1-1393128-1 [TE]

Magnetic blowouts available for switching DC loads;
1-1393128-1
型号: 1-1393128-1
厂家: TE CONNECTIVITY    TE CONNECTIVITY
描述:

Magnetic blowouts available for switching DC loads

文件: 总4页 (文件大小:458K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
General Purpose  
Panel/Plug-in Relays  
Potter & Brumfield  
PRD Series Power Relay  
n
n
n
n
n
Contact ratings to 50A  
Magnetic blowouts available for switching DC loads  
Contact arrangement up to 2 form C (2CO)  
1 form C auxiliary switch available  
UL class B insulation  
Typical applications  
Industrial controls, lighting.  
Approvals  
Contact ratings (continued)  
UL E22575; CSA LR15734; VDE 40020133 (available only on PRD with DC  
coil and Termination code 1)  
Type  
Load  
Cycles  
UL 5081)  
Models with all screw terminals are UL Listed. Others are UL Recognized.  
Technical data of approved types on request.  
Models with screws or quick connects for main terminals  
Code F, AgCdO, 1 pole  
50A, 240VAC, general purpose2)  
30A, 277VAC, resistive  
1.5HP, 120VAC  
2HP, 250VAC  
10A, 600VAC  
Code F, AgCdO, 2 pole  
50A, 240VAC, general purpose2)  
30A, 240VAC  
20x103  
100x103  
100x103  
100x103  
100x103  
Contact Data  
Contact arrangement  
1 and 2 form A (NO); 1 and 2 form C (CO);  
1 form X (NO-DM)  
600VAC,125VDC  
50A  
Ag, AgCdO, W  
1A, 12VDC or 12VAC  
75mΩ max.  
75mV  
Rated voltage  
Rated current  
Contact material  
Min. recommended contact load  
Initial contact resistance  
Initial voltage drop  
Frequency of operation  
Operate/releases time max.  
Bounce time max.  
20x103  
100x103  
100x103  
100x103  
100x103  
100x103  
20A, 277VAC  
1.5HP, 120VAC  
2HP, 250VAC  
10A, 600VAC  
7200 ops/hr  
40/20ms  
10ms  
2) In order to achieve 50A rating with contact code F, termination Code 0 or A is required.  
Code H, Ag with magnetic blowout, 1 or 2 pole  
Contact ratings  
20A, 125VDC  
1/3HP, 125VDC  
100x103  
100x103  
Type  
Load  
Cycles  
UL 5081)  
Code J, AgCdO with magnetic blowout, 1 or 2 pole  
20A, 125VDC  
1/3HP, 125VDC  
Code N, W stationary with AgCdO movable, 1 or 2 pole  
25A, 250VAC  
Models with screws or quick connects for main terminals  
Code Y, Ag, 1 pole  
25A, 277VAC  
100x103  
100x103  
100x103  
100x103  
100x103  
100x103  
100x103  
1HP, 120VAC  
2HP, 250VAC  
10A, 600VAC  
100x103  
100x103  
100x103  
1HP, 125VAC  
2HP, 250VAC  
7A, 50VDC, resistive  
Code Y, Ag, 2 pole  
25A, 240VAC  
UL 5081)  
100x103  
100x103  
100x103  
100x103  
100x103  
100x103  
Models with box lugs for main terminals  
Code P, Ag, 1 form X  
20A, 277VAC  
1HP, 120VAC  
2HP, 250VAC  
7A, 50VDC, resistive  
10A, 600VAC  
50A, 277VAC, general purpose  
30A, 277VAC, ballast  
15A, 277VAC, tungsten  
102LRA, 17FLA, 240VAC  
120LRA, 20FLA, 120VAC  
1.5HP, 120VAC  
100x103  
6x103  
6x103  
30x103  
30x103  
30x103  
30x103  
Code G, AgCdO, 1 pole  
30A, 277VAC, resistive  
1.5HP, 120VAC  
2HP, 250VAC  
10A, 600VAC  
Code G, AgCdO, 2 pole  
30A, 240VAC  
100x103  
100x103  
100x103  
100x103  
