TIS150-148 [TRACOPOWER]
Industrial Power Supplies (TIS Series, 50?600 Watt); 工业电源( TIS系列, 50 ? 600瓦)型号: | TIS150-148 |
厂家: | TRACO ELECTRONIC AG |
描述: | Industrial Power Supplies (TIS Series, 50?600 Watt) |
文件: | 总12页 (文件大小:297K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Industrial Power Supplies
TIS Series
75 - 600 Watt
Features
Switch mode power supplies for
DIN-rail mounting
4 power ranges with 3, 6, 12 and 24 A
output current (24 VDC models)
Selectable 115/ 230 VAC input
Very low ripple and noise
EMI complies with EN50081-2 and
EN50082-2
Conducted EMI to EN55011 class B
For system operation available with
built-in functions:
RED: Redundancy module for N+1
systems with true current sharing.
SIG: Signal module with AC-Power-
fail, DC- OK Signal and
The switching power supplies of the TIS series have been particulary de-
signed for applications in industrial process control systems and machine
tools. Excellent specifications and high immunity against electrical distur-
bances guarantee reliable power for sensitive loads in rugged industrial
environments. With help of optional function modules specific requirements
for system applications can be met by a standard product. With the UDS
module the power supplies can be extended to a perfect DC-UPS with auto-
matic battery- backup. This function is very often required in applications
where a time delayed shutdown of a system is necessary. To monitor and
control the power supply a signal module can be installed. For parallel
operation with active power sharing a redundancy option is available. This
flexibility makes the TIS series power supplies a cost effective solution for
many industrial applications.
external ON/ OFF control
UDS: DC-UPS module for uninter-
ruptable battery backed-up
power systems.
Worldwide Safety Approvals
Easy snap-on mounting on DIN-rails
or chassis mounting
2 Year Product Warranty
Models
Ordercode
Input Voltage
Output Power
max.
Output Voltage
nom.
Output Current
max.
(includes terminal plugs)
TIS 75-112
TIS 75-124
TIS 75-148
12 VDC
24 VDC
48 VDC
6.0 A
3.0 A
1.5 A
115 / 230 VAC
selectable
75 W
TIS 150-124
TIS 150-148
115 / 230 VAC
selectable
24 VDC
48 VDC
6.0 A
3.0 A
150 W
TIS 300-124
TIS 300-148
TIS 300-172
24 VDC
48 VDC
72 VDC
12 A
6.0 A
4.2 A
115 / 230 VAC
selectable
300 W
500 W
TIS 500-124
230 VAC
24 VDC
20 A
TIS 600-124
TIS 600-128
TIS 600-148
TIS 600-172
24 VDC
28 VDC
48 VDC
72 VDC
24 A
22 A
12 A
8.5 A
115 / 230 VAC
selectable
600 W
300 W
TIS 300-124 DCI
300 - 800 VDC
24 VDC
12 A
http:/ / www.tracopower.com
Page 1
Industrial Power Supplies
TIS Series
75-600 Watt
Input Specifications
Input voltage range – TIS 75, TIS 150, TIS 300, TIS 600
93 – 132 VAC / 187 – 264 VAC
187 – 264 VAC
– TIS 500
– TIS 300 DCI
300 – 800 VDC
Input frequency
47 – 63 Hz
Input current at full load (typ.)
– TIS 75
115 VAC
1.7 A
230 VAC
0.9 A
– TIS 150
3.0 A
1.7 A
– TIS 300
5.4 A
3.3 A
– TIS 500
5.5 A
– TIS 600
10.5 A
6.4 A
Inrush current (< 2 ms)
– TIS 75
115 VAC
< 16.5 A
230 VAC
< 33 A
< 70 A
< 70 A
< 70 A
< 80 A
– TIS 150
< 35
< 35
A
A
– TIS 300
– TIS 500
– TIS 600
< 70
A
Output Specifications
Output voltage adj. range – 12 VDC models
– 24 VDC models
12 – 14 VDC
24 – 28 VDC
28 – 32 VDC
– 28 VDC models
– 48 VDC models
48 – 52 VDC (48 – 55 VDC on request))
60 – 76 VDC
– 72 VDC models
Regulation – Input variation
± 0.2 % max.
– Load variation (10 – 90 %) – TIS 75, TIS 150
± 1.0 % max.
– TIS 300, TIS 500, TIS 600
± 0.3 % max.
