SENS-RDR [SYSTEMSENSOR]

Photoelectric Smoke Detectors; 光电感烟探测器
SENS-RDR
型号: SENS-RDR
厂家: SYSTEMSENSOR ADVANCED IDEAS.    SYSTEMSENSOR ADVANCED IDEAS.
描述:

Photoelectric Smoke Detectors
光电感烟探测器

光电
文件: 总2页 (文件大小:184K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Photoelectric  
Smoke Detectors  
System Sensor’s i3series smoke detectors represent  
significant advancement in conventional detection.  
The i3 family is founded on three principles: installation  
ease, intelligence, and instant inspection.  
Features  
• Plug-in detector line, mounting base included  
Installation ease. The i3 line redefines installation ease with its  
plug-in design. This allows an installer to pre-wire the bases included  
with the heads. The large wire entry port and in-line terminals  
provide ample room for neatly routing the wiring inside the base.  
The base accommodates a variety of back box mounting methods,  
as well as direct mounting with drywall anchors. To complete the  
installation, i3 heads plug in to the base with a simple Stop-Drop ’N  
Lockaction.  
• Large wire entry port  
• In-line terminals with SEMS screws  
• Mounts to octagonal and single-gang backboxes, 4-square  
backboxes, or direct to ceiling  
• Stop-Drop ’N Lock attachment to base  
• Removable detector cover and chamber  
• Built-in remote maintenance signaling  
• Drift compensation and smoothing algorithms  
• Simplified sensitivity measurement  
• Wide angle, dual color LED indication  
• Loop testing via EZ Walk feature  
Intelligence. i3 detectors offer a number of intelligent features  
to simplify testing and maintenance. Drift compensation and  
smoothing algorithms are standard with the i3 line to minimize  
nuisance alarms. Two-wire i3 detectors needing cleaning can  
generate a remote maintenance signal, when connected to the  
2W-MOD2 loop test/maintenance module, or to a panel equipped  
with the i3 protocol. This signal is indicated by LEDs located at the  
module and the panel. The SENS-RDR, a wireless device, displays the  
sensitivityof i3 detectors in terms of percent per-foot-obscuration.  
• Built-in test switch  
Instant inspection. The i3 series provides wide-angle red and  
green LED indicators for instant inspection of the detector’s  
condition: normal standby, out-of-sensitivity, alarm, or freeze trouble.  
When connected to the 2W-MOD2 loop test/maintenance module  
or a panel with the i3 protocol, the EZ Walk loop test feature is  
available on two-wire i3 detectors. This feature verifies the initiating  
loop wiring by providing LED status indication at each detector.  
Agency Listings  
S911  
ꢀ011446  
7272-1209:210  
290-01-E  
209ꢀ  
Smoke Detector Specifications  
Architectural/Engineering Specifications  
Smoke detector shall be a System Sensor i3 Series model number_______, listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The  
detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 1ꢀ5°F  
(57.2°C). The detector shall include a mounting base for mounting to ꢀ½-inch and 4-inch octagonal, single gang, and 4-inch square back boxes with a plaster  
ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws. The detector shall allow pre-wiring of  
the base and the head shall be a plug-in type. The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box.  
The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms. The detector shall provide  
dual color LED indication which blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When  
used in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control  
panel, and shall provide a loop testing capability to verify the circuit without testing each detector individually.  
Electrical Specifications  
Operating Voltage  
Nominal: 12/24V non-polarized  
Minimum: 8.5V  
Maximum: ꢀ5V  
Maximum Ripple Voltage  
Standby Current  
ꢀ0% peak to peak of applied voltage  
2-wire: 50 µA maximum average; 4-wire: 50 µA maximum average  
2-wire: 1ꢀ0 mA limited by control panel; 4-wire: 20 mA @12V, 2ꢀmA @ 24V  
2-wire: 100 µA; 4-wire: n/a  
Maximum Alarm Current  
Peak Standby Current  
Alarm Contact Ratings  
Physical Specifications  
Dimensions (including base)  
Weight  
2-wire: n/a; 4-wire: 0.5 A @ ꢀ0V AC/DC  
5.ꢀ inches (127 mm) diameter; 2.0 inches (51 mm) height  
6.ꢀ oz. (178 grams)  
Operating Temperature Range  
Operating Humidity Range  
Thermal Sensor  
2W-B and 4W-B: ꢀ2°F–120°F (0°C–49°C); 2WT-B and 4WT-B: ꢀ2°F–100°F (0°C–ꢀ7.8°C)  
0 to 95% RH non-condensing  
1ꢀ5°F (57.2°C) fixed  
Freeze Trouble  
2WT-B and 4WT-B only: 41°F (5°C)  
2.5%/ft. nominal  
Sensitivity  
Input Terminals  
14–22 AWG  
Mounting  
ꢀ½-inch octagonal back box  
4-inch octagonal back box  
Single gang back box  
4-inch square back box with a plaster ring  
Direct mount to ceiling  
LED Modes  
Power Up Sequence for LED Indication  
LED Mode  
Green LED  
Red LED  
Condition  
Duration  
Power up  
Blink every 10 seconds  
Blink every 10 seconds  
off  
Initial LED status indication  
80 seconds  
Normal (standby)  
Out of sensitivity  
Freeze trouble  
Alarm  
Blink every 5 seconds  
off  
off  
off  
Blink every 5 seconds  
Blink every 10 seconds  
Solid  
Ordering Information  
Model  
Thermal  
Wiring  
2-wire  
2-wire  
4-wire  
4-wire  
Alarm Current  
2W-B  
No  
1ꢀ0 mA max. limited by control panel  
1ꢀ0 mA max. limited by control panel  
20 mA @ 12V, 2ꢀmA @ 24V  
20 mA @ 12V, 2ꢀmA @ 24V  
2WT-B  
Yes  
4W-B  
No  
4WT-B  
Yes  
Accessories  
2W-MOD2  
SENS-RDR  
2-wire loop test / maintenance module  
Sensitivity reader  
RT  
Removal / replacement tool  
A77-AB2  
Retrofit adapter bracket, 6.6 in. (16.76cm) diameter  
©2006 System Sensor.  
ꢀ825 Ohio Avenue • St. Charles, IL 60174  
Phone: 800-SENSOR2 • Fax: 6ꢀ0-ꢀ77-6495  
Product specifications subject to change without notice. Visit systemsensor.com for  
current product information, including the latest version of this data sheet.  
A05-0ꢀ18-006 • 7/06 • #1676  

