B84143-G150-R110 [TDK]
Three Phase EMI Filter, 300V, 50/60HzHz, METAL PACKAGE;型号: | B84143-G150-R110 |
厂家: | TDK ELECTRONICS |
描述: | Three Phase EMI Filter, 300V, 50/60HzHz, METAL PACKAGE |
文件: | 总14页 (文件大小:556K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
EMC filters
3-line filters
for converters and power electronics
Series/Type:
B84143G*R110
Date:
May 2014
© EPCOS AG 2014. Reproduction, publication and dissemination of this publication, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
3-line filters
B84143G*R110
for converters and power electronics
Power line filters for 3-phase systems
Rated voltage UR: 520/300 V AC
Rated current IR: 8 A to 220 A
Construction
3-line filters
Metal case
Book size
Features
High insertion loss
Optimized leakage current
Space saving by optimized footprint
Litz wires on the load side reduce mounting time
Low weight
Degree of protection: IP 201)
Optimized for long motor cables
and operation under full load
Design complies with CSA C22.2 No.8
ENEC and UL approval (480 V)
Typical applications
Frequency converters for motor drives, e.g.
elevators, pumps, traction systems, conveyor systems,
HVAC systems (heating, ventilation and air
conditioning)
Wind farms
Power supplies
Terminals
Line: Terminal blocks
Load: Litz wires
Marking
Marking on component:
Manufacturer's logo, ordering code, rated voltage, rated
current, rated temperature, climatic category, date code,
approvals
Minimum data on packaging:
Manufacturer's logo, ordering code, quantity, date code
1) According to IEC 60529
Please read Cautions and warnings and
Important notes at the end of this document.
Page 2 of 14
3-line filters
B84143G*R110
for converters and power electronics
Typical circuit diagram
Filters for 8 A ... 25 A
Filters for 36 A ... 220 A
Please read Cautions and warnings and
Important notes at the end of this document.
Page 3 of 14
3-line filters
B84143G*R110
for converters and power electronics
Technical data and measuring conditions
Rated voltage VR
520/300 V AC (50/60 Hz)
Rated voltage for IT mains supply Filters 8 A: Up to 480/275 V AC (50/60 Hz)
Filters 20 A ... 220 A: Up to 460/265 V AC (50/60 Hz)
See also chapter "General technical information", section 7.
Rated current IR
Test voltage Vtest
Referred to 40 °C rated temperature
2250 V DC, 2 s (line/line)
2720 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 ꢀ IR for 3 min per hour or
2.5 ꢀ IR for 30 s per hour
Leakage current lLK
Climatic category (IEC 60068-1)
Approvals
At VR and 50 Hz
25/100/21 (ꢁ25 °C/+100 °C/21 days damp heat test)
IEC 60939, UL 1283 for 480 V AC
Characteristics and ordering codes
Approvals
480 V
Terminal cross section
Line side: Load side:
IR
ILK
Rtyp
Approx. weight Ordering code
terminal
blocks
mm2
litz wires
mm2
A
mA
mΩ kg
VR = 520/300 V AC
8
20
25
36
50 16
66 25
4
4
4
6
1.5
2.5
2.5
6.0
10
16
25
35
35
1.64
1.64
1.64
5.0
5.0
5.0
5.0
5.0
5.0
5.0
40
10
10
1.3
B84143G0008R110 ×
×
×
ꢁ
×
×
×
×
×
×
×
1.3
1.3
2.8
3.3
4.4
4.9
7.5
8.0
B84143G0020R110 ×
B84143G0025R110 ×
B84143G0036R110 ×
B84143G0050R110 ×
B84143G0066R110 ×
B84143G0090R110 ×
B84143G0120R110 ×
B84143G0150R110 ×
B84143G0220R110 ×
5.2
2.4
1.8
1.2
1.0
0.7
90 25
120 50
150 50
220 95
70
0.4 11.5
× = Approval granted
Please read Cautions and warnings and
Important notes at the end of this document.
Page 4 of 14
3-line filters
B84143G*R110
for converters and power electronics
Dimensional drawings
B4143G0008R110, B4143G0020R110, B4143G0025R110 (8 A to 25 A)
General tolerances according to ISO 2768ꢁcL
Dimensions in mm
B4143G0036R110 (36 A)
General tolerances according to ISO 2768ꢁcL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 5 of 14
3-line filters
B84143G*R110
for converters and power electronics
B4143G0050R110 (50 A)
General tolerances according to ISO 2768ꢁcL
Dimensions in mm
B4143G0066R110, B4143G0090R110 (66 A and 90 A)
General tolerances according to ISO 2768ꢁcL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 6 of 14
3-line filters
B84143G*R110
for converters and power electronics
B4143G0120R110, B4143G0150R110 (120 A and 150 A)
General tolerances according to ISO 2768ꢁcL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 7 of 14
3-line filters
B84143G*R110
for converters and power electronics
B4143G0220R110 (220 A)
General tolerances according to ISO 2768ꢁcL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 8 of 14
3-line filters
B84143G*R110
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
Filters for 8 A
Filters for 20 A and 25 A
Filters for 36 A ... 220 A
Please read Cautions and warnings and
Important notes at the end of this document.