3HP, 240VAC  
Factory ratings  
Models with box lugs for main terminals  
Code R, Ag with magnetic blowout, 1 form X  
60A, 28VDC, resistive  
100x103  
100x103  
100x103  
100x103  
100x103  
100x103  
100x103  
30A, 125VDC  
20A, 277VAC  
1.5HP, 120VAC  
2HP, 250VAC  
10A, 600VAC  
Mechanical endurance  
DC Coil, 1x106 ops.; AC Coil 5x105 ops.  
1) Any PRD relay deviating electrically or physically from the standard models in the table is  
not UL or CSA listed. All horsepower ratings are for single phase motors..  
Auxiliary Snap-Action Switch Contact Data  
Contact arrangement  
Rating  
1 form C (CO)  
5A, 120VAC, 60Hz., 25°C  
Ag  
Contact material  
1
06-2016, Rev. 0616  
Catalog and product specification according  
to IEC 61810-1 and to be used only together  
with the ‘Definitions’ section.  
Catalog and product data is subject to the  
terms of the disclaimer and all chapters of  
the ‘Definitions’ section, available at  
http://relays.te.com/definitions  
Catalog product data, ‘Definitions’ section,  
application notes and all specifications are  
subject to change.  
www.te.com  
© 2015 Tyco Electronics Corporation,  
a TE Connectivity Ltd. company.  
General Purpose  
Panel/Plug-in Relays  
Potter & Brumfield  
PRD Series Power Relay (Continued)  
Coil Data  
Insulation Data  
Coil voltage range  
6 to 110VDC  
6 to 480VAC  
Class B  
Initial dielectric strength  
between open contacts  
between contact and coil  
between adjacent contacts  
Initial insulation resistance  
between insulated elements  
2000Vrms  
2000Vrms  
2000Vrms  
Coil insulation system according UL  
Coil versions, DC coil  
Coil  
code  
Rated  
voltage  
VDC  
6
12  
24  
Operate  
voltage  
VDC  
4.5  
9
18  
Release  
voltage  
VDC  
0.6  
1.2  
2.4  
Coil  
resistance  
Ω 10ꢀ  
18  
71  
288  
1150  
6050  
Rated coil  
power  
100MΩ  
W
2
2
2
2
6
Other Data  
12  
24  
48  
110  
Material compliance: EU RoHS/ELV, China RoHS, REACH, Halogen content  
refer to the Product Compliance Support Center at  
www.te.com/customersupport/rohssupportcenter  
Ambient temperature  
48  
110  
36  
82.5  
4.8  
11  
2
All figures are given for coil without preenergization, at ambient temperature +23°C.  
Other coil voltages on request.  
AC coil: -55ºC to 45ºC  
DC coil: -55°C to 80°C  
Category of environmental protection  
Coil versions, AC coil  
IEC 61810  
Terminal type  
Weight  
RT0 - open relay  
Screw, Quick connects, Box lugs  
284g  
Coil  
Rated  
voltage  
VAC  
6
Operate  
voltage  
VAC  
Release  
voltage  
VAC  
0.6  
Coil  
resistance  
Ω 15ꢀ  
0.86  
Rated coil  
power  
VA  
code  
Packaging/unit  
tray/20 pcs., box/40pcs.  
6
5.1  
9.8  
12  
24  
120  
240  
480  
12  
24  
120  
240  
480  
10.2  
20.4  
102  
204  
408  
1.2  
2.4  
12  
24  
3.2  
12  
290  
1200  
4500  
9.8  
9.8  
9.8  
9.8  
Accessories  
Product Code Description  
35D013  
Metal dust cover  
48  
9.8  
All figures are given for coil without preenergization, at ambient temperature +23°C.  
Other coil voltages on request.  
