5451 [SYSTEMSENSOR]

Plug-in Smoke Detector; PLUG -IN烟雾探测器
5451
型号: 5451
厂家: SYSTEMSENSOR ADVANCED IDEAS.    SYSTEMSENSOR ADVANCED IDEAS.
描述:

Plug-in Smoke Detector
PLUG -IN烟雾探测器

文件: 总4页 (文件大小:170K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
C o n v e n t i o n a l  
D e t e C t i o n  
400 Series  
Plug-in Smoke Detector  
Models Available  
1451  
1451A  
Ionization Detector  
Ionization Detector,  
ULC Listed  
5451  
Thermal Rate-of-Rise  
Product Overview  
Low standby current  
System Sensor’s 400 Series plug-in smoke detectors are designed to meet the  
performance criteria designated by UL/ULC. The ion units have a sensing chamber  
sealed from back pressure air flow, dirt, and insects. This chamber is protected  
by a fine mesh screen which can be cleaned or replaced. Additional key features  
include a recessed mounting option, interchangeable ion, thermal detectors, a vari-  
ety of mounting bases, and a full line of optional accessories.  
Two visible LEDs “blink” in standby and  
provide a 360° field viewing angle  
Wide variety of mounting bases with  
built-in shorting spring  
Detector head plugs easily into base  
Built-in test switch  
Ionization. All 400 Series ionization smoke detectors include a specially designed dual  
source, dual unipolar detector chamber design which will sense the presence of smoke  
particles produced by fast combustion as well as slow smoldering fires. This chamber  
exhibits increased stability, significantly reduces nuisance alarms, and provides better  
performance at higher air velocities.  
Field sensitivity metering of detector to  
meet the requirements of NFPA 72  
Built-in tamper-resistant feature  
SEMS screws for easy wiring  
Optional recessed mounting  
Thermal. The 400 Series thermal rate-of-rise with fixed heat detector contains a  
unique dual thermistor heat sensing circuit to provide maximum performance and  
solid state reliability. The Model 5451 is designed to initiate an alarm at 135°F and  
to respond to a temperature increase in excess of 15° per minute. This enables the  
heat detector to communicate an alarm to the central control panel prior to reaching  
the static set point for these high rates of rise, providing a timely response to both  
rapid and slow temperature increases. This model should be used in applications  
where rapid response is desired and where rapid temperature increases would only be  
caused by a fire emergency.  
Removable cover and insect screen for  
field cleaning  
Mounting Base Selection Guide  
Base Model  
Loop  
Type  
Current  
Limit Resistor  
Alarm  
Contact Type  
Nominal  
Voltage  
Current Draw  
on Alarm (mA)  
Number  
B401B  
B401BR  
B402B  
B404B  
Version  
UL/ULC  
UL/ULC  
UL/ULC  
UL/ULC  
2-wire*  
2-wire*  
4-wire  
No  
12/24VDC††  
24VDC  
10–100**  
10–62  
Yes  
Yes  
Yes  
Form A&C  
24VDC  
14–39  
4-wire  
Form A&C+A  
Supervisory  
120VAC  
75 mA AC Max  
B406B  
B401†  
B401R†  
UL/ULC/EN-54 2-wire*  
No  
No  
Yes  
Form C  
24VDC  
12–100**  
10–100**  
10–62  
UL/EN-54  
EN-54  
2-wire*  
2-wire*  
12/24VDC††  
24VDC  
*Functionality contingent on panel compatibility.  
**Must be limited by control panel.  
Relay Contact Ratings:  
Resistive or Inductive  
†Flangeless base  
†† Although B401B and B401 bases are capable  
of operating at 12 and 24 VDC, they cannot be  
