PS12 [SYSTEMSENSOR]
Signaling Strobe and Sounder; 信号频闪和发声器型号: | PS12 |
厂家: | SYSTEMSENSOR ADVANCED IDEAS. |
描述: | Signaling Strobe and Sounder |
文件: | 总4页 (文件大小:226K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
PS12/24ADA
Signaling Strobe
and Sounder
A Division of Pittway
3825 Ohio Avenue, St. Charles, IL 60174
1-800-SENSOR2 (736-7672), Fax 630-377-6495
http://www.systemsensor.com
Models Available
PS2415ADA
PS241575ADA
PS2475ADA
PS24110ADA
PS1215ADA
PS121575ADA
Features
• Low combined strobe/horn current draw from 90 mA
• New “Euro-Style” appearance
System Sensor PS12/24ADA Series integrated sounder/
strobes comply with the Americans with Disabilities Act
(ADA) and the demanding requirements of the new
• Easily fits into single gang backbox
• Fits double gang backbox with optional semi-flush plate Standard UL 1971 for the Hearing Impaired. The 15/75
• Multiple Light intensities
version is UL 1971 listed at 15 cd.
–24 VDC: 15, 15/75, 75 or 110 cd models
–12 VDC: 15 or 15/75 cd models
• Available in Red or White
• No measurable in-rush in excess of peak current
• Wall mount only
To insure compliance with ADA and UL 1971, use the
System Sensor 75 candela models for non-sleeping areas,
and 110 candela models for sleeping areas. Available in red
or white at 12 or 24 VDC, the PS12/24ADA series of
signaling strobes can be mounted directly to a standard 2″
backbox or 4″ backbox with the optional semi-flush plate.
Specifications
Input terminals:
Shipping Weight:
PS12/24ADA
Series Strobes:
Operating
18 – 12 AWG
Dimensions:
4″
3″
13 oz. (369g)
Temperature Range:
Mounting:
32°F to 120° F (0°C to 49°C)
7″
Surface:
2″ × 4″ × 11/
single gang box
2″ × 4″ × 11/
″ standard
single gang box
4″ standard
Semi-flush:
2
1
/ ″
2
1
3 / ″
2
APPROVED
© System Sensor 8/96
This document is not intended to be used for installation purposes.
A05-250-02
General Description
All PS12/24ADA Series integrated sounder/strobes are
suitable for primary signaling in public mode life safety
intensity, or for 12VDC operation with 15 or 15/75 cd light
intensity. They feature low current draw with no
applications. The sounder/strobes can be connected to the measurable in-rush in excess of peak current. The
alarm indicating circuit of a UL listed fire alarm control
panel. They are compatible with DC line supervision.
Panels may have full-wave rectified, unfiltered power
supplies. The sounder/strobes are available for either
24VDC operation, with 15, 15/75, 75, or 110 cd light
sounder/strobe is intended for wall mounting only to a 2″
electrical backbox. Mounting to a 4″ square electrical
backbox can be done with the addition of the PS-FP
accessory mounting plate.
Electrical Ratings – Strobe/Mini Horn
Average Operating
Average Operating
Peak
In-rush Current in
Current from
Current from Full Wave
Model
Supply
Voltage Range
20–30VDC
20–30VDC
20–30VDC
20–30VDC
10.5–17VDC
10.5–17VDC
Operating Current
Excess of Peak
Operating Current (mA)
Regulated Supply
Rectified, Unfiltered Supply
Red
PS2415ADA
White
(mA)
180
220
400
500
380
560
(mA)
90
(mArms)*
105
PS2415ADAW
PS241575ADAW
PS2475ADAW
PS24110ADAW
PS1215ADAW
PS121575ADAW
0
0
0
0
0
0
PS241575ADA
PS2475ADA
PS24110ADA
PS1215ADA
PS121575ADA
108
185
225
185
240
135
215
260
212
285
* For additional information, see installation manual D900-08-00.
Actual 12 volt operating voltage cannot be less than 8.5 VDC or greater than 18.7 VDC; actual 24 volt operating voltage cannot be less than 16 VDC or greater than 33 VDC.
Engineering Specifications
Sounder/Strobe shall be a System Sensor Model ______
listed to Standard UL 1971 for the Hearing Impaired and
shall be approved for Fire Protective Service. Sounder/
Strobe shall be wired as a Primary Signaling Notification
appliance. Sounder/strobe shall also comply with the
Americans with Disabilities Act requirements for visible
signaling appliances. Sounder/Strobe shall operate on 12
or 24VDC from a regulated DC supply or full-wave
rectified, unfiltered supply. The sounder/strobe shall be
powered from a non-coded power supply. Sounder/Strobe
shall have no measurable in-rush current in excess of
operating peak current. Visual signaling devices are to be
installed in all non-sleeping/corridor and sleeping areas
per plans and specifications. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system.
