EPS10-1 AND EPS10-2  
Alarm Pressure Switches  
System Sensor EPS10 Series switches are designed  
for use in wet, dry, deluge, and pre-action automatic  
sprinkler systems to indicate a discharge from  
a sprinkler.  
Features  
The EPS10-1 has a single SPDT switch while the EPS10-2 model  
contains two SPDT switches. The EPS10 Series features field  
adjustable pressure sensitivity to provide an alarm response between  
4 and 20 psi. It is factory set to respond at 4 – 8 psi on rising or falling  
pressure. The pressure adjustment wheel requires no special tools  
and does not affect switch synchronization on the EPS10-2. The  
EPS10 Series switches are NEMA 4 rated.  
• Sensitivity adjustment wheel, no special tools required  
• Reinforced diaphragm resists pressure spikes  
• Two conduit entrances  
• Both one- and two-switch models available  
Agency Listings  
S739  
CS169  
3005863  
VdS  
7770-1209:147  
167-93-E  
G4020028-27  
Specifications, EPS10-1 and EPS10-2  
Architectural/Engineering Specifications EPS10-1 (SPDT), EPS10-2 (2/SPDT)  
Model shall be an EPS10-1 or EPS10-2 pressure type waterflow switch as manufactured by System Sensor of St. Charles, IL. They shall be installed on the  
sprinkler system with connection as shown on the drawings and/or as specified herein. Pressure switches shall be of the bellows-activated type. Switches shall  
have a maximum service pressure rating of 250 psi and shall be factory adjusted to operate at a pressure of 4 – 8 psi. There shall be one (1) or two (2) SPDT  
contacts rated at 10.0 Amp @ 125/250 VAC and 2.5 Amp @ 6/12/24 VDC. The contractor shall furnish and install, where indicated on the plans, pressure switches  
according to appropriate NFPA standards. Switches shall be provided with a ½˝ NPT male pressure connection to be connected to the alarm check valve of a  
“wetsprinkler system, into the intermediate chamber of adrysystem, or to a pre-action or deluge valve. They shall be activated by any flow of water equal to  
or in excess of the discharge from one sprinkler head. Switches shall provide 1 knockout type and 1 open hole for ½˝ conduit fitting attachment and a ground  
screw provision for electrical grounding. The switch enclosure shall be weatherproof and carry a UL 4x/NEMA 4 rating when used with proper electrical fittings  
and conduit. The cover shall incorporate tamper-resistant screws. The unit shall be listed by Underwriters Laboratories, Inc. and approved by Factory Mutual.  
Specifications, EPS10-1 and EPS10-2 (continued)  
Physical/Operating Specifications  
Maximum Operating  
Pressure  
250 psi  
Operating Temperature Range Indoor or outdoor use:  
–40°F to 160°F (–40°C to 71°C)  
Maximum Adjustment  
Pressure Range  
4 to 20 psi  
Cover Tamper Switch  
UL Models: Optional P/N 546-8000  
ULC Models: Factory Installed  
Differential  
Approximately 3 psi throughout range  
Operates at rising pressure 4 to 8 psi  
Enclosure  
Rated UL 4x, NEMA 4 for indoor or outdoor use  
1.2 lbs. (.54 Kg)  
Factory Setting  
Switch Contact Ratings  
Shipping Weight  