used with the 5451 in 12 V applications.  
(60% power factor) load.  
2.0A at 30 VAC/DC  
Form A:  
Form C: 0.6A at 110VDC, 2.0A at 30VDC  
1.0A at 125VAC, 2.0A at 30VAC  
Junction Box Selection Guide*  
Single  
Gang  
No  
3.5” Octagon  
4” Octagon  
4” Square  
No  
50 mm  
Yes  
60 mm  
Yes  
75 mm  
No  
B401/B401R  
B401B/BR  
No  
No  
Yes  
Yes  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
B402B/B406B Yes  
B404B No  
Yes  
Yes  
Yes  
Yes  
No  
Yes  
No  
No  
* Box depth contingent on base and wire size.  
Refer to National Electrical Code of local applicable codes for appropriate recommendations.  
Specifications  
Operating Voltage/Alarm Current:  
Mounting base dependent (see chart  
on page 2)  
Size:  
Humidity Range:  
10 – 93% RH non-condensing  
3.2”/8.1 cm height  
4.0”/10.2 cm diameter,  
unflanged base  
6.2”/15.7 cm diameter,  
flanged base  
Air Velocity Rating:  
Ionization: 1200 fpm maximum  
Standby Current:  
Ion:  
120 µA maximum  
Thermal:  
Smoke Detector Spacing:  
For ion detectors on smooth ceilings  
(as defined in NFPA 72), spacing of  
30 feet (900 sq. ft.) may be used  
as a guide. For thermal detectors on  
smooth ceilings (as defined in NFPA  
72), spacing of 50 feet (2500 sq. ft.)  
may be used. Other spacing may be  
used depending on ceiling height, high  
air movements, and other conditions  
or response requirements.  
Construction:  
Flame retardant Noryl plastic  
100 µA maximum  
Sensitivity:  
1.9% + 6%/ft. Ion  
Operating Temperature:  
1451:  
32°F to 120°F (0°C to 49°C)  
5451:  
Weight:  
1451:  
0.5 lb. (227 gm)  
5451:  
0.3 lb. (136 gm)  
32°F to 100°F (0°C to 38°C)  
Alarm Point, Thermal:  
135°F (57.2°C) or 15°F/min.  
rate of rise  
(–)  
(–)  
(–)  
OPTIONAL  
OPTIONAL  
(–)  
(–)  
RA400Z  
RA400Z  
(–)  
(–)  
2
2
EOL  
RESISTOR  
3
3
(+)  
(+)  
1
1
4
4
(+)  
(+)  
(+)  
(+)  
OPTIONAL FAULT TOLERANT WIRING  
B401 Series  
(+)  
RED (+)  
PURPLE  
(–)  
(–)  
RA400Z  
(OPTIONAL)  
RA400Z  
(OPTIONAL)  
(–)  
4
4
3
3
2
2
BLK  
5
9
5
14  
13  
12  
14  
13  
12  
11  
COM  
N.C.  
N.O.  
COM  
N.C.  
(+)  
(+)  
1
1
(–)  
N.O.  
11  
10  
10  
AUXILIARY  
CONTACTS  
AUXILIARY  
CONTACTS  
9
8
8
ALARM CIRCUIT  
B402B  
120 VAC  
120 VAC  
(–)  
(+)  
(–)  
3
3
RA400Z  
(OPTIONAL)  
RA400Z  
2
4
2
4
9
(OPTIONAL)  
1
1
14  
13  
12  
11  
14  
13  
12  
11  
COM  
N.C.  
N.O.  
COM  
N.C.  
N.O.  
5
5
(+)  
6
6
10  
10  
AUXILIARY  
AUXILIARY  
FORM C  
CONTACTS  
7
7
9
8
8
FORM C  
CONTACTS  
SUPERVISION CIRCUIT  
EOL  
RESISTOR  
ALARM  
CONTROL  
PANEL  
ALARM CIRCUIT  
B404B  
(+)  
EOL  
RESISTOR  
4
4
3
5
3
2
2
5
1
1
14  
13  
COM  
N.C.  
N.O.  
14  
13  
COM  
N.C.  
N.O.  
12  
12  
AUXILIARY  
CONTACTS  
AUXILIARY  
CONTACTS  
(–)  
OPTIONAL NFPA CLASS “A” WIRING  
B406B  
Ordering Information  
Part No.  
Description  
1451  
Ionization detector. Must be mounted to one of the B40X series bases listed in Mounting Base Guide.  
Same as above, Canadian model  
1451A  
5451  
Fixed heat detector with rate-of-rise. Alarm point at 57.2°C (135°F). Must be mounted to one of the 400  
Series Bases listed in Mounting Base Guide.  
Accessories  
Description  
RA400Z  
Remote annunciator for 2- or 4-wire systems, 3–32V. Use with ion and photo plug-in detectors.  
Fits standard U.S. single gang electrical box.  
