PSME-1200-30 [WALL]
AC/DC Switching Power Supplies;型号: | PSME-1200-30 |
厂家: | WALL INDUSTRIES,INC. |
描述: | AC/DC Switching Power Supplies |
文件: | 总7页 (文件大小:889K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
PSME1200 SERIES
Rev A
Wall Industries, Inc.
1200 Watts, Medical AC/DC Switching Power Supplies
FEATURES
• RoHS Compliant
• Remote Setting