(± 1.5 % in parallel operation)
Ripple and Noise (20MHz Bandwidth)
< 50 mV pk-pk
Electronic short circuit protection
current limitation at 110 % typ.
(constant current, automatic restart)
Overvoltage protection, triggerpoint at
140 % typ. Vout nom.
Hold-up time
– TIS 75 ... TIS 300
– TIS 500
115 VAC
230 VAC
min. 30 ms
min. 40 ms
min. 25 ms
min. 25 ms
– TIS 600
min. 15 ms
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http:/ / www.tracopower.com Page 2
Industrial Power Supplies
TIS Series
75-600 Watt
General Specifications
Temperature ranges – Operating (ambient temp.)
– Derating above 50 °C
– 25 °C…+70 °C max.
2% / °C
– Storage (non operating)
Humidity (non condensing)
Temperature coefficient
– 25 °C…+ 85 °C
95 % rel H max.
0.02 % / °C
Switching frequency
80 kHz typ. (Pulswidth modulation)
Efficiency
– TIS 75 ... TIS 300
– TIS 500
85 % typ.
90 % typ.
88 % typ.
– TIS 600
Isolation
according to EN 60950, UL 1950, UL 508C
Reliability, calculated MTBF (MIL-HDBK-217 E) – TIS 75 / 150
450000 h @ +25°C/ 420000 h @ +25°C
360000 h @ +25°C/ 340000 h @ +25°C
300000 h @ +25°C
– TIS 300 / 500
– TIS 600
Safety standards
Safety approvals
IEC 60950, EN 60950 (SELV),
UL/ cUL 1950, UL 508C
UL/ cUL 1950 recognized, File E18138
UL/ cUL 508C listed, File E210002
UL/ cuL 1604 listed, File E213613 (Class I,Division
2, Groups A, B, C and D hazardous locations)
CB-Scheme
Electromagnetic compatibility (EMC), Emissions
EN 50081-1 / EN 50081-2
EN 55011 class B, EN 55022 class B,
FCC part 15, level B
– Conducted RI suppression on input
– Radiated RI suppression
EN 55011 class A, EN 55022 class A,
FCC part 15, level A
Electromagnetic compatibility (EMC), Immunity
– Electrostatic discharge (ESD)
EN 50082-2
IEC / EN 61000-4-2 4 kV / 8 kV
IEC / EN 61000-4-3 10 V / m
IEC / EN 61000-4-4 2 kV
IEC / EN 61000-4-5 2 kV / 4 kV
IEC / EN 61000-4-6 10 V
IEC / EN 61000-4-8 30 A / m
– Radiated RF field immunity
– Electrical fast transient / burst immunity
– Surge immunity
– Immunity to conducted RF disturbances
– Power frequency field immunity
Safety class
Degree of Protection 1 (IEC 536)
IP 20 (IEC 529)
Case protection
Environment
– Vibration
– Shock
IEC 60068-2-6,1 gn, 200 sweeps, each axis
IEC 60068-2-27, 15 gn, 11 ms, each axis
Enclosure material
Aluminium (chassis) / stainless steel (cover)
Mounting (snap-on with selflocking spring)
for 35 mm DIN-rails as per EN 50022
Connection
Plugable screw terminals (plugs included)
(TIS 600: screw terminal blocks)
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http:/ / www.tracopower.com Page 3
Industrial Power Supplies
TIS Series
75-600 Watt
PowerSupplieswithRedundancyFunction
With this option a parallel operation of up to 5 units is possible. Decoupling diodes and current share lines allow to build
true N +1 redundant systems with active current sharing for all units. This function also includes an alarm relay to signal
a single unit failure.
This option is available for TIS 150 W, TIS 300 W and TIS 600 W models. Please note: A combination with other
options is not possible.
Models
Ordercode
Input Voltage
Output Power
max.
Output Voltage
nom.
Output Current
max.