B401BH  
Sounder base with B401. Requires an external 24 VDC power supply.  
1
Mounts to 4” square electrical box (1 / ” minimum depth).  
2
MOD400R  
Detector sensitivity test tool. (See below.) Use with most analog or digital multimeters.  
Satisfies requirement of NFPA 72 for sensitivity testing. (See below.)  
RMK400  
SMK400  
Recessed mounting kit for use with B401 or B401R mounting bases only. (See below.)  
Surface mounting kit provides for entry of surface wiring conduit.  
For use with B401 or B401R mounting bases only.  
EOLR-1  
RS14  
End of line relay for power supervision, 12/24 VDC, 4-wire only.  
Replacement insect screen for 1451.  
DUST45  
CRT400  
M02-04-01  
M02-09-00  
XR5  
Replacement protective dust cover for plug-in 400 Series.  
Cover removal tool for 1451.  
Test magnet.  
Test magnet with 32 inch telescoping handle.  
Detector removal tool. Allows installation and/or removal of ion, photo,  
and thermal detector heads from base in high ceiling installations.  
XP-4  
Extension pole for XR5. Comes in three 5 ft. sections.  
The MOD400R Field Sensitivity Test Module can be used with  
System Sensor’s Recessed Mounting Kit, RMK400, provides  
a simple installation solution where applications demand a  
lower profile smoke detector and reduces the depth of any  
400 Series plug-in detector by almost an inch. A special  
metal mounting bracket secures the kit and the base to  
the junction box and ceiling panel. (For use with B401 and  
B401R bases only.)  
any standard DC voltmeter or multimeter to check the sensitivity  
range of System Sensor’s detectors (satisfies NFPA 72 require-  
ment for sensitivity testing).  
System Sensor Sales and Service  
System Sensor Headquarters  
3825 Ohio Avenue  
St. Charles, IL 60174  
Ph: 800/SENSOR2  
Fx: 630/377-6495  
www.systemsensor.com  
System Sensor Canada  
Ph: 905.812.0767  
Fx: 905.812.0771  
System Sensor in China  
Ph: 86.29.8832.0119  
Fx: 86.29.8832.5119  
System Sensor – Far East  
Ph: 85.22.191.9003  
Fx: 85.22.736.6580  
System Sensor – India  
Ph: 91.124.237.1770 x.2700  
Fx: 91.124.237.3118  
System Sensor Europe  
Ph: 44.1403.891920  
Fx: 44.1403.891921  
System Sensor in Singapore  
Ph: 65.6273.2230  
Fx: 65.6273.2610  
System Sensor – Australia  
Ph: 613.54.281.142  
Fx: 613.54.281.172  
System Sensor – Russia  
Ph: 70.95.937.7982  
Fx: 70.95.937.7983  
© 2005 System Sensor. The company reserves the right to change product specifications without notice.  
A05-0205-005•3/05•#1427  

相关型号:

5451035

Printed-circuit board connector - BCVP-508R- 9 GN
PHOENIX

5451077

Printed-circuit board connector - BCVP-508R-13 GN
PHOENIX

5451093

Printed-circuit board connector - BCVP-508R-15 GN
PHOENIX

5451255

Printed-circuit board connector - BCVP-508RF- 8 GN
PHOENIX

5451271

Printed-circuit board connector - BCVP-508RF-10 GN
PHOENIX

5451284

Printed-circuit board connector - BCVP-508RF-11 GN
PHOENIX

5451307

Printed-circuit board connector - BCVP-508RF-13 GN
PHOENIX

5451310

Printed-circuit board connector - BCVP-508RF-14 GN
PHOENIX

5451323

Printed-circuit board connector - BCVP-508RF-15 GN
PHOENIX

5451336

Printed-circuit board connector - BCVP-508RF-16 GN
PHOENIX

5451349

Printed-circuit board connector - BCVP-508RF-17 GN
PHOENIX

5451352

Printed-circuit board connector - BCVP-508RF-18 GN
PHOENIX