Page 9 of 14
3-line filters
B84143G*R110
for converters and power electronics
Cautions and warnings
Please read all safety and warning notes carefully before installing the EMC filter and putting it
into operation (see ). The same applies to the warning signs on the filter. Please ensure that
the signs are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the
appropriate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in low-
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warning
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Danger-
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed
and the last to be disconnected. Depending on the magnitude of the leakage currents, the par-
ticular specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter or filter, such as with circuits able to cause reso-
nances, impermissible voltages at higher frequencies etc. can lead to bodily injury and death as
well as cause substantial material damages (e.g. destruction of the filter housing).
EMC filters and filters must be protected in the application against impermissible exceeding of
the rated currents by overcurrent protective circuitry.
In case of leakage currents >3.5 mA you shall mount the PE conductor stationary with the
required cross section before beginning of operation and save it against disconnecting. For
leakage currents IL1) <10 mA the PE conductor must have a KU value2) of 4.5 A3); for leakage
currents IL ≥10 mA the PE conductor must have a KU value of 6.4)
Output chokes and output filters must be protected in the application against impermissible
exceeding of the component temperature.
The converter output frequency must be within the specified range to avoid resonances and
uncontrolled warming of the output chokes and output filters.
1) IL = leakage current let-go
2) The KU value (symbol KU) is a classification parameter of safety-referred failure types designed to ensure protection against hazardous
body currents and excessive heating.
3) A value of KU = 4.5 with respect to interruptions is attained with: a) a permanently connected protective earth circuit ≥2.5 mm2
connected via shroud connectors (IEC 60309ꢁ2) and b) a protective earth circuit.
4) KU = 6 with respect to interruptions is achieved for fixedꢁconnection lines ≥10 mm2 where the type of connection and line layout
correspond to the requirements for PEN conductors as specified in relevant standards.
Please read Cautions and warnings and
Important notes at the end of this document.
Page 10 of 14
3-line filters
B84143G*R110
for converters and power electronics
The table below summarizes the safety instructions that must be observed without fail. A detailed
description can be found in the relevant chapters of the databook.
Topic
Instructions
Reference chapter
(data book),
paragraph
Selecting a filter
When selecting a filter, it is mandatory to observe the Selection guide for
rated data of the equipment (such as its rated input
current, rated voltage, harmonic content etc.) as well
as the derating instructions in Chapters 9 and 10.
converter filters
Rated voltage
When power distribution systems deviating from the
Power distribution
symmetric TN-S system it is to check the suitability of systems,
the EMC filters and the allowed voltages including the
fault cases.
7
Protection from
residual voltages
Discharge resistors
Active parts must be discharged within 5 s to a Safety regulations,
voltage of less than 60 V (or 50 µ C). If this limit 6.1
cannot be observed due to the operating mode, the
hazardous point must be permanently marked in a
clearly visible way.
Filters which are not permanently connected (e.g.
when the test voltage is applied to the filter at the
incoming goods inspection) must be discharged after
the voltage has been switched off.
Safety regulations,
6.2
Installing and
removing of EMC
filters
When installing and removing our EMC filters, a Safety regulations,
voltage-free state must be set up and secured with 6.4
observance of the five safety rules described in
EN 50110-1.
Installation
Use in IT systems
The special features of the IT system ("first fault case" Power distribution
and other fault cases) shall be observed.
system (network
types), 7.6
Safety notes on
leakage currents
The filter leakage currents specified in the data book Leakage current,
are intended for user information only.The maximum 8.4
leakage current of the entire electrical equipment or Leakage current,
appliance has to be limited for safety reasons. Please 8.6
obtain the applicable limits for your application from
the relevant regulations, provisions and standards.
Voltage derating
If the permissible limits for the higher-frequency Voltage derating,
voltages at the filter are exceeded, the filter may be 9.8
damaged or destroyed.
Hazards caused by
overloading the filters
Current derating at
elevated ambient
temperatures
Non-observance of the current derating may lead to Current derating,
overheating and consequently represents
hazard.
a fire 10.1
Please read Cautions and warnings and
Important notes at the end of this document.
Page 11 of 14
3-line filters
B84143G*R110
for converters and power electronics
Topic
Instructions
Reference chapter
(data book),
paragraph
Protective earth
connection at
operating currents
>250 A
For operating currents greater than 250 A, we Mounting
recommend the PE connection to be set up between instructions, point
the feed (filter: line) and output (filter: load) not via the
PE terminal bolt in the filter housing.
2
Mounting position
Note the mounting position of the filters! It must Mounting
always be ensured that natural convection is not instructions, point
impaired.