All sounder/strobes shall be capable of semi-flush wall
mounting to a standard 2″ × 4″ × 11/
″ backbox, without a
2
separate mounting plate or to a 4″ × 4″ × 11/
″ backbox
2
with a separate mounting plate.
Standard Light Distribution
Vertical Dispersion
Horizontal Dispersion
Degree
0
5-30
35
Percent of Rating
ZERO AXIS
0˚
0
5
100
90
65
46
34
27
22
18
16
15
13
12
12
12
Degree
0
5-25
30-45
50
55
60
65
70
Percent of Rating
100
90
75
55
45
40
35
35
30
30
25
25
40
–45˚
45˚
45
W
A
L
10
15
20
50
55
60
65
70
75
80
85
90
L
75
80
85
LIGHT
90
–90˚
90˚
25
WALL
90˚ 85 80 75 70 65 60 55 50 45
FLOOR
40
35
30
A polar light distribution in both horizontal and vertical directions is mandated for the strobes by the Standard UL 1971 for the Hearing Impaired, with
specific minimum intensity percentages as shown in the graphs above. With its specially designed lens/reflector system, the PS12/24ADA Strobe
Retrofit Plate Series meets or exceeds these requirements at all angles.
Page 2
A05-250-02
Wiring
From
Cut and
Remove for
Independent
Operation
Control
Panel
or
To
Next
From
Blk
Red
To
Next
Device
or
Control
Panel
or
Device
Previous
Device
Previous
Device
EOL
Note: Remove paper
shield; cut and
remove red and
black wires between
the horn and strobe.
Mounting
Sounder/Strobe
2 Inch Box
4 Inch Box with PS-FP
4 Inch Box with Plaster
Ring and PS-FP
2 Inch Box with PS-FP
Page 3
A05-250-02
Ordering Information
Signaling Strobe – UL 1971 Compliant
Strobe and Sounder
Operating
Voltage
24 VDC
24 VDC
24 VDC
24 VDC
12 VDC
12 VDC
Current Combined
(Average mA)
Peak
Red
White
Product
Candela
15
15/75**
75
110
15
(dBA)*
90 dBA
90 dBA
90 dBA
90 dBA
83 dBA
83 dBA
PS2415ADA
PS241575ADA
PS2475ADA
PS24110ADA
PS1215ADA
PS121575ADA
PS-FP
PS2415ADAW
PS241575ADAW
PS2475ADAW
PS24110ADAW
PS1215ADAW
PS121575ADAW
PS-FPW
Signaling Strobe/Sounder
Signaling Strobe/Sounder
Signaling Strobe/Sounder
Signaling Strobe/Sounder
Signaling Strobe/Sounder
Signaling Strobe/Sounder
Semi-Flush Mounting Plate
90
108
185
225
185
240
15/75**
*dBA measured in anechoic room at 10 feet.
**Measured to be 75 cd at 0˚ viewing angle (See Light Distribution Graph).
How to Order
PS1215ADAW
W = White Strobe
15 = 15 cd, UL 1971 Strobe
1575 = 15 cd, UL 1971
75 = 75 cd, UL 1971 Strobe
110 = 110 cd, UL 1971 Strobe
12 = 12 Volt
24 = 24 Volt
SS = Signal Strobe
PS = Mini-Alert Sounder/Strobe
RP = Retrofit Plate
MASS = Multi-Alert Sounder/Strobe
MAEH = Multi-Alert Sounder/Strobe with Electromechanical Tone
V4R = 400 Series Speaker, Red
SP1R = SP101 Series Speaker (Strobe), Red
SP1W = SP101 Series Speaker (Strobe), White
System Sensor Worldwide Distribution
In the Far East:
System Sensor
Pittway Far East, Ltd.
Suite 706, World Shipping Centre
7 Canton Road
Tsimshatsui, Kowloon, Hong Kong
Telephone: 852-2730-9090
Fax: 852-2736-6580
In Canada:
In the United Kingdom:
System Sensor Europe, Ltd.
Horsham Gates III, North St.
Horsham, West Sussex
RH13 5PJ, United Kingdom
Telephone: 44-1403-276500
Fax: 44-1403-276501
In India:
System Sensor India
A-204 Maheshwari Nagar
Orkay Mills Lane
Andheri East, Mumbai 400093
Telefax: 91-022-8202564
System Sensor Canada
6581 Kitimat Road, Unit #7
Mississauga, Ontario
Canada L5N 3T5
Telephone: 905-812-0767
Fax: 905-812-0771
Page 4
A05-250-02
相关型号:
PS120
Silicon Controlled Rectifier, 20A I(T)RMS, 20000mA I(T), 100V V(DRM), 100V V(RRM), 1 Element
HUTSON
©2020 ICPDF网 联系我们和版权申明