Dimensions  
PRD/PRDA 1, 3, 5 and 7  
PRD/PRDA 11  
PRD-3_P and R  
2 MTG. HOLES  
DIA.  
.187 + .005  
– .003  
2.5 MAX.  
.875 MAX.  
(22.23)  
.875 MAX.  
(22.23)  
.31  
(7.9)  
3.375 MAX.  
(85.73)  
.31  
(7.9)  
.31  
(7.9)  
(63.3)  
1.687  
(42.85)  
.81  
(20.6)  
4.75 + .13  
(
)
– .08  
4
3
2
COIL  
1
4
3
2
2
6
5
6
5
6
5
8
7
2.51 MAX. 2.50  
2.51 MAX.  
(63.75)  
(63.8)  
(63.5)  
COIL  
1
BOX LUG  
CONNECTOR  
1.875  
COIL  
1.875  
(47.63)  
1.875  
(47.63)  
(47.63)  
1
2 MTG. HOLES  
DIA.  
.81  
(20.6)  
2 MTG. HOLES  
DIA.  
.187 + .005  
– .003  
.59 MAX.  
(15.0)  
2.5 MAX.  
(64)  
.187 + .005  
– .003  
4.75 + .13  
(
)
4.75 + .13  
– .08  
(
)
– .08  
2.28 MAX.  
(57.9)  
2.50 MAX.  
(63.5)  
2.28 MAX.  
(57.9)  
2.50 MAX.ON PRD7  
(63.5)  
.375  
(9.53)  
2.23  
3.00  
(56.6)  
(76.2)  
.375  
(9.53)  
.375  
(9.53)  
3.375  
(85.73)  
4.250 MAX.  
(107.95)  
3.375 MAX.  
(85.73)  
2.5 MAX.  
(63.5)  
W/O AUX SWITCH  
W/O AUX SWITCH  
2
06-2016, Rev. 0616  
www.te.com  
© 2015 Tyco Electronics Corporation,  
a TE Connectivity Ltd. company.  
Catalog and product specification according  
to IEC 61810-1 and to be used only together  
with the ‘Definitions’ section.  
Catalog and product data is subject to the  
terms of the disclaimer and all chapters of  
the ‘Definitions’ section, available at  
http://relays.te.com/definitions  
Catalog product data, ‘Definitions’ section,  
application notes and all specifications are  
subject to change.  
General Purpose  
Panel/Plug-in Relays  
Potter & Brumfield  
PRD Series Power Relay (Continued)  
Terminal assignment for models with magnetic blowout  
PRD3 with blowout  
PRD7 with blowout  
PRD 11 with blowout  
THIS SIDE OF MAGNET  
ATTRACTS NORTH SEEKING  
POLE OF COMPASS.  
THIS SIDE OF MAGNET  
ATTRACTS NORTH SEEKING  
POLE OF COMPASS.  
THIS SIDE OF MAGNET  
ATTRACTS NORTH SEEKING  
POLE OF COMPASS.  
-
-
+
+
-
-
POLARITY  
MARKING  
POLARITY  
MARKING  
POLARITY  
MARKING  
Product code structure  
Typical product code  
PRD  
-7  
A
Y
0
-120  
Type  
PRD Open relay  
PRDA Open relay with aux. 1 form C (CO) snap-action switch  
Main contact arrangement  
1 form A (1 NO)  
1 form C (1 CO)  
7V 2 form A (2 NO) with 3mm contact gap 1)  
1
5
3
7
1 form X (1 NO-DM)  
2 form A (2 NO)  
11 2 form C (2 CO)  
1) Code 7V is only available as a UL Recognized model, not UL Listed  
Coil input  
A
AC, 50/60Hz  
D
DC  
Main contact material and type  
Y
G
F
H
J
N
P
R
.312” (7.92mm) dia. Ag [25A max. rating]  
.312” (7.92mm) dia. AgCdO [30A max. rating]  
.312” (7.92mm) dia. AgCdO [50A max. rating]  
Ag with magnetic blowout [20A DC max. rating]  
AgCdO with magnetic blowout [20A DC max. rating]  
2)  
3)  
4)  
W stationary & AgCdO movable [25A max. rating]  
5)  
Ag [50A max. rating]  
5)  
Ag with magnetic blow out [50A max. rating]  
2) Available with Main contact arrangement code 1, 5, 7 or 11 only, and Termination code 0 or A only.  
3) Available with Main contact arrangement code 3, 7 or 11 only  
