Long postignition time  
Short postignition time  
Interval from establishment of flame to the release of «BV2»  
Ignition safety time  
TSA  
3/10  
CC1N7118en  
09.10.2002  
Siemens Building Technologies  
HVAC Products  
Ordering  
Oil burner control without plug-in base  
refer to «Type summary»  
refer to Data Sheet 7201  
Electrical connections  
-
-
-
Plug-in base AGK11...  
Cable holders AGK65..., AGK66, AGK67...  
Cable strain relief elements for AGK67...  
Electrical connections  
refer to Data Sheet 7203  
-
-
-
Plug-in base AGK13  
Plug-in housing AGK56  
Cover AGK68  
Flame detectors  
-
-
Photoresistive detectors QRB1...  
Blue-flame detectors QRC1...  
refer to Data Sheet 7714  
refer to Data Sheet 7716  
Pedestal (empty housing)  
AGK21  
-
To increase the overall height of the LOA...to that of the LAI... / LAB...  
Remote reset module  
ARK21A27  
KF8819  
-
For use with the LOA26... / LOA36... printed circuit board versions  
Adapter  
-
-
For replacing LAB1... / LAI... by LOA...  
No rewiring of plug-in base required  
Demo case  
KF8891  
KF8843  
KF8885  
-
-
For showing the functioning of burner controls  
Refer to Operating Instructions B7989  
Test case, for making functional tests  
-
-
For testing burner controls  
Refer to Operating Instructions B7986  
Test adapter  
-
-
-
-
-
For testing burner controls  
With switch for manual startup of burner  
With switch for simulating the oil preheater’s release contact  
With 2 pairs of jacks for measuring the flame detector current  
Refer to Mounting Instructions C7981  
Test adapter  
KF8833  
KF8840  
-
-
-
For testing burner controls fitted to the burner  
With signal lamps for program indication  
With 2 jacks for measuring the flame detector current  
Test adapter  
-
-
-
-
-
For testing burner controls fitted to the burner  
With signal lamps for program indication  
With switch for simulating the flame signal  
With holes for checking the control voltages at the tabs of the burner control  
With 2 jacks for measuring the flame detector’s resistance  
4/10  
Siemens Building Technologies  
HVAC Products  
CC1N7118en  
09.10.2002  
Technical data  
General unit data  
Mains voltage  
AC 220 V –15 %...AC 240 V +10 %  
AC 100 V –15 %...AC 110 V +10 %  
Mains frequency  
50...60 Hz ±6 %  
External primary fuse (Si)  
Power consumption  
Degree of protection  
Safety class  
10 A (fast)  
approx. 3 VA  
IP 40, must be ensured through mounting  
I
Perm. cable lengths  
- Detector cable laid separately  
- Remote reset laid separately  
Mounting position  
max. 3 m with 100 pF/m line capacitance  
max. 20 m  
max. 20 m  
optional  
Weight  
approx. 180 g  
Input current to  
-
-
Terminal 1  
Terminal 3  
5 A (short-time 15 A for max. 0.5 s)  
5 A (excl. current draw of burner motor and  
oil preheater)  
Max. perm. current at  
cos ꢀ O 0.6  
Terminal Terminal Terminal Terminal Terminal Terminal  
4
5
6
7
8
10  
LOA24.171B27  
LOA24.171B17  
LOA24.571C27  
LOA25.173C27  
LOA25.173C17  
LOA28.173A27  
LOA24.173A27  
LOA24.174A27  
LOA26.171B27  
LOA36.171A27  
1 A  
1 A  
