QM8B [TDK]

AC-DC电源;
QM8B
型号: QM8B
厂家: TDK ELECTRONICS    TDK ELECTRONICS
描述:

AC-DC电源

文件: 总17页 (文件大小:2070K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
QM8 Series  
https://emea.lambda.tdk.com/qm  
https://product.tdk.com/en/power/qm  
1200W - 2000W  
Modular power supply  
Medical  
Industrial  
Test  
Broadcast  
Renewable  
Comms  
Features  
Benefits  
BF ready medical isolation (MOPP)  
Low speed, low audible noise fans  
Up to 18 outputs  
Eases design into systems (including BF)  
Enhanced patient / user experience  
Eliminates need for additional supplies  
Remote monitoring and control  
Low cost of ownership  
PMBus™ communication option  
7 year warranty  
Input  
QM8  
QM8B  
Output power -  
Output power -  
Frequency  
90-264Vac  
1200W  
180-264Vac  
1500W  
2000W  
47 - 63 Hz (440Hz with reduced PFC)  
Input fuses  
25A / 250Vac HBC Fast acting (not user accessible) in both Live and Neutral lines (single fusing optional)  
<45A at 25°C and 264Vac (cold start)  
Inrush current  
Leakage current  
Touch current  
Power factor  
See ‘How To Create A Product Description’ for details  
<100µA (with 4 or fewer modules). For other configurations, contact sales for details.  
> 0.95 (at 230Vac, 100% load)  
Isolation  
2 x MOPPs (3rd edition 60601)  
Reinforced  
Input to output / signals  
4kVac, 5.7kVdc type tested to 4kVac (equivalent to 5.7kVdc), production tested to 4.3kVdc.  
Input to earth  
Basic  
Basic  
1 x MOPP, 1.5kVac  
1 x MOPP, 1.5kVac  
200Vdc  
Output / signals to earth  
Output / signals to output / signals Basic  
How To Create A Product Description  
The extensive range of output modules and options make it possible to achieve almost any combination of Volts and Amps. You can create  
your own QM configuration online at https://config.emea.tdk-lambda.com/. This method checks your configuration and offers the optimum  
solution. Alternatively, you can do this manually by using the guide below.  
1.  
Calculate total output power to select the appropriate converter, then select required Cooling, Connection, Leakage Current and Controls/  
Signals from the following table:  
QM8  
F
S
D
L
T5H  
blank none  
E5L 5V / 250mA, Enable  
QM8 1500W high line  
QM8B 2000W high line  
Converter  
8 slots wide  
E5H 5V / 2A, 5V / 250mA, Enable  
E12H 12V / 1A, 5V / 250mA, Enable  
T5L 5V / 250mA, Inhibit  
T5H 5V / 2A, 5V / 250mA, Inhibit  
T12H 12V / 1A, 5V / 250mA, Inhibit  
Standby  
/ Signals  
F
R
C
Variable speed Forward air - standard  
Reverse air (contact sales for details)  
Customer air - no fan (contact sales for details)  
Cooling  
P5H  
5V / 2A, see PMBusapp note  
see specification page for details  
Input  
Connection  
S
Screw  
Leakage Current  
L
214µA  
77µA  
D
E
Dual AC fuses  
Single AC fuse in Live line  
(contact sales for details)  
(max at 264Vac, 63Hz)  
Input fuse  
Must also add the leakage current from  
modules and options  
R
2.  
3.  
Select Output Modules using the output voltages tables and the module specifications.  
Contact TDK-Lambda to validate configuration and issue a part number.  
QM8_Datasheet_260431 - v11.0  
1
QM8 Series  
Possible Outputs - see individual module data for full specifications  
Maximum Output  
Current  
Maximum Output  
Power  
Module name  
Slots used  
Output voltage range  
DM (ch2)  
1 of 2 outputs in single slot  
2.8V 3.8V  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10A  
37A  
33W  
122W  
50W  
SB  
1 slot  
3.3V  
4.25V  
5V  
3.63V  
5.75V  
5V  
DM (ch2)  
1 of 2 outputs in single slot  
10A  
SA  
1
15A  
75W  
SB  
1
5V  
5.5V  
30A  
150W  
300W  
400W  
550W  
244W  
300W  
600W  
120W  
120W  
100W  
150W  
300W  
600W  
780W  
1080W  
120W  
150W  
300W  
540W  
300W  
540W  
120W  
200W  
120W  
100W  
150W  
300W  
600W  
720W  
1200W  
120W  
200W  
300W  
540W  
600W  
600W  
1044W  
200W  
300W  
600W  
720W  
1200W  
200W  
600W  
1200W  
600W  
1200W  
SC  
2
5V  
5.5V  
60A  
ZD  
3
5V  
5.3V  
80A  
ZF  
4
5V  
5.3V  
110A  
37A  
YC  
2
6.6V  
10V  
7.26V  
11V  
YC  
2
30A  
YF  
4
10V  
11V  
60A  
DH (ch1 or ch2)  
1 of 2 outputs in single slot  
10.2V  
11.9V  
11.9V  
12V  
13.8V  
16.1V  
16.1V  
12V  
10A  
DM (ch1)  
1 of 2 outputs in single slot  
10A  
DM (ch2)  
1 of 2 outputs in single slot  
8.3A  
12.5A  
25A  
SA  
1
SB  
1
12V  
13.2V  
13.2V  
12.8V  
12.8V  
17.25V  
15V  
SC  
2
12V  
50A  
ZD  
3
12V  
65A  
ZF  
4
12V  
90A  
DH (ch1 or ch2)  
1 of 2 outputs in single slot  
12.75V  
15V  
8A  
SA  
1
10A  
SB  
1
15V  
16.5V  
16V  
20A  
ZC  
2
15V  
36A  
SB  
1
18V  
19.8V  
19.2V  
27.6V  
27.6V  
28.2V  
24.5V  
24V  
16.7A  
30A  
ZC  
2
18V  
DH (ch1 or ch2)  
1 of 2 outputs in single slot  
20.4V  
20.4V  
20.8V  
23.5V  
24V  
5A  
YB  
1
9.8A  
5A  
DM (ch1)  
1 of 2 outputs in single slot  
DM (ch2)  
1 of 2 outputs in single slot  
4.16A  
6.25A  
12.5A  
25A  
SA  
1
SB  
1
24V  
26.4V  
26.4V  
25.6V  
26.4V  
31V  
SC  
2
24V  
ZD  
3
24V  
30A  
YF  
4
24V  
50A  
DH (ch1 or ch2)  
1 of 2 outputs in single slot  
23.0V  
27.6V  
28V  
4.4A  
7.25A  
10.7A  
19.3A  
20A  
YB  
SB  
ZC  
YC  
SC  
ZF  
YB  
SB  
SC  
ZD  
YF  
YB  
YC  
YF  
YC  
YF  
1
1
2
2
2
4
1
1
2
3
4
1
2
4
2
4
34.5V  
30.8V  
30V  