Service Use  
EPS10-1: One set SPDT (Form C)  
EPS10-2: Two sets SPDT (Form C)  
10.0 A, ½ HP @ 125/250 VAC  
2.5 A @ 6/12/24 VDC  
Automatic Sprinkler: NFPA 13  
One or Two Family Dwelling: NFPA 13D  
Residential Occupancies up to 4 Stories: NFPA 13R  
National Fire Alarm Code: NFPA 72  
Pressure Connection  
Dimensions  
½˝ NPT male glass reinforced nylon  
Warranty  
3 years  
5.12˝ H × 3.325˝ W × 4.250˝ L  
(13.0 cm × 8.4 cm × 10.8 cm)  
Typical Sprinkler Applications  
WIRE TO  
ALARM  
INDICATING  
CIRCUIT  
OF FIRE ALARM  
CONTROL PANEL  
TO  
WIRE TO ALARM  
WIRE TO  
ALARM  
INDICATING  
CIRCUIT  
OF FIRE  
ALARM  
SPRINKLER  
SYSTEM  
INDICATING CIRCUIT  
OF FIRE ALARM  
CONTROL PANEL  
EPS10  
EPS10  
EPS10  
TO  
SPRINKLER  
SYSTEM  
TO  
ALARM  
CHECK  
VALVE  
WATER  
MOTOR  
GONG  
ALARM  
CHECK  
VALVE  
SPRINKLER  
SYSTEM  
WATER  
MOTOR  
GONG  
CONTROL  
PANEL  
CHECK  
VALVE  
DRY  
PIPE  
VALVE  
WATER  
MOTOR  
GONG  
RETARD  
RETARD  
WATER  
BY-PASS  
VALVE  
LOCAL ALARM  
SHUT OFF  
VALVE  
WATER LOCAL ALARM  
BY-PASS SHUT OFF  
WATER  
BY-PASS  
VALVE  
LOCAL ALARM  
SHUT OFF  
VALVE  
OS & Y  
VALVE  
OS & Y  
VALVE  
OS & Y  
VALVE  
VALVE  
VALVE  
WET SYSTEM  
WET SYSTEM  
DRY SYSTEM  
Pressure Switch Basic Dimensions  
Electrical Connections  
41/  
4  
MODEL EPS10-2  
SWITCHES AT 0 PSI  
MODEL EPS10-1  
SWITCH AT 0 PSI  
B
COM  
A
B
COM  
A
B
COM  
A
GROUND  
SCREW  
(GREEN)  
SW1  
SW2  
HEX  
ADJUSTMENT  
SCREW  
SWITCH #2  
SWITCHES AT 4-8 PSI (HIGH TRIP PT.)  
SWITCH AT 4-8 PSI (HIGH TRIP PT.)  
B
COM  
A
B
COM  
A
B
COM  
A
SW1  
SW2  
SWITCH 1  
BOTH SWITCHES ACTIVATE SIMULTANEOUSLY  
51/  
8″  
MAIN ADJUSTMENT  
WHEEL  
LOCKING  
SCREW  
1
/
2
NPT  
Ordering Information  
Part No.  
Description  
EPS10-1  
Alarm Waterflow Pressure Switch, One SPDT, 4–20 PSI  
Alarm Waterflow Pressure Switch, Two SPDT, 4–20 PSI  
ULC/Canadian Version  
EPS10-2  
EPSA10-1  
EPSA10-2  
Replacement Parts  
S07-66-02  
WFDW  
ULC/Canadian Version  
Replacement Tamper Screws for Cover of EPS  
Replacement Tamper Proof Wrench for Cover of EPS  
Cover Tamper Switch for EPS Series  
546-8000  
©2006 System Sensor.  
3825 Ohio Avenue • St. Charles, IL 60174  
Phone: 800-SENSOR2 • Fax: 630-377-6495  
Product specifications subject to change without notice. Visit systemsensor.com for  
current product information, including the latest version of this data sheet.  
A05-0176-009 • 9/06 • #1676  

相关型号:

EPSA10-2

Alarm Pressure Switches
SYSTEMSENSOR

EPSA120-1

Supervisory Pressure Switches
SYSTEMSENSOR

EPSA120-2

Supervisory Pressure Switches
SYSTEMSENSOR

EPSA120050U

AC-DC POWER SUPPLY
CUI

EPSA120050UB

SWITCHING POWER SUPPLY
CUI

EPSA120050UE

SWITCHING POWER SUPPLY
CUI

EPSA120100U

12 W WALL PLUG - SWITCHING POWER SUPPLY
CUI

EPSA120100U-P5N-EJ

AC/DC WALL MOUNT ADAPTER 12V 12W
CUI

EPSA120100U-P5P-EJ

AC/DC WALL MOUNT ADAPTER 12V 12W
CUI

EPSA120100U-P5RP-EJ

AC/DC WALL MOUNT ADAPTER 12V 12W
CUI

EPSA120100U-P6P-EJ

AC/DC WALL MOUNT ADAPTER 12V 12W
CUI

EPSA120100U-P6RP-EJ

AC/DC WALL MOUNT ADAPTER 12V 12W
CUI