AC/DC Front End
FPS SERIES
FPS
Y
E
A
R
2
S
warranty
■ Features
■
Power Supply Identification
FPS 1000 - 48 /PS
ꢀ● Compact, 1U high, and, high power density
Size: 127(W)×41(H)×290(D) mm
ꢀ
3
Power Density: 11W/inch ,
Senes O/P Power O/P Voltage Option
Maximum Output Power: 1kW
ꢀ● Universal Input: AC85-265V
1000(W)
3000(W)
12(V)
24(V)
48(V)
Blank: Standard Model
/P : IEC Inlet Type (on front panel)
/S : I²C Opton built-in
ꢀ● Up to 3000W (3 units) in 19"rack
ꢀ● Hot swap / N+1 redundant parallel operation available
/PS : IEC inlet +I²C Option
2
ꢀ● I C option available (/S, /PS model)
Note: FPS3000 is 3x FPS + FPS-S1U in one rack.
FPS3000 can include 3x FPS with same ratings.
ꢀ● Front IEC inlet model (AC input) available,
(/P, /PS model)
ꢀ
FPS-S1U /PS
Senes Option
■ Applications
Blank: Standard Model
(For FPS1000-*, FPS1000-*/S)
/P : IEC Inlet Type (on front panel,
for FPS1000-*/P, FPS1000-*/PS)
Note: FPS-S1U does not have FPS1000. This is 1U rack
only. Up to 3x FPS1000 (with same voltage rating)
can be installed into FPS-S1U.
■ Product Line up
1000W
Output Voltage
Output Current
Model
12V
24V
48V
72A
40A
21A
FPS1000-12
FPS1000-24
FPS1000-48
■
Conformity to RoHS Directive
This means that, in conformity with EU Directive 2002/95/
EC, lead, cadmium, mercury, hexavalent chromium, and
specific bromine-based flame retardants, PBB and PBDE,
have not been used, except for exempted applications.
FPS3000 - □
Shelf type: 3 units of FPS1000 mounting in a 19-inch
shelf (FPS-S1U) with maximum 3kW
Size: 440(W)×43.6(H)×351(D) mm
・All specifications are subject to change without notice.
A-47
FPS1000
FPS1000 Specifications
MODEL
(*1)
(*1) Hz
ꢀ
FPS1000-12
FPS1000-24
FPS1000-48
ITEMS/UNITS
Voltage Range
V
AC85 - 265 continuous (Universal input)
Frequency
47 - 63, single phase
Power Factor (115/230VAC)(typ)
Input Efficiency (typ) (*2) %
Current (100/200VAC) (max)
More than 0.98 at maximum output power
81 / 83
84 / 86
12.0 / 6.0
Less than 40
Less than 1.1
24
85 / 88
A
A
Inrush Current
(*3)
Leakage Current (230VAC)
Nominal Voltage
mA
VDC
A
12
72
48
21
FPS
Maximum Current
Maximum Power
(*Fig.1)
40
W
864
960
1008
Voltage Set Point
12V +/-1%
24V +/-1%
0.40%
48V +/-1%
Maximum Line Regulation(*5)
Output Maximum Load Regulation(*6)
Temperature Coefficient
Warm Up Drift
0.80%
200PPM/℃
0.1% of rated Vout for 8hrs after 30min warm-up. Constant line, load and temperature.
150 200 300
20 at rated output voltage and less than 80% of rated load.
Maximum Ripple & Noise (*4) mVp-p
Hold-up Time (100VAC)(typ) ms
Voltage Adjustable Range
VDC
10.5 - 13.2
21.5 - 29
43 - 58
Over Current Protection(*Fig.1)
105 - 125% of maximum output current.
31 - 34
Over Voltage Protection (*8) VDC
Over Temperature Protection
14.3 - 15.7
62 - 66
Inverter shut down method, automatic reset.
Possible. Refer to instruction manual.
Remote Sensing
(*7)
Remote ON/OFF Control
Parallel Operation
Series Operation
By electrical signal or dry contact. ON: 0 - 0.6V or short. OFF: 2 - 15V or open.
Possible. Refer to instruction manual.
(*9)
(*10)
Possible. Refer to instruction manual.
Function
Over Temperature Alarm Signal
DC OK signal
Open collector signal. Normal: ON, Max.sink current: 10mA.
Open collector signal. On when Vout>80+/-5% rated output. Max.sink current: 10mA
Open collector signal. On when Vin > 85VAC, Max.sink current: 10mA.
11.2 - 12.5VDC. 0.25A maximum output current.
Possible, via Vout trim pin in the I/O connector. Refer to instruction manual.
AC OK, DC OK, DC FAIL
AC Fail Signal
AUX-BIAS Power Supply
Output Voltage Trimming
Front Panel Indicators
I²C Interface
Optional. Refer to instruction manual.
Operating Temperature
Storage Temperature
Operating Humidity
℃
℃
%RH
%RH
0 to 50: 100% load. Derate 2%/℃, 50 to 60
-30 to 85
10 - 90, no condensation.
Environment Storage Humidity
Vibration
10 - 95, no condensation.
Built to meet ETS 300 019
Shock
Built to meet ETS 300 019
Cooling
By internal fans. Variable speed control.
Withstand Voltage
Isolation
Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. Output-Ground: 500Vrms, 1min.
More than 100Mohm at 25℃ and 70% RH. Output-Ground: 500VDC
Approved by UL60950-1, EN60950-1, CSA C22.2 No.60950-1
EN55022B, FCC part 15J-B, VCCI-B
Isolation Resistance
Safety Standards
Standards
EMI
(*11)
Weight (typ)
Mechanical
g
2000
Size (W x H x D)
mm
127 x 41 x 290 (Refer to outline drawing.)
(*1) For cases where conformance to various safety standards (UL, EN etc.)
is required, to be described as 100-240Vac (50/60Hz).
Vout (V)
(*2) At 100/200VAC, rated load and 25℃ ambient temperature.
(*3) Not applicable for the noise filter inrush current less than 0.2ms.
(*4) Measured with JEITA RC-9131 1:1 probe, 20MHz B.W.
(*5) From 85-132Vac or 170-265VAC, constant load.
V2
V1
(*6) From no-load to rated load, constant input voltage.
Model
V1
FPS1000 FPS1000 FPS1000
Measured at the sensing point in remote sense.
-12
12V
-24
24V
29V
33A
40A
-48
(*7) Remote sensing can compensate up to 1V drop on
each load wire.
V1
V2
l1
48V
58V
(*8) Inverter shut down method. Reset by AC voltage
recycle or by ON/OFF control.
13.2V
66A
72A
17.25A
21A
(*9) Derate maximum output power by 10% for input
l2
.
voltage less than 100VRMS
(*10) Series operation is not applicable for units
with I2C bus option (/S, /PS model).
l1
l2
Iout(A)
Fig.1 Rated output current vs rated output voltage
(*11) For FPS 1000-12/P(S), when used not with FPS-S1U or FPS-T1U
racks, an EMI suppressor clamp should be attached to the AC cable,
as close as possible to the AC inlet, to meet class B.
・All specifications are subject to change without notice.
A-48
FPS 1000
Outline Drawing
FPS1000
【
】
FRONT VIEW
SEE NOTE 4
SEE NOTE 2
REAR VIEW
FPS
IN/OUT CONNECTOR
SEE NOTE 1
NOTES
AIR FLOW
1. CONNECTOR TYPE: PCIB24W9M400A1, POS- DIRECTION
ITRONIC. FEMALE CONNECTOR TYPE: PCIB-
24W9F400A1,-S1031(not attached with unit)
2. LED INDICATORS. REFER TO INSTRUCTION
MANUAL.
3. MOUNTING SCREWS MUST NOT PENETRATE
MORE THAN 3mm INTO THE UNIT.
4. MODEL NAME, INPUT AND OUTPUT RATING
AND SAFETY APPROVALS SYMBOLS ARE
DESCRIBED ON TOP SURFACE LABEL.
5. ALLOW MINIMUM 50mm OF UNRESTRICTED
3 MOUNTING HOLES M3 MARKED "A" SEE NOTE 3
(unit: mm)
PIN
PIN
PIN
AIR SPACE AT THE REAR OF UNIT. DO NOT
OBSTRUCT AIR FLOW TO THE UNIT FRONT
PANEL.