28V  
30V  
33V  
36V  
39.6V  
38.4V  
55.2V  
52.8V  
52.8V  
51.2V  
52.8V  
62V  
16.7A  
29A  
36V  
40.8V  
48V  
4.9A  
6.25A  
12.5A  
15A  
48V  
48V  
48V  
25A  
55.2V  
56V  
3.62A  
10.7A  
16.7A  
6.25A  
12.5A  
61.6V  
79.2V  
105.6V  
105.6V  
72V  
96V  
96V  
Note. ‘Maximum Output Current’ and ‘Maximum  
Output Power’ above are the maximum available from  
the module. It is not possible to exceed the ‘Output  
Power’ of the unit given on the previous page.  
QM8_Datasheet_260431 - v11.0  
QM8 Series  
2
Output Specification  
Turn on time  
2s max  
at 90Vac (180Vac above 1200W) and 100% rated output power  
240Vac & above 50% rated power, configuration dependent  
Efficiency  
up to 91%  
20ms min  
16ms min  
at 1200W output power. QM8B - 1 cycle ride-through.  
at 2000W (QM8B) or 1500W (QM8) output power  
Hold up  
converter protection shuts down all outputs (except standby supplies) and fan, auto  
restarts. Shutdown temperature varies according to ambient, output power and input voltage.  
Over temperature protection  
Yes  
Environment  
Temperature  
-20°C to 70°C operational, -40°C to 70°C storage.  
50°C to 70°C derate total output power and each output current by 2.5% per °C  
Additionally, the 0.25A standby supply provided with the E5H, E12H, T5H and T12H options derates by 2.4% per °C from  
25°C to 50°C when the unit is inhibited (fan not running)  
Derating  
Low temperature startup  
Humidity  
-40°C  
5 - 95% RH non condensing  
±3 x 30g shocks in each plane, total 18 shocks (11ms (+/-0.5msec), half sine)  
Conforms to EN60068-2-27, EN60068-2-47, IEC68-2-27, IEC68-2-47, JIS C0041-1987.  
Conforms to MIL-STD-810G, Method 516.6, Pro IV  
Shock  
Single axis 10 - 500 Hz at 2g (sweep and endurance at resonance) in all 3 planes  
Conforms to EN60068-2-6, IEC68-2-6  
Vibration  
Conforms to MIL-STD-810G, Method 514.6, Pro I  
Altitude  
Pollution  
IP Rating  
5000 metres operational, 5000 metres storage/transportation  
Degree 2, Material group IIIb  
IPX0  
Emissions EN61000-6-3:2007, EN60601-1-2:2015 - see application notes for best installation practice  
(as per CISPR.11/32) Class B, FCC47 part 15 subpart B - ‘L’ leakage current variants  
(Units with ‘R’ type leakage current option achieve Class A)  
Radiated electric field  
EN55011, EN55032  
(as per CISPR.11/32) Class B, FCC47 part 15 subpart B - ‘L’ leakage current variants  
(Units with ‘R’ type leakage current option achieve Class A)  
Conducted emissions  
EN55011, EN55032  
Conducted harmonics  
Flicker  
EN61000-3-2  
EN61000-3-3  
Class A and Class C  
Compliant - dmax only  
Immunity EN61000-6-2:2005, EN60601-1-2:2015 - see application notes for best installation practice  
Criteria  
F type cooling only  
A
Electrostatic discharge  
EN61000-4-2  
Level 4  
Proximity fields, EN60601-1-2, Levels as defined in  
standard, Criteria A  
Electromagnetic field  
EN61000-4-3  
Level 3  
A
Tested at 5kHz and 100kHz  
Fast / burst transient  
EN61000-4-4  
EN61000-4-5  
EN61000-4-6  
EN61000-4-8  
Level 4  
Level 3  
Level 3  
Level 4  
Class 3  
compliant  
Level 3  
3kV  
A
A
A
A
A
Surge immunity  
Conducted RF immunity  
Power frequency magnetic field  
Criteria B for 5s and 1 cycle interruptions  
above 180Vac input  
Voltage dips, variations, interruptions EN61000-4-11  
Voltage sags  
Semi F-47  
EN61000-4-12  
ANSI C62.41  
EN61000-4-14  
A
A
A
Ring wave  
30Ω Neutral Grounding (0.5µs-100kHz Ring Wave)  
See EMC report for full details.  
Voltage fluctuations  
Class 3  
Approvals / Accreditations  
IEC/EN 62368-1, UL62368-1 / CSA 22.2 No 62368-1  
File E135494  
File E135494  
IEC/EN 60950-1, UL60950-1 / CSA 22.2 No 60950-1  
IEC/EN 60601-1, UL/CSA 60601-1, ANSI/AAMI ES60601-1, CAN/CSA-C22.2 No 60601-1  
IEC/EN 61010-1  
File E349607  
Designed to meet  
Low Voltage Directive (LVD), electromagnetic compatibility (EMC) and Restriction  
of Hazardous Substances (RoHS)  
CE Mark (EN62368-1)  
CB certificate and Report available on request  
Designed and manufactured under the control of ISO9001 and ISO13485 (including risk management).  
QM8_Datasheet_260431 - v11.0  
3
QM8 Series  
Standby / Signals  
Maximum power per channel  
See table below  
Available signals (Exx or Txx type)  
PSU inhibit (Txx type) or enable (Exx type), AC Good  
PMBus™ control of power supply  
fan speed and fail warning  
Serial number, date of manufacture, run time, on/off power cycles  
For further details, see the product range application notes, PMBus™ section  
Available signals (Pxx type)  
xxL = 13.1µA, xxH = 15µA  
Must also add the leakage current from modules and selected filter option.  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Available Output Voltages (at PSU signal connector)  
Standby 1  
Standby 2  
Option  
type  
PSU on/off  
Max  
Max  
Txx or Exx option  
V
Power  
V
Power  
Current  
Current  
Pin  
1
2
3
4
5
6
7
8
5L  
5H or 12H  
Standby 2 +  
Standby 2 -  
1
9
2
Do not connect  
E5L  
E5H  
E12H  
T5L  
5V  
5V  
5V  
5V  
5V  
5V  
250mA 1.25W  
not available  
Enable  
Enable  
Enable  
Inhibit  
Inhibit  
Inhibit  
Standby 1 + Standby 1 +  
Standby 1 - Standby 1 -  
PSU on/off+ PSU on/off+  
PSU on/off- PSU on/off-  
AC fail Out AC fail Out  
AC fail Rtn AC fail Rtn  
