ZC20A [SYSTEMSENSOR]

Flow Switch Tester; 流量开关测试仪
ZC20A
型号: ZC20A
厂家: SYSTEMSENSOR ADVANCED IDEAS.    SYSTEMSENSOR ADVANCED IDEAS.
描述:

Flow Switch Tester
流量开关测试仪

开关 测试
文件: 总4页 (文件大小:114K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
S P R I N K L E R  
S Y S T E M S  
M O N I T O R I N G  
Zonecheck  
Flow Switch Tester  
Manifold Models  
Zonecheck Manifold Model  
UL/FM Models  
ULC Models  
with  
with  
110 V Pump  
110 V Pump  
ZC20  
ZC25  
ZC30  
ZC40  
ZC20A  
ZC25A  
ZC30A  
ZC40A  
Retrofit Models  
UL/FM Models  
ULC Models  
International  
Models with  
220V Pump  
with  
with  
110V Pump  
110V Pump  
ZCR20  
ZCR25  
ZCR30  
ZCR40  
ZCR60  
ZCR80  
ZCR20A  
ZCR25A  
ZCR30A  
ZCR40A  
ZCR60A  
ZCR80A  
ZCR20E  
ZCR25E  
ZCR30E  
ZCR40E  
ZCR60E  
ZCR80E  
Replacement Parts  
ZCK-1 Zonecheck 110V Keyswitch  
ZCK-1E Zonecheck 220V Keyswitch  
ZCK-1EG Zonecheck 220V Keyswitch (German)  
ZCP-110 Zonecheck 110V Pump  
ZCP-220 Zonecheck 220V Pump  
ZCRK Zonecheck Replacement Kit  
Product Overview  
Simplifies compliance to NFPA 25 for  
quarterly flow switch testing  
System Sensor’s Zonecheck flow switch tester is an automatic method for  
performing quarterly flow switch tests per NFPA 25.  
Does not require opening the inspector’s  
test connection  
Code Compliance. Quarterly flow switch tests are mandated by NFPA 25.  
Zonecheck simplifies testing by re-circulating the water within the pipe around  
the flow switch, to simulate the flow of one sprinkler head in operation. This  
simulation is achieved without having to open the inspector’s test connection.  
Saves as much as 400 gallons of water  
per flow switch per year  
Environmental Savings. Zonecheck re-circulates the water within the pipe, so no  
water is expelled from the system. Over the course of one year, Zonecheck can  
save as much as 400 gallons of water per flow switch, per year.  
Does not activate the building’s fire pump  
Testing initiated by a key switch  
Key switches may be interconnected  
to control all Zonechecks from one  
master switch  
Ensured Life Safety. Since Zonecheck does not require opening the inspector’s  
test connection, a building’s fire pump is not activated, to avoid unnecessary fire  
department dispatches. This also reduces the likelihood of the fire pump being  
turned off manually during flow switch testing, thereby ensuring the sprinkler  
system’s integrity.  
Significantly reduces testing time  
Includes a System Sensor flow switch  
with each model  
Time Savings. Zonecheck’s pump is activated by the turn of a key switch. The  
key switch may be wired to initiate one pump locally, or can be interconnected.  
When interconnected, any key switch may activate all Zonecheck pumps, to  
significantly reduce testing time.  
Offered in manifold and retrofit  
configurations  
Applications Flexibility. All Zonechecks are equipped with a System Sensor flow  
switch. Models include manifold and retrofit configurations with either 110V or  
220V pumps, and UL, ULC, or International style flow switches.  
Standard Specifications  
Electrical Specifications  
Working Pressure Rating  
175 PSI  
Pump Operating Voltages  
UL, ULC, FM models: 1.63A @ 110V,  
Key Switch Operation Modes  
Self-test: Wired locally  
60Hz  
@ 220V, 50Hz  
International models : 0.88A  
Group test: Interconnected  
Operating Temperature Range  
32°F - 120°F (0°C - 49°C)  
Key Switch LED Operation  
Ready state: No LED  
Test initiation: Green LED  
Flow switch activation: Red LED for  
ZCK-1  
Key Switch Operating Voltage  
ZCK-1: 110VAC  
Compatible Pipe (Manifold Models)  
Schedule 10, 2- 4diameter  
ZCK-1E, ZCK-1EG: 220VAC  
Compatible Pipe (Retrofit Models)  
Schedule 10 and 40, 2- 8diameter  
(50 mm through 200 mm)  
Key Switch Mounting Options  
Includes back box for surface or flush  
