NV1-3G0FF-M [TDK]
AC-DC电源;型号: | NV1-3G0FF-M |
厂家: | TDK ELECTRONICS |
描述: | AC-DC电源 |
文件: | 总4页 (文件大小:1097K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
NV-Power NV-175M
https://emea.tdk-lambda.com/nv
https://product.tdk.com/en/power/nv
180-200W Configurable
Medical power supply.
Medical
Industrial
Test
Broadcast
Renewable
Comms
Features
Benefits
•ꢀHighꢀefficiency
Minimisesꢀheatꢀinꢀsystem
•ꢀLowꢀprofile
Fitsꢀ1Uꢀapplications
•ꢀLowꢀearthꢀleakageꢀandꢀClassꢀBꢀEMC
•ꢀ2ꢀxꢀMOPPsꢀisolation
Simplifiesꢀsystemꢀdesign,ꢀreducesꢀcost
Simplifiesꢀsystemꢀdesign
Lowꢀcostꢀofꢀownership
•ꢀ3ꢀyearꢀwarranty
Input
90-264Vac
Input Voltage
Input Frequency
45 - 63Hz
(100 - 240Vac nominal)
EN61000-3-2 compliant
Fast acting (not user accessible)
123µA at 120Vac (60Hz), 257µA max at 240Vac (60Hz)
Input Harmonics
Input Fuse
Inrush Current
<40A at 25°C and 230Vac (cold start)
Earth Leakage
Current
Worst case leakage current is less than 300µA at 264Vac, 63Hz (normal condition, 0.5mA Single Fault Condition)
Lower leakage versions available, contact sales office for details
Isolation
2 x MOPPs (3rd edition 60601)
Input to Output
type tested to 4kVac (equivalent to 5.7kVdc), production tested to 4.3kVdc
4kVac
1 x MOOP (3rd edition 60601)
1.5kVac, 2.3kVdc
Input to Earth
Output to Earth
200Vdc
QUICK SELECTOR - example configurations
Additionalꢀvariantsꢀavailable,ꢀseeꢀ“HowꢀtoꢀCreateꢀaꢀProductꢀDescription”
Model
Ch1
Ch3
Ch4
NV1-1T000-M
NV1-1G000-M
NV1-3G0TT-M
NV1-3G0FF-M
12V / 15A
24V / 7.5A
24V / 7.5A
24V / 7.5A
-
-
-
-
12V / 5A
15V / 5A
-12V / 1A
-15V / 1A
How To Create A Product Description
Confirm availability of created product with TDK-Lambda
Blank standard, vertical connector
Case
Option
Connector
Option
Right angled connector
#o/p
Ch1
0
Ch32
Ch43
NV1-
-M
R
(see handbook for ‘R’ connection
and mechanical details)
Medical with 4kVac (2 x MOPPs)
input to output isolation
Number of outputs
Letter / number from ‘Available
Outputs’ table to represent
output voltage
Blank no case
-C U chassis + cover
-U U chassis
Ch1, Ch3,
Ch4
-F End fan + case1
-I End fan + case + IEC inlet1
1. Needs 0H, 3H, 5H, TH or FH type channel 4.
The fan speed is temperature dependent, ensuring optimum cooling and lowest audible noise.
2. For negative output channel 3, follow chosen letter by ‘Y’. For example, TY channel 3 = -12V / 5A.
3. For positive output channel 4, follow chosen letter by ‘P’. For example, TP channel 4 = +12V / 1A.
NV175M_Datasheet_69924 - v18.0
1
NV-Power NV-175M
Available Outputs
Otherꢀoutputꢀoptionsꢀareꢀavailable,ꢀpleaseꢀcontactꢀsalesꢀofficeꢀwithꢀyourꢀrequirements
Adjustment
Range
Adjustment
Range
Adjustment
Range
Channel 1
Channel 2
Channel 31
Channel 42
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
T
F
-12V / 1A
-15V / 1A
T
F
12V / 15A
15V / 12A
12 - 15V3
12 - 15V4
T
F
G
0
12V / 5A
15V / 5A
24V / 2.5A
Omit
12 - 15V
12 - 15V
18 - 24V
3HP +3.3V / 2A6
5HP +5V / 2A6
TH
FH
0H
0
Not available
-12V / 2A6
-15V / 2A6
Fan supply only
Omit
G
24V / 7.5A
24 - 28V5
1. Followꢀlettersꢀinꢀredꢀbyꢀ‘Y’ꢀforꢀnegativeꢀoutputꢀchannelꢀ3.
2. Followꢀlettersꢀinꢀredꢀbyꢀ‘P’ꢀforꢀpositiveꢀoutputꢀchannelꢀ4.
3. 12ꢀ-ꢀ12.5Vꢀifꢀ24Vꢀchannelꢀ3ꢀfitted.