250mA 1.25W 5V  
250mA 1.25W 12V  
250mA 1.25W  
2A  
1A  
10W  
12W  
10  
not available  
9
10  
T5H  
250mA 1.25W 5V  
250mA 1.25W 12V  
2A  
1A  
10W  
12W  
Do not connect  
T12H  
see PMBus™  
application note  
P5H  
5V  
2A  
1A  
10W  
12W  
not available  
not available  
Pin P5H or P12H  
option  
see PMBus™  
application note  
1
2
Standby +  
Standby -  
P12H 12V  
1
2
3
4
Do not connect  
Fan fail  
5
6
7
8
9
10  
Address 0  
Address 1  
Address 2  
Address 3  
SCL - Clock  
SDA - Data  
11  
12  
11 Control line in  
12 GND  
Output Specification  
Standby 1  
Standby 2  
Rise time  
<30ms  
<1%  
<3%  
No  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
pk-pk, using 20MHz bandwidth  
Ripple and noise  
Voltage setting accuracy  
Remote sense  
of set voltage  
Minimum load  
0W  
on any output  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
0.02%  
<1.5%  
<1%  
for 0-100% load change  
Line regulation  
<0.1%  
<0.4%  
<5%  
for 90-264Vac input change  
for 100% load change on any output  
of set voltage for 25-50% load change  
for recovery to 1% or 100mV of set voltage  
Latching, output shuts down, cycle ac to reset  
Auto recovers  
Cross regulation  
Transient deviation  
Recovery  
1ms  
Over voltage protection  
Over current protection  
Short circuit protection  
Yes  
Constant Current  
Constant Current  
Auto recovers  
QM8_Datasheet_260431 - v11.0  
QM8 Series  
4
DH Module - single slot width, 2 output channels  
Maximum module power  
200W  
Total power from channel 1 + channel 2  
Maximum power per channel see table below  
Available signals  
Module good, module inhibit  
20.5µA  
Must also add the leakage current from other modules, any standby supply and selected filter option.  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Pin  
1
2
3
4
5
6
7
8
Connection  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Do not connect  
CH1 +  
Channel 1  
Channel 2  
Module good collector  
Module good emitter  
Module inhibit anode  
Module inhibit cathode  
CH1 0V  
9
Adjustment  
Range (Volts)  
Output Max C  
Adjustment  
Range (Volts)  
Output Max C  
power  
Current  
10A  
Current  
power  
load  
load  
10  
2
10.2  
-
13.8  
10A  
8A  
120W 1000µF/A  
120W 1000µF/A  
120W 750µF/A  
120W 1000µF/A  
120W 750µF/A  
120W 750µF/A  
120W 750µF/A  
V ADJ  
Do not connect  
9
10  
12.75 - 17.25  
10.2a  
-
13.8  
120W 1000µF/A  
1
20.4  
-
27.6  
5A  
CH2 +  
12.75 - 17.25  
8A  
12.75b - 17.25  
8A  
120W 1000µF/A  
20.4  
-
-
-
27.6  
27.6  
31  
5A  
CH2 0V  
20.4c  
23.0d  
-
-
27.6  
31  
5A  
120W 750µF/A 20.4  
120W 750µF/A 23.0  
5A  
4.4A  
4.4A  
Channel 1 and channel 2 of DH are both adjusted by single potentiometer. The V2 set = V2max x V1set / V1max  
a, b, c, d - for output voltages below 10.8V(a), 13.5V(b), 21.6V(c) or 24.4V(d), a Minimum load of 1W must be applied to channel 1  
Output Specification  
Rise time  
<50ms  
zero  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
at full load with resistive load.  
Turn on overshoot  
Ripple and noise  
0°C - 70°C  
pk-pk, using 20MHz bandwidth  
1.5%  
2.25%  
<1%  
No  
-20°C - 0°C  
Voltage setting accuracy  
Remote sense  
of set voltage (3% for channel 2)  
Except for notes a, b, c and d above.  
Minimum load  
0W  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
Line regulation  
Cross regulation  
Transient deviation  
Recovery  
0.03%  
<6%  
<0.1%  
3%  
for 5-100% load change  
for 90-264Vac input change  
for 5-100% load change on any output  
of set voltage for 50% load change (above 25% load)  
for recovery to 1% or 100mV of set voltage  
Latching, module shuts down (both outputs), cycle ac to restart.  
<4%  
3ms  
Over voltage protection  
Yes  
Protects channel 1 and channel 2, shuts down both outputs, auto-recovers when fault  
clears.  
Module current protection  
Hiccup  
Short circuit protection  
Yes  
Yes  
Indefinitely protected, see application notes for details  
Module protection shuts down both outputs, cycle ac to restart.  
Over temperature protection  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required channel 1 and channel 2 voltages (from the table above)  
For example, if you need 12V / 10A and 24V / 3A, you would choose 12/24DHS as your required module.  
V1  
/
V2  
DH  
S
Output  
connection  
S
Screw terminal  
Channel 1 required voltage  
Channel 2 required voltage  
Module type  
QM8_Datasheet_260431 - v11.0  
5
QM8 Series  
DM Module - single slot width, 1 or 2 output channels  
Maximum module power  
200W  
Total power from channel 1 + channel 2  
Maximum power per channel see table below  
Available signals  
Remote sense (channels 1 & 2), channel 1 good, channel 2 good, Channel 2 inhibit, module inhibit  
22.3µA  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Must also add the leakage current from other modules, and standby supply and selected filter option.  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Pin  
1
2
3
4
5
6
7
8
Connection  
Ch2 sense +  
Ch2 sense -  
Ch2 inhibit anode  
Ch2 inhibit cathode  
Ch2 good collector  
Ch2 good emitter  
Ch1 good collector  
Ch1 good emitter  
Module inhibit anode  
Channel 1  
Channel 2  
CH1 +  
Adjustment  
Range (Volts)  