mounting. For pre-wiring, use a  
41116x 41116back box.  
Flow switch activation: Green LED for  
ZCK1E + ZCK1EG  
Service Use  
Inspection, Testing and Maintenance of  
Water-Based Fire Protection Systems:  
NFPA25  
Flow Switch Included with Zonecheck  
UL/FM Models with 110V Pump  
Retrofit Model Manifold Model  
National Fire Alarm Code: NFPA 72  
Manifold Assembly Length  
(Manifold Models)  
25.6(65 cm)  
Flow Switch Model Included  
ZCR20  
ZCR25  
ZCR30  
ZCR40  
ZCR60  
ZCR80  
ZC20  
ZC25  
ZC30  
ZC40  
WFD20  
WFD25  
WFD30-2  
WFD40  
WFD60  
WFD80  
Component Connections (included)  
(Manifold Models)  
2 - 1NPT/25mm British Standard  
Thread elbows  
Component Connections (included)  
(Retrofit Models)  
2 - 1NPT/25mm British Standard  
Thread elbows  
2 - 25mm British Standard  
Thread elbows  
ULC Models with 110 V Pump  
Retrofit Model Manifold Model  
Flow Switch Model Included  
WFD20A  
Valves (included)  
Red: Standard valve  
Green: Contains check valve  
ZCR20A  
ZCR25A  
ZCR30A  
ZCR40A  
ZCR60A  
ZCR80A  
ZC20A  
ZC25A  
ZC30A  
ZC40A  
WFD25A  
Warranty  
3 years  
WFD30-2A  
WFD40A  
Approximate Weight  
WFD60A  
Style  
Weight  
WFD80A  
ZCR20  
ZCR25  
ZCR30  
ZCR40  
ZCR60  
ZCR80  
ZC20  
31 lbs. (14.1 kg)  
31.5 lbs. (14.3 kg)  
32 lbs. (14.5 kg)  
33 lbs. (14.9 kg)  
34 lbs. (15.4 kg)  
35 lbs. (15.9 kg)  
37 lbs. (16.8 kg)  
39 lbs. (17.7 kg)  
41 lbs. (18.6 kg)  
45 lbs. (28.8 kg)  
International Models with 220V Pump  
Retrofit Model  
ZCR20E  
ZCR25E  
ZCR30E  
ZCR40E  
ZCR60E  
ZCR80E  
Flow Switch Model Included  
WFD20E  
WFD25E  
WFD30E  
WFD40E  
ZC25  
WFD60E  
ZC30  
WFD80E  
ZC40  
For flow switch specifications, refer to the appropriate flow switch  
instructions manuals.  
Zonecheck Installation  
For flow switch specifications, refer to the appropriate flow switch instructions manuals.  
WATERFLOW  
DETECTOR  
RED VALVE  
ZONECHECK  
PUMP  
GREEN  
VALVE  
WATERFLOW  
DETECTOR  
RED VALVE  
ZONECHECK  
PUMP  
GREEN  
VALVE  
CORRECT  
Pump stripes  
(horizontal)  
Correct Horizontal Installation  
Correct Vertical Installation  
INCORRECT  
Pump stripes  
(vertical)  
ZONECHECK  
PUMP  
ZONECHECK  
PUMP  
Incorrect Horizontal Installation  
Incorrect Horizontal Installation  
Electrical Wiring Diagrams  
FOR INTERCONNECTING MULTIPLE ZONECHECK UNITS  
TO EARTH GND.  
OR ATTACH TO  
JUNCTION BOX  
AC GROUND  
GND  
AC  
AC POWER  
AC  
PUMP  
PUMP  
WIRING DIAGRAM FOR STAND ALONE APPLICATION  
WF INPUT  
TO EARTH GND.  
OR ATTACH TO  
JUNCTION BOX  
}
}
AC GROUND  
INTER-CONNECT  
GND  
AC  
WATERFLOW  
DETECTOR  
AC POWER  
AC  
PUMP  
PUMP  
PUMP  
WF INPUT  
}
INTER-CONNECT  
}
TO EARTH GND.  
OR ATTACH TO  
JUNCTION BOX  
WATERFLOW  
DETECTOR  
AC GROUND  
GND  
AC  
AC POWER  
AC  
PUMP  
PUMP  
PUMP  
NOTE:  
WF INPUT NOT REQUIRED FOR  
KEYSWITCH OPERATION IF WATERFLOW  
DETECTOR IS CONNECTED TO PANEL  
OR OTHER MONITORING DEVICE.  
WF INPUT  
}
}
INTER-CONNECT  
AC POWER AND PUMP WIRING  
MUST CONFORM TO NEC OR  
YOUR LOCAL CODES.  
WATERFLOW  
DETECTOR  
PUMP  
TO NEXT  
ZONECHECK  
SWITCH FOR  
INTERCONNECT  
Engineering Specifications  
Ordering Information  
Manifold Model Number Pipe Size  
Pump Voltage  
110V  
Flow Switch  
WFD20  
General/Retrofit Model Specifications  
ZC20  
2″  
Model shall be a Zonecheck Flow Switch  
/
Tester model ___________________ as manufac-  
tured by System Sensor. Flow Switch Tester  
shall be installed on a sprinkler system riser as  
designated on the drawings and/or as speci-  
fied herein. Flow Switch Tester assembly shall  
mount on any clear pipe span of the appropri-  
ate nominal size, either in a vertical upflow or  
horizontal run, between 6and 12from the  
ZC25  
21 2″  
3″  
110V  
WFD25  
ZC30  
110V  
WFD30-2  
WFD40  
ZC40  
4″  
110V  
ZC20A  
ZC25A  
ZC30A  
