U7Y0123 [TDK]
AC-DC电源;型号: | U7Y0123 |
厂家: | TDK ELECTRONICS |
描述: | AC-DC电源 |
文件: | 总4页 (文件大小:1255K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
CFE400M
https://emea.tdk-lambda.com/cfe
https://product.tdk.com/en/power/cfe
300W convection / 400W fan
cooled, AC-DC power supply
Medical
Industrial
Test
Broadcast
Renewable
Comms
Features
Benefits
•ꢀConvection cooled
•ꢀReinforced isolation
•ꢀFullꢀdigitalꢀcontrol
Silent operation
Simplifiesꢀequipmentꢀdesign
Improves Product Performance
Minimises heat in system
Low cost of ownership
•ꢀErP and Climate Savers Gold level
•ꢀ5 year warranty
Input
47 - 63Hz
Input Voltage
Input Harmonics
Input Fuse
85-264Vac (100-240Vac nominal)
EN61000-3-2 compliant
Input Frequency
(440Hz with reduced PFC - consult sales office)
<25A at 25°C and 230Vac (cold start)
(meets EN61000-3-3).
Inrush Current
Dual fuses (Live + Neutral)
Fast acting (not user accessible)
140µA at 120Vac (60Hz), 280µA max at 240Vac (60Hz)
Earth Leakage Current
Worst case leakage current is less than 300µA at 240Vac, 63Hz (normal condition, 0.5mA Single Fault Condition)
Touch Current is <100µA NC, <500µA SFC at 264Vac, 60Hz
Quick Selector (Standard models). Additional variants available - see below
Output
Convection cooled units / units without fan
U-Chassis Cover + Chassis
Description
Units with top fan
Cover + Chassis
Order Code
Description
Current
(fan/conv)
Volts
Order Code
Order Code
Description
12V 33.3A / 25A CFE400M-12-5C-N1UML-NT U7Y0032 CFE400M-12-5C-N1CML-NT U7Y0087 CFE400M-12-5C-TFCML-NT U7Y0098
24V 16.7A / 12.5A CFE400M-24-5C-N1UML-NT U7Y0054 CFE400M-24-5C-N1CML-NT U7Y0101 CFE400M-24-5C-TFCML-NT U7Y0112
48V 8.3A / 6.25A CFE400M-48-5C-N1UML-NT U7Y0123 CFE400M-48-5C-N1CML-NT U7Y0134 CFE400M-48-5C-TFCML-NT U7Y0145
How To Create A Product Description
Adjustment
Fan Option
Output
-Y = ORing FET included
-N = ORing FET not included
range
-NN No fan, no fan supply
12
24
48
10.8 - 14.4 V
21.6 - 28.8 V
43.2 - 50 V
-N1 No fan, 12V / 0.25A fan supply
Top fan, no additional fan supply
-TF
(needs ‘C’ cover’)
M = Molex
Adjustable by potentiometer
Input
Cover Connec-
Fan
Option
Earth ORing Remote
Leakage FET On/Off
Vout - Standby
CFE400M-
tor
N = none
E = Enable
T = Inhibit
Standby Supply
NN = None (only with ‘N’ remote on/off)
5C = 5V / 80mA (0.5W standby mode power)
U = Chassis only
C = Chassis + cover (also for ‘TF’ fan)
L = 300µA
Confirm availability of created product with sales office
Isolation
Input to Output Reinforced
2 x MOPPs (3rd edition 60601)
4kVac, 5.7kVdc type tested to 4kVac (equivalent to 5.7kVdc), production tested to 4.3kVdc.
Input to Earth
Basic
1.5kVac, 2.3kVdc Output to Earth 1.5kVac
CFE400M_Datasheet_72709 - v20.0
1
CFE400M
Output Specification
Fan cooled Convection
400W
300W
Continuous (including fan supply) or RMS (including Peak power)
See handbook for details.
Output Power
Peak Power
450W
450W
for 10 seconds. RMS power not to exceed Output Power stated above
Including Line regulation of 0.25% (for 90-264Vac input change), Load regulation of 1%
(for 0-100% load change) and thermal regulation of 0.02%/°C (0-50°C)
Total Regulation
better than 2.25%
Ripple & Noise
Voltage Setting Accuracy
Turn on Time
Efficiency
1%
±1%
pk-pk, using EIAJ test method & 20MHz bandwidth
at 50% load
1.5s max
up to 94%
13ms
at 90 Vac & 100% rated output power
for 48V and 24V (up to 91% for 12V). At 230Vac, 75% load
minimum at 100% of 400W load
Hold up
Min Load
None
of set voltage for 50% of 300W load change
(in 500µs within the range 25 - 100% load)
Transient Response
<5%
Recovery
2ms max
Yes
for recovery to 2% of set voltage
Short circuit protection
Over Temperature protection
Over Voltage Protection
Fan supply
Auto recovery after removal of short circuit
Yes
Primary - auto recovers, secondary - cycle power to restart
Latching, need to cycle ac to restart unit.
