TSP480-124-3PAC500 [TRACOPOWER]

Industrial Power Supplies;
TSP480-124-3PAC500
型号: TSP480-124-3PAC500
厂家: TRACO ELECTRONIC AG    TRACO ELECTRONIC AG
描述:

Industrial Power Supplies

文件: 总6页 (文件大小:522K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Industrial Power Supplies  
TSP-3P Series, 240–960 Watt  
CB  
Features 200% Peak Power!  
Scheme  
EMC  
LVD  
IEC 60950-1 UL 60950-1  
UL 508  
ATEX II3G  
IECEx  
EN 60950-1  
EN 61558-2-16  
EN 60204  
3-phase input 3AC 400V or 3AC 500V  
200 % boost power for up to 5 seconds  
Alternative to AC transformers  
Fully regulated 24 VDC output with  
10 A, 20 A or 40 A  
Rugged metal case design qualified for  
harsh industrial environment  
High efficiency >92%  
Operating temperature range:  
–25°C to +60°C (full power)  
Overload and over temperature protection  
Industrial safety approvals  
Cost effective design  
3-year product warranty  
The TRACOPOWER TSP-3P series of high performance DIN-rail power supplies of-  
fers an economical solution to generate a regulated DC voltage from three-phase  
mains networks. The smart design achieves a very high efficiency at ultra compact  
size and very competitive cost. The series provides models with 240, 480 and 960  
Watt output power all with additional power reserve of up to 200%.  
This high peak power guarantees a reliable start-up of loads with high inrush cur-  
rents such as motors, valves and other industrial loads. In many applications these  
switching power supplies can also replace mains transformers with rectifiers.  
Models  
Order Code  
Output Power  
Input Voltage  
Output Voltage  
*Output Current  
(nom.)  
(nom.)  
(nom.)  
(nom.)  
TSP 240-124-3PAC400  
TSP 240-124-3PAC500  
TSP 480-124-3PAC400  
TSP 480-124-3PAC500  
TSP 960-124-3PAC400  
TSP 960-124-3PAC500  
3 AC 400 V  
3 AC 500 V  
3 AC 400 V  
3 AC 500 V  
3 AC 400 V  
3 AC 500 V  
24 VDC  
24 VDC  
24 VDC  
24 VDC  
24 VDC  
24 VDC  
10 A  
10 A  
20 A  
20 A  
40 A  
40 A  
240 W  
480 W  
960 W  
* 200% peak current for up to 5 sec.  
http://www.tracopower.com  
Page 1 of 6  
Industrial Power Supplies  
TSP-3P Series  
240–960 Watt  
Input Specifications  
Input voltage range  
star-net configuration (2-phase operation not possible)  
400 VAC models: 320 – 440 VAC  
500 VAC models: 400 – 550 VAC (derating below 410 VAC see graph 2)  
Input voltage frequency  
Harmonic limits  
47 – 63 Hz  
EN 61000-3-2, Class B (for <16 A per phase)  
>0.8 at full load  
Power factor  
Recommended circuit breaker,  
6.0 A characteristic B  
Output Specifications  
Output voltage:  
24 VDC (fixed)  
Regulation  
– Input / load variation  
1 % max. + voltage drop at low input voltage and/or  
boost power, see graph 1 & 2  
Boost power  
– max. current  
– duty cycle  
200 % of nominal output current  
<10 %  
– max. cycle time  
– input voltage requirements  
5 sec limited by timer (automatic restart after 30 sec.)  
see graph 1 & 2  
Ripple and noise  
(20MHz bandwidth)  
– nominal operation  
– boost power operation  
100 mV pk-pk typ.  
up to 750 mV pk-pk  
Rise time  
200 ms typ.  
Current limitation  
at 230 % of nominal output current, constant current  
33 V typ.  
Overvoltage protection  
Overtemperature protection  
Power back immunity  
switch off at overtemperature (automatic restart)  
35 VDC continuouse, 40 VDC for one second  
Output Power Derating  
Graph 1: 400 VAC input models  
Graph 2: 500 VAC input models  
VDCout  
25  
VDCout  
25  
100%load
24  
50% load  
24  
23  
22  
21  
23  
22  
21  
VACin  
VACin  
320 330 340 350 360 370  
430 440  
400 410 420 430 450 460  
540 550  
General Specifications  
Temperature range  
– Full power operation  
– Max. operating  
– Start up  
–25°C to +60°C  
+70°C, 2.5 %/K derating above +60°C  
–40°C  
– In accordance to UL508  
–25°C to +40°C  
Cooling  
convection cooling, no internal fan  
95 % rel. H max.  
Humidity (non condensing)  
Reliability, calculated MTBF at +25°C acc. to IEC 61709 – TSP 240 & 480 >1 Mio h  
– TSP 960 >800‘000 h  
Isolation  
according to IEC/EN 60950-1, UL 60950-1, UL 508  
Class of protection  
Degree of protection  
safety class I (IEC 536)  
IP 20 (IEC/EN 60529)  
http://www.tracopower.com  
Page 2 of 6  
Industrial Power Supplies  
TSP-3P Series  
240–960 Watt  
General Specifications  
Electromagnetic compatibility (EMC), Emissions  
EN 61000-6-3  
– Conducted RI suppression on input  
– Radiated RI suppression  
Electromagnetic compatibility (EMC), Immunity  
EN 55011 class B, EN 55022 class B,  
EN 55011 class B, EN 55022 class B,  
EN 61000-6-2  
– Electrostatic discharge (ESD)  
– Radiated RF field immunity  
IEC/EN 61000-4-2  
IEC/EN 61000-4-3  
8 kV / 15 kV criteria tba  
10 V/m  
4 kV  
criteria tba  
criteria tba  