Output Max C  
Adjustment  
Range (Volts)  
Output Max C  
power  
Current  
Current  
power  
load  
load  
CH1 0V  
11  
2.8  
-
-
3.8  
10A  
10A  
33W 500µF/A  
50W 500µF/A  
12  
2
Channel 1 unused  
4.25  
5.75  
CH1  
V ADJ  
9
11.9  
20.8  
-
-
16.1  
28.2  
10A  
5A  
120W 500µF/A  
120W 500µF/A  
Channel 2 unused  
10 Module inhibit cathode  
11  
12  
CH2  
V ADJ  
Ch1 sense +  
Ch1 sense -  
1
2.8  
-
-
-
-
3.8  
10A  
10A  
8.3A  
33W 500µF/A  
CH2 +  
4.25  
11.9  
23.5  
5.75  
16.1  
50W 500µF/A  
100W 500µF/A  
11.9  
-
16.1  
10A  
120W 500µF/A  
CH2 0V  
24.5 4.16A 100W 500µF/A  
2.8  
-
-
-
3.8  
10A  
10A  
33W 500µF/A  
50W 500µF/A  
20.8  
21.6  
-
-
28.2  
28.2  
5A  
5A  
120W 500µF/A  
4.25  
5.75  
120W 500µF/A 23.5  
24.5 4.16A 100W 500µF/A  
Output Specification  
Rise time  
Ch1  
Ch2  
<20ms  
<50ms  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
Load type dependent, no overshoot at full load with resistive load  
Turn on overshoot  
<5%  
<5%  
Ripple and noise  
0°C - 70°C  
pk-pk, using 20MHz bandwidth  
1.5%  
2.25%  
<1%  
75mV  
75mV  
<1%  
1.5% for ch2 outputs >10V, 2% for outputs 11-17V  
2% for ch2 outputs >10V, 2.5% for outputs 11-17V  
of set voltage  
-20°C - 0°C  
Voltage setting accuracy  
Remote sense  
Yes  
0W  
0.5V (voltage at the output terminals must be within the specified adjustment range)  
Refer to application note for details.  
Minimum load  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
Line regulation  
0.02%  
max of 50mV or <1% of set voltage  
for 0-100% load change  
<0.1%  
1.5%  
for 90-264Vac input change  
Cross regulation  
for 100% load change on any output  
of set voltage for 50% load change (above 25% load).  
250mV for outputs below 5V  
Transient deviation  
<4%  
<5%  
Recovery  
3ms  
7ms  
for recovery to 1% or 100mV of set voltage  
Over voltage protection  
Over current protection  
Short circuit protection  
Yes  
Latching, module shuts down (both outputs), cycle ac to restart.  
Ch1 protection shuts down both outputs.  
Hiccup  
Hiccup  
Constant current  
Constant current  
Ch1 protection shuts down both outputs. Refer to application note for details.  
Ch1 protection shuts down both outputs, cycle ac to restart. Ch2  
Over temperature  
protection  
Yes  
Yes  
protection shuts down ch2 only, auto recovers when fault clears.  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required channel 1 and channel 2 voltages (from the table above)  
For example, if you need 12V / 10A and 3.3V / 10A, you would choose 12/3.3DMS as your required module.  
V1  
/
V2  
DM  
S
Output  
connection  
Channel 1 required voltage  
S
Screw terminal  
(enter 12 if not needed)  
Channel 2 required voltage  
Module type  
(enter 5 if not needed)  
QM8_Datasheet_260431 - v11.0  
QM8 Series  
6
SA Module - single slot width, 1 output channel  
Maximum power per channel see table below  
Available signals  
Remote sense (5V module only)  
14.6µA  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Must also add the leakage current from other modules, any standby supply and selected filter option.  
Pin  
1
2
3
4
5
6
7
8
Connection  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Maximum capacitive  
CH1 +  
Output voltage  
Current  
Output power  
Do not connect  
load  
5V  
15A  
12.5A  
10A  
75W  
150W  
150W  
150W  
1000µF/A  
1000µF/A  
1000µF/A  
750µF/A  
Remote sense +  
Remote sense -  
Do not connect  
12V  
15V  
24V  
CH1 0V  
9
10  
10  
2
9
6.25A  
1
Output Specification  
Rise time  
<75ms  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
Load type dependent, no overshoot at full load with resistive load  
6% for 12V output  
Turn on overshoot  
<5% or 250mV  
pk-pk, using 20MHz bandwidth  
Ripple and noise  
0°C - 70°C, >5% load  
-20°C - 0°C, >5% load  
≤5% load  
1%  
2%  
2%  
Voltage setting accuracy  
Remote sense  
<1%  
of set voltage  
Yes  
On 5V module only  
on any output  
Minimum load  
No  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
<0.02%  
<1%  
for 0-100% load change  
Line regulation  
<0.2%  
<0.2%  
<5% or 250mV  
5ms  
for 90-264Vac input change  
Cross regulation  
for 100% load change on any output  
Transient deviation  
Recovery  
of set voltage for 50% load change (above 25% load)  
for recovery to 1% or 100mV of set voltage  
Latching, module shuts down, cycle ac to restart  
Auto recovers after removal of load  
Over voltage protection  
Over current protection  
Short circuit protection  
Yes  
Hiccup  
Yes  
Indefinitely protected, see application notes for details  
Module protection shuts down output, cycle ac to restart.  
Over temperature protection  
Yes  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required output voltage (from the table above)  
For example, if you need 15V / 10A, you would choose 15SASL as your required module.  
V1  
SA  
S
L
Remote sense (5V  
SA module only)  
No remote sense  
(all other variants)  
R
L
Option Code  
Required output voltage  
Module type  
Output  
connection  
S
Screw terminal  
QM8_Datasheet_260431 - v11.0  
7
QM8 Series  
SB Module - single slot width, 1 output channel  
Maximum power per channel see table below  
Available signals  
Remote sense, module good, module inhibit  