Yes
12V / 0.25A
Depending on ‘Fan Option’ selected. See ‘how to create a product description’ for details
For N+1 redundancy with ORing FET option.
To increase output power requires optional droop share (contact sales office for details)
Parallel connection
Possible
Global Signals
Remote on/off
Enable - TTL logic level low (relative to Standby 0V) enables channel 1 and fan supply
Inhibit - TTL logic level low (relative to Standby 0V) inhibits channel 1 and fan supply
Standby Supply
Power Good
ORing FET
5V / 80mA isolated supply, not affected by remote on/off.
Logic high indicates ac supply is good and Ch1 is within regulation. Not available on units with no standby supply.
Allows redundant connection of power supplies with no additional/external diodes required.
Environment
See derating chart. Fan cooled is with 1.5m/s air blown from input to output (approximately 12CFM)
-40°C to 70°C storage (max 12 months).
Temperature
Fan cooling required if the unit is mounted with no free air
circulation above (see handbook for mounting details)
Low Temp Startup
Humidity
-20°C
5 - 95% RH non condensing
±3 x 30g shocks in each plane, total 18 shocks
30g shock = 11ms (+/-0.5msec), half sine
Shock
Conforms to EN60068-2-27, EN60068-2-47, IEC68-2-27,
IEC68-2-47, JIS C0041-1987.
Conforms to MIL-STD-810E/F, Method 516.5, Pro I, IV, VI
Single axis 10 - 500 Hz at 2g (sweep and endurance at
resonance) in all 3 planes
Vibration
Conforms to EN60068-2-6, IEC68-2-6
Conforms to MIL-STD-810E, Method 514.4, Pro I, Cat 1,9
Medical approval = -200 to 5000 metres operational (-200 to 3000m for 2nd edition 60601)
Non medical approval = -200 to 5000 metres operational
-200 to 5000m storage/transportation
Altitude
Pollution
Degree 2, Material group IIIb
Emissions EN61000-6-3:2007, EN60601-1-2:2007
Radiated Electric Field
EN55011, EN55032
(as per CISPR.11/22) Class B, FCC47 part 15 subpart B
see application note for details
Conducted Emissions
Conducted Harmonics
Flicker
EN55011, EN55032
EN61000-3-2
(as per CISPR.11/22) Class B, FCC47 part 15 subpart B
Class A
EN61000-3-3
Compliant - dmax only
CFE400M_Datasheet_72709 - v20.0
CFE400M
2
Immunity EN61000-6-2:2005
Criteria
Level 4
Level 3 for Fan supply
Not applicable to open frame units
A
Electrostatic Discharge
EN61000-4-2
Electromagnetic Field
Fast / Burst Transient
Surge Immunity
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
Level 3
Level 4
Level 3
Level 3
Level 3
A
A
A
A
A
A
Conducted RF Immunity
Power Frequency Magnetic Field
Criteria B for 5 sec interruption
Criteria B for 1 cycle interruption
Voltage Dips, Variations, Interruptions EN61000-4-11 Class 3
Criteria B for dip to 40% for 5 cycles below 154Vac (300W convection)
or 176Vac (400W forced air cooled)
Ring Wave
EN61000-4-12 Level 3
EN61000-4-14 Class 3
A
A
Voltage Fluctuations
Approvals / Accreditations
IEC/EN 62368-1, UL62368-1 / CSA 22.2 No 62368-1
File E135494
File E135494
IEC/EN 60950-1, UL60950-1 / CSA 22.2 No 60950-1
IEC/EN 60601-1, UL/CSA 60601-1, ANSI/AAMI ES60601-1
CAN/CSA-C22.2 No 60601-1-08
File E349607
IEC/EN 61010-1 (designed to meet)
Low Voltage Directive (LVD), electromagnetic compatibility
(EMC) and Restriction of Hazardous Substances (RoHS)
CE Mark (EN62368-1)
CB certificate and Report available on request
Please check with technical sales for status of approvals
Designed and manufactured under the control of ISO9001 and ISO13485 (including risk management).