4. 14.5ꢀ-ꢀ15Vꢀifꢀ24Vꢀchannelꢀ3ꢀfitted
5. 24ꢀ-ꢀ26Vꢀifꢀ24Vꢀchannelꢀ3ꢀfitted.
6. 1.5Aꢀmaxꢀwithꢀ‘-F’ꢀorꢀ‘-I’option.
Output Specification
Turn on time
1.5s max
at 90Vac and 100% rated output power
configuration dependent
at 90Vac
Efficiency
up to 90%
16ms min
<1%
Hold up
Ripple and Noise
Voltage Accuracy
Remote Sense
Minimum Load
(or 50mV if higher) pk-pk, using EIAJ test method & 20MHz bandwidth
±1%
±4% for Channel 4 with ‘T’ or ‘F’ type outputs, +4/-3% for all other channel 4.
Channel 1. Max 0.5V total line drop
Yes
No
on any output
Including Line (for 90-264Vac input change), Load (for 0-100% load change) and
Cross (for 0-100% load change on any other output) regulation.
1%
Total Regulation
(or 50mV if greater)
of set voltage for 50% load change
(in 50µs within the range 25-100% load)
Transient Response
<4%
Recovery
500µs
Yes
for recovery to 1% of set voltage
See Application Notes for details
Over Voltage Protection
Short Circuit Protection
Over Temperature Protection
Yes
Yes
Single output units with 12V, 15V or 24V (T, F or G). Average output power must not
exceed 180W over any 5 minute period
Peak Output Power
Ch1 Good Signal
200W
Yes
Provides a Logic ‘Low’ signal after Channel 1 output is within 90% (±5%) of nominal
Environment
0°C to 50°C operational, -40°C to 70°C storage (max 12 months).
Full load, with either ‘-F’ option fitted or 2m/s air blown from input to output (approximately 10CFM)
Temperature
Derating
50°C to 65°C derate each output by 2.5% per °C
-20°C
Low Temp Startup
Humidity
5 - 95% RH non condensing
±3 x 30g shocks in each plane, total 18 shocks
30g shock = 11ms (+/-0.5msec), half sine
Conforms to EN60068-2-27, EN60068-2-47, IEC68-2-27, IEC68-2-47, JIS C0041-1987.
Conforms to MIL-STD-810E/F, Method 516.5, Pro I, IV, VI
Shock
Single axis 10 - 500 Hz at 2g (sweep and endurance at resonance) in all 3 planes
Conforms to EN60068-2-6, IEC68-2-6
Vibration
Conforms to MIL-STD-810E, Method 514.4, Pro I, Cat 1,9
Altitude
3000 metres operational (4000m for NV1-1G000-M for 60601-1 3rd edition)
Degree 2, Material group IIIb
Pollution
Immunity EN61000-6-2:2005, EN60601-1-2:2007
Criteria
Air discharge 15kV, Contact discharge 8kV. Not applicable to open
frame units
A
A
A
Electrostatic Discharge
Electromagnetic Field
Fast / Burst Transient
EN61000-4-2
EN61000-4-3
EN61000-4-4
Level 4
Level 3
Level 4
12V/m
ac input tested to 4.4kV
dc output tested to 2.2kV
Common mode - 2.2kV, Differential - 1.1kV
Surge Immunity
EN61000-4-5
EN61000-4-6
EN61000-4-8
Level 3
Level 3
Level 4
A
A
A
A
12V
Conducted RF Immunity
Power Frequency Magnetic Field
30A/m
Criteria B for 5 sec interruption and dips to 40% for 5 cycles below
154Vac nominal input
Voltage Dips, Variations, Interruptions EN61000-4-11 Class 3
Emissions EN61000-6-3:2007, EN60601-1-2:2007
(as per CISPR.11/22) Class B, FCC47 part 15 subpart B
see application note for details. Additional filtering required for IEC inlet version.