2 A  
2 A  
5 A  
1 A  
1A  
1 A  
1 A  
2 A  
2 A  
1.5 A  
0.1 A  
5 A  
5 A  
1 A  
1 A  
1 A  
Environmental  
conditions  
Transport  
DIN EN 60 721-3-2  
class 2K2  
Climatic conditions  
Mechanical conditions  
Temperature range  
Humidity  
class 2M2  
-50...+60 °C  
< 95 % r.h.  
Operation  
DIN EN 60 721-3-3  
class 3K5  
Climatic conditions  
Mechanical conditions  
Temperature range  
Humidity  
class 3M2  
-20...+60 °C  
< 95 % r.h.  
Condensation, formation of ice and ingress of water are not permitted!  
5/10  
Siemens Building Technologies  
HVAC Products  
CC1N7118en  
09.10.2002  
Flame detectors  
QRB...  
For measuring circuits and detector cable lengths, refer to Data Sheets 7714 (QRB...)  
and 7716 (QRC...).  
Type of burner control  
QRB... (typically)  
Max. perm. detector  
current  
Min. detector current  
required (with flame)  
Max. detector current  
possible (with flame)  
(without flame)  
LOA24.171B27 / LOA24.171B17  
LOA24.571C27  
70 µA  
5.5 µA  
210 µA  
LOA25.173C27 / LOA25.173C17  
LOA26.171B27  
LOA28.173A27  
LOA24.173A27  
LOA24.174A27  
LOA36.171A27  
45 µA  
70 µA  
5.5 µA  
5.5 µA  
45 µA  
900 µA  
QRC1...  
Type of burner control  
QRC... (typically)  
Max. perm. detector  
current  
Min. detector current  
required (with flame)  
Max. detector current  
possible (with flame)  
(without flame)  
LOA24.171B27  
LOA24.571C27  
LOA26.171B27  
70 µA  
5.5 µA  
110 µA  
LOA24.171B17  
70 µA  
---  
5.5 µA  
---  
90 µA  
---  
LOA25.173C27 ¹)  
LOA25.173C17 ¹)  
LOA28.173A27 ¹)  
LOA24.173A27  
LOA24.174A27  
45 µA  
70 µA  
5.5 µA  
5.5 µA  
45 µA  
LOA36.171A27  
110 µA  
¹) These types of LOA... may not be used in connection with QRC...blue-flame detec-  
tors  
Data given in the above table only apply under the folllowing conditions:  
- Mains voltage AC 230 V  
- Ambient temperature 23 °C  
QRB...  
QRC...  
Measuring curcuit for  
detector current  
12  
11  
bl  
12  
sw  
1
LOA...  
LOA...  
11  
bl  
Legend  
7118v02/0102  
7118v01/0102  
br  
sw  
+
+
µA DC DC microammeter  
with an internal resistance of  
Ri = max. 5 k  
µA DC  
µA DC  
bl  
Blue  
sw  
br  
Black  
Brown  
QRB...  
QRC1...  
Only with LOA36...  
Indication of flame  
strength  
Detector current LED lit  
-
-
With QRB...  
With QRC...  
min. 60 µA ±15 %  
min. 40 µA ±15 %  
6/10  
Siemens Building Technologies  
HVAC Products  
CC1N7118en  
09.10.2002  
Function  
Preconditions for  
startup  
S
S
S
S
Burner control is reset  
Contacts in the line are closed  
No undervoltage  
Flame detector is darkened, no extraneous light  
Undervoltage detection  
An additional electronic circuit ensures that if mains voltage drops below approximately  
AC 165 V, burner startup will be prevented, or – without release of oil – lockout will be  
triggered.  
Control sequence in the  
event of fault  
Whenever lockout occurs, the outputs for the fuel valves, the burner motor, oil prehea-  
ter and ignition equipment will immediately be deactivated (< 1 second).  
The lockout indication lamp changes to red and terminal 10 («AL») for remote lockout  
