PS12 [SYSTEMSENSOR]

Signaling Strobe and Sounder; 信号频闪和发声器
PS12
型号: PS12
厂家: SYSTEMSENSOR ADVANCED IDEAS.    SYSTEMSENSOR ADVANCED IDEAS.
描述:

Signaling Strobe and Sounder
信号频闪和发声器

文件: 总4页 (文件大小:226K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
PS12/24ADA  
Signaling Strobe  
and Sounder  
A Division of Pittway  
3825 Ohio Avenue, St. Charles, IL 60174  
1-800-SENSOR2 (736-7672), Fax 630-377-6495  
http://www.systemsensor.com  
Models Available  
PS2415ADA  
PS241575ADA  
PS2475ADA  
PS24110ADA  
PS1215ADA  
PS121575ADA  
Features  
• Low combined strobe/horn current draw from 90 mA  
• New “Euro-Style” appearance  
System Sensor PS12/24ADA Series integrated sounder/  
strobes comply with the Americans with Disabilities Act  
(ADA) and the demanding requirements of the new  
• Easily fits into single gang backbox  
• Fits double gang backbox with optional semi-flush plate Standard UL 1971 for the Hearing Impaired. The 15/75  
• Multiple Light intensities  
version is UL 1971 listed at 15 cd.  
–24 VDC: 15, 15/75, 75 or 110 cd models  
–12 VDC: 15 or 15/75 cd models  
• Available in Red or White  
• No measurable in-rush in excess of peak current  
• Wall mount only  
To insure compliance with ADA and UL 1971, use the  
System Sensor 75 candela models for non-sleeping areas,  
and 110 candela models for sleeping areas. Available in red  
or white at 12 or 24 VDC, the PS12/24ADA series of  
signaling strobes can be mounted directly to a standard 2  
backbox or 4backbox with the optional semi-flush plate.  
Specifications  
Input terminals:  
Shipping Weight:  
PS12/24ADA  
Series Strobes:  
Operating  
18 – 12 AWG  
Dimensions:  
4  
3″  
13 oz. (369g)  
Temperature Range:  
Mounting:  
32°F to 120° F (0°C to 49°C)  
7″  
Surface:  
2″ × 4″ × 11/  
single gang box  
2″ × 4″ × 11/  
standard  
single gang box  
4standard  
Semi-flush:  
2
1
/ ″  
2
1
3 / ″  
2
APPROVED  
© System Sensor 8/96  
This document is not intended to be used for installation purposes.  
A05-250-02  
General Description  
All PS12/24ADA Series integrated sounder/strobes are  
suitable for primary signaling in public mode life safety  
intensity, or for 12VDC operation with 15 or 15/75 cd light  
intensity. They feature low current draw with no  
applications. The sounder/strobes can be connected to the measurable in-rush in excess of peak current. The  
alarm indicating circuit of a UL listed fire alarm control  
panel. They are compatible with DC line supervision.  
Panels may have full-wave rectified, unfiltered power  
supplies. The sounder/strobes are available for either  
24VDC operation, with 15, 15/75, 75, or 110 cd light  
sounder/strobe is intended for wall mounting only to a 2″  
electrical backbox. Mounting to a 4square electrical  
backbox can be done with the addition of the PS-FP  
accessory mounting plate.  
Electrical Ratings – Strobe/Mini Horn  
Average Operating  
Average Operating  
Peak  
In-rush Current in  
Current from  
Current from Full Wave  
Model  
Supply  
Voltage Range  
20–30VDC  
20–30VDC  
20–30VDC  
20–30VDC  
10.5–17VDC  
10.5–17VDC  
Operating Current  
Excess of Peak  
Operating Current (mA)  
Regulated Supply  
Rectified, Unfiltered Supply  
Red  
PS2415ADA  
White  
(mA)  
180  
220  
400  
500  
380  
560  
(mA)  
90  
(mArms)*  
105  
PS2415ADAW  
PS241575ADAW  
PS2475ADAW  
PS24110ADAW  
PS1215ADAW  
PS121575ADAW  
0
0
0
0
0
0
PS241575ADA  
PS2475ADA  
PS24110ADA  
PS1215ADA  
PS121575ADA  
108  
185  
225  
185  
240  
135  
215  
260  
212  
285  
* For additional information, see installation manual D900-08-00.  
Actual 12 volt operating voltage cannot be less than 8.5 VDC or greater than 18.7 VDC; actual 24 volt operating voltage cannot be less than 16 VDC or greater than 33 VDC.  
Engineering Specifications  
Sounder/Strobe shall be a System Sensor Model ______  
listed to Standard UL 1971 for the Hearing Impaired and  
shall be approved for Fire Protective Service. Sounder/  
Strobe shall be wired as a Primary Signaling Notification  
appliance. Sounder/strobe shall also comply with the  
Americans with Disabilities Act requirements for visible  
signaling appliances. Sounder/Strobe shall operate on 12  
or 24VDC from a regulated DC supply or full-wave  
rectified, unfiltered supply. The sounder/strobe shall be  
powered from a non-coded power supply. Sounder/Strobe  
shall have no measurable in-rush current in excess of  
operating peak current. Visual signaling devices are to be  
installed in all non-sleeping/corridor and sleeping areas  
