TIB120-124EX [TRACOPOWER]
Industrial Power Supplies;型号: | TIB120-124EX |
厂家: | TRACO ELECTRONIC AG |
描述: | Industrial Power Supplies |
文件: | 总6页 (文件大小:644K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Industrial Power Supplies
TIB 120EX Series, 120 Watt
• UL Hazloc Class I, division 2 approval
and ATEX certification
• SEMI F47 compliant for voltage sag
immunity
• Rugged metal case with optional
side-mounting
• Very high efficiency up to 94%
• Back power immunity
•
150% peak current for 4 sec.
• Operating Temp –40°C to +70°C
(full load up to 60°C)
• Adjustable output voltage
• High Reliability: MTBF 1 mill hrs per
IEC 61709
CB
Scheme
UL508
UL60950-1
ATEX II3G
• Short circuit and overload protection
• 5-year product warranty
The TIB 120-EX family of next generation of 120 Watt din rail power supplies fea-
ture high efficiency operation of up to 94% enabling a slim design with alterna-
tive side-mounting for flat panels (DC OK Indicator on both front and side panel).
These products certified to UL Hazloc Class 1 / Div 2, and ATEX (EN60079-0,
EN60079-7. EN600079-15) for operation in hazardous locations. These convec-
tion cooled power supplies have a -40°C to +60°C full load operating tempera-
ture range. 150% peak power for up to 4 seconds which is ideal for stepper
motors, solenoids or actuators. The TIB 080-EX series has an important Back
Power Immunity feature that helps protect against shut-down or malfunction
with loads such as inductors and decelerating motors that can feed voltage back
to the power supply. Outputs are radio-interference-suppressed to impede ra-
diation at long output lines which reduces the common mode current to within
limits of telecommunication ports. The series operate with a high power factor
of up to 99% which also minimizes inrush current.
Other output power of same series:
www.tracopower.com/overview/tib-ex
Additional qualifications include IEC/EN/UL 60950-1, UL508 and CB Report
with EMC compliance to IEC/EN61000-6-2 and IEC/EN61000-6-3.
Models
Output Power
Output Voltage
nom. (adjustable)
Output Current
Efficiency
Order Code
(max.)
(max.)
(typ.)
TIB 120-112EX
TIB 120-124EX
TIB 120-148EX
120 W
120 W
120 W
12 VDC (11.8–15.0)
24 VDC (23.5–28.0)
48 VDC (47.0–56.0)
10 A
5 A
94.0 %
94.0 %
94.0 %
2.5 A
www.tracopower.com
Page 1 of 6
TIB 120EX Series, 120 Watt
Input Specifications
Input voltage
– nominal ranges
– effective ranges
100 – 240VAC
85 – 264VAC
(below 90 VAC a derating of 3%/V is required)
Input voltage frequency
45 – 65 Hz
Standby power cunsumption
2.2/2.2 W (115/230 VAC)
0.97/0.8 (115/230 VAC)
class A, D
Power Factor Correction (PFC)
Harmonic limits
Inrush current
– acc. EN 61000-3-2
15/30A max. (115/230 VAC)
Output Specifications
Output voltage adjustment 1)
12 Vout models: 11.8 – 15.0 V
24 Vout models: 23.5 – 28.0 V
48 Vout models: 47.0 – 56.0 V
Regulation
– Input variation
– Load variation (10–90 %)
0.1 % max.
0.5 % max.
Temperature coefficient
Hold-up time
0.02 %/K
20ms min.
2s max.
Start-up time
Ripple and Noise (20MHz bandwidth)
12 & 24 Vout models: 100 mVp-p max.
48 Vout models: 200 mVp-p max.
Output overvoltage protection (OVP) 2)
12 Vout models: 16 – 19V
24 Vout models: 32 – 35V
48 Vout models: 56 – 60V
Power back immunity 3)
< OVP level
Operation
– Nominal operation
100 % of Iout nom.
– Peak power operation
– Constant current (cc)
105 –150 % of Iout nom.
> 155 % of Iout nom.
Duty cycle 4)
– Threshold
> 105 %
(for peak and cc mode)
– CC or peak opeartion timer
– normal operation / off period
4 s max. (switch off)
10 s typ. (automatic restart after switch off or
peak and cc operation timer reset)
Short circuit
DC OK signal
Switch off after 4s delay, automatic restart
– Threshold for Vout
12 Vout models: on: > 10.9 V typ., off: < 10.7V typ.
24 Vout models: on: > 22.5 V typ., off: < 21.5 V typ.
48 Vout models: on: > 45 V typ., off: < 43 V typ.
relay contact closed, 1 A max., < 100 mOhm
(also indicated by green LEDs: front and side)
relay contact open, 30 V max.
– DC ON
– DC OFF
1) Output voltage can be adjusted as indicated. However, output power has to be maintained at nominal value. This means the output
nominal current has to be reduced in accordance with the increase of output voltage.