14.6µA  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Must also add the leakage current from other modules, any standby supply and selected filter option.  
Pin  
1
2
3
4
5
6
7
8
Connection  
Do not connect  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Max Capaci-  
tive Load  
CH1 +  
Adjustment Range (Volts)  
Current  
Output power  
Module good collector  
Module good emitter  
Module inhibit anode  
Module inhibit cathode  
Remote sense +  
3.3  
5
-
-
-
-
-
3.63  
5.5  
37A  
30A  
122W  
150W  
300W  
300W  
300W  
300W  
1000µF/A  
1000µF/A  
1000µF/A  
1000µF/A  
1000µF/A  
750µF/A  
CH1 0v  
Remote sense -  
12  
15  
18  
24  
13.2  
16.5  
19.8  
26.4  
25A  
9
10  
Do not connect  
20A  
10  
2
9
1
16.7A  
12.5A  
V ADJ  
-
-
-
28  
48  
30.8  
52.8  
10.7A  
6.25A  
300W  
300W  
500µF/A  
250µF/A  
Output Specification  
Rise time  
<75ms  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
Load type dependent  
Turn on overshoot  
<5%  
Ripple and noise  
max of  
1% or 50mV  
2% or 100mV  
4%  
pk-pk, using 20MHz bandwidth  
0°C - 70°C, >5% load  
-20°C - 0°C, >5% load  
≤5% load  
Voltage setting accuracy  
<1%  
of set voltage  
Remote sense  
Yes  
0W  
0.5V (voltage at the output terminals must remain within the adjustment range specified above)  
Minimum load  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
Line regulation  
0.016%  
<1%  
for 0-100% load change  
<0.1%  
0.1%  
for 90-264Vac input change  
Cross regulation  
(5mV for outputs below 5V) for 100% load change on any output  
of set voltage for 50% load change (above 25% load)  
250mV for outputs below 5V  
Transient deviation  
<5%  
Recovery  
1ms  
Yes  
for recovery to 1% or 100mV of set voltage  
Latching, module shuts down, cycle ac to restart.  
Auto recovers after removal of load  
Over voltage protection  
Over current protection  
Short circuit protection  
Hiccup  
Yes  
Indefinitely protected, see application notes for details  
Module protection shuts down output, cycle ac to restart.  
Over temperature protection  
Yes  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required output voltage (from the table above)  
For example, if you need 12.2V / 24.5A, you would choose 12.2SBS as your required module.  
V1  
SB  
S
Output  
connection  
S
Screw terminal  
Required output voltage  
Module type  
QM8_Datasheet_260431 - v11.0  
QM8 Series  
8
SC Module - two slots width, 1 output channel  
Maximum power per channel see table below  
Available signals  
Remote sense, module good, module inhibit  
13.8µA  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Must also add the leakage current from other modules, any standby supply and selected filter option.  
Pin  
1
2
3
4
5
6
7
8
Connection  
Do not connect  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Maximum ca-  
pacitive load  
Module good collector  
Module good emitter  
Module inhibit anode  
Module inhibit cathode  
Remote sense +  
Adjustment Range (Volts)  
Current  
Output power  
CH1 +  
5
-
-
-
-
-
5.5  
60A  
50A  
300W  
600W  
600W  
600W  
600W  
1000µF/A  
1000µF/A  
750µF/A  
300µF/A  
250µF/A  
12  
24  
36  
48  
13.2  
26.4  
39.6  
52.8  
Remote sense -  
Do not connect  
9
10  
25A  
CH1 0v  
16.7A  
12.5A  
10  
2
9
V ADJ  
1
Output Specification  
Rise time  
<75ms  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
Turn on overshoot  
<5%  
Load type dependent  
Ripple and noise  
Vout<10V  
Vout>10V pk-pk, using 20MHz bandwidth  
0°C - 70°C, >5% load  
-20°C - 0°C, >5% load  
≤5% load  
1.5%  
3%  
1%  
2%  
4%  
4%  
Voltage setting accuracy  
<1%  
Yes  
of set voltage  
Remote sense  
0.5V (voltage at the output terminals must remain within the adjustment range specified above)  
Minimum load  
0W  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
0.016%  
<1%  
<0.1%  
0.1%  
<5%  
1ms  
for 0-100% load change  
Line regulation  
for 90-264Vac input change  
Cross regulation  
Transient deviation  
Recovery  
for 100% load change on any output  
of set voltage for 50% load change (above 25% load)  
for recovery to 1% or 100mV of set voltage  
Latching, module shuts down, cycle ac to restart.  
Auto recovers after removal of load  
Indefinitely protected, see application notes for details  
Over voltage protection  
Over current protection  
Short circuit protection  
Yes  
Hiccup  
Yes  
Module protection shuts down output, cycle ac to restart.  
Over temperature protection  
Yes  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required output voltage (from the table above)  
For example, if you need 12.2V / 49A, you would choose 12.2SCS as your required module.  
V1  
SC  
S
Output  
connection  
S
Screw terminal  
Required output voltage  
Module type  
QM8_Datasheet_260431 - v11.0  
9
QM8 Series  
YB Module - single slot width, 1 output channel  
Maximum power per channel see table below  
Available signals  
Module good, module inhibit  
20.5µA  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Must also add the leakage current from other modules, any standby supply and selected filter option.  
Pin  
1
2
3
4
5
6
7
8
Connection  
Do not connect  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Ch1 +  
Maximum ca-  
pacitive load  
