for converters and power electronics
Preliminary Data
Power line filters for 3-phase systems
Rated voltage VR: 300/520 V AC
Rated current IR: 80 A to 150 A
Construction
3-line filters
Metal case
Features
High insertion loss
Dedicated for delta connection grids
Low leakage current
Very compact design
Available as book-size style or low profile
Degree of protection: IP 001)
ENEC, UL and cUL approval
Typical applications
Frequency converters for motor drives eg.
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
elevators
pumps
machines
HVAC systems (heating, ventilation and air conditioning)
textile machines, packing machines
Terminals
Finger-safe terminals
Marking
Marking on component:
Manufacturer's logo, ordering code, rated voltage, rated
current, rated temperature, climatic category, date code,
approvals, warning label
Minimum data on packaging:
Manufacturer's logo, ordering code, quantity, date code
1) According to IEC 60529
Please read Cautions and warnings and
Important notes at the end of this document.
Page 2 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
Typical circuit diagrams
B84743*0080R712, B84743*0100R712
B84743*0150R712
Please read Cautions and warnings and
Important notes at the end of this document.
Page 3 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
Technical data and measuring conditions
Rated voltage VR [L–PE / L–L]
Test voltage Vtest
300/520 V AC (50/60 Hz)
2240 V DC, 2 s (line/line)
2720 V DC, 2 s (line/case)
Rated temperature TR
Operating temperature Top
Temperature rise1)
50 °C
ꢀ25 °C ... +100 °C
≤ 30 K
Operating humidity
30% ... 95% RH (No dewdrop)
ꢀ40 °C ... +100 °C
10% ... 95% RH (No dewdrop)
2.0 MΩ ... 2.3 MΩ
Storage temperature
Storage humidity
Insulation resistance2)
Overload capability (thermal)
1.5 ꢁ IR for 3 min per hour or
2.5 ꢁ IR for 30 s per hour
3)
Leakage current lLK
At 200 V AC and 60 Hz
Climatic category (IEC 60068-1)
Approvals
25/100/21 (ꢀ25 °C/+100 °C/21 days damp heat test)
IEC 60939, UL 1283, CSA C22.2 No.8
1) On surface of case
2) With resistor connected to ground
3) 200 V AC delta-connection with one corner grounded
Characteristics and ordering codes
*)
Approvals
IR
Terminal
cross section
ILK
Rtyp
Approx. Ordering code
weight
L1-L1'/
L2-L2'/
L3-L3'
mΩ
A
mm2
mA
kg
VR = 300/520 V AC
80
80
80
50
50
50
50
50
50
50
50
50
50
50
50
< 2.0
< 2.0
< 9.4
< 9.4
< 2.0
< 2.0
< 9.4
< 9.4
< 2.0
< 2.0
< 9.4
< 9.4
0.70
0.70
0.70
0.70
0.55
0.55
0.55
0.55
0.50
0.50
0.50
0.50
2.2
2.2
2.2
2.2
2.6
2.6
2.6
2.6
4.5
4.5
4.5
4.5
B84743C0080R712
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
B84743E0080R712
B84743A0080R712
B84743D0080R712
B84743C0100R712
B84743E0100R712
B84743A0100R712
B84743D0100R712
B84743C0150R712
B84743E0150R712
B84743A0150R712
B84743D0150R712
80
100
100
100
100
150
150
150
150
*) Tolerance 15 %
× = Approval granted
Please read Cautions and warnings and
Important notes at the end of this document.
Page 4 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
Current derating I/IR as a function of ambient temperature TA
Please read Cautions and warnings and
Important notes at the end of this document.
Page 5 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
Dimensional drawings
B84743A0080R712, B84743C0080R712 (80 A)
General tolerances according to ISO 2768ꢀcL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 6 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
B84743D0080R712, B84743E0080R712 (80 A)
General tolerances according to ISO 2768ꢀcL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 7 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
B84743A0100R712, B84743C0100R712 (100 A)
General tolerances according to ISO 2768ꢀcL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 8 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
B84743D0100R712, B84743E0100R712 (100 A)
General tolerances according to ISO 2768ꢀcL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 9 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
B84743A0150R712, B84743C0150R712 (150 A)
General tolerances according to ISO 2768ꢀcL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 10 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
B84743D0150R712, B84743E0150R712 (150 A)
General tolerances according to ISO 2768ꢀcL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 11 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
Insertion loss (typical values at Z = 50 Ω)
Filters for 80 A
Please read Cautions and warnings and
Important notes at the end of this document.
Page 12 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
Insertion loss (typical values at Z = 50 Ω)
Filters for 100 A
Please read Cautions and warnings and
Important notes at the end of this document.
Page 13 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
Insertion loss (typical values at Z = 50 Ω)
Filters for 150 A
Please read Cautions and warnings and
Important notes at the end of this document.
Page 14 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
Cautions and warnings
Please read all warning and safety notes carefully before installing the filter and putting it into op-
eration (see ). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appro-
priate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The filters may be used only for their intended application within the specified values in low-
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warning
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. Filters contain components that store an electric charge. Dangerous
voltages can continue to exist at the filter terminals for longer than five minutes even after the
power has been switched off.