criteria tba  
criteria tba  
criteria tba  
criteria tba  
criteria tba  
criteria tba  
criteria tba  
– Electrical fast transient  
burst immunity input IEC/EN 61000-4-4  
burst immunity output IEC/EN 61000-4-4  
L – L IEC/EN 61000-4-5  
2 kV  
2 kV  
– Surge immunity  
L – PE IEC/EN 61000-4-5  
4 kV  
+ Output – - Output IEC/EN 61000-4-5  
+ Output – PE IEC/EN 61000-4-5  
– Output – PE IEC/EN 61000-4-5  
0.5 kV  
0.5 kV  
0.5 kV  
10 V  
– Immunity to conducted RF disturbances  
– Mains voltage dips and interruptions  
IEC/EN 61000-4-6  
IEC/EN 61000-4-11  
Safety standards  
– Information technology equipment  
– Industrial control equipment  
IEC/EN 60950-1, UL 60950-1  
UL 508 listed, CSA C22.2 No. 107.1  
– Equipment for use in explosive atmospheres  
– Electrical equipment for machines  
– Electronic equipment for power installations  
– Safety of power transformers  
IEC 60079-0, IEC 60079-15, ATEX 94/9/EC  
EN 60204  
EN 50178  
EN 61558-2-16  
Safety approvals and  
– CB report for IEC 60950-1  
– SIQ certificate for EN 60950-1  
– IECEx test report for IEC 60079-15  
www.tracopower.com/products/tsp3p-cb.pdf  
www.tracopower.com/products/tsp3p-siq.pdf  
www.tracopower.com/products/tsp3p-iecex.pdf  
www.tracopower.com/products/tsp3p-atex.pdf  
www.tracopower.com/products/tsp3p-ul508.pdf  
II3G Ex nA nC llC T3  
– UL approvals for UL 508 listed  
– Curtis-Straus certificate for UL 60950-1 (2nd) www.tracopower.com/products/tsp3p-ul.pdf  
– Bureau Veritas for other standards  
www.tracopower.com/products/tsp3p-bv.pdf  
Environmental compliance – Reach  
www.tracopower.com/products/tsp3p-reach.pdf  
RoHS directive 2002/95/EC  
– RoHS  
Environment  
Status signals  
– Vibration acc. IEC 60068-2-6;  
– Shock acc. IEC 60068-2-27  
0.075 mm / 10 – 55 Hz,  
11ms / 15 g  
– DC-OK relay contact  
DC OK = contact closed at >20...22 VDC  
rated: 30 VDC/1.0 A for 24 VDC models  
green LED at >20...22 VDC  
– DC-OK indication  
– Phase error indication  
red blinking LED if one or two phases are missing  
(function only if earth is connected)  
– Overload / Overtemperature  
– Automatic restart indication  
red LED on at >100% nominal load (5 sec. count down  
for boost power is activated)  
red blinking LED at temperature shut down (manual  
restart required - mains disconnect for 5 sec.)  
red blinking LED during overload recovery periode  
Enclosure material  
Mounting  
aluminium (chassis) / stainless steel (cover)  
– DIN-rail mounting  
for DIN-rails as per EN 50022-35x15/7.5  
(snap-on with self-locking spring)  
– Wall mounting (option)  
with wall mounting bracket - see page 6  
Connection  
screw terminals  
Installation instructions  
www.tracopower.com/products/tsp3p-inst.pdf  
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.  
http://www.tracopower.com  
Page 3 of 6  
Industrial Power Supplies  
TSP-3P Series  
240–960 Watt  
Outline Dimensions  
54.0 (2.13)  
110.0 (4.33)  
240 Watt models  
_
+
DC-OK  
DC-ON  
OVER-LOAD  
RESTART  
PHASE FAULT  
L1 L2 L3  
25.0  
(0.98)  
14.5  
(0.57)  
Weight: 575 g (1.27 lb)  
80.0 (3.15)  
125.0 (4.92)  
480 Watt models  
_
_
+ +  
DC-OK  
DC-ON  
OVER-LOAD  
RESTART  
PHASE FAULT  
L1 L2 L3  
46.0  
(1.81)  
17.0  
(0.67)  
25.0  
(0.98)  
25.0  
(0.98)  
Weight: 1.05 kg (2.31 lb)  
Dimensions in [mm], ( ) = Inch  
Tolerances: 0.5 mm ( 0.02)  
http://www.tracopower.com  
Page 4 of 6  
Industrial Power Supplies  
TSP-3P Series  
240–960 Watt  
Outline Dimensions  
960 Watt models  
Weight: 2.35 kg (5.19 lb)  
25.0  
(0.98)  
25.0  
(0.98)  
21.0  
(0.83)  
123.0  
(4.84)  
125.0 (4.92)  
165.0 (6.50)  
OVER-LOAD  
RESTART  
DC-OK  
DC-ON  
_
_
PHASE FAULT  
+
+
L1 L2 L3  
Dimensions in [mm], ( ) = Inch  
Tolerances: 0.5 mm ( 0.02)  
http://www.tracopower.com  
Page 5 of 6  
Industrial Power Supplies  
TSP-3P Series  
240–960 Watt  
TSP–WMK Wall Mounting Bracket  
Order code  
For models  
Content of kit  
TSP-WMK03  
TSP-WMK02  
240 W  
480 W & 960 W  
1 bracket  
2 brackets  
85.0 (3.35)  
TSP-WMK03  
42.5 (1.67)  
34.5 (1.36)  
34.5 (1.36)  
ø
ø
4.25 (0.17)  
4.25 (0.17)  
TSP 240-124-3PAC400  
TSP 240-124-3PAC500  
ø
4.25 (0.17)  
R 2.12 (0.083)  
2.0 (0.08)  
4 x positioning holes  
15.0  
(0.59)  
15.0  
(0.59)  
TSP-WMK02  
Material: 2 mm Mild Steel  
Tolerance: 0.1mm ( 0.004)  
46.0 (1.81)  
33.0 (1.30)  
TSP 480-124-3PAC400  
TSP 480-124-3PAC500  
96.0 (3.78)  
25 (0.98)  
ø
4.3 (0.17)  
2x  
ø4.3 (0.17)  
TSP 960-124-3PAC400  
TSP 960-124-3PAC500  
4 x positioning holes  
173.0 (6.81)  
15.0  
(0.59)  
Specifications can be changed any time without notice.  
Rev. 03/12  
Jenatschstrasse 1 · CH-8002 Zurich · Switzerland  
Tel. +41 43 311 45 11 · Fax +41 43 311 45 45 · info@traco.ch · www.tracopower.com  
Page 6 of 6  