4) Available with Main contact arrangement code 1, 5, 7 or 11 only.  
5) Available with Main contact arrangement code 3 only, and Termination code 4 only.  
Termination  
PRD types only  
0
1
3
4
#8-32 screw term. for main contacts, #6-32 screw term. for coil.  
.250” (6.35mm) QC for main contacts and coil (VDE approved Termination code)  
#8-32 screw term. for main contacts, .250” (6.35mm) QC for coil.  
Box lug term. which accept #6 - #14 wire for main contacts, #6-32 screw term. for coil. 6)  
6) Available with Main contact arrangement code 3 only, and Main contact material code P or R only.  
PRDA (with aux. switch) types only  
A
B
L
#8-32 screw term. for main contacts, #6-32 screw term. for coil, screw term. for aux. switch  
.250” (6.35mm) QC for main contacts, coil and aux. switch  
Twin .250” (6.35mm) QC for main contacts, .250” (6.35mm) QC for coil and aux. switch  
Coil voltage  
Coil code: please refer to coil versions table  
3
06-2016, Rev. 0616  
Catalog and product specification according  
to IEC 61810-1 and to be used only together  
with the ‘Definitions’ section.  
Catalog and product data is subject to the  
terms of the disclaimer and all chapters of  
the ‘Definitions’ section, available at  
http://relays.te.com/definitions  
Catalog product data, ‘Definitions’ section,  
application notes and all specifications are  
subject to change.  
www.te.com  
© 2015 Tyco Electronics Corporation,  
a TE Connectivity Ltd. company.  
General Purpose  
Panel/Plug-in Relays  
Potter & Brumfield  
PRD Series Power Relay (Continued)  
Product Code  
PRD-3AY0-120  
PRD-3AG0-120  
PRD-3AJ0-120  
PRD-3AJ3-24  
PRD-3DH0-24  
PRD-3DY0-12  
PRD-3DY0-24  
PRD-3DY0-110  
PRD-5AY0-24  
PRD-5AY0-120  
PRD-5AY1-120  
PRD-5AY0-240  
PRD-5DF0-12  
PRD-5DY0-12  
PRD-5DY0-24  
PRD-7AG0-120  
PRD-7AY0-24  
Arrangement  
Material  
Ag  
AgCdO, 30A  
AgCdO, mag blowout  
Coil  
Terminals  
Part Number  
7-1393127-9  
6-1393127-9  
7-1393127-4  
7-1393127-5  
8-1393127-6  
9-1393127-5  
9-1393127-6  
9-1393127-4  
1393128-6  
1393128-5  
1-1393128-1  
1393128-7  
2-1423100-4  
1-1393128-6  
1-1393128-7  
9-1393129-5  
1393130-9  
1 form X, 1 NO-DM  
120VAC  
Screw  
24VAC  
24VDC  
12VDC  
24VDC  
110VDC  
24VAC  
120VAC  
Screw / QC  
Screw  
Ag, mag blowout  
Ag  
1 form C, 1 CO  
QC  
Screw  
240VAC  
12VDC  
AgCdO, 50A  
Ag  
24VDC  
120VAC  
24VAC  
2 form A, 2 NO  
AgCdO, 30A  
Ag  
PRD-7AY0-120  
PRD-7AY0-240  
PRD-7AY3-120  
PRD-7DG0-24  
PRD-7DH0-48  
PRD-7DY0-12  
PRD-7DY0-24  
PRD-11AF0-240  
PRD-11AG0-24  
PRD-11AG0-120  
PRD-11AG0-240  
PRD-11AH0-120  
PRD-11AY0-24  
PRD-11AY0-120  
PRD-11AY0-240  
PRD-11AY0-480  
PRD-11DF0-12  
PRD-11DF0-110  
PRD-11DG0-12  
PRD-11DG0-24  
PRD-11DH0-12  
PRD-11DH0-24  
PRD-11DH0-48  
PRD-11DH0-110  
PRD-11DJ0-24  
PRD-11DY0-12  
PRD-11DY0-24  
PRD-11DY0-48  
PRD-11DY0-110  
PRDA-11AGA-120  
PRDA-11AYA-120  
120VAC  
240VAC  
120VAC  
24VDC  
48VAC  
12VDC  
24VDC  
240VAC  
24VAC  
120VAC  
240VAC  
120VAC  
24VAC  
120VAC  
240VAC  
480VAC  
12VDC  
110VDC  
