1013X [TE]

WILMAR™ Protective Relays - 1000 Series; 丰益™保护继电器 - 1000系列
1013X
型号: 1013X
厂家: TE CONNECTIVITY    TE CONNECTIVITY
描述:

WILMAR™ Protective Relays - 1000 Series
丰益™保护继电器 - 1000系列

继电器
文件: 总1页 (文件大小:40K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Phase Failure Relays  
WILMARProtective Relays 1000 Series  
Function:  
47  
ANSI/IEEE C37.90-1978  
UL file No. E58048  
CSA file No. LR61158  
TERMINAL STRIPS  
#6 - 32 SCREWS  
Phase failure relays protect motors, equipment and  
personnel from damage or injury caused by open  
phase, reversed phase sequence, or low voltage in a  
three phase system. Models are available for 50 and  
60 Hz with voltages up to 575 volts. Motor control  
switchboards are a common application.  
Operation:  
The contacts of the relay will close only when it  
senses normal conditions of three phase power at  
the proper phase sequence.  
13  
3
/16  
The relay contacts will remain in their normally open  
position (de-energized) when voltage with incorrect  
phase sequence is applied, one or more phases are  
open, or at undervoltage condition.  
11  
/64" DIA.  
4 MTG. HOLES  
PART NUMBER SELECTION  
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.  
PART NUMBER SELECTION  
Sample Part No.  
1004X  
Type:  
1001 = 120 V, 60 Hz, 3 phase,L-L  
1007 = 208 V, 60 Hz, 3 phase, L-L  
1002 = 230 V, 60 Hz, 3 phase,L-L  
1012 = 300 V, 60 Hz, 3 phase, L-L  
1013 = 350 V, 60 Hz, 3 phase, L-L  
1003 = 380 V, 50 Hz, 3 phase, L-L  
1004 = 460 V, 60 Hz, 3 phase,L-L  
1005 = 525 V, 60 Hz, 3 phase,L-L  
1006 = 575 V, 60 Hz, 3 Phase, L-L  
Mounting:  
PRODUCT SPECIFICATIONS  
Part Number  
1000 Series  
Nominal Voltage .............................  
Voltage Drop-Out ...........................  
Pick-Up to Drop-Out Differential ....  
Ambient Operating Temperature ....  
Temperature Drift ...........................  
Time Delay .....................................  
Output Contacts .............................  
Contact Ratings ..............................  
See Table  
75% to 100% of nominal, screwdriver adjustable  
3% approx.  
-40oC to +70oC  
X = Flange  
± 1%  
Blank - Stud  
See Curve  
Consult factory for additional models and options  
One set, normally open  
10 amp at 28 VDC resistive  
10 amp at 230 VAC resistive  
Notes:  
1.  
Remove screw for access to the undervoltage  
adjustment.  
2. Clockwise rotation of the adjustment  
potentiometer will raise the drop-out voltage.  
30  
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)  

相关型号:

1014-0100

MATRIX DRUCKER TRAGBAR SERIELL 40SPALTEN
ETC

1014-12

RF Manual 16th edition
NXP

1014-16/A200

GLEITLAGER KUNSTSTOFF 10ST D 10MM
ETC

1014-16/M250

GLEITLAGER KUNSTSTOFF 10ST D 10MM
ETC

1014-2

2 Watt - 28 Volts, Class C Microwave 1000 - 1400 MHz
MICROSEMI

1014-2

RF Manual 16th edition
NXP

1014-6A

6 Watts, 28 Volts, Class C Microwave 1000 - 1400 MHz
ADPOW

1014-6A

6 Watts - 28 Volts, Class C Microwave 1000 - 1400 MHz
MICROSEMI

1014-6A

RF Manual 16th edition
NXP

1014-TAB1D434

WIRELESS PRODUCT SELECTOR GUIDE
ETC

1014-TAB1D868

WIRELESS PRODUCT SELECTOR GUIDE
ETC

10140-3000PC

3M Mini D Ribbon (MDR) Connectors
3M