Module good collector  
Module good emitter  
Module inhibit anode  
Module inhibit cathode  
Do not connect  
Adjustment Range (Volts)  
Current  
Output power  
20.4  
27.6  
40.8  
55.2  
-
-
-
-
27.6  
34.5  
55.2  
62  
9.8A  
7.25A  
4.9A  
200W  
200W  
200W  
200W  
500µF/A  
500µF/A  
375µF/A  
375µF/A  
9
10  
3.62A  
Ch1 0V  
Output Specification  
Rise time  
<75ms  
zero  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
Turn on overshoot  
Ripple and noise  
0°C - 70°C  
at full load with resistive load. Load type dependent, <7% overshoot with capacitive load  
pk-pk, using 20MHz bandwidth  
1.5%  
2.25%  
<2%  
No  
-20°C - 0°C  
Voltage setting accuracy  
Remote sense  
of set voltage  
Minimum load  
0W  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
0.03%  
<6%  
<0.1%  
<1%  
<8%  
5ms  
for 5-100% load change  
Line regulation  
for 90-264Vac input change  
Cross regulation  
Transient deviation  
Recovery  
for 100% load change on any output  
of set voltage for 50% load change (above 25% load)  
for recovery to 1% or 100mV of set voltage  
Latching, module shuts down, cycle ac to restart.  
Auto recovers  
Over voltage protection  
Over current protection  
Short circuit protection  
Yes  
Hiccup  
Yes  
Indefinitely protected, see application notes for details  
Module protection shuts down output, cycle ac to restart.  
Over temperature protection  
Yes  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required output voltage (from the table above)  
For example, if you need 41V / 4A, you would choose 41YBS as your required module.  
V1  
YB  
S
Output  
connection  
S
Screw terminal  
Required output voltage  
Module type  
QM8_Datasheet_260431 - v11.0  
QM8 Series  
10  
YC Module - two slots width, 1 output channel  
Maximum power per channel see table below  
Available signals  
Module good, module inhibit  
29.2µA  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Must also add the leakage current from other modules, any standby supply and selected filter option.  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Max Capaci-  
tive Load  
Adjustment Range (Volts)  
Current  
Output Power  
See application  
notes for signal  
connection details  
6.6  
10  
30  
56  
96  
-
-
-
-
-
7.26  
11  
37A  
30A  
244W  
300W  
600W  
600W  
600W  
1000µF/A  
1000µF/A  
1000µF/A  
350µF/A  
125µF/A  
33  
20A  
61.6  
105.6V  
10.7A  
6.25A  
Output Specification  
Rise time  
<75ms  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
Load type dependent  
Turn on overshoot  
<5%  
Ripple and noise  
pk-pk, using 20MHz bandwidth  
0°C - 70°C, >5% load  
-20°C - 0°C, >5% load  
≤5% load  
1%  
2%  
4%  
Voltage setting accuracy  
<1%  
of set voltage  
Remote sense  
Yes  
0W  
0.5V (voltage at the output terminals must remain within the adjustment range specified above)  
Minimum load  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
0.016%  
<1%  
for 0-100% load change  
Line regulation  
<0.1%  
0.1%  
<5%  
for 90-264Vac input change  
Cross regulation  
Transient deviation  
Recovery  
(10mV for outputs below 10V) for 100% load change on any output  
of set voltage for 50% load change (above 25% load)  
for recovery to 1% or 100mV of set voltage  
Latching, module shuts down, cycle ac to restart.  
Auto recovers  
1ms  
Over voltage protection  
Over current protection  
Short circuit protection  
Yes  
Hiccup  
Yes  
Indefinitely protected, see application notes for details  
Module protection shuts down output, cycle ac to restart.  
Over temperature protection  
Yes  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required output voltage (from the table above)  
For example, if you need 58V / 10A, you would choose 58YCS as your required module.  
V1  
YC  
S
Output  
connection  
S
Screw terminal  
Required output voltage  
Module type  
QM8_Datasheet_260431 - v11.0  
11  
QM8 Series  
YF Module - four slots width, 1 output channel  
Maximum power per channel see table below  
Available signals  
Module good, module inhibit  
27.6µA  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Must also add the leakage current from other modules, any standby supply and selected filter option.  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Max Capaci-  
tive Load  
Adjustment Range (Volts)  
Current  
Output power  
10  
24  
48  
72  
96  
-
-
-
-
-
11  
26.4  
60A  
50A  
600W  
1200W  
1200W  
1200W  
1200W  
1000µF/A  
650µF/A  
500µF/A  
150µF/A  
125µF/A  
Ch1 0V  
52.8  
25A  
79.2  
16.7A  
12.5A  
105.6V  
See application  
notes for signal  
connection details  
Output Specification  
Rise time  
<75ms  
<5%  
Vout<20V  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
Turn on overshoot  
Load type dependent  
Ripple and noise  
Vout>20V pk-pk, using 20MHz bandwidth  
0°C - 70°C, >5% load  
-20°C - 0°C, >5% load  
≤5% load  
1.5%  
3%  
1%  
2%  
4%  
4%  
Voltage setting accuracy  
<1%  
Yes  
of set voltage  
Remote sense  
0.5V (voltage at the output terminals must remain within the adjustment range specified above)  
Minimum load  
0W  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
0.016%  
<1%  
<0.1%  
0.1%  
<5%  
1ms  
for 0-100% load change  
Line regulation  