相关型号:

TSP4B137M010AH6710D540

TSP, Tantalum, Polymer Tantalum, HRA, 130 uF, 20%, 10 VDC, 4B
KEMET

TSP4B277M006AH6510D540

TSP, Tantalum, Polymer Tantalum, HRA, 270 uF, 20%, 6.3 VDC, 4B
KEMET

TSP4B277M006AH6610D540

TSP, Tantalum, Polymer Tantalum, HRA, 270 uF, 20%, 6.3 VDC, 4B
KEMET

TSP4B607M003AH6610D540

TSP, Tantalum, Polymer Tantalum, HRA, 600 uF, 20%, 3 VDC, 4B
KEMET

TSP4D138M006AH6610D540

TSP, Tantalum, Polymer Tantalum, HRA, 1,300 uF, 20%, 6.3 VDC, 4D
KEMET

TSP4D197M016AH6510D540

Tantalum Capacitor, Polarized, Tantalum (solid Polymer), 16V, 20% +Tol, 20% -Tol, 190uF, Surface Mount, 3531
KEMET

TSP4D197M016AH6620D540

TSP, Tantalum, Polymer Tantalum, HRA, 190 uF, 20%, 16 VDC, 4D
KEMET

TSP4D197M016AH6720D540

TSP, Tantalum, Polymer Tantalum, HRA, 190 uF, 20%, 16 VDC, 4D
KEMET

TSP4D407M010AH6610D540

TSP, Tantalum, Polymer Tantalum, HRA, 400 uF, 20%, 10 VDC, 4D
KEMET

TSP4D407M010AH6620D540

TSP, Tantalum, Polymer Tantalum, HRA, 400 uF, 20%, 10 VDC, 4D
KEMET

TSP4D407M010AH6710D540

TSP, Tantalum, Polymer Tantalum, HRA, 400 uF, 20%, 10 VDC, 4D
KEMET

TSP4D407M010AH6720D540

TSP, Tantalum, Polymer Tantalum, HRA, 400 uF, 20%, 10 VDC, 4D
KEMET