Outline & Connection Drawings
177.80
CHASSIS WITH COVER
177.80
14.00
150.00
A
A
A
A
OUTPUT VOLTAGE
ADJUSTMENT
6.80
165.00
5.65
CHASSIS WITH TOP MOUNTED FAN
177.80
J5
CH1 +VE
0V COMMON
J6
PIN 1
J2
OUTPUT VOLTAGE
ADJUSTMENT
J1
J1
PIN 1
5.40
OUTPUT VOLTAGE
ADJUSTMENT
3.00
PIN CONNECTION
PIN
MATING PARTS
CONNECTOR
CONNECTION
1
2
EARTH
HOUSING
CRIMP PIN
08-52-0113
MANUFACTURER
1
2
3
4
5
6
7
8
FAN SUPPLY
REMOTE ON/OFF
PWR GOOD
FAN SUPPLY RTN
STANDBY RTN
STANDBY
NOT CONNECTED
09-50-8051
22-01-2085
N/A
J1
J2
MOLEX
MOLEX
MOLEX
0850-0032
3
4
5
LIVE
NOT CONNECTED
NEUTRAL
J5 & J6
TAG 19073-0165
Connectors are not included with the product but they are available from
TDK-Lambda
1 off input connector and 3 crimps are available as part number is 94910.
1 off feature connector and 8 crimps are available as part number 95109.
- SENSE
+ SENSE
NOTE:
A 6 OFF FIXING HOLES FOR M3, MAXIMUM PENETRATION 3.3mm,
MAXIMUM TORQUE 0.9Nm.
ALL TOLERANCES +/-0.5mm (unless otherwise specified)
.
All specifications at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
CFE400M_Datasheet_72709 - v20.0
3
CFE400M
TDK-Lambda France SAS
TDK-Lambda Americas
Tel: +1 800-LAMBDA-4 or 1-800-526-2324
powersolutions@us.tdk-lambda.com
www.us.lambda.tdk.com
Tel: +33 1 60 12 71 65
france@fr.tdk-lambda.com
www.emea.lambda.tdk.com/fr
Italy Sales Office
Tel: +39 02 61 29 38 63
info.italia@it.tdk-lambda.com
www.emea.lambda.tdk.com/it
TDK Electronics do Brasil Ltda
Tel: +55 11 3289-9599
sales.br@tdk-electronics.tdk.com
www.tdk-electronics.tdk.com/en
Netherlands
info@nl.tdk-lambda.com
www.emea.lambda.tdk.com/nl
TDK-Lambda Germany GmbH
Tel: +49 7841 666 0
info.germany@de.tdk-lambda.com
TDK-Lambda Corporation
Tel: +81-3-6778-1113
www.jp.lambda.tdk.com
www.emea.lambda.tdk.com/de
TDK-Lambda (China) Electronics Co. Ltd.
Tel: +86 21 6485-0777
powersolutions@cn.tdk-lambda.com
www.lambda.tdk.com.cn
TDK-Lambda Singapore Pte Ltd.
Tel: +65 6251 7211
tls.mkt@sg.tdk-lambda.com
www.sg.lambda.tdk.com
Austria Sales Office
Tel: +43 2256 655 84
info@at.tdk-lambda.com
www.emea.lambda.tdk.com/at
TDK India Private Limited, Power Supply Division
Switzerland Sales Office
Tel: +41 44 850 53 53
info@ch.tdk-lambda.com
www.emea.lambda.tdk.com/ch
Tel: +91 80 4039-0660
mathew.philip@in.tdk-lambda.com
www.sg.lambda.tdk.com
Nordic Sales Office
Tel: +45 8853 8086
info@dk.tdk-lambda.com
www.emea.lambda.tdk.com/dk
TDK-Lambda UK Ltd.
Tel: +44 (0) 12 71 85 66 66
powersolutions@uk.tdk-lambda.com
www.emea.lambda.tdk.com/uk
TDK-Lambda Ltd.
Tel: +9 723 902 4333
info@tdk-lambda.co.il
www.emea.lambda.tdk.com/il
C.I.S.
Commercial Support:
Tel: +7 (495) 665 2627
Technical Support:
Tel: +7 (812) 658 0463
info@tdk-lambda.ru
www.emea.lambda.tdk.com/ru
For additional information, please visit
https://product.tdk.com/en/power
Errors and omissions excepted
CFE400M_Datasheet_72709 - v20.0