EPSA10-1 [SYSTEMSENSOR]
Alarm Pressure Switches; 报警压力开关型号: | EPSA10-1 |
厂家: | SYSTEMSENSOR ADVANCED IDEAS. |
描述: | Alarm Pressure Switches |
文件: | 总2页 (文件大小:187K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
EPS10-1 AND EPS10-2
Alarm Pressure Switches
System Sensor EPS10 Series switches are designed
for use in wet, dry, deluge, and pre-action automatic
sprinkler systems to indicate a discharge from
a sprinkler.
Features
The EPS10-1 has a single SPDT switch while the EPS10-2 model
contains two SPDT switches. The EPS10 Series features field
adjustable pressure sensitivity to provide an alarm response between
4 and 20 psi. It is factory set to respond at 4 – 8 psi on rising or falling
pressure. The pressure adjustment wheel requires no special tools
and does not affect switch synchronization on the EPS10-2. The
EPS10 Series switches are NEMA 4 rated.
• Sensitivity adjustment wheel, no special tools required
• Reinforced diaphragm resists pressure spikes
• Two conduit entrances
• Both one- and two-switch models available
Agency Listings
S739
CS169
3005863
7770-1209:147
167-93-E
G4020028-27
Specifications, EPS10-1 and EPS10-2
Architectural/Engineering Specifications EPS10-1 (SPDT), EPS10-2 (2/SPDT)
Model shall be an EPS10-1 or EPS10-2 pressure type waterflow switch as manufactured by System Sensor of St. Charles, IL. They shall be installed on the
sprinkler system with connection as shown on the drawings and/or as specified herein. Pressure switches shall be of the bellows-activated type. Switches shall
have a maximum service pressure rating of 250 psi and shall be factory adjusted to operate at a pressure of 4 – 8 psi. There shall be one (1) or two (2) SPDT
contacts rated at 10.0 Amp @ 125/250 VAC and 2.5 Amp @ 6/12/24 VDC. The contractor shall furnish and install, where indicated on the plans, pressure switches
according to appropriate NFPA standards. Switches shall be provided with a ½˝ NPT male pressure connection to be connected to the alarm check valve of a
“wet”sprinkler system, into the intermediate chamber of a“dry”system, or to a pre-action or deluge valve. They shall be activated by any flow of water equal to
or in excess of the discharge from one sprinkler head. Switches shall provide 1 knockout type and 1 open hole for ½˝ conduit fitting attachment and a ground
screw provision for electrical grounding. The switch enclosure shall be weatherproof and carry a UL 4x/NEMA 4 rating when used with proper electrical fittings
and conduit. The cover shall incorporate tamper-resistant screws. The unit shall be listed by Underwriters Laboratories, Inc. and approved by Factory Mutual.
Specifications, EPS10-1 and EPS10-2 (continued)
Physical/Operating Specifications
Maximum Operating
Pressure
250 psi
Operating Temperature Range Indoor or outdoor use:
–40°F to 160°F (–40°C to 71°C)
Maximum Adjustment
Pressure Range
4 to 20 psi
Cover Tamper Switch
UL Models: Optional P/N 546-8000
ULC Models: Factory Installed
Differential
Approximately 3 psi throughout range
Operates at rising pressure 4 to 8 psi
Enclosure
Rated UL 4x, NEMA 4 for indoor or outdoor use
1.2 lbs. (.54 Kg)
Factory Setting
Switch Contact Ratings
Shipping Weight
Service Use
EPS10-1: One set SPDT (Form C)
EPS10-2: Two sets SPDT (Form C)
10.0 A, ½ HP @ 125/250 VAC
2.5 A @ 6/12/24 VDC
Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 Stories: NFPA 13R
National Fire Alarm Code: NFPA 72
Pressure Connection
Dimensions
½˝ NPT male glass reinforced nylon
Warranty
3 years
5.12˝ H × 3.325˝ W × 4.250˝ L
(13.0 cm × 8.4 cm × 10.8 cm)
Typical Sprinkler Applications
WIRE TO
ALARM
INDICATING
CIRCUIT
OF FIRE ALARM
CONTROL PANEL
TO
WIRE TO ALARM
WIRE TO
ALARM
INDICATING
CIRCUIT
OF FIRE
ALARM
SPRINKLER
SYSTEM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
EPS10
EPS10
EPS10
TO
SPRINKLER
SYSTEM
TO
ALARM
CHECK
VALVE
WATER
MOTOR
GONG
ALARM
CHECK
VALVE
SPRINKLER
SYSTEM
WATER
MOTOR
GONG
CONTROL
PANEL
CHECK
VALVE
DRY
PIPE
VALVE
WATER
MOTOR
GONG
RETARD
RETARD
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
WATER LOCAL ALARM
BY-PASS SHUT OFF
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
OS & Y
VALVE
OS & Y
VALVE
OS & Y
VALVE
VALVE
VALVE
WET SYSTEM
WET SYSTEM
DRY SYSTEM
Pressure Switch Basic Dimensions
Electrical Connections
41/
4″
MODEL EPS10-2
SWITCHES AT 0 PSI
MODEL EPS10-1
SWITCH AT 0 PSI
B
COM
A
B
COM
A
B
COM
A
GROUND
SCREW
(GREEN)
SW1
SW2
HEX
ADJUSTMENT
SCREW
SWITCH #2
SWITCHES AT 4-8 PSI (HIGH TRIP PT.)
SWITCH AT 4-8 PSI (HIGH TRIP PT.)
B
COM
A
B
COM
A
B
COM
A
SW1
SW2
SWITCH 1
BOTH SWITCHES ACTIVATE SIMULTANEOUSLY
51/
8″
MAIN ADJUSTMENT
WHEEL
LOCKING
SCREW
1
/
2
″ NPT
Ordering Information
Part No.
Description
EPS10-1
Alarm Waterflow Pressure Switch, One SPDT, 4–20 PSI
Alarm Waterflow Pressure Switch, Two SPDT, 4–20 PSI
ULC/Canadian Version
EPS10-2
EPSA10-1
EPSA10-2
Replacement Parts
S07-66-02
WFDW
ULC/Canadian Version
Replacement Tamper Screws for Cover of EPS
Replacement Tamper Proof Wrench for Cover of EPS
Cover Tamper Switch for EPS Series
546-8000
©2006 System Sensor.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0176-009 • 9/06 • #1676
相关型号: