MU4 [TDK]
AC-DC电源;型号: | MU4 |
厂家: | TDK ELECTRONICS |
描述: | AC-DC电源 |
文件: | 总9页 (文件大小:2486K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MU4 Series
https://emea.lambda.tdk.com/mu
https://product.tdk.com/en/power
600W / 800W
1U Modular power supply
Medical
Industrial
Test
Broadcast
Renewable
Comms
Features
Benefits
• Extremely low audible noise fan
Enhanced patient / user experience
Eases design into systems (including BF)
Eliminates need for additional supplies
Remote monitoring and control
Low cost of ownership
• BF ready medical isolation (MOPP)
• Up to 5 outputs
• PMBus™ communication option
• 7 year warranty
Input
Output power
Input voltage
Frequency
600W
800W
85-264Vac (Contact sales for operation below 90Vac)
47 - 63 Hz (440Hz with reduced PFC)
180-264Vac
Input fuses
10A / 250Vac HBC Fast acting (not user accessible) in both Live and Neutral lines (single fusing optional)
Inrush current
Leakage current
Touch current
Power factor
<45A at 25°C and 264Vac (cold start)
300µA max
<100µA
> 0.9 (at 230Vac, 100% load)
Isolation
2 x MOPPs (3rd edition 60601)
Reinforced
Input to output / signals
4kVac, 5.7kVdc type tested to 4kVac (equivalent to 5.7kVdc), production tested to 4.3kVdc.
Input to earth
Basic
Basic
1 x MOPP, 1.5kVac
Output / signals to earth
1 x MOPP, 1.5kVac
Output / signals to output / signals Basic
200Vdc (1 x MOPP between modules is available, contact sales for details)
How To Create A Product Description
The extensive range of output modules and options make it possible to achieve almost any combination of Volts and Amps. You can create
your own MU configuration online at https://config.emea.tdk-lambda.com/. This method checks your configuration and offers the optimum
solution. Alternatively, you can do this manually by using the guide below.
1.
Calculate total output power to select the appropriate converter, then select required Cooling, Input Connection, Input Fuse, Leakage
Current and Controls/Signals from the following table:
2.
3.
Select Output Modules using the output voltages tables and the module specifications.
Contact TDK-Lambda to validate configuration and issue a part number.
MU4
F
S
D
L
T5H
Converter
4 slots wide
600W low line, 800W
high line
MU4
F
blank none
E5H 5V / 2A, AC good + Enable
T5H 5V / 2A, AC good + Inhibit
Q5H0000 5V / 2A, see PMBus™ app note
Standby
/ Signals
Cooling
Variable speed Forward air - standard
see specification page for details
Input
Connection
S
Screw
D
E
Dual AC fuses
Single AC fuse in Live line
(contact sales for details)
Leakage Current
(max at 264Vac, 63Hz)
Input fuse
L
300µA
MU4_Datasheet_260815 - v1.1
1
MU4 Series
Possible Outputs - see individual module data for full specifications
Maximum Output
Current
Maximum Output
Power
Module name
Slots used
Output voltage range
SB
ZC
SB
YC
YC
SB
SB
YC
YC
1
2
1
2
2
1
1
2
2
3.3V
3.3V
6V
-
-
-
-
-
-
-
-
-
6V
6V
30A
54A
20A
30A
20A
10A
5A
150W
260W
240W
300W
480W
240W
240W
480W
480W
15V
12V
30V
30V
52V
60V
104V
6.6V
12V
15V
30V
30V
60V
10A
5A
Note. ‘Maximum Output Current’ and ‘Maximum
Output Power’ above are the maximum available from
the module. It is not possible to exceed the ‘Output
Power’ of the unit given on the previous page.
MU4_Datasheet_260815 - v1.1
MU4 Series
2
Output Specification
Turn on time
2s max
at 85Vac (180Vac for 800W) and 100% rated output power
Efficiency
Up to 90%
230Vac, 100% rated power, 25°C, configuration dependent
12ms min
10ms min
at 600W output power (for 30-52Vdc SB module and 60 -104Vdc YC module, 9ms min)
at 800W output power (for 30-52Vdc SB module and 60 -104Vdc YC module, 7ms min)
Hold up
converter protection shuts down all outputs (except standby supplies) and fan, auto
restarts. Shutdown temperature varies according to ambient, output power and input voltage.
Over temperature protection
Yes
Environment
Temperature
-20°C to 70°C operational, -40°C to 70°C storage.
Derating
50°C to 70°C derate total output power and each output current by 2.5% per °C
-40°C, all specification parameters may not be achieved
Low temperature startup
Audible noise
Humidity
As low as 36dBA, 25°C, 115Vac/240Vac and 80% unit power (fan speed increases with load / temperature)
5 - 95% RH non condensing
±3 x 30g shocks in each plane, total 18 shocks (11ms (+/-0.5msec), half sine)
Conforms to EN60068-2-27, EN60068-2-47, IEC68-2-27, IEC68-2-47, JIS C0041-1987.
Conforms to MIL-STD-810G, Method 516.6, Pro IV
Shock
Single axis 10 - 500 Hz at 2g (sweep and endurance at resonance) in all 3 planes
Conforms to EN60068-2-6, IEC68-2-6
Vibration
Conforms to MIL-STD-810G, Method 514.6, Pro I
Altitude
Pollution
IP Rating
5000 metres operational (4000 metres for 60601-1), 5000 metres storage/transportation
Degree 2, Material group IIIb
IPX0
Emissions EN61000-6-3:2007, EN60601-1-2:2015 - see application notes for best installation practice
(as per CISPR.11/32) Class B, FCC47 part 15 subpart B - ‘L’ leakage current variants
(Units with ‘R’ type leakage current option achieve Class A)
Radiated electric field
EN55011, EN55032
(as per CISPR.11/32) Class B, FCC47 part 15 subpart B - ‘L’ leakage current variants
(Units with ‘R’ type leakage current option achieve Class A)
Conducted emissions
EN55011, EN55032
Conducted harmonics
Flicker
EN61000-3-2
EN61000-3-3
Class A and Class C
Compliant - dmax only
Immunity EN61000-6-2:2005, EN60601-1-2:2015 - see application notes for best installation practice
Criteria
F type cooling only
A
Electrostatic discharge
EN61000-4-2
Level 4
Proximity fields, EN60601-1-2, Levels as defined in
Electromagnetic field
EN61000-4-3
Level 3
A
standard, Criteria A
Tested at 5kHz and 100kHz
Fast / burst transient
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
Level 4
Level 3
Level 3
Level 4
Class 3
compliant
Level 3
Class 3
A
A
A
A
A
Surge immunity
Conducted RF immunity
Power frequency magnetic field
Criteria B for 5s and 1 cycle interruptions
above 180Vac input
Voltage dips, variations, interruptions EN61000-4-11
Voltage sags
Semi F-47
Ring wave
EN61000-4-12
EN61000-4-14
A
A
Voltage fluctuations
See EMC report for full details.
Approvals / Accreditations
IEC/EN 62368-1, UL62368-1 / CSA 22.2 No 62368-1
File E135494
File E135494
IEC/EN 60950-1, UL60950-1 / CSA 22.2 No 60950-1
IEC/EN 60601-1, UL/CSA 60601-1, ANSI/AAMI ES60601-1, CAN/CSA-C22.2 No 60601-1
IEC/EN 61010-1
File E349607
Designed to meet
Low Voltage Directive (LVD), electromagnetic compatibility (EMC) and Restriction
of Hazardous Substances (RoHS)
CE Mark (EN62368-1)
Electrical Equipment (Safety) Regulations, electromagnetic compatibility (EMC)
and Restriction of Hazardous Substances (RoHS)
UKCA (EN62368-1)
CB certificate and Report available on request
Designed and manufactured under the control of ISO9001 and ISO13485 (including risk management).
MU4_Datasheet_260815 - v1.1
3
MU4 Series
Standby / Signals
Maximum power per channel
See table below
Available signals (Exx or Txx type)
PSU inhibit (Txx type) or enable (Exx type), AC Good
PMBus™ control of power supply
fan speed and fail warning
Serial number, date of manufacture, run time, on/off power cycles
For further details, see the product range application notes, PMBus™ section
Available signals (Qxx type)
Conector information
10 way housing Molex 51110-1060
12way housing Molex 51110-1260
Crimp terminal
Molex 50394
Available Output Voltages (at PSU signal con-
Txx or Exx option
Pin
1
2
5H
Standby +
Standby -
nector)
Standby 1
Option
PIN 2
3
4
5
6
Do not connect
Do not connect
PSU on/off+
PSU on/off-
AC fail Out
PSU on/off
Max
PIN 1
PIN 9
type
V
Power
Current
E5H
T5H
5V
5V
2A
2A
10W
10W
Enable
Inhibit
7
8
AC fail Rtn
9
10
Fan fail Out
Fan fail Rtn
see PMBus™
application note
Q5H0000 5V
2A
10W
PIN 10
Pin Q5Hxxxx option
1
2
Standby +
Standby -
3
4
Do not connect
Fan fail
PIN 1
PIN 2
5
6
7
8
9
10
Address 0
Address 1
Address 2
Address 3
SCL - Clock
SDA - Data
11 Control line in
12 GND
PIN 12
PIN 11
Output Specification
Rise time
<30ms
<2%
(with resistive load) to 90% of voltage, monotonic rise above 10%
pk-pk, using 20MHz bandwidth
Ripple and noise
Voltage setting accuracy
Remote sense
<3%
of set voltage
No
Minimum load
0W
on any output
of rated voltage per °C
Temperature coefficient
Load regulation
0.02%
<1.0%
<0.1%
<0.4%
<5%
for 0-100% load change
Line regulation
for 90-264Vac input change
for 100% load change on any output
of set voltage for 25-50% load change
for recovery to 1% or 100mV of set voltage
Latching, output shuts down, cycle ac to reset
Auto recovers
Cross regulation
Transient deviation
Recovery
1ms
Over voltage protection
Over current protection
Short circuit protection
Yes
Constant Current
Constant Current
Auto recovers
MU4_Datasheet_260815 - v1.1
MU4 Series
4
SB Module - single slot width, 1 output channel
Maximum power per channel see table below
Available signals
Remote sense, module good, module inhibit or enable
Conector information
10 way housing Molex 51110-1060
Crimp terminal
Molex 50394
Pin
Connection
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)
1
2
3
4
5
6
7
8
9
Remote Sense +
Remote Sense -
Current share
Max Capaci-
tive Load
10
2
1
Adjustment Range (Volts)
Current
Output power
3.3
6
-
-
-
-
6.0
15
30
52
30A
20A
10A
5A
150W
240W
240W
240W
500µF/A
500µF/A
500µF/A
200µF/A
Do not connect
9
V ADJ
Module good collector
Module good emitter
Module enable/inhibit
anode
Module enable/inhibit
cathode
15
30
CH1 +
CH1 -
10
Output Specification
Rise time
<75ms
<5%
(with resistive load) to 90% of voltage, monotonic rise above 10%
Load type dependent
Turn on overshoot
Ripple and noise
max of
1% or 50mV
2% or 100mV
4%
pk-pk, using 20MHz bandwidth
2% above 6V output
0°C - 70°C, >5% load
-20°C - 0°C, >5% load
≤5% load
2% above 6V output
Voltage setting accuracy
<1%
of set voltage
Remote sense
Option
0W
0.5V (voltage at the output terminals must remain within the adjustment range specified above)
Minimum load
of rated voltage per °C
Temperature coefficient
Load regulation
Line regulation
0.02%
<1%
for 0-100% load change
<0.1%
0.1%
for 90-264Vac input change
Cross regulation
(5mV for outputs below 5V) for 100% load change on any output
of set voltage for 25% to 75% load change
250mV for outputs below 5V
Transient deviation
<5%
Recovery
1ms
Yes
for recovery to 1% or 100mV of set voltage (between 6V and 30V recovery is 1.5ms)
Latching, module shuts down, cycle ac to restart.
Over voltage protection
Over current protection
Short circuit protection
Hiccup
Yes
Auto recovers after removal of load
Indefinitely protected, see application notes for details
Module protection shuts down output, cycle ac to restart.
Over temperature protection
Yes
Shutdown temperature varies according to ambient, output power and input voltage.
How To Create A Product Description
Choose your required output voltage (from the table above)
For example, if you need 12V / 20A with remote sense, you would choose 12SBSF or G as your required module.
L none
V1
SB
S
L
Remote sense, Output enable,
output good (including LED)
F
Module
Option
Required output voltage
Module type
Remote sense, Output inhibit,
output good (including LED)
G
Output
connection
S
Screw terminal
MU4_Datasheet_260815 - v1.1
5
MU4 Series
YC Module - two slots width, 1 output channel
Maximum power per channel see table below
Available signals
Module good, module inhibit or enable
Conector information
10 way housing Molex 51110-1060
Crimp terminal
Molex 50394
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)
See application
notes for signal
Max Capaci-
Adjustment Range (Volts)
Current
Output Power
tive Load
connection details
6.6
12
30
60
-
-
-
-
12
30
30A
20A
10A
5A
300W
480W
480W
480W
500µF/A
275µF/A
200µF/A
100µF/A
V ADJ
See application notes
before adjusting
60
104
Output Specification
Rise time
<75ms
(with resistive load) to 90% of voltage, monotonic rise above 10%
Load type dependent
Turn on overshoot
<5%
Ripple and noise
pk-pk, using 20MHz bandwidth
2% above 12V output
0°C - 70°C, >5% load
-20°C - 0°C, >5% load
≤5% load
1%
2%
4%
Voltage setting accuracy
<1%
of set voltage
Remote sense
Option
0W
0.5V (voltage at the output terminals must remain within the adjustment range specified above)
Minimum load
of rated voltage per °C
Temperature coefficient
Load regulation
0.02%
<1%
for 0-100% load change
Line regulation
<0.1%
0.1%
<5%
for 90-264Vac input change
Cross regulation
Transient deviation
Recovery
(10mV for outputs below 10V) for 100% load change on any output
of set voltage for 25% to 75% load change
for recovery to 1% or 100mV of set voltage
Latching, module shuts down, cycle ac to restart.
Auto recovers
1ms
Over voltage protection
Over current protection
Short circuit protection
Yes
Hiccup
Yes
Indefinitely protected, see application notes for details
Module protection shuts down output, cycle ac to restart.
Over temperature protection
Yes
Shutdown temperature varies according to ambient, output power and input voltage.
How To Create A Product Description
Choose your required output voltage (from the table above)
For example, if you need 60V / 5A with remote sense, you would choose 60YCSG as your required module.
L none
V1
YC
S
L
Remote sense, Output enable,
output good (including LED)
F
Module
Option
Required output voltage
Module type
Remote sense, Output inhibit,
output good (including LED)
G
Output
connection
S
Screw terminal
MU4_Datasheet_260815 - v1.1
MU4 Series
6
ZC Module - two slots width, 1 output channel
Maximum power per channel see table below
Available signals
Module good, module inhibit or enable
Conector information
10 way housing Molex 51110-1060
Crimp terminal
Molex 50394
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)
Maximum ca-
pacitive load
Adjustment Range (Volts)
3.3
Current
Output Power
-
6
54
260W
500µF/A
V ADJ
Ch1 +
See application notes
before adjusting
Ch1 0V
See application
notes for signal
connection details
Output Specification
Rise time
<75ms
<5%
(with resistive load) to 90% of voltage, monotonic rise above 10%
Load type dependent
Turn on overshoot
Ripple and noise
pk-pk, using 20MHz bandwidth
0°C - 70°C, >5% load
-20°C - 0°C, >5% load
≤5% load
1%
2%
4%
Voltage setting accuracy
<1%
of set voltage
Remote sense
Option
0W
0.5V (voltage at the output terminals must remain within the adjustment range specified above)
Minimum load
of rated voltage per °C
Temperature coefficient
Load regulation
0.02%
<5%
for 1-100% load change
Line regulation
<0.1%
0.1%
<5%
for 90-264Vac input change
Cross regulation
Transient deviation
Recovery
for 100% load change on any output
of set voltage for 25% to 75% load change
for recovery to 1% or 100mV of set voltage
Latching, module shuts down, cycle ac to restart.