相关型号:

SEOA

SURFACE MOUNT HIGH EFFICIENCY RECTIFIER
GOOD-ARK

SEOA

SURFACE MOUNT HIGH EFFICIENT RECTIFIERS
SYNSEMI

SEOA

SURFACE MOUNT HIGH EFFICIENT RECTIFIERS
EIC

SEOA_05

SURFACE MOUNT HIGH EFFICIENT RECTIFIERS
EIC

SEOB

SURFACE MOUNT HIGH EFFICIENCY RECTIFIER
GOOD-ARK

SEOB

SURFACE MOUNT HIGH EFFICIENT RECTIFIERS
EIC

SEOB

SURFACE MOUNT HIGH EFFICIENT RECTIFIERS
SYNSEMI

SEOB-S

Rectifier Diode, 1 Phase, 1 Element, 1.5A, 100V V(RRM), Silicon, DO-214AC, SMAJ, 2 PIN
GOOD-ARK

SEOD

SURFACE MOUNT HIGH EFFICIENCY RECTIFIER
GOOD-ARK

SEOD

SURFACE MOUNT HIGH EFFICIENT RECTIFIERS
EIC

SEOD

SURFACE MOUNT HIGH EFFICIENT RECTIFIERS
SYNSEMI

SEOD-S

Rectifier Diode, 1 Phase, 1 Element, 1.5A, 200V V(RRM), Silicon, DO-214AC, SMAJ, 2 PIN
GOOD-ARK