2) In case of an internal error a second voltage regulation loop keeps the output voltage at a save level, the power supply turns off and
restarts after typ. 10 seconds.
3) When external voltage is supplied above set output voltage and below OVP threshold, the power supply will function normally without
switch off or destruction, even if external voltage is applied continuously.
4) In case of overload or short circuit, the unit switches the output voltage off after 4 seconds and tries to restart every typ. 10 seconds.
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
www.tracopower.com
Page 2 of 6
TIB 120EX Series, 120 Watt
General Specifications
Operating temperature range
Derating
–40°C to +70°C max.
2 %/K above +60°C
Cooling
convection cooling, no internal fan
switch off at overtemperature
5–95 % rel. H max.
Overtemperature protection
Humidity (non condensing)
Altitude during operation
2000 m max.
Isolation Voltage
– Input/Ouput
– Input/Chassis
– Ouput/Chassis
4250 VDC
1500 VDC
750 VDC
Creepage Clearance
– Input/Ouput
8 mm
– Input/Chassis
– Output/Chassis
4 mm
1.5 mm
MTBF (acc. to IEC 61709 at 25°C)
Safety standards – Information technology equipment
> 1‘450‘000 h
IEC/EN 60950-1, UL 60950-1
CSA 22.2 No 60950-1-03
UL 508
EN 60079-15, EN 60079-15, EN 60079-15
(EX II3G Ex ec nC IIC GC)
Class I, Division 2
– Safety low voltage switchgear and controlgear
– ATEX for hazardous location
– UL HazLoc
– Certification documents
www.tracopower.com/overview/tib
Electromagnetic compatibility (EMC), Emissions
– Conducted emission input
EN 61000-6-3, EN 61204-3
EN 55032, EN 55011 class B
EN 55032, EN 55011 class B
– Radiated RI emission
Electromagnetic compatibility (EMC), Immunity
EN 61000-6-2, EN 61204-3
EN 50121-4
– Railway applications signalling apparatus
– Railway applications rolling stock apparatus
– Electrostatic discharge (ESD)
– Radiated RF field immunity
– Electrical fast transient / burst immunity
– Surge immunity
EN 50121-3-2
IEC/EN 61000-4-2 4 kV/8 kV criteria A
IEC/EN 61000-4-3 10 V/m
IEC/EN 61000-4-4 2 kV
IEC/EN 61000-4-5 1 kV/2 kV criteria B
criteria A
criteria B
– Immunity to conducted RF disturbances
– Power frequency field immunity
– Mains voltage dips and interruptions
– Voltage sag immunity
IEC/EN 61000-4-6 10 V
IEC/EN 61000-4-8 30 A/m
IEC/EN 61000-4-11
criteria A
criteria A
criteria B/C
criteria A
SEMI F47 (230 VAC)
Environment
– Railway applications shock and vibration
– Vibration acc. IEC 60068-2-6-3
– Shock acc. IEC 60068-2-27
according EN 61373
3 axis, 2 g sine sweep, 10–55 Hz, 11 okt/min
3 axis, 25 g half sine, 11 ms
Enclosure material
Mounting
– Chassis
– Cover
aluminium
stainless steel
– DIN-rail mounting
for DIN-rails as per EN 50022-35ꢀ15/7.5
Environmental compliance – Reach
www.tracopower.com/products/reach-declaration.pdf
RoHS directive 2011/65/EU
– RoHS
Connection
screw terminals
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
www.tracopower.com
Page 3 of 6
TIB 120EX Series, 120 Watt
Function Specification
Output Characteristic
Characteristic: Output voltage vs output current for overload conditions until switch off after
4s at nominal input voltages
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
www.tracopower.com
Page 4 of 6
TIB 120EX Series, 120 Watt
Output Characteristic (continued)
Derating: max load vs input voltage
160
140
120
100
80
4 seconds
continious
60
40
20
30
40
50
60
70
80
-40
Ambient Temperature [°C]
Derating: Load vs ambient temperature
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
www.tracopower.com
Page 5 of 6
TIB 120EX Series, 120 Watt
Outline Dimensions
* Measurement from front panel to DIN-Rail
36
1
118,6*
114,2
M3
6,35
Combi Head
24 VDC/5 A DC OK
DC
ON
V adj.
Industrial Power Supply
120 W
Model
TIB 120-124EX
100-240 VAC, 50-60 Hz
1.50-0.78 A
L
N
9,5
M3
DIN-Rail
Hook
Combi Head
Weight: 461g (16.26 oz)
Alternative side mounting:
24 VDC/5 A DC OK
DC
ON
DC ON
V adj.
Industrial Power Supply
120 W
Model
TIB 120-124EX
100-240 VAC, 50-60 Hz
1.50-0.78 A
L
N
©
Copyright 2019 Traco Electronic AG
Specifications can be changed without notice!
Rev. March 22, 2019
www.tracopower.com
Page 6 of 6