(includes terminal plugs)
TIS 150-124 RED
TIS 150-148 RED
115 / 230 VAC
selecta ble
24 VDC
18 VDC
6.0 A
12 A
150 W
300 W
600 W
TIS 300-124 RED
TIS 300-148 RED
115 / 230 VAC
selecta ble
24 VDC
48 VDC
12 A
6.0 A
TIS 600-124 RED
TIS 600-148 RED
115 / 230 VAC
selecta ble
24 VDC
48 VDC
24 A
12 A
Con1
Pin3
Con2 - Pin3/ 4
+Vout
L
AC
Bus
Indica tor
Con1
Pin2
DC
-Vout
N
Con2 - Pin1/ 2
Con1
Pin1
Current
Share-
line
I-Sense
V-Sense
Con3 - Pin4
Con3 - Pin3
Con3 - Pin2
Con3 - Pin1
Unit OK
Common
Unit OK
Regula tor
Unit
O K
Specifications
Raiting per relay contact
60 VDC / 0.36 A max.
Specifications can be changed without notice
http:/ / www.tracopower.com
Page 4
Industrial Power Supplies
TIS Series
75-600 Watt
Power Supplies with Powerfail Functions
These models provide 3 functions required in many process control system applications:
• AC-Powerfail signal (relay contact)
• DC-OK signal (relay contact)
• Remote ON/ OFF
Models
Ordercode
Input Voltage
Output Power
max.
Output Voltage
nom.
Output Current
(includes terminal plugs)
max.
TIS 150-124 SIG
TIS 150-148 SIG
115 / 230 VAC
selectable
24 VDC
48 VDC
6.0 A
3.0 A
150 W
300 W
600 W
TIS 300-124 SIG
TIS 300-148 SIG
115 / 230 VAC
selectable
24 VDC
48 VDC
12 A
6.0 A
TIS 600-124 SIG
TIS 600-148 SIG
115 / 230 VAC
selectable
24 VDC
48 VDC
24 A
12 A
Con1
Pin3
Con2 - Pin3/ 4
L
+Vout
AC
O utput
O K
Con1
Pin2
DC
N
-Vout
Con2 - Pin1/ 2
Con1
Pin1
Con3 - Pin2
Con3 - Pin1
+
Remote
O N/ O FF
-
Con3 - Pin7
Con3 - Pin6
Common
AC-Powerfail
Mains
Fail
Detection
Ma ins O K
(Relay A)
Con3 - Pin5
Con3 - Pin4
Con3 - Pin3
DC-O K
Common
DC-O K
DC-O K
Detection
DC-O K
(Relay B)
Specifications
DC-OK signal trigger point – Models with 24 Vout
– Models with 48 Vout
> 22.8 VDC ± 0.5 V
> 45.6 VDC ± 1.0 V
relay B closed (pin 4 – pin 3)
relay B closed (pin 4 – pin 3)
AC-Powerfail signal
Vin < 93 resp. < 187 VAC relay A closed (pin 7 – pin 6)
Raiting per relay contact
60 VDC / 0.36 A max.
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http:/ / www.tracopower.com Page 5
Industrial Power Supplies
TIS Series
75-600 Watt
DC-UPS-System
In addition to the standard power supply function, these
models include a professional battery management system
to charge and monitor an external battery. In case of a
power failure the battery is switched automatically and
without any interruption to the DC-output. If mains power
is available again, the battery is switched off. The hold-up
time is limited only by battery capacity and load. Charge
current and voltage can be adjusted to values as required
by battery type. Power fail and low battery alarm signals
are available via two independent relay contacts. During
norma l opera tion the ba ttery sta tus is monitored by
periodically loading the battery for short time. If a cell
resistance is high, there is a relay alarm available. The
battery is fully protected under any operational conditions.
The power supply is short circuit protected even in battery-
backup operation, however for safety reason the battery
should be fused with a fast blow fuse. Battery mode can
be activated by connection of Pin 7 and 8.
Complete external battery modules (3.2 Ah or 7 Ah standard) with lead batteries are available on request.
Models
Ordercode
Input Voltage
Output Power
max.
Output Voltage
nom.
Output Current
max.