1
2
3
4
5
6
7
8
9
19
20
21
23
FUNCTION
FUNCTION
DC_OK
SIGNAL_RTN
AC_FAIL
TEMP_ALARM
-S
V_TRIM
CS
+12V_AUX
FUNCTION
NUMBER.
NUMBER.
9
NUMBER.
24
22
2
1
2
3
4
5
6
7
8
+v
+v
-v
+v
-v
17
18
19
20
21
22
23
24
SDA (I C)
2
10
11
12
13
14
15
16
SCL (I C)
2
A0 (I C)
2
6. IN OUT CONNECTOR BACK VIEW AND PINS
ASSIGNMENT:
A1 (I C)
2
A2 (I C)
-v
ACG
ACL
ACN
ON/OFF
+S
FPS1000/P
【
】
FRONT VIEW
SEE NOTE 4
SEE NOTE 2
IEC320
AC INLET
REAR VIEW
OUTPUT CONNECTOR SEE NOTE 1
AC CABLE
LOCK OPTION
AIR FLOW
DIRECTION
NOTES
1. CONNECTOR TYPE: PCIB24W9M400A1, PO-
SITRONIC. FEMALE CONNECTOR TYPE:
PCIB24W9F400A1,-S1031(not attached with
unit)
2. LED INDICATORS. REFER TO INSTRUCTION
MANUAL.
3. MOUNTING SCREWS MUST NOT PENETR-
ATE MORE THAN 3mm INTO THE UNIT.
4. MODEL NAME, INPUT AND OUTPUT RATING
AND SAFETY APPROVALS SYMBOLS ARE
DESCRIBED ON TOP SURFACE LABEL.
5. ALLOW MINIMUM 50mm OF UNRESTRICTED
AIR SPACE AT THE REAR OF UNIT. DO NOT
OBSTRUCT AIR FLOW TO THE UNIT FRONT
PANEL.
3 MOUNTING HOLES M3 MARKED "A" SEE NOTE 3
(unit: mm)
PIN
PIN
PIN
1
2
3
4
5
6
7
8
9
19
20
21
23
FUNCTION
FUNCTION
DC_OK
SIGNAL_RTN
AC_FAIL
TEMP_ALARM
-S
V_TRIM
CS
+12V_AUX
FUNCTION
NUMBER.
NUMBER.
9
NUMBER.
24
22
2
1
2
3
4
5
6
7
8
+v
+v
-v
+v
-v
-v
17
18
19
20
21
22
23
24
SDA (I C)
2
10
11
12
13
14
15
16
SCL (I C)
2
A0 (I C)
2
A1 (I C)
2
A2 (I C)
NC
NC
NC
6. IN OUT CONNECTOR BACK VIEW AND PINS
ASSIGNMENT:
ON/OFF
+S
・All specifications are subject to change without notice.
A-49
FPS-S1U
FPS-S1U Specifications
MODEL
(*2)
(*2) Hz
ꢀ
FPS-S1U
ITEMS/UNITS
Voltage Range
Input Frequency
Current (100/200VAC)(max)
Output Maximum Power (*1)
V
AC85 - 265 continuous (Universal input)
47 - 63, Single phase
A
12.0 / 6.0 for each FPS1000 unit installed
3000
W
Remote Sensing
(*3)
Possible.
Separate control for each FPS1000 unit, by electrical signal or dry contact.
On: 0 - 0.6V or short. OFF: 2 - 15V or open.
Possible.
Remote ON/OFF Control
FPS
Parallel Operation
Series Operation
Over Temperature Alarm
Signal
(*6)
(*4)
Possible. Up to 2 racks of the same voltage and current rating.
Separate control for each FPS1000 unit, open collector signal.
Normal: ON, max.sink current: 10mA
Separate control for each FPS1000 unit, open collector signal.
On when Vout>80%+/-5% max.sink current: 10mA
Separate control for each FPS1000 unit, open collector signal.
On when Vin > 85VAC, max.sink current: 10mA.
11.2 - 12.5VDC. Maximum output current: 0.25A x Number of installed FPS1000 units.
Possible. Refer to instruction manual.