for 90-264Vac input change  
Cross regulation  
Transient deviation  
Recovery  
for 100% load change on any output  
of set voltage for 50% load change (above 25% load)  
for recovery to 1% or 100mV of set voltage  
Latching, module shuts down, cycle ac to restart.  
Auto recovers  
Over voltage protection  
Over current protection  
Short circuit protection  
Yes  
Hiccup  
Yes  
Indefinitely protected, see application notes for details  
Module protection shuts down output, cycle ac to restart.  
Over temperature protection  
Yes  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required output voltage (from the table above)  
For example, if you need 48V / 25A, you would choose 48YFS as your required module.  
V1  
YF  
S
Output  
connection  
S
Screw terminal  
Required output voltage  
Module type  
QM8_Datasheet_260431 - v11.0  
QM8 Series  
12  
ZC Module - two slots width, 1 output channel  
Maximum power per channel see table below  
Available signals  
Module good, module inhibit  
29.2µA  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Must also add the leakage current from other modules, any standby supply and selected filter option.  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Maximum ca-  
pacitive load  
Adjustment Range (Volts)  
Current  
Output Power  
15  
18  
28  
-
-
-
16.0  
19.2  
30  
36A  
30A  
540W  
540W  
540W  
1000µF/A  
1000µF/A  
500µF/A  
19.3A  
See application  
notes for signal  
connection details  
Output Specification  
Rise time  
<75ms  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
Load type dependent  
Turn on overshoot  
<5%  
Ripple and noise  
pk-pk, using 20MHz bandwidth  
0°C - 70°C, >5% load  
-20°C - 0°C, >5% load  
≤5% load  
1%  
2%  
4%  
Voltage setting accuracy  
<1%  
of set voltage  
Remote sense  
Yes  
0W  
0.5V (voltage at the output terminals must remain within the adjustment range specified above)  
Minimum load  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
0.016%  
<3.5%  
<0.1%  
0.1%  
<5%  
for 1-100% load change  
Line regulation  
for 90-264Vac input change  
Cross regulation  
Transient deviation  
Recovery  
for 100% load change on any output  
of set voltage for 50% load change (above 25% load)  
for recovery to 1% or 100mV of set voltage  
Latching, module shuts down, cycle ac to restart.  
Auto recovers after removal of load  
Indefinitely protected, see application notes for details  
30ms  
Yes  
Over voltage protection  
Over current protection  
Short circuit protection  
Hiccup  
Yes  
Module protection shuts down output, cycle ac to restart.  
Over temperature protection  
Yes  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required output voltage (from the table above)  
For example, if you need 15V / 36A, you would choose 15ZCS as your required module.  
V1  
ZC  
S
Output  
connection  
S
Screw terminal  
Required output voltage  
Module type  
QM8_Datasheet_260431 - v11.0  
13  
QM8 Series  
ZD Module - three slots width, 1 output channel  
Maximum power per channel see table below  
Available signals  
Module good, module inhibit  
28.3µA  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Must also add the leakage current from other modules, any standby supply and selected filter option.  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Adjustment Range (Volts) at PSU  
Maximum ca-  
pacitive load  
Current  
Output power  
output terminal  
5
-
-
-
-
5.3  
80A  
65A  
30A  
15A  
400W  
780W  
720W  
720W  
1000µF/A  
1000µF/A  
750µF/A  
250µF/A  
12  
24  
48  
12.8  
25.6  
51.2  
See application  
notes for signal  
connection details  
Output Specification  
Rise time  
<75ms  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
Turn on overshoot  
<5%  
Load type dependent  
Ripple and noise  
Vout<10V  
Vout>10V pk-pk, using 20MHz bandwidth  
0°C - 70°C, >5% load  
-20°C - 0°C, >5% load  
≤5% load  
1.5%  
3%  
1%  
2%  
4%  
4%  
Voltage setting accuracy  
<1%  
Yes  
of set voltage  
Remote sense  
0.5V (voltage at the output terminals must remain within the adjustment range specified above)  
Minimum load  
0W  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
0.016%  
<3.5%  
<0.1%  
0.1%  
<5%  
for 1-100% load change (<2.5% for 5-5.3V output)  
for 90-264Vac input change  
Line regulation  
Cross regulation  
Transient deviation  
Recovery  
for 100% load change on any output  
of set voltage for 50% load change (above 25% load)  
for recovery to 1% or 100mV of set voltage  
Latching, module shuts down, cycle ac to restart.  
Auto recovers after removal of load  
30ms  
Yes  
Over voltage protection  
Over current protection  
Short circuit protection  
Hiccup  
Yes  
Indefinitely protected, see application notes for details  
Module protection shuts down output, cycle ac to restart.  
Over temperature protection  
Yes  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required output voltage (from the table above)  
For example, if you need 48V / 16A, you would choose 48ZDS as your required module.  
V1  
ZD  
S
Output  
connection  
S
Screw terminal  
Required output voltage  
Module type  
QM8_Datasheet_260431 - v11.0  
QM8 Series  
14  
ZF Module - four slots width, 1 output channel  
Maximum power per channel see table below  