(includes terminal plugs)
115 / 230 VAC
selectable
TIS 300-124 UDS
TIS 600-124 UDS
300 W
600 W
24 VDC
24 VDC
12 A
24 A
115 / 230 VAC
selectable
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http:/ / www.tracopower.com Page 6
Industrial Power Supplies
TIS Series
75-600 Watt
DC-UPS-System
Con3 - Pin2
Con3 - Pin1
Ba ttery +
Ba ttery -
L
V
Battery Charger
I
Con1
Pin3
+Vout
AC
Con2 - Pin3/ 4
O utput
O K
Con1
Pin2
DC
N
-Vout
Con2 - Pin1/ 2
Con1
Pin1
VBat>18V
Bat ON/ OFF
Mains Fail
Ba ttery Switch
Logic
Con4
Pin8
Con4 - Pin3
Con4 - Pin2
Con4 - Pin1
AC-Powerfail
Common
AC-Power OK
Mains
Fail
Detection
Con4
Pin7
AC-Powerfa il
(Relay A)
Con4 - Pin6
Con4 - Pin5
Con4 - Pin4
Ba ttery Low / failure
Common
Battery O K
Battery
Test
Low Ba ttery
(Relay B)
Specifications
Charging current (factory set)
– TIS 300-124 UDS
– TIS 600-124 UDS
1.2 A
2.4 A
Adjustment range of charging current – TIS 300-124 UDS
– TIS 600-124 UDS
0.15...1.5 A
0.25...2.5 A
Holding current for charging battery atvoltage 27.3 VDC
Overload at short circuit during battery operation
< 50 mA
system switches off
AC-Powerfail signal
Vin < 93 resp. < 187 VAC
Battery voltage below 22 V
relay A closed (pin 2 – pin 3)
relay B closed (pin 5 – pin 6)
60 VDC / 0.36 A max.
Low battery signal
Raiting per relay contact
During battery charge operation
output current reduction by 1.4 x battery charge current
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http:/ / www.tracopower.com Page 7
Industrial Power Supplies
TIS Series
75-600 Watt
Battery-Pack for DC-UPS Systems
The Battery Pack contains high quality, maintenance free lead-acid batteries with 3.2 Ah resp. 7.0 Ah capacity. The
batteries are fixed together with a re-settable electronic fuse on a solid mounting frame. Together with power supply
models TIS 300-124 UDS or TIS 600-124 UDS the battery pack provides a complete and reliable DC-UPS system.
Backup time is depending on load current and battery capacity.
Models
Ordercode
Battery Voltage
Battery Capacity
Permissable Charge
Current max.
(25°C, 20h-rate)
TIS 24-32 AP
TIS 24-70 AP
24 VDC
24 VDC
3.2 Ah
7.0 Ah
1.2 A
2.4 A
Specifications
Max. charge voltage
Temperature coefficient
Temperature range
27...27.6 VDC
– 36mV / °C
– at charge operation
– 15 °C...+50 °C
– 20 °C...+60 °C
– 20 °C...+60 °C
– at load operation
– Storage
Average lifetime on standby operation at tA =20 °C
4...5 years
1.0 m
Cable length
Cable diameter
– TIS 24-32 AP
– TIS 24-70 AP
2.5 mm2 (AWG 12)
4.0 mm2 (AWG 11)
Weight
– TIS 24-32 AP
– TIS 24-70 AP
4.6 kg (10.1 lb)
5.9 kg (13.0 lb)
Recommended combinations – TIS 24-32 AP
(power supplies) – TIS 24-70 AP
TIS 300-124 UDS
TIS 600-124 UDS
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http:/ / www.tracopower.com Page 8
Industrial Power Supplies
TIS Series
75-600 Watt
Optional Mounting Systems Dimensions mm (inches)
TIS 150
TIS 75
L N
+
–
adj
+
–
OUTPUT
INPUT
Nom. Freq.: 50/60 Hz
Nom. Voltage: 115/230 VAC
Nom. Current: 1,7/0,9 A
Nom. Voltage: 24 VDC
Nom. Current: 6 A
Output
O
K
Output
Industrial Switching
Power Supply
Industrial Switching
Output
Power Supply
O
K
Output
Nom. Voltage: 24 VDC
Nom. Current: 3 A
TIS-75-124
TIS150-124
24VDC / 6 A
Input
24VDC / 3 A
CAUTION
Do not open.
Risk of high voltage.
CAUTION
Nom. Freq.: 50/60 Hz
Nom. Voltage: 115/230 V
AC
Do not open. Risk of high voltage.
Nom. Current: 3,7/1,7 A
Read instruction manual.
Read instruction manual.
Check line selection switch
before connection.
N L
Check line selection switch before connection.
56.7 (2.23)
56.7 (2.23)
90 (3.54)
45 (1.77)
157 (6.18)
80 (3.15)
38.5
(1.52)
Weight:
TIS 75 0.48 kg (1.06 lb)
TIS 150 0.80 kg (1.76 lb)
TIS 300
++
– –
Nom. Voltage: 24 VDC
Nom. Current: 12 A
O
K
Output
Output
Industrial Switching
Power Supply
TIS 300-124
24VDC / 12A
Input
Nom. Freq.: 50/60 Hz
CAUTION
Do not open. Risk of high voltage.