Function DC OK Signal
AC Fail Signal
AUX-BIAS Power Supply
Output Voltage Trimming
AC Input Connector
Output Terminals
FPS-S1U: IEC inlet for each power supply module. FPS-S1U/P: None
Bus-bars. Refer to outline drawing.
Number of Power Supply Modules (*5)
Operating Temperature
Storage Temperature
Operating Humidity
Storage Humidity
Vibration
Maximum 3 FPS1000 modules of the same output voltage rating.
0 to 50: 100% load. Derate 2%/℃, 50 to 60.
-30 to 85
℃
℃
%RH
%RH
10 - 90, no condensation.
Environment
10 - 95, no condensation.
Built to meet ETS 300 019
Shock
Built to meet ETS 300 019
Withstand Voltage
Isolation Resistance
Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. Output-Ground: 500Vrms, 1min.
More than 100MΩ at 25℃ and 70% RH. Output-Ground: 500VDC
UL60950-1, EN60950-1, CSA C22.2 No.60950-1
3700
Isolation
Standards Safety Standards
Weight (typ)
Mechanical
g
Size (W x H x D)
mm
440 x 44 x 351 (Refer to outline drawing.)
(*1) For input voltage lower than 100VAC, maximum output power is 2700W.
(*2) For cases where conformance to various safety standards (UL, EN etc.) is required, to be described as 100-240VAC (50/60Hz).
(*3) Remote sensing can compensate up to 1V drop on each load wire.
(*4) Not applicable for units with I2C bus option.
(*5) The output of all the FPS1000 modules are connected in parallel in the rack.
(*6) Up to 3 racks with max.8 FPS1000 units of the same voltage and current rating.
・All specifications are subject to change without notice.
A-50
FPS-S1U
Outline Drawing
SIGNAL & CONTROL
FPS-S1U
【
】
CONNECTOR D-TYPE 25 PINS
I2C INTERFACE
ADDRESS SWITCH
(SEE NOTE 3)
OUTPUT
BUS BAR
MODULE "A"
MODULE "B"
MODULE "C"
SIDE MOUNTING HOLES
MARKED "D" 3 ON EACH SIDE
(SEE NOTE 5.)
SEE NOTE 1.
SEE NOTE 2.
FPS
HOLES FOR BLANK PANEL
MOUNTING: USE FLAT
HEAD SCREWS M3x6- 6
PLACES MARKED "A"
UNIT : mm
NOTES
(*1)ꢀMOUNTING HOLES FOR 19" RACK, USE M6x12 TO FIX THE UNIT
TO A RACK.ꢀ
APPROVALS SYMBOLS WILL BE SHOWN HERE ACCORDING TO
THE SPECIFICATIONS.
(*5)ꢀMOUNTING HOLES M5 FOR MOUNTING BRACKETS . USE M5x8
SCREWS TO FIX THE BRACKETS TO THE CHASSIS. SCREWS
MUST NOT PENETRATE THE CHASSIS MORE THAN 6 mm.
(*6)ꢀTHE FPS-S1U RACK IS SHOWN WITH 3 FPS1000 UNITS
INSTALLED.
(*2)ꢀM6x16 SCREWS FOR LOAD WIRES FIXING, USE M6 LUG FOR
THE LOAD WIRES, RECOMMENDED TIGHTENING TORQUE 42 - 56
Kgf.cm
(*3)ꢀREFER TO INSTRUCTION MANUAL FOR SETTING DETAILS.
(*4)ꢀMODEL NAME , VOLTAGE AND CURRENT RATING AND SAFETY
SIGNALS & CONTROL CONNECTOR PINS ASSIGNMENT
CONNECTOR DESCRIPTION:
13
1
D-TYPE RIGHT ANGLE, 25 POSITIONS,
FRONT METAL SHELL,
OUTPUT TERMINAL COVER.
INSTALL AFTER LOAD
25
14
AMP P/N: 747846-4
CABELS CONNECTION.
PIN NUMBER.
9
10
11
12
13
14
15
16
FUNCTION
PIN NUMBER.
FUNCTION
V_TRIM_B
TEMP_ALARM_B
DC_OK_B
TEMP_ALARM_A
ON/OFF_A
DC_OK_A
PIN NUMBER.
