1800 [TE]
WILMAR? Protective Relays - 1800 Series; 丰益?保护继电器 - 1800系列型号: | 1800 |
厂家: | TE CONNECTIVITY |
描述: | WILMAR? Protective Relays - 1800 Series |
文件: | 总2页 (文件大小:78K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Paralleling Relays
WILMAR™ Protective Relays – 1800 Series
Function:
• ANSI/IEEE C37.90-1978
• UL file No. E58048
25
• CSA file No. LR61158
#6 - 32 STUDS
6 PLACES
Application:
These relays are designed for automatic paralleling
(synchronizing) of generators. The relays sense the
phase angle displacement and the amplitude differ-
ence between two voltages and permit paralleling
only when both voltages are equal and in phase. A
short time delay is provided to assure that the
frequencies are essentially the same at the moment
of paralleling. The basic series is designed to parallel
two or more energized AC generators. The “Dead
Bus” type provides paralleling of AC generators to
themainbus. Theypermitelectricalconnectionofan
energized generator to an un-energized line (Dead
Bus). If the bus is energized, connection of the
generator to the bus is permitted only when both are
synchronized.
3
4
1
/2
/8
7
3
11
/64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
A. 3 Phase, 4 Wire System
PRODUCT SPECIFICATIONS
Connect phase "A" of LINE 1 to terminal 1
Connect phase "A" of LINE 2 to terminal 3
Connect the neutrals to terminals 2 & 4
Part Number
1800 Series
Sensing Voltage ............................. 120 V, 230 V, 277 V, 380 V, 460 V, 575 V, & 415 V
50-500 Hz
Line Frequency ...............................
Pick-Up Adjustment .......................
B. 3 Phase, 3 Wire or 1 Phase, 2 Wire System
Connect phase "A" of LINE 1 to terminal 1
Connect phase "B" of LINE 1 to terminal 2
Connect phase "A" of LINE 2 to terminal 3
Connect phase "B" of LINE 2 to terminal 4
External adjustment for field sensing of 10-30% of
nominal input voltage. (Vertical voltage differential of 6
to 18 electrical degrees).
Fixed @ 60 milliseconds is provided to assure that the
frequencies of both input lines are sufficiently close to
permit paralleling within the preset window.
Time Delay .....................................
Output Contacts .............................
Consult factory for additional models and options.
One set N.O., one set N.C.
5 amp resistive at 120 VAC or 28 VDC
36
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
Paralleling Relays
Selection Guide
(Typical Applications)
Sensing Voltage
Series 1800
Generator to Generator
Series 1800DB
Generator to Bus
Series 1800DDB
Bus to Bus
Permits paralleling of two generators
only when they are "on-line" and
their voltages are equal and in phase
(synchronized)
Normally used to permit
paralleling of a generator to a
bus when: (a) both line
Permits paralleling of two power
lines (buses) when: (a) both line
voltages are equal and in phase, or:
voltages are equal and in phase, (b) when either bus is "hot" and the
or: (b) when the generator is
other bus is "dead"
"on-line" and the bus is "dead"
120 Volts
230 Volts
380 Volts
460 Volts
575 Volts
415 Volts
277 Volts
1810X
1820X
1830X
1840X
1850X
1860X
1870X
1810DBX
1820DBX
1830DBX
1840DBX
1850DBX
1860DBX
1870DBX
1810DDBX
1820DDBX
1830DDBX
1840DDBX
1850DDBX
1860DDBX
1870DDBX
Condition
Not
Series 1800
Contacts
Series 1800DB
Contacts
Series 1800DDB
Contacts
Energized
Synch.
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
Energized
Line 1
Line 2
Line 1
Line 2
Line 1
Line 2
Line 1
Line 2
Line 1
Line 2
X
X
X
X
X
1
2
3
4
5
Open
Close
Open
Close
Open
Close
Close
Close
Open
Close
Yes
No
No
Close
Close
Close
Close
Open
Open
Open
Open
Open
Close
Open
Open
Close
Open
Close
Open
Open
Close
Open
Close
X
X
X
X
X
Output Contact Options: 1. Two Form A. (Add -A to Model Number)
2. Two Form B. (Add -B to Model Number)
37
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
相关型号:
1800-02D-L4L-B
Peizoresistive Sensor, Differential, 0Psi Min, 10Psi Max, TO-8, CAN PACKAGE
HONEYWELL
©2020 ICPDF网 联系我们和版权申明