Available signals  
Module good, module inhibit  
27.6µA  
Additional Leakage Current  
(max at 264Vac, 63Hz)  
Must also add the leakage current from other modules, any standby supply and selected filter option.  
AVAILABLE OUTPUT VOLTAGES (at PSU output terminals)  
Adjustment Range  
Maximum ca-  
pacitive load  
Current  
Output power  
Ch1 +  
(Volts)  
5
-
-
-
5.3  
110A  
90A  
29A  
550W  
1080W  
1044W  
1000µF/A  
12  
36  
12.8  
38.4  
1000µF/A  
300µF/A  
Ch1 0V  
See application  
notes for signal  
connection details  
Output Specification  
Rise time  
<75ms  
(with resistive load) to 90% of voltage, monotonic rise above 10%  
Turn on overshoot  
<5%  
Load type dependent  
Ripple and noise  
Vout<10V  
Vout>10V pk-pk, using 20MHz bandwidth  
0°C - 70°C, >5% load  
-20°C - 0°C, >5% load  
≤5% load  
1.5%  
3%  
1%  
2%  
4%  
4%  
Voltage setting accuracy  
<1%  
Yes  
of set voltage  
Remote sense  
0.5V (voltage at the output terminals must remain within the adjustment range specified above)  
Minimum load  
0W  
of rated voltage per °C  
Temperature coefficient  
Load regulation  
0.016%  
<3.5%  
<0.1%  
0.1%  
<5%  
for 1-100% load change (<2.5% for 5-5.3V output)  
for 90-264Vac input change  
Line regulation  
Cross regulation  
Transient deviation  
Recovery  
for 100% load change on any output  
of set voltage for 50% load change (above 25% load)  
for recovery to 1% or 100mV of set voltage  
Latching, module shuts down, cycle ac to restart.  
Auto recovers after removal of load  
30ms  
Yes  
Over voltage protection  
Over current protection  
Short circuit protection  
Hiccup  
Yes  
Indefinitely protected, see application notes for details  
Module protection shuts down output, cycle ac to restart.  
Over temperature protection  
Yes  
Shutdown temperature varies according to ambient, output power and input voltage.  
How To Create A Product Description  
Choose your required output voltage (from the table above)  
For example, if you need 12V / 90A, you would choose 12ZFS as your required module.  
V1  
ZF  
S
Output  
connection  
S
Screw terminal  
Required output voltage  
Module type  
QM8_Datasheet_260431 - v11.0  
15  
QM8 Series  
270.00 MAX (INCLUDING ENDCAP)  
175.00  
21.20  
200.00 MAX  
21.30  
L N E  
TERMINAL COVER REMOVED  
205.00  
21.20  
PRESS BOTH TABS THEN  
LEVER FORWARD TO  
REMOVE.  
REVERSE TO RE-FIT.  
Standard  
airflow  
Reverse  
airflow  
ACCESS TO SCREW  
TERMINALS BY  
REMOVING COVER  
Units with factory fitted fan (‘F’ or ‘R’ type cooling)  
268.00 MAX  
175.00  
200.00 MAX  
21.20  
21.30  
L N E  
205.00  
21.20  
SCREW TERMINALS  
Units with Customer Air (‘C’ type cooling)  
Customer fixings. 8 holes M4. Max thread penetration:- 4.5mm  
QM8_Datasheet_260431 - v11.0  
QM8 Series  
16  
TDK-Lambda France SAS  
TDK-Lambda Americas  
Tel: +1 800-LAMBDA-4 or 1-800-526-2324  
powersolutions@us.tdk-lambda.com  
www.us.lambda.tdk.com  
Tel: +33 1 60 12 71 65  
france@fr.tdk-lambda.com  
www.emea.lambda.tdk.com/fr  
Italy Sales Office  
Tel: +39 02 61 29 38 63  
info.italia@it.tdk-lambda.com  
www.emea.lambda.tdk.com/it  
TDK Electronics do Brasil Ltda  
Tel: +55 11 3289-9599  
sales.br@tdk-electronics.tdk.com  
www.tdk-electronics.tdk.com/en  
Netherlands  
info@nl.tdk-lambda.com  
www.emea.lambda.tdk.com/nl  
TDK-Lambda Germany GmbH  
Tel: +49 7841 666 0  
info.germany@de.tdk-lambda.com  
TDK-Lambda Corporation  
Tel: +81-3-6778-1113  
www.jp.lambda.tdk.com  
www.emea.lambda.tdk.com/de  
TDK-Lambda (China) Electronics Co. Ltd.  
Tel: +86 21 6485-0777  
powersolutions@cn.tdk-lambda.com  
www.lambda.tdk.com.cn  
TDK-Lambda Singapore Pte Ltd.  
Tel: +65 6251 7211  
tls.mkt@sg.tdk-lambda.com  
www.sg.lambda.tdk.com  
Austria Sales Office  
Tel: +43 2256 655 84  
info@at.tdk-lambda.com  
www.emea.lambda.tdk.com/at  
TDK India Private Limited, Power Supply Division  
Switzerland Sales Office  
Tel: +41 44 850 53 53  
info@ch.tdk-lambda.com  
www.emea.lambda.tdk.com/ch  
Tel: +91 80 4039-0660  
mathew.philip@in.tdk-lambda.com  
www.sg.lambda.tdk.com  
Nordic Sales Office  
Tel: +45 8853 8086  
info@dk.tdk-lambda.com  
www.emea.lambda.tdk.com/dk  
TDK-Lambda UK Ltd.  
Tel: +44 (0) 12 71 85 66 66  
powersolutions@uk.tdk-lambda.com  
www.emea.lambda.tdk.com/uk  
TDK-Lambda Ltd.  
Tel: +9 723 902 4333  
info@tdk-lambda.co.il  
www.emea.lambda.tdk.com/il  
C.I.S.  
Commercial Support:  
Tel: +7 (495) 665 2627  
Technical Support:  
Tel: +7 (812) 658 0463  
info@tdk-lambda.ru  
www.emea.lambda.tdk.com/ru  
For additional information, please visit  
https://product.tdk.com/en/power  
Errors and omissions excepted  
QM8_Datasheet_260431 - v11.0  
17  
QM8 Series  

相关型号:

QMA6351A2-003-3GT50G-50

RF QMA Connector, Female, Panel Mount
AMPHENOL

QMB-032-00ENN-3BA

CIRCUIT BREAKER
QUALTEK

QMB-032-11C3N-3BA

CIRCUIT BREAKER
QUALTEK

QMB-052-00ENN-3BA

CIRCUIT BREAKER
QUALTEK

QMB-052-11C3N-3BA

CIRCUIT BREAKER
QUALTEK

QMB-072-00ENN-3BA

CIRCUIT BREAKER
QUALTEK

QMB-072-11C3N-3BA

CIRCUIT BREAKER
QUALTEK

QMB-102-00ENN-3BA

CIRCUIT BREAKER
QUALTEK

QMB-102-11C3N-3BA

CIRCUIT BREAKER
QUALTEK

QMB-122-00ENN-3BA

CIRCUIT BREAKER
QUALTEK

QMB-122-11C3N-3BA

CIRCUIT BREAKER
QUALTEK

QMB-152-00ENN-3BA

CIRCUIT BREAKER
QUALTEK