17
18
19
20
21
22
23
24
FUNCTION
CS
FLAT HEAD
SCREW M3x6
-2 PLACES-
1
2
3
4
5
6
7
8
NC
NC
NC
SEE NOTE 4
V_TRIM_C
SIGNAL_RTN
DC_OK_C
+S
AC_FAIL_B
ON/OFF_B
AC_FAIL_A
SCL(l2C)
SDA(l2C)
-S
TEMP_ALARM_C
AC_FAIL_C
ON/OFF_C
V_TRIM_A
+12V_AUX
25
PS MODULE "A"
BLANK PANEL
PS MODULE "B"
INFORMATION:
(OPTIONAL)
ORDER NAME: FPS-BP
PS MODULE "C"
UNIT : mm
AIR FLOW
DIRECTION
・All specifications are subject to change without notice.
A-51
FPS-S1U/P
SIGNAL & CONTRO
FPS-S1U / P
【
】
CONNECTOR D-TYP 25 PINS
I2C INTERFACE
ADDRESS SWITCH
(SEE NOTE 3.)
OUTPUT
BUS BAR
SIDE MOUNTING HOLES
MARKED "D" 3 ON EACH SIDE
(SEE NOTE 5.)
SEE NOTE 1.
SEE NOTE 2.
FPS
HOLES FOR BLANK PANEL
MOUNTING: USE FLAT
HEAD SCREW M3x6-
6PLACES MARKED "A"
UNIT : mm
NOTES
(*1)ꢀMOUNTING HOLES FOR 19" RACK, USE M6x12 TO FIX THE UNIT
TO A RACK.ꢀ
(*3)ꢀREFER TO INSTRUCTION MANUAL FOR SETTING DETAILS.
(*4)ꢀMODEL NAME , VOLTAGE AND CURRENT RATING AND SAFETY
APPROVALS SYMBOLS WILL BE SHOWN HERE ACCORDING TO
THE SPECIFICATIONS.
(*5)ꢀMOUNTING HOLES M5 FOR MOUNTING BRACKETS . USE M5x8
SCREWS TO FIX THE BRACKETS TO THE CHASSIS. SCREWS
MUST NOT PENETRATE THE CHASSIS MORE THAN 6 mm.
(*6)ꢀTHE FPS-S1U/P RACK IS SHOWN WITH 3 FPS1000/P UNITS
INSTALLED.
(*2)ꢀM6x16 SCREWS FOR LOAD WIRES FIXING. USE M6 LUG FOR THE
LOAD WIRES. RECOMMENDED TIGHTENING TORQUE 42 - 56
Kgf.cm
SIGNALS & CONTROL CONNECTOR PINS ASSIGNMENT
CONNECTOR DESCRIPTION:
D-TYPE RIGHT ANGLE, 25 POSITIONS,
FRONT METAL SHELL.
13
1
25
14
AMP P/N: 747846-4
OUTPUT TERMINAL COVER.
INSTALL AFTER LOAD
CABLES CONNECTION.
PIN NUMBER.
FUNCTION
V_TRIM_B
PIN NUMBER.
9
10
11
12
13
14
15
16
FUNCTION
PIN NUMBER.
17
18
19
20
21
22
23
24
FUNCTION
1
2
3
4
5
6
7
8
CS
NC
NC
NC
TEMP_ALARM_B
DC_OK_B
V_TRIM_C
SIGNAL_RTN
DC_OK_C
+SENSE
AC_FAIL_B
ON/OFF_B
AC_FAIL_A
SEE NOTE 4
2
TEMP_ALARM_A
ON/OFF_A
SCL(I C)
FLAT HEAD
SCREW M3x6
-2 PLACES-
2
SDA(I C)
DC_OK_A
-SENSE
V_TRIM_A
TEMP_ALARM_C
AC_FAIL_C
ON/OFF_C
+12V_AUX
25
PS MODULE "A"
BLANK PANEL
INFORMATION:
(OPTIONAL)
PS MODULE "B"
ORDER NAME: FPS-BP
AIR FLOW
DIRECTION
PS MODULE "C"
UNITS:mm
・All specifications are subject to change without notice.
A-52
相关型号:
©2020 ICPDF网 联系我们和版权申明