Auto recovers after removal of load
Indefinitely protected, see application notes for details
30ms
Yes
Over voltage protection
Over current protection
Short circuit protection
Hiccup
Yes
Module protection shuts down output, cycle ac to restart.
Over temperature protection
Yes
Shutdown temperature varies according to ambient, output power and input voltage.
How To Create A Product Description
Choose your required output voltage (from the table above)
For example, if you need 3.3V / 54A with remote sense, you would choose 3.3ZCSJ as your required module.
Default - Remote sense,
J Output inhibit, output good
(including LED), current share
Remote sense, Output enable,
H output good (including LED),
current share
V1
ZC
S
J
Module
Option
Required output voltage
Module type
Output
connection
S
Screw terminal
MU4_Datasheet_260815 - v1.1
7
MU4 Series
GLOBAL OPTION SLOT
SLOT 1
SLOT 2
SLOT 3
SLOT 4
254.0 MAX
257.5
Standard
airflow
Reverse
airflow
31.5 TYP
187.50 TYP
UNDERNEATH VIEW OF FIXINGS (M4, MAX THREAD PENETRATION 4.0mm)
DIMENSION TOLERANCES: 0.00 ±0.2 0.0±0.4
RECOMMENDED TORQUE: M4 1.1 - 1.3Nm
Units with factory fitted fan (‘F’ or ‘R’ type cooling)
253.0 MAX
30.5 TYP
187.50 TYP
UNDERNEATH VIEW OF FIXINGS (M4, MAX THREAD PENETRATION 4.0mm)
DIMENSION TOLERANCES: 0.00 ±0.2 0.0±0.4
RECOMMENDED TORQUE: M4 1.1 - 1.3Nm
Units with Customer Air
(‘C’ type cooling)
MU4_Datasheet_260815 - v1.1
MU4 Series
8
TDK-Lambda France SAS
TDK-Lambda Americas
Tel: +33 1 60 12 71 65
Tel: +1 800-LAMBDA-4 or 1-800-526-2324
tla.powersolutions@tdk.com
www.us.lambda.tdk.com
tlf.fr.powersolutions@tdk.com
www.emea.lambda.tdk.com/fr
Italy Sales Office
Tel: +39 02 61 29 38 63
tlf.it.powersolutions@tdk.com
www.emea.lambda.tdk.com/it
TDK Electronics do Brasil Ltda
Tel: +55 11 3289-9599
sales.br@tdk-electronics.tdk.com
www.tdk-electronics.tdk.com/en
Netherlands
tlf.nl.powersolutions@tdk.com
www.emea.lambda.tdk.com/nl
TDK-Lambda Germany GmbH
Tel: +49 7841 666 0
tlg.powersolutions@tdk.com
TDK-Lambda Corporation
Tel: +81-3-6778-1113
www.jp.lambda.tdk.com
www.emea.lambda.tdk.com/de
TDK-Lambda (China) Electronics Co. Ltd.
Tel: +86 21 6485-0777
tlc.powersolutions@tdk.com
www.lambda.tdk.com.cn
Austria Sales Office
Tel: +43 2256 655 84
tlg.at.powersolutions@tdk.com
TDK-Lambda Singapore Pte Ltd.
Tel: +65 6251 7211
tls.marketing@tdk.com
www.sg.lambda.tdk.com
www.emea.lambda.tdk.com/at
Switzerland Sales Office
Tel: +41 44 850 53 53
tlg.ch.powersolutions@tdk.com
www.emea.lambda.tdk.com/ch
TDK India Private Limited, Power Supply Division
Tel: +91 80 4039-0660
mathew.philip@tdk.com
www.sg.lambda.tdk.com
Nordic Sales Office
Tel: +45 8853 8086
tlg.dk.powersolutions@tdk.com
www.emea.lambda.tdk.com/dk
TDK-Lambda UK Ltd.
Tel: +44 (0) 12 71 85 66 66
tlu.powersolutions@tdk.com
www.emea.lambda.tdk.com/uk
TDK-Lambda Ltd.
Tel: +9 723 902 4333
tli.powersolutions@tdk.com
www.emea.lambda.tdk.com/il-en
For Additional Information, please visit
https://product.tdk.com/en/power/
MU4_Datasheet_260815 - v1.1
9
MU4 Series