The protective earth connections shall be the first to be made when the filter is installed and the
last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective earth connection must be observed.
Impermissible overloading of the filter or filter, such as with circuits able to cause resonances,
impermissible voltages at higher frequencies etc. can lead to bodily injury and death as well as
cause substantial material damages (e.g. destruction of the filter housing).
Filters must be protected in the application against impermissible exceeding of the rated cur-
rents by overcurrent protective devices.
In case of leakage currents >3.5 mA you shall mount the PE conductor stationary with the re-
quired cross section before beginning of operation and save it against disconnecting. For leak-
age currents IL ≤10 mA the PE conductor must have a KU value2) of 4.53); for leakage currents
1)
IL >10 mA the PE conductor must have a KU value of 64).
Output chokes and output filters must be protected in the application against impermissible ex-
ceeding of the component temperature.
The converter output frequency must be within the specified range to avoid resonances and un-
controlled warming of the output chokes and output filters.
Because the product can become very hot during operation, there is the risk of burns if
touched. The product can remain hot for some time after the power is switched off!
1) IL = leakage current let-go
2) The KU value (symbol KU) is a classification parameter of safety-referred failure types designed to ensure protection against hazardous
body currents and excessive heating.
3) A value of KU = 4.5 with respect to interruptions is attained with: a) permanently connected protective earth connection ≥1.5 mm2 and
b) a protective earth connection ≥2.5 mm2 via connectors for industrial equipment (IEC 60309ꢀ2)
4) KU = 6 with respect to interruptions is achieved for fixed-connection lines ≥10 mm2 where the type of connection and installation corre-
spond to the requirements for PEN conductors as specified in relevant standards.
Please read Cautions and warnings and
Important notes at the end of this document.
Page 15 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
The table below summarizes the safety instructions that must be observed without fail. A detailed
description can be found in the relevant chapters of the databook.
Reference chapter
(data book),
Topic
Instructions
paragraph
Selecting a filter
When selecting a filter, it is mandatory to observe the Selection guide for
rated data of the equipment (such as its rated input
current, rated voltage, harmonic content etc.) as well
as the derating instructions in Chapters 9 and 10.
converter filters
Rated voltage
When power distribution systems deviating from the
symmetric TN-S system is to check the suitability of
the filters and the allowed voltages including the fault
cases.
Power distribution
systems,
7
Protection from
Active parts must be discharged within 5 s to a Safety regulations,
residual voltages
voltage of less than 60 V (or 50 μ C). If this limit 6.1
Discharge resistors cannot be observed due to the operating mode, the
hazardous point must be permanently marked in a
clearly visible way.
Filters which are not permanently connected (e.g.
when the test voltage is applied to the filter at the
incoming goods inspection) must be discharged after
the voltage has been switched off.
Safety regulations,
6.2
Installing and
removing of filters
When installing and removing our filters, a Safety regulations,
voltage-free state must be set up and secured with 6.4
observance of the five safety rules described in
EN 50110-1.
Installation
Use in IT systems The special features of the IT system ("first fault case" Power distribution
and other fault cases) shall be observed.
system (network
types), 7.6
Safety notes on
leakage currents
The filter leakage currents specified in the data book Leakage current,
are intended for user information only.The maximum 8.4
leakage current of the entire electrical equipment or Leakage current,
appliance has to be limited for safety reasons. Please 8.6
obtain the applicable limits for your application from
the relevant regulations, provisions and standards.
Voltage derating
If the permissible limits for the higher-frequency Voltage derating,
voltages at the filter are exeeded, the filter may be 9.8
damaged or destroyed.
Hazards caused by
overloading the
filters
Current derating at Non-observance of the current derating may lead to Current derating,
elevated ambient
temperatures
overheating and consequently represents a fire 10.1
hazard.
Please read Cautions and warnings and
Important notes at the end of this document.
Page 16 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
Reference chapter
(data book),
Topic
Instructions
paragraph
Protective earth
connection at
For operating currents greater than 250 A, we Mounting
recommend the PE connection to be set up between instructions,
operating currents the feed (filter: line) and output (filter: load) not via the point 2
>250 A
PE terminal bolt in the filter housing.
Mounting position
Note the mounting position of the filters! It must Mounting
always be ensured that natural convection is not instructions,
impaired.
point 13
Long motor cables Long motor cables cause parasitic currents in the
Mounting
installation. The cable lengths indicated for the output instructions,
chokes and output filters serve for orientation. The
user must check the technical parameters and
especially the choke temperatures for the respective
application.
point 15
Display of ordering codes for TDK Electronics products
The ordering code for one and the same product can be represented differently in data sheets,
data books, other publications, on the company website, or in order-related documents such as
shipping notes, order confirmations and product labels. The varying representations of the or-
dering codes are due to different processes employed and do not affect the specifications
of the respective products.
Detailed information can be found on the Internet under
www.tdk-electronics.tdk.com/orderingcodes.