2″  
110V  
WFD20A  
WFD25A  
WFD30-2A  
WFD40A  
Flow Switch  
WFD20  
21 2″  
/
110V  
3″  
110V  
flow switch. Flow Switch Tester shall consist of ZC40A  
a recirculating pump, operating at nominal  
4″  
110V  
Retrofit Model Number  
Pipe Size  
Pump Voltage  
110V  
110V or 220V as appropriate, two (2) sets of  
valves and elbows to facilitate the circulation  
of the water, a System Sensor vane-type water-  
flow detector, and a key switch to activate the  
recirculating pump. When activated, the pump  
shall circulate the water within the sprinkler  
riser around the waterflow detector vane to  
simulate the flow of one sprinkler head in oper-  
ation. The activating key switch shall provide  
the means to be wired locally to one  
Zonecheck Flow Switch Tester, or intercon-  
nected with other key switches for group  
activation. Flow Switch Tester shall be avail-  
able for manifold and retrofit installation  
applications. Zonecheck Flow Switch Tester  
retrofit models shall be listed by Underwriters  
Laboratories, Inc.  
ZCR20  
2″  
/
ZCR25  
2 1 2″  
110V  
WFD25  
ZCR30  
3″  
4″  
6″  
8″  
2″  
110V  
WFD30-2  
WFD40  
ZCR40  
110V  
ZCR60  
110V  
WFD60  
ZCR80  
110V  
WFD80  
ZCR20A  
ZCR25A  
ZCR30A  
ZCR40A  
ZCR60A  
ZCR80A  
ZCR20E  
ZCR25E  
ZCR30E  
ZCR40E  
ZCR60E  
ZCR80E  
110V  
WFD20A  
WFD25A  
WFD30-2A  
WFD40A  
WFD60A  
WFD80A  
WFD20E  
WFD25E  
WFD30E  
WFD40E  
WFD60E  
WFD80E  
21 2″  
/
110V  
3″  
110V  
4″  
110V  
6″  
110V  
8″  
110V  
50 mm  
65 mm  
80 mm  
100 mm  
150 mm  
200 mm  
220V  
Manifold Model Specifications  
220V  
Zonecheck Automatic Flow Switch Tester mani-  
fold models shall further consist of a schedule  
10 pipe assembly of the appropriate nominal  
size. Manifold assembly shall provide grooved  
ends for accepting the appropriate grooved  
connection fittings. Manifold assembly shall  
include no less than two drain ports with the  
appropriate drain plugs. Manifold Zonecheck  
models shall come with the pump, valves,  
elbows, pipe assembly, drain plugs, and System  
Sensor waterflow detector pre-assembled.  
Zonecheck Flow Switch Tester manifold models  
shall be listed by Underwriters Laboratories,  
Inc.  
220V  
220V  
220V  
220V  
Replacement Model No. Description  
ZCK-1  
110V Keyswitch  
220V Keyswitch  
ZCK-1E  
ZCK-1EG  
ZCP-110  
ZCP-220  
ZCRK  
220V Keyswitch (German)  
110V Pump  
220V Pump  
Zonecheck Replacement Kit  
System Sensor Sales and Service  
System Sensor Headquarters  
3825 Ohio Avenue  
St. Charles, IL 60174  
Ph: 800/SENSOR2  
Fx: 630/377-6495  
Documents-on-Demand  
800/736-7672 x3  
System Sensor Canada  
Ph: 905.812.0767  
Fx: 905.812.0771  
System Sensor in China  
Ph: 86.29.524.6253  
Fx: 86.29.524.6259  
System Sensor – Far East  
Ph: 85.22.191.9003  
Fx: 85.22.736.6580  
System Sensor – India  
Ph: 91.124.637.1770 x.2700  
Fx: 91.124.637.3118  
System Sensor Europe  
Ph: 44.1403.276500  
Fx: 44.1403.276501  
System Sensor in Singapore  
Ph: 65.6273.2230  
Fx: 65.6273.2610  
System Sensor – Australia  
Ph: 613.54.281.142  
Fx: 613.54.281.172  
www.systemsensor.com  
© 2003 System Sensor. The company reserves the right to change product specifications without notice.  
A05-0272-003•02/03•#1070  

相关型号:

ZC245A

32-BIT BUS TRANSCEIVER WITH 3-STATE OUTPUTS
TI

ZC24PD-222

Power Splitter/Combiner
MINI

ZC24PD-222+

Power Splitter/Combiner
MINI

ZC24PD-222-S+

Power Splitter/Combiner
MINI

ZC25

Flow Switch Tester
SYSTEMSENSOR

ZC2512

THICK FILM CHIP RESISTORS AND JUMPERS
RCD

ZC2512B

THICK FILM CHIP RESISTORS AND JUMPERS
RCD

ZC2512BP

THICK FILM CHIP RESISTORS AND JUMPERS
RCD

ZC2512BU

THICK FILM CHIP RESISTORS AND JUMPERS
RCD

ZC2512P

THICK FILM CHIP RESISTORS AND JUMPERS
RCD

ZC2512U

THICK FILM CHIP RESISTORS AND JUMPERS
RCD

ZC25A

Flow Switch Tester
SYSTEMSENSOR