2112 [SYSTEMSENSOR]

Photoelectronic Smoke Detectors; 光电烟雾探测器
2112
型号: 2112
厂家: SYSTEMSENSOR ADVANCED IDEAS.    SYSTEMSENSOR ADVANCED IDEAS.
描述:

Photoelectronic Smoke Detectors
光电烟雾探测器

光电
文件: 总4页 (文件大小:85K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
INSTALLATION AND MAINTENANCE INSTRUCTIONS  
2112/24S and 2112/24TS  
Photoelectronic Smoke Detectors  
3825 Ohio Avenue, St. Charles, Illinois 60174  
1-800-SENSOR2, FAX: 630-377-6495  
Specifications  
Diameter:  
5.5 inches (140 mm)  
Height (including mounting bracket): 1.9 inches (48 mm)  
Weight:  
5.3 oz. (150 g)  
Operating Temperature Range  
Model 2112/24S:  
Model 2112/24TS:  
Operating Humidity Range:  
Latching Alarm:  
32° to 120°F (0° to 50°C)  
32° to 100°F (0° to 38°C)  
10% to 93% Relative Humidity, Noncondensing  
Reset by momentary power interruption  
Heat Sensor (2112/24TS only):  
Electrical Ratings  
System Voltage (nominal):  
Minimum:  
135°F Fixed Temperature Electronic Thermistor  
12 or 24 VDC  
8.5 VDC  
Maximum:  
35 VDC  
Maximum Ripple Voltage:  
Standby Current:  
30% of nom. Voltage (peak to peak)  
50 µA maximum  
Alarm Current:  
17 mA typical, 23 mA max. at 12V  
19 mA typical, 25 mA max. at 24V  
0.8 VDC minimum  
Reset Voltage:  
Reset Time:  
Start-up Time:  
EOL Relay:  
0.3 seconds maximum  
30 seconds maximum (after 60 sec. reset)  
A77-716B, 12/24 Volt  
Alarm Initiation Contact Ratings  
Resistive or Inductive Load (60% power factor)  
Form A:  
0.5A @ 30 VAC/DC  
Before Installing  
Installation of these detectors is simplified by the use of a  
Please thoroughly read the System Sensor manual I56-407, mounting bracket and a plug-in screw terminal block that  
Guide for Proper Use of System Smoke Detectors, which pro- can be prewired to the system, allowing the detector to be  
vides detailed information on detector spacing, placement, easily installed or removed for cleaning. The detector’s sen-  
zoning, wiring, and special applications. Copies of this sitivity can be tested in place using the MOD400R Test  
manual are available at no charge from System Sensor.  
Module.  
NOTICE: This manual shall be left with the owner/user of  
this equipment.  
An LED on the detector provides a local visual indication of  
the detector’s status. If power is applied to the detector, and  
it is functioning normally in standby mode within the listed  
sensitivity ranges, the status LED blinks once every ten sec-  
onds. The LED also provides a visual indication that main-  
tenance is required. If the LED stops blinking, the detector  
is either not powered, out of the listed sensitivity range,  
and/or unable to function properly. The test switch will not  
operate if the detector is below the insensitive limit. The  
LED will also latch on when the detector is in alarm.  
IMPORTANT: This detector must be tested and maintained  
following NFPA 72 requirements. The detector should be  
cleaned at least once a year.  
General Description  
Model 2112/24S is a 4-wire photoelectronic smoke detector  
that uses a state-of-the-art optical sensing chamber. This  
detector is designed to provide open area protection. Model  
2112/24TS features a restorable, built-in, fixed-temperature  
(135°F) thermal detector.  
D200-62-00  
1
I56-932-12R  
Figure 1. Surface mounting of 2112/24S smoke  
detector on 31/  
-inch and 4-inch octagonal box:  
separate grounded conduit. Do not mix fire system wiring  
in the same conduit as any other electrical wiring. Twisted  
pair may be used to provide additional protection against  
electrical interference.  
2
Smoke detectors and alarm system control panels have  
specifications for allowable loop resistance. Consult the  
control panel specifications for the total loop resistance al-  
lowed for the control panel being used before wiring the  
detector loops.  
A78-2563-00  
Mounting  
1
Each 2112/24S and 2112/24TS detector is supplied with a Wire connections are made by stripping about /  
4
inch of  
mounting bracket that permits the detector to be mounted: insulation from the end of the feed wire, inserting the wire  
1. To a single gang box, or  
2. Directly to a 31/  
-inch or 4-inch octagonal box, or  