indication receives voltage.  
This state is also maintained in the event of mains voltage failure.  
Cause  
Response  
Mains voltage failure  
New start  
Extraneous light on burner startup  
Lockout; with LOA25... / LOA28...: Preven-  
tion of start  
Lockout  
Repetition  
No flame at the end of «TSA»  
Loss of flame during operation  
Reset  
After lockout, the burner control can be reset after 60...90 seconds (also refer to  
«Warning notes»).  
Indications  
Lockout position  
Flame strength  
The lockout position is indicated with the lamp integrated in the lockout reset button.  
Only with LOA36...  
Indication of the flame strength (green LED) is used for checking the flame signal.  
To ensure reliable burner operation, this LED must be lit.  
If the green LED flickers or extinguishes during burner operation, the light conditions at  
the burner are poor, caused by dirt for instance.  
Operation  
Only with LOA36...  
When the contacts of the control thermostat are closed, the orange LED is lit, indicating  
the start of the oil preheater’s heating up phase (if present).  
7/10  
Siemens Building Technologies  
HVAC Products  
CC1N7118en  
09.10.2002  
Connection diagram and internal diagram  
Control sequence  
A´  
A´  
A´  
A
A
A
B
C
C
C
D
D
D
R
LOA24.171B27  
LOA24.171B17  
LOA24.571C27  
1
8
3
tz2  
y
SB  
W
tz1  
f
EK1  
fr  
c
d
g
L1  
e
x
z
a
OH  
OW  
M
b
FR  
5
K
V
t3n  
t4  
TZ  
3
3
6
7
4
1
2
10  
8
7
6
4
9
11  
12  
t1  
t3  
tw  
SB  
Z
TSA  
OW  
W
R
BV1  
BV2  
FS  
QRB  
OH  
5
Z
AL  
N
BV1  
11  
12  
Si  
QRC  
br  
L
M
7118d04/0402  
BV2  
N
1
B
R
LOA24.173A27  
LOA24.174A27  
1
8
3
3
7
6
tz2  
z
SB  
W
tz1  
f
EK1  
fr  
x
c d  
g
y
L1  
2
e
a
b
OH  
OW  
M
FR  
5
K
V
TZ  
1
10  
8
3
7
6
4
9
11  
12  
t3n´  
SB  
Z
t1  
t3  
t3n  
t4  
tw  
OW  
W
R
TSA  
QRB  
OH  
Z
BV1  
4
5
AL  
N
BV1  
Si  
QRC  
br  
BV2  
FS  
L
M
BV2  
N
11  
12  
1
7118d01/0402  
B
R
LOA25.173C27  
LOA25.173C17  
LOA28.173A27  
1
8
3
3
SB  
W
tz2  
z
tz1  
EK1  
fr**  
x
y
c d  
e f  
g
L1  
2
OH  
OW  
OW  
a
b
FR  
5
K
V
1
2
TZ  
3
1
10  
8
7
6
4
9
11  
12  
SB  
W
R
M
Z
3
6
7
4
t3n´  
t1  
t3  
tw  
OW  
TSA  
OH  
Z
AL  
BV1  
BV1  
BV2  
QRB.  
t4  
Si  
M
L
5
BV2  
FS  
N
11  
12  
7118d02/0402  
fr** Not provided with the LOA28.173A27  
1) LOA25.173C27 / LOA25.173C17  
2) LOA28.173A27  
8/10  
Siemens Building Technologies  
HVAC Products  
CC1N7118en  
09.10.2002  
Connection diagram and internal diagram  
Control sequence  
A´  
A
B
C
D
R
LOA26.171B27  
tz2  
z
tz1  
1
8
3
3
6
SB  
W
EK1  
fr  
a
x
y
c d  
e
f g  
L1  
FR  
5
b
OH  
OW  
M
With ARK21  
remote lockout  
reset module  
K
V
t3n  
TZ  
1
2
10  
8
3
7
6
4
9
11  
12  
SB  
t1  
tw  
OW  
Z
W
R
QRB  
OH  
SA  
BV1  
7
4
5
Z
AL  
t3  
TSA  
SA  
N
BV1  
10  
Si  
N
QRC  
br  
L
M
BV2  
t4  
N
1
BV2  
FS  
11  
12  
2
10  
13  
9
EK2  
7118d05/0402  
14  
ARK21A27  
A´  
A
B
C
D
R
LOA36.171A27  
tz2  
z
tz1  
1
8
3
3
6
SB  
W
EK1  
fr  
x
y
c d  
f
g
LED1  
e
L1  
2
a
b
FR  
5
OH  
OW  
M
With ARK21  
remote lockout  
reset module  
K
V
L2  
t3n  
TZ  
1
10  
8
3