Nom. Voltage: 115/230 V
Nom. Current: 5,4/3,3 A
AC
Read instruction manual.
N L
Check line selection switch before connection.
207 (8.15)
130 (5.12)
83 (3.27)
38.5
(1.52)
Weight:
TIS 300
1.4 kg (3.09 lb)
Tolerances: ±0.5 mm (±0.02)
Specifications can be changed without notice
http:/ / www.tracopower.com
Page 9
Industrial Power Supplies
TIS Series
75-600 Watt
Optional Mounting Systems Dimensions mm (inches)
TIS 500
CAUTION
Do not open. Risk of high voltage.
Read instruction manual.
Industrial Switching
Power Supply
TIS 500-124
24VDC / 20A
N L
++
– –
Nom. Freq.: 50/60 Hz
Nom. Voltage: 24VDC
Nom. Current: 20 A
Output
Nom. Voltage: 230 VAC
Nom. Current: 5,3 A
Input
220 (8.66)
130 (5.12)
83 (3.27)
46 (1.81)
Weight:
TIS 500
1.9 kg (4.19 lb)
TIS 600
N L
++
– –
Nom. Freq.: 50/60 Hz
Nom. Voltage: 115/230 VAC
Nom. Current: 10,5/6,4 A
Input
Nom. Voltage: 72 VDC
Nom. Current: 8 A
Output
Industrial Switching
Power Supply
TIS 600-124
24VDC / 24A
CAUTION
Do not open. Risk of high voltage.
Read instruction manual.
Check line selection switch before connection.
243 (9.57)
179 (7.05)
82.6 (3.25)
32
(1.26)
Weight:
TIS 600
2.0 kg (4.41 lb)
Tolerances: ±0.5 mm (±0.02)
Specifications can be changed without notice
http:/ / www.tracopower.com
Page 10
Industrial Power Supplies
TIS Series
75-600 Watt
Optional Mounting Systems Dimensions mm (inches)
Wall mounting
A
7.5 (0.30)
B
C
4.6 (0.18)
Models
Order code
A
B
C
D
E
TIS 75W
MK-75
37 (1.46)
14.5 (0.57)
13.5 (0.53)
13.5 (0.53)
13.5 (0.53)
37.5 (1.48)
–
134.5 (5.30)
134.5 (5.30)
134.5 (5.30)
134.5 (5.30)
197.0 (7.76)
150.5 (5.93)
150.5 (5.93)
150.5 (5.93)
150.5 (5.93)
207.0 (8.15)
TIS 150W
TIS 300W
TIS 500W
TIS 600W
MK-150
MK-300
MK-500
MK-600
132 (5.20)
132 (5.20)
132 (5.20)
190 (7.48)
105 (4.13)
105 (4.13)
105 (4.13)
115 (4.53)
Rugged DIN-Rail mounting
A
B
C
countersink M4
Models
Order code
A
B
C
TIS 150W
TIS 300W
TIS 500W
TIS 600W
RMK-150
RMK-300
RMK-500
standard
t.b.a .
t.b.a .
t.b.a .
t.b.a .
t.b.a .
t.b.a .
t.b.a .
t.b.a .
t.b.a .
180 (7.09)
165 (6.50)
15.0 (0.59)
Tolerances: ±0.5 mm (±0.02)
Specifications can be changed without notice
http:/ / www.tracopower.com
Page 11
Industrial Power Supplies
TIS Series
75-600 Watt
Outline Dimensions mm (inches)
204 (8.03)
184 (7.24)
TIS-24-32 AP
14
(0.55)
Detail A
7
(0.28)
A
A
)
)
)
5
(
1
(
(
(
1
1
7
(0.28)
B
B
Detail B
9
(
(
6
Weight (incl. batteries):
TIS-24-32 AP
TIS-24-70 AP
4.6 kg (10.1 lb)
5.9 kg (13.0 lb)
272 (10.71)
252 (9.92)
TIS-24-70 AP
A
A
)
(
(
1
1
B
B
(
6
Specifications can be changed without notice
Tolerances: ±0.5 mm (±0.02)
Rev. 05/ 01
Jenatschstrasse 1 • CH-8002 Zurich • Switzerland
Tel. +41-1284 2911 • Fax +41-1201 1168 • e mail: sales traco.ch • internet: http:// www.tracopower.com
Page 12
-
@