12VDC  
24VDC  
12VDC  
24VDC  
48VDC  
110 VDC  
24 VDC  
12 VDC  
24 VDC  
48 VAC  
110 VDC  
120 VAC  
1393130-7  
1-1393130-0  
1-1393130-2  
1-1393130-6  
2-1393130-1  
2-1393130-8  
2-1393130-9  
3-1423100-0  
1-1393127-1  
1393127-9  
1-1393127-2  
1-1393127-6  
2-1393127-9  
2-1393127-6  
3-1393127-0  
3-1393127-1  
2-1423100-2  
2-1423100-9  
3-1393127-5  
3-1393127-8  
4-1393127-7  
4-1393127-9  
5-1393127-0  
4-1393127-6  
5-1393127-5  
6-1393127-1  
6-1393127-2  
6-1393127-3  
6-1393127-0  
7-1393131-4  
7-1393131-9  
Screw / QC  
Screw  
AgCdO, 30A  
Ag, mag blowout  
Ag  
2 form C, 2 CO  
AgCdO, 50A  
AgCdO, 30A  
Ag, mag blowout  
Ag  
AgCdO, 50A  
AgCdO, 30A  
Ag, mag blowout  
AgCdO, mag blowout  
Ag  
AgCdO, 30A  
PRD accessory  
Product Code  
35D013  
Description  
Metal dust cover enclosure  
Part Number  
5-1393158-2  
5.31 MAX.  
(134.9)  
3.13 MAX.  
(79.5)  
.97  
(24.64)  
35D013 Dust Cover  
4.125  
(104.77)  
PRD dust cover has a steel base  
with knockouts for 0.5” (12.7mm) dia.  
conduit and a cover fitted with two  
screws. Fits PRD relays, except with  
auxiliary contacts. Finished in gray  
baked enamel.  
.687  
(17.45)  
.50  
2.06  
.093  
(12.7)  
(52.3)  
(2.36)  
1.50  
(38.1)  
1.875  
(47.63)  
1.625  
(41.28)  
3.38 MAX.  
(85.9)  
.75  
(19.1)  
Mounting:  
.812  
.937  
Three No. 10 holes on  
1.875” (47.63mm) x  
4.125” (104.77mm)  
(20.62)  
(23.86)  
2.56  
(65.0)  
.88 DIA.  
(22.4)  
.218 DIA.  
(5.54)  
3 MTG. HOLES  
5.125  
(130.18)  
4
KNOCKOUT HOLES  
centers.  
4 HOLES TAPPED #8-32  
Note: Additional unused holes may be present in dust cover base.  
2 KNOCKOUT HOLES EACH END  
4
06-2016, Rev. 0616  
Catalog and product specification according  
to IEC 61810-1 and to be used only together  
with the ‘Definitions’ section.  
Catalog and product data is subject to the  
terms of the disclaimer and all chapters of  
the ‘Definitions’ section, available at  
http://relays.te.com/definitions  
Catalog product data, ‘Definitions’ section,  
application notes and all specifications are  
subject to change.  
www.te.com  
© 2015 Tyco Electronics Corporation,  
a TE Connectivity Ltd. company.  

相关型号:

1-1393128-6

Magnetic blowouts available for switching DC loads
TE

1-1393128-7

Magnetic blowouts available for switching DC loads
TE

1-1393130-0

Magnetic blowouts available for switching DC loads
TE

1-1393130-2

Magnetic blowouts available for switching DC loads
TE

1-1393130-6

Magnetic blowouts available for switching DC loads
TE

1-1393146-1

General Purpose Relays Industrial Relays
TE

1-1393146-9

Plug-in version, PCB terminals, chassis- or DIN-rail mount
TE

1-1393147-0

Plug-in version, PCB terminals, chassis- or DIN-rail mount
TE

1-1393147-1

Plug-in version, PCB terminals, chassis- or DIN-rail mount
TE

1-1393147-5

Plug-in version, PCB terminals, chassis- or DIN-rail mount
TE

1-1393148-4

Plug-in version, PCB terminals, chassis- or DIN-rail mount
TE

1-1393148-6

Plug-in version, PCB terminals, chassis- or DIN-rail mount
TE