per plans and specifications. The strobe light shall consist  
of a xenon flash tube and associated lens/reflector system.  
All sounder/strobes shall be capable of semi-flush wall  
mounting to a standard 2″ × 4″ × 11/  
backbox, without a  
2
separate mounting plate or to a 4″ × 4″ × 11/  
backbox  
2
with a separate mounting plate.  
Standard Light Distribution  
Vertical Dispersion  
Horizontal Dispersion  
Degree  
0
5-30  
35  
Percent of Rating  
ZERO AXIS  
0˚  
0
5
100  
90  
65  
46  
34  
27  
22  
18  
16  
15  
13  
12  
12  
12  
Degree  
0
5-25  
30-45  
50  
55  
60  
65  
70  
Percent of Rating  
100  
90  
75  
55  
45  
40  
35  
35  
30  
30  
25  
25  
40  
–45˚  
45˚  
45  
W
A
L
10  
15  
20  
50  
55  
60  
65  
70  
75  
80  
85  
90  
L
75  
80  
85  
LIGHT  
90  
–90˚  
90˚  
25  
WALL  
90˚ 85 80 75 70 65 60 55 50 45  
FLOOR  
40  
35  
30  
A polar light distribution in both horizontal and vertical directions is mandated for the strobes by the Standard UL 1971 for the Hearing Impaired, with  
specific minimum intensity percentages as shown in the graphs above. With its specially designed lens/reflector system, the PS12/24ADA Strobe  
Retrofit Plate Series meets or exceeds these requirements at all angles.  
Page 2  
A05-250-02  
Wiring  
From  
Cut and  
Remove for  
Independent  
Operation  
Control  
Panel  
or  
To  
Next  
From  
Blk  
Red  
To  
Next  
Device  
or  
Control  
Panel  
or  
Device  
Previous  
Device  
Previous  
Device  
EOL  
Note: Remove paper  
shield; cut and  
remove red and  
black wires between  
the horn and strobe.  
Mounting  
Sounder/Strobe  
2 Inch Box  
4 Inch Box with PS-FP  
4 Inch Box with Plaster  
Ring and PS-FP  
2 Inch Box with PS-FP  
Page 3  
A05-250-02  
Ordering Information  
Signaling Strobe – UL 1971 Compliant  
Strobe and Sounder  
Operating  
Voltage  
24 VDC  
24 VDC  
24 VDC  
24 VDC  
12 VDC  
12 VDC  
Current Combined  
(Average mA)  
Peak  
Red  
White  
Product  
Candela  
15  
15/75**  
75  
110  
15  
(dBA)*  
90 dBA  
90 dBA  
90 dBA  
90 dBA  
83 dBA  
83 dBA  
PS2415ADA  
PS241575ADA  
PS2475ADA  
PS24110ADA  
PS1215ADA  
PS121575ADA  
PS-FP  
PS2415ADAW  
PS241575ADAW  
PS2475ADAW  
PS24110ADAW  
PS1215ADAW  
PS121575ADAW  
PS-FPW  
Signaling Strobe/Sounder  
Signaling Strobe/Sounder  
Signaling Strobe/Sounder  
Signaling Strobe/Sounder  
Signaling Strobe/Sounder  
Signaling Strobe/Sounder  
Semi-Flush Mounting Plate  
90  
108  
185  
225  
185  
240  
15/75**  
*dBA measured in anechoic room at 10 feet.  
**Measured to be 75 cd at 0˚ viewing angle (See Light Distribution Graph).  
How to Order  
PS1215ADAW  
W = White Strobe  
15 = 15 cd, UL 1971 Strobe  
1575 = 15 cd, UL 1971  
75 = 75 cd, UL 1971 Strobe  
110 = 110 cd, UL 1971 Strobe  
12 = 12 Volt  
24 = 24 Volt  
SS = Signal Strobe  
PS = Mini-Alert Sounder/Strobe  
RP = Retrofit Plate  
MASS = Multi-Alert Sounder/Strobe  
MAEH = Multi-Alert Sounder/Strobe with Electromechanical Tone  
V4R = 400 Series Speaker, Red  
SP1R = SP101 Series Speaker (Strobe), Red  
SP1W = SP101 Series Speaker (Strobe), White  
System Sensor Worldwide Distribution  
In the Far East:  
System Sensor  
Pittway Far East, Ltd.  
Suite 706, World Shipping Centre  
7 Canton Road  
Tsimshatsui, Kowloon, Hong Kong  
Telephone: 852-2730-9090  
Fax: 852-2736-6580  
In Canada:  
In the United Kingdom:  
System Sensor Europe, Ltd.  
Horsham Gates III, North St.  
Horsham, West Sussex  
RH13 5PJ, United Kingdom  
Telephone: 44-1403-276500  
Fax: 44-1403-276501  
In India:  
System Sensor India  
A-204 Maheshwari Nagar  
Orkay Mills Lane  
Andheri East, Mumbai 400093  
Telefax: 91-022-8202564  
System Sensor Canada  
6581 Kitimat Road, Unit #7  
Mississauga, Ontario  
Canada L5N 3T5  
Telephone: 905-812-0767  
Fax: 905-812-0771  
Page 4  
A05-250-02  

相关型号:

PS12-1W

PS12 Series High Performance Solid State Relays
TE

PS12-1Y

PS12 Series High Performance Solid State Relays
TE

PS120

120W Single Output Industrial DIN Rail Power Supply
ALTECH

PS120

Silicon Controlled Rectifier, 20A I(T)RMS, 20000mA I(T), 100V V(DRM), 100V V(RRM), 1 Element
HUTSON

PS120

Power Shielded Inductor
ALLIED

PS120-1R0M-RC

Power Shielded Inductor
ALLIED

PS120-1R5M-RC

Power Shielded Inductor
ALLIED

PS120-2R2M-RC

Power Shielded Inductor
ALLIED

PS120-3R3M-RC

General Purpose Inductor
ALLIED

PS120-R22M-RC

Power Shielded Inductor
ALLIED

PS120-R33M-RC

Power Shielded Inductor
ALLIED

PS120-R47M-RC

Power Shielded Inductor
ALLIED