13
Long motor cables
Long motor cables cause parasitic currents in the
Mounting
installation. The cable lengths indicated for the output instructions, point
chokes and output filters serve for orientation. The
user must check the technical parameters and
especially the choke temperatures for the respective
application.
15
Display of ordering codes for EPCOS products
The ordering code for one and the same product can be represented differently in data sheets,
data books, other publications and the website of EPCOS, or in order-related documents such as
shipping notes, order confirmations and product labels. The varying representations of the
ordering codes are due to different processes employed and do not affect the specifications of the
respective products. Detailed information can be found on the Internet under
www.epcos.com/orderingcodes
Please read Cautions and warnings and
Important notes at the end of this document.
Page 12 of 14
3-line filters
B84143G*R110
for converters and power electronics
Symbols and terms
Symbol
English
German
α
Insertion loss
Einfügungsdämpfung
Bemessungskapazität
CR
CX
CY
∆V
dv/dt
f
Rated capacitance
Capacitance X capacitor
Capacitance Y capacitor
Voltage drop (input to output)
Rate of voltage rise
Frequency
Kapazität X-Kondensator
Kapazität Y-Kondensator
Spannungsabfall im Filter
Spannungsanstiegsgeschwindigkeit
Frequenz
fM
fP
Converter output frequency
Pulse frequency
Motorfrequenz
Pulsfrequenz
fR
fres
IC
ILK
Imax
IN
Rated frequency
Bemessungsfrequenz
Resonanzfrequenz
Strom durch Kondensator
Filter-Ableitstrom
Maximalstrom
Nennstrom
Resonant frequency
Current through capacitor
Filter leakage current
Maximum current
Nominal current
Iop
Ipk
Iq
IR
IS
L
Operating current (design current)
Rated peak withstand current
Capacitive reactive current
Rated current
Interference current
Inductance
Betriebsstrom
Bemessungs-Stoßstromfestigkeit
Kapazitiver Blindstrom
Bemessungsstrom
Störstrom
Induktivität
LR
Lstray
PL
R
Rated inductance
Stray inductance
Power loss
Resistance
Bemessungsinduktivität
Streuinduktivität
Verlustleistung
Widerstand
Ris
Rtyp
TA
Tmax
Tmin
TR
uk
Veff
VK
VLE
VN
VR
Vpeak
Vtest
VX
VY
XL
Z
Insulation resistance
DC resistance, typical value
Ambient temperature
Upper category temperature
Lower category temperature
Rated temperature
Refered voltage drop in %
RMS voltage
Isolationswiderstand
Gleichstromwiderstand, Richtwert
Umgebungstemperatur
Obere Kategorietemperatur
Untere Kategorietemperatur
Bemessungstemperatur
Bezogener Spannungsabfall in %
Effektivspannung
Voltage drop
Spannungsabfall
Voltage line to earth; voltage line to ground Spannung Phase zu Erdpotential
Nominal voltage
Rated voltage
Peak voltage
Nennspannung
Bemessungsspannung
Spitzenspannung
Test voltage
Prüfspannung
Voltage over X capacitor
Voltage over Y capacitor
Inductive reactance
Impedance
Spannung über X-Kondensator
Spannung über Y-Kondensator
Induktiver Blindwiderstand
Scheinwidertand
|Z|
Impedance, absolute value
Scheinwiderstand (Betragswert)
Please read Cautions and warnings and
Important notes at the end of this document.
Page 13 of 14
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical re-
quirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application.
As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar
with them than the customers themselves. For these reasons, it is always ultimately incum-
bent on the customer to check and decide whether an EPCOS product with the properties de-
scribed in the product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or
failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in
which the malfunction or failure of an electronic component could endanger human life or
health (e.g. in accident prevention or lifesaving systems), it must therefore be ensured by
means of suitable design of the customer application or other action taken by the customer
(e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by
third parties in the event of malfunction or failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our Ma-
terial Data Sheets on the Internet (www.epcos.com/material). Should you have any more de-
tailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order. We also
reserve the right to discontinue production and delivery of products. Consequently, we
cannot guarantee that all products named in this publication will always be available. The
aforementioned does not apply in the case of individual agreements deviating from the fore-
going for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current ver-
sion of the "General Terms of Delivery for Products and Services in the Electrical In-
dustry" published by the German Electrical and Electronics Industry Association
(ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CeraLink, CeraPlas, CSMP, CSSP,
CTVS, DeltaCap, DigiSiMic, DSSP, FilterCap, FormFit, MiniBlue, MiniCell, MKD, MKK,
MLSC, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap, SIFERRIT, SIFI,
SIKOREL, SilverCap, SIMDAD, SiMic, SIMID, SineFormer, SIOV, SIP5D, SIP5K, TFAP,
ThermoFuse, WindCap are trademarks registered or pending in Europe and in other coun-
tries. Further information will be found on the Internet at www.epcos.com/trademarks.
Page 14 of 14
相关型号:
©2020 ICPDF网 联系我们和版权申明