into the appropriate terminal, and tightening the screw to  
secure the wire in place.  
2
3. To a 4 inch square electrical box by using a plaster ring.  
4. Directly to the ceiling using drywall anchors, if permit-  
ted by local codes and/or the authority having jurisdic-  
tion.  
Installation  
WARNING  
Remove power from the control unit or initiating device cir-  
cuits before installing detectors.  
Tamper-resistant Feature  
This detector includes a tamper-resistant feature that pre-  
vents its removal from the bracket without the use of a tool.  
To make the detector tamper-resistant, remove the smaller  
tab by breaking it at the scribed line on the tamper resistant  
tab on the detector mounting bracket (see Figure 2), then  
install the detector. To remove the detector from the bracket  
once it has been made tamper resistant, use a small screw-  
driver to depress the tamper-resistant tab, located in the  
slot on the mounting bracket, and turn the detector coun-  
terclockwise.  
1. Wire the plug-in screw terminal block per Figure 3 and  
plug the terminal block into the detector.  
2. Align the arrows on the detector with the arrows on the  
mounting bracket.  
3. Turn the detector clockwise in the mounting bracket un-  
til it clicks into place.  
4. After all detectors have been installed, apply power to  
the control unit or initiating device circuits.  
5. Test the detector as described in TESTING. (See page 3.)  
6. Reset the detector at the system control panel.  
7. Notify the proper authorities the system is in operation.  
Wiring Installation Guidelines  
All wiring must be installed in compliance with the Na-  
tional Electrical Code, applicable local codes, and any spe-  
cial requirements of the local authority having jurisdiction.  
Proper wire gauges should be used. The conductors used to  
connect smoke detectors to control panels and accessory  
devices should be color-coded to reduce the likelihood of  
wiring errors. Improper connections can prevent a system  
from responding properly in the event of a fire.  
CAUTION  
Dust covers are an effective way to limit the entry of dust  
into smoke detector sensing chambers. However, they may  
not completely prevent airborne dust particles from enter-  
ing the detector. Therefore, System Sensor recommends the  
removal of detectors before beginning construction or other  
dust producing activity. Be sure to remove dust covers from  
any sensors that were left in place during construction as  
part of returning the system to service.  
The screw terminal block accepts 14 – 22 gauge wire. For  
best system performance, all wiring should be installed in  
Figure 2. 2112/24S and 2112/24TS smoke detector mounting bracket:  
TAMPER RESISTANT TAB  
(CUT OFF SMALL TAB TO  
ACTIVATE TAMPER-RESIST  
FEATURE)  
TAMPER SLOT  
(DEPRESS TAB TO  
REMOVE DETECTOR)  
ALIGNMENT  
ARROWS  
A78-2333-01  
D200-62-00  
2
I56-932-12R  
Figure 3. Wiring diagram for the 2112/24S and 2112/24TS detector:  
+
POWER  
TO  
DETECTORS  
EOL POWER  
SUPERVISION  
RELAY (SHOWN  
ENERGIZED)  
A77-716 12/24V  
+
+
+
+
P
W
R
P
W
R
UL LISTED  
CONTROL  
PANEL  
+
+
EOL RESISTOR  
SPECIFIED BY  
PANEL  
MANUFACTURER  
+
INITIATING  
LOOP  
OPTIONAL CLASS A WIRING  
A78-2336-03  
Testing  
Hold the heat source about 12 inches from the detector  
in order to avoid damage to the plastic. The detector will  
reset only after it has had sufficient time to cool and the  
power source has been momentarily interrupted.  
NOTE: Before testing, notify the proper authorities that  
the smoke detector system is undergoing mainte-  
nance and will be temporarily out of service. Dis-  
able the zone or system undergoing maintenance  
to prevent unwanted alarms.  
Both smoke and heat detection testing are recommended  
for verifying system protection capability.  
Detectors must be tested after installation and following  
periodic maintenance. Test the 2112/24S as follows:  
A. Test Switch  
A detector that fails to activate with any of the above tests  
should first be cleaned as outlined in MAINTENANCE. If  
1. A recessed test switch is located on the detector hous- the detector still fails to activate, return it for repair.  
ing (See Figure 4).  