7
6
4
9
11  
12  
SB  
t1  
tw  
OW  
Z
W
R
QRB  
OH  
SA  
BV1  
7
4
5
Z
AL  
t3  
TSA  
SA  
N
BV1  
10  
Si  
N
QRC  
br  
L
M
BV2  
EK2  
t4  
N
1
BV2  
FS  
11  
12  
2
10  
13  
9
7118d05/0402  
14  
ARK21A27  
Legend  
AL  
Alarm device  
Fuel valve  
Lockout reset button  
Remote lockout reset button  
Flame relay with contacts «fr»  
Bridging contact for release contact of «OH»  
Flame signal  
OW  
OH  
QRB  
QRC  
Release contact of oil preheater  
Oil preheater  
Photoresistive detector  
BV...  
EK1  
EK2  
FR  
fr  
Blue-flame detector  
bl = blue, br = brown, sw = black  
Control thermostat or pressurestat  
Actuator with automatic setback  
Safety limit thermostat  
External primary fuse  
Thermal-electric sequence switch  
Contacts of «TZ»  
Limit thermostat or pressure switch  
Flame signal amplifier  
Ignition transformer  
R
FS  
K
SA  
SB  
Si  
TZ  
tz...  
W
Catch of flame relay for locking contact «tz1»  
in the event of premature flame signals or for locking  
the contact when the flame signal is correct  
Indication of faults (red)  
Indication of operation (green)  
Indication of flame strength (green)  
Burner motor  
L1  
L2  
LED1  
M
V
Z
TSA  
tw  
t1  
Ignition safety time  
Waiting time  
Prepurge time  
A´  
A
B
Beginning of the startup sequence with burners using an «OH»  
Beginning of the startup sequence with burners using no «OH»  
Time of flame establishment  
t3  
Preignition time  
C
D
Running position  
Controlled shutdown by «R»  
t3n  
t3n´  
t4  
Long postignition time  
Short postignition time  
Interval between flame signal and release of «BV2»  
Control signals delivered by the LOA...  
Required input signals  
Permissible input signals  
9/10  
Siemens Building Technologies  
HVAC Products  
CC1N7118en  
09.10.2002  
Dimensions  
Dimensions in mm  
22  
LOA...  
41,5  
88  
91  
LOA2...  
LOA3...  
xxxxxxxxxx  
xxxxxxxxxx  
7118m03/0300  
36,5  
Status indication, orange  
Indication of flame strength, green  
83,5  
67,5  
*
Remote lockout reset  
module ARK21A27  
23  
12  
*
*
+
+
7118m04/0300  
Remote lockout reset module for use with the LOA26... / LOA36...  
Printed circuit board with no housing.  
Degree of protection IP 00, which means that protection against electric shock hazard  
must be ensured through mounting.  
Do not place any metal objects in the hatched area.  
The module must be fitted with the help of spacers made of plastic.  
Do not use spacers made of metal.  
2002 Siemens Building Technologies  
Subject to change!  
10/10  
Siemens Building Technologies  
HVAC Products  
CC1N7118en  
09.10.2002  

相关型号:

LOA24.174A27

Oil Burner Controls
SIEMENS

LOA24.571C27

Oil Burner Controls
SIEMENS

LOA670

Lead (Pb) Free Product - RoHS Compliant
OSRAM

LOA670-HK

SIDELED
INFINEON

LOA670-J

SIDELED
INFINEON

LOA670-J1K1-1

Optoelectronic Device
INFINEON

LOA670-J1K1-24

Visible LED, Clear
INFINEON

LOA670-JM

SIDELED
INFINEON

LOA670-K

SIDELED
INFINEON

LOA670-L

SIDELED
INFINEON

LOA672-LP

Super SIDELED High-Current LED
INFINEON

LOA672-N

Super SIDELED High-Current LED
INFINEON