Please read Cautions and warnings and
Important notes at the end of this document.
Page 17 of 20
3-line filters
B84743*R712
for converters and power electronics
Preliminary Data
Symbols and terms
Symbol
English
German
α
Insertion loss
Einfügungsdämpfung
Bemessungskapazität
CR
CX
CY
ΔV
dv/dt
f
Rated capacitance
Capacitance X capacitor
Capacitance Y capacitor
Voltage drop (input to output)
Rate of voltage rise
Frequency
Kapazität X-Kondensator
Kapazität Y-Kondensator
Spannungsabfall im Filter
Spannungsanstiegsgeschwindigkeit
Frequenz
fM
fP
Converter output frequency
Pulse frequency
Motorfrequenz
Pulsfrequenz
fR
fres
IC
ILK
Imax
IN
Rated frequency
Bemessungsfrequenz
Resonanzfrequenz
Strom durch Kondensator
Filter-Ableitstrom
Maximalstrom
Nennstrom
Resonant frequency
Current through capacitor
Filter leakage current
Maximum current
Nominal current
Iop
Ipk
Iq
IR
IS
L
Operating current (design current)
Rated peak withstand current
Capacitive reactive current
Rated current
Interference current
Inductance
Betriebsstrom
Bemessungs-Stoßstromfestigkeit
Kapazitiver Blindstrom
Bemessungsstrom
Störstrom
Induktivität
LR
Lstray
PL
R
Rated inductance
Stray inductance
Power loss
Resistance
Bemessungsinduktivität
Streuinduktivität
Verlustleistung
Widerstand
Ris
Rtyp
TA
Tmax
Tmin
TR
uk
Veff
VK
VLE
VN
VR
Vpeak
Vtest
VX
VY
XL
Z
Insulation resistance
DC resistance, typical value
Ambient temperature
Upper category temperature
Lower category temperature
Rated temperature
Referred voltage drop in %
RMS voltage
Isolationswiderstand
Gleichstromwiderstand, Richtwert
Umgebungstemperatur
Obere Kategorietemperatur
Untere Kategorietemperatur
Bemessungstemperatur
Bezogener Spannungsabfall in %
Effektivspannung
Voltage drop
Spannungsabfall
Voltage line to earth; voltage line to ground Spannung Phase zu Erdpotential
Nominal voltage
Rated voltage
Peak voltage
Nennspannung
Bemessungsspannung
Spitzenspannung
Test voltage
Prüfspannung
Voltage over X capacitor
Voltage over Y capacitor
Inductive reactance
Impedance
Spannung über X-Kondensator
Spannung über Y-Kondensator
Induktiver Blindwiderstand
Scheinwidertand
|Z|
Impedance, absolute value
Scheinwiderstand (Betragswert)
Please read Cautions and warnings and
Important notes at the end of this document.
Page 18 of 20
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical re-
quirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application.
As a rule, we are either unfamiliar with individual customer applications or less familiar with
them than the customers themselves. For these reasons, it is always ultimately incumbent on
the customer to check and decide whether a product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or
failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in
which the malfunction or failure of an electronic component could endanger human life or
health (e.g. in accident prevention or lifesaving systems), it must therefore be ensured by
means of suitable design of the customer application or other action taken by the customer
(e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by
third parties in the event of malfunction or failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our Ma-
terial Data Sheets on the Internet (www.tdk-electronics.tdk.com/material). Should you have
any more detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order. We also
reserve the right to discontinue production and delivery of products. Consequently, we
cannot guarantee that all products named in this publication will always be available. The
aforementioned does not apply in the case of individual agreements deviating from the fore-
going for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to our General
Terms and Conditions of Supply.
Page 19 of 20
Important notes
7. Our manufacturing sites serving the automotive business apply the IATF 16949 stan-
dard. The IATF certifications confirm our compliance with requirements regarding the quality
management system in the automotive industry. Referring to customer requirements and cus-
tomer specific requirements (“CSR”) TDK always has and will continue to have the policy of
respecting individual agreements. Even if IATF 16949 may appear to support the acceptance
of unilateral requirements, we hereby like to emphasize that only requirements mutually
agreed upon can and will be implemented in our Quality Management System. For clari-
fication purposes we like to point out that obligations from IATF 16949 shall only become
legally binding if individually agreed upon.
8. The trade names EPCOS, CarXield, CeraCharge, CeraDiode, CeraLink, CeraPad, CeraPlas,
CSMP, CTVS, DeltaCap, DigiSiMic, ExoCore, FilterCap, FormFit, LeaXield, MiniBlue,
MiniCell, MKD, MKK, ModCap, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap,
PowerHap, PQSine, PQvar, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SiMic, SIMID,
SineFormer, SIOV, ThermoFuse, WindCap, XieldCap are trademarks registered or pend-
ing in Europe and in other countries. Further information will be found on the Internet at
www.tdk-electronics.tdk.com/trademarks.
Release 2020-06
Page 20 of 20
相关型号:
©2020 ICPDF网 联系我们和版权申明