2. Press and hold the recessed test switch with a 0.18 Notify the proper authorities the system is back in  
inch maximum diameter tool such as an allen wrench operation.  
or small screwdriver.  
3. The detector’s LED should light within 5 seconds.  
B. Test Module (System Sensor Model No. MOD400R)  
The MOD400R test module can be used with a DMM or  
analog voltmeter to check the detector sensitivity as de-  
scribed in the test module’s manual.  
Maintenance  
NOTE: Before removing the detector, notify the proper au-  
thorities that the smoke detector system is under-  
going maintenance and will be temporarily out of  
service. Disable the zone or system undergoing  
maintenance to prevent unwanted alarms.  
C. Smoke Entry Test  
Hold a smoldering punk stick or cotton wick at the side  
of the detector and gently blow smoke through the de-  
tector until the unit alarms.  
D. Direct Heat Method (Model 2112/24TS only – Hair dryer  
of 1000-1500 watts)  
Direct the heat toward either of the side thermistors.  
Figure 4. Top and side views showing position of test switch:  
LED  
PUSH RECESSED  
TEST MODULE  
SOCKET  
SWITCH WITH A  
0.18MAX. DIAMETER TOOL  
RECESSED TEST  
SWITCH  
A78-2564-05  
D200-62-00  
3
I56-932-12R  
1. Remove cover by turning counter clockwise in direction Figure 5. Removal of cover and screen for cleaning:  
of arrow.  
2. Vacuum the cover carefully (See Figure 5).  
3. Remove the sensing chamber cover.  
REMOVABLE  
SCREEN/COVER  
4. Clean the sensing chamber by vacuuming or blow  
ing out dust and particles.  
(PART NO. C58-357-XX))  
5. Replace the sensing chamber cover, aligning the arrow on the  
top of the chamber cover with the arrow on the housing.  
6. Replace the cover by placing over the sensing chamber  
cover and twisting until it snaps into place.  
7. Reinstall the detector.  
SENSING  
CHAMBER COVER  
HOUSING  
8. Notify the proper authorities that the system is back in  
operation.  
A78-2565-07  
Please refer to insert for the Limitations of Fire Alarm Systems  
Three-Year Limited Warranty  
System Sensor warrants its enclosed smoke detector to be free from de-  
fects in materials and workmanship under normal use and service for a  
period of three years from date of manufacture. System Sensor makes no  
other express warranty for this smoke detector. No agent, representative,  
dealer, or employee of the Company has the authority to increase or alter  
the obligations or limitations of this Warranty. The Company’s obligation  
of this Warranty shall be limited to the repair or replacement of any part of  
the smoke detector which is found to be defective in materials or work-  
manship under normal use and service during the three year period com-  
mencing with the date of manufacture. After phoning System Sensor’s toll  
free number 800-SENSOR2 (736-7672) for a Return Authorization number,  
send defective units postage prepaid to: System Sensor, Repair Depart-  
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please  
include a note describing the malfunction and suspected cause of failure.  
The Company shall not be obligated to repair or replace units which are  
found to be defective because of damage, unreasonable use, modifica-  
tions, or alterations occurring after the date of manufacture. In no case  
shall the Company be liable for any consequential or incidental damages  
for breach of this or any other Warranty, expressed or implied whatsoever,  
even if the loss or damage is caused by the Company’s negligence or fault.  
Some states do not allow the exclusion or limitation of incidental or conse-  
quential damages, so the above limitation or exclusion may not apply to  
you. This Warranty gives you specific legal rights, and you may also have  
other rights which vary from state to state.  
D200-62-00  
4
I56-932-12R  
2001 System Sensor  
©

相关型号:

MILL-MAX
MILL-MAX
MILL-MAX

2112-1-01-50-7

PCB Terminal
MILL-MAX

2112-1-01-80-00-00-07-0

PCB Terminal, ROHS COMPLIANT
MILL-MAX
MILL-MAX
MILL-MAX

2112-2-01-44-00-00-07-0

PCB Terminal, ROHS COMPLIANT
MILL-MAX

2112-2-01-44-7

PCB Terminal
MILL-MAX
MILL-MAX
MILL-MAX

2112-3-01-44-00-00-07-0

PCB Terminal, ROHS COMPLIANT
MILL-MAX