Paralleling Relays  
WILMARProtective Relays 1800 Series  
Function:  
ANSI/IEEE C37.90-1978  
UL file No. E58048  
25  
CSA file No. LR61158  
#6 - 32 STUDS  
6 PLACES  
Application:  
These relays are designed for automatic paralleling  
(synchronizing) of generators. The relays sense the  
phase angle displacement and the amplitude differ-  
ence between two voltages and permit paralleling  
only when both voltages are equal and in phase. A  
short time delay is provided to assure that the  
frequencies are essentially the same at the moment  
of paralleling. The basic series is designed to parallel  
two or more energized AC generators. The “Dead  
Bus” type provides paralleling of AC generators to  
themainbus. Theypermitelectricalconnectionofan  
energized generator to an un-energized line (Dead  
Bus). If the bus is energized, connection of the  
generator to the bus is permitted only when both are  
synchronized.  
3
4
1
/2  
/8  
7
3
11  
/64" DIA.  
4 MTG. HOLES  
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.  
A. 3 Phase, 4 Wire System  
PRODUCT SPECIFICATIONS  
Connect phase "A" of LINE 1 to terminal 1  
Connect phase "A" of LINE 2 to terminal 3  
Connect the neutrals to terminals 2 & 4  
Part Number  
1800 Series  
Sensing Voltage ............................. 120 V, 230 V, 277 V, 380 V, 460 V, 575 V, & 415 V  
50-500 Hz  
Line Frequency ...............................  
Pick-Up Adjustment .......................  
B. 3 Phase, 3 Wire or 1 Phase, 2 Wire System  
Connect phase "A" of LINE 1 to terminal 1  
Connect phase "B" of LINE 1 to terminal 2  
Connect phase "A" of LINE 2 to terminal 3  
Connect phase "B" of LINE 2 to terminal 4  
External adjustment for field sensing of 10-30% of  
nominal input voltage. (Vertical voltage differential of 6  
to 18 electrical degrees).  
Fixed @ 60 milliseconds is provided to assure that the  
frequencies of both input lines are sufficiently close to  
permit paralleling within the preset window.  
Time Delay .....................................  
Output Contacts .............................  
Consult factory for additional models and options.  
One set N.O., one set N.C.  
5 amp resistive at 120 VAC or 28 VDC  
36  
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)  
Paralleling Relays  
Selection Guide  
(Typical Applications)  
Sensing Voltage  
Series 1800  
Generator to Generator  
Series 1800DB  
Generator to Bus  
Series 1800DDB  
Bus to Bus  
Permits paralleling of two generators  
only when they are "on-line" and  
their voltages are equal and in phase  
(synchronized)  
Normally used to permit  
paralleling of a generator to a  
bus when: (a) both line  
Permits paralleling of two power  
lines (buses) when: (a) both line  
voltages are equal and in phase, or:  
voltages are equal and in phase, (b) when either bus is "hot" and the  
or: (b) when the generator is  
other bus is "dead"  
"on-line" and the bus is "dead"  
120 Volts  
230 Volts  
380 Volts  
460 Volts  
575 Volts  
415 Volts  
277 Volts  
1810X  
1820X  
1830X  
1840X  
1850X  
1860X  
1870X  
1810DBX  
1820DBX  
1830DBX  
1840DBX  
1850DBX  
1860DBX  
1870DBX  
1810DDBX  
1820DDBX  
1830DDBX  
1840DDBX  
1850DDBX  
1860DDBX  
1870DDBX  
Condition  
Not  
Series 1800  
Contacts  
Series 1800DB  
Contacts  
Series 1800DDB  
Contacts  
Energized  
Synch.  
N.C.  
N.O.  
N.C.  
N.O.  
N.C.  
N.O.  
Energized  
Line 1  
Line 2  
Line 1  
Line 2  
Line 1  
Line 2  
Line 1  
Line 2  
Line 1  
Line 2  
X
X
X
X
X
1
2
3
4
5
Open  
Close  
Open  
Close  
Open  
Close  
Close  
Close  
Open  
Close  
Yes  
No  
No  
Close  
Close  
Close  
Close  
Open  
Open  
Open  
Open  
Open  
Close  
Open  
Open  
Close  
Open  
Close  
Open  
Open  
Close  
Open  
Close  
X
X
X
X
X
Output Contact Options: 1. Two Form A. (Add -A to Model Number)  
2. Two Form B. (Add -B to Model Number)  
37  
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)  

相关型号:

1800-01A-K

Industrial Control IC
ETC

1800-01A-L

Industrial Control IC
ETC

1800-01D-K

Industrial Control IC
ETC

1800-01D-L

Industrial Control IC
ETC

1800-01G-K

Industrial Control IC
ETC

1800-01G-L

Industrial Control IC
ETC

1800-02

TO-8, 0 psi to 3 psi, 0 psi to 150 psi Silicon Pressure Sensors
HONEYWELL

1800-02A-K

Industrial Control IC
ETC

1800-02A-L

Industrial Control IC
ETC

1800-02D-K

Industrial Control IC
ETC

1800-02D-L

Industrial Control IC
ETC

1800-02D-L4L-B

Peizoresistive Sensor, Differential, 0Psi Min, 10Psi Max, TO-8, CAN PACKAGE
HONEYWELL