Radiated Electric Field
EN55011, EN55032
Conducted Emissions
Conducted Harmonics
Flicker
EN55011, EN55032
EN61000-3-2
(as per CISPR.11/22) Class B, FCC47 part 15 subpart B
Class A
EN61000-3-3
Compliant - dmax only
NV175M_Datasheet_69924 - v18.0
NV-Power NV-175M
2
Approvals / Accreditations
Notes
IEC/EN 62368-1, UL62368-1 / CSA 22.2 No 62368-1
File E135494
File E135494
IEC/EN 60950-1, UL60950-1 / CSA 22.2 No 60950-1
IEC/EN 60601-1, UL/CSA 60601-1, ANSI/AAMI ES60601-1
CAN/CSA-C22.2 No 60601-1-08
File E349607
IEC/EN61010
Designed to meet
Low Voltage Directive (LVD), electromagnetic compatibility
(EMC) and Restriction of Hazardous Substances (RoHS)
CE Mark (EN62368-1)
CB certificate and Report available on request
Please check with technical sales for status of approvals
Designed and manufactured under the control of ISO9001 and ISO13485 (including risk management).
Mating Parts (Molex or Equivalent)
Conn
Housing
Pins
J1
39-01-2245
09-50-8051
45750-3112
08-52-0113
J2
Inputꢀandꢀoutputꢀconnectorsꢀ
areꢀnotꢀincludedꢀwithꢀtheꢀ
product.ꢀTheyꢀareꢀavailableꢀ
fromꢀTDK-Lambda
Top View
NV175 models without
cover or chassis
Part
Contents
No
94910 1ꢀoffꢀinputꢀconnectorꢀ
andꢀ3ꢀcrimps
94668 1ꢀoffꢀoutputꢀ
connectorꢀandꢀ20ꢀ
crimps
128.20
Side View
End View
Top View
NV175-F models
Top View
NV175-F models
Side View
NV175-C & NV175-U
models
Side View
NV175-F models
Bottom View
NV175-C & NV175-U
models
Bottom View
NV175-F models
Notes: 1. All customer fixings M3
NV175M_Datasheet_69924 - v18.0
2. Maximum thread penetration 4.5mm
3. Maximum torque 0.9Nm
4. All tolerances +/-0.5mm
3
NV-Power NV-175M
TDK-Lambda France SAS
TDK-Lambda Americas
Tel: +1 800-LAMBDA-4 or 1-800-526-2324
powersolutions@us.tdk-lambda.com
www.us.lambda.tdk.com
Tel: +33 1 60 12 71 65
france@fr.tdk-lambda.com
www.emea.lambda.tdk.com/fr
Italy Sales Office
Tel: +39 02 61 29 38 63
info.italia@it.tdk-lambda.com
www.emea.lambda.tdk.com/it
TDK Electronics do Brasil Ltda
Tel: +55 11 3289-9599
sales.br@tdk-electronics.tdk.com
www.tdk-electronics.tdk.com/en
Netherlands
info@nl.tdk-lambda.com
www.emea.lambda.tdk.com/nl
TDK-Lambda Germany GmbH
Tel: +49 7841 666 0
info.germany@de.tdk-lambda.com
TDK-Lambda Corporation
Tel: +81-3-6778-1113
www.jp.lambda.tdk.com
www.emea.lambda.tdk.com/de
TDK-Lambda (China) Electronics Co. Ltd.
Tel: +86 21 6485-0777
powersolutions@cn.tdk-lambda.com
www.lambda.tdk.com.cn
TDK-Lambda Singapore Pte Ltd.
Tel: +65 6251 7211
tls.mkt@sg.tdk-lambda.com
www.sg.lambda.tdk.com
Austria Sales Office
Tel: +43 2256 655 84
info@at.tdk-lambda.com
www.emea.lambda.tdk.com/at
TDK India Private Limited, Power Supply Division
Switzerland Sales Office
Tel: +41 44 850 53 53
info@ch.tdk-lambda.com
www.emea.lambda.tdk.com/ch
Tel: +91 80 4039-0660
mathew.philip@in.tdk-lambda.com
www.sg.lambda.tdk.com
Nordic Sales Office
Tel: +45 8853 8086
info@dk.tdk-lambda.com
www.emea.lambda.tdk.com/dk
TDK-Lambda UK Ltd.
Tel: +44 (0) 12 71 85 66 66
powersolutions@uk.tdk-lambda.com
www.emea.lambda.tdk.com/uk
TDK-Lambda Ltd.
Tel: +9 723 902 4333
info@tdk-lambda.co.il
www.emea.lambda.tdk.com/il
C.I.S.
Commercial Support:
Tel: +7 (495) 665 2627
Technical Support:
Tel: +7 (812) 658 0463
info@tdk-lambda.ru
www.emea.lambda.tdk.com/ru
Forꢀadditionalꢀinformation,ꢀpleaseꢀvisitꢀ
https://product.tdk.com/en/power
Errorsꢀandꢀomissionsꢀexcepted
NV175M_Datasheet_69924 - v18.0
NV-Power NV-175M
4
相关型号:
©2020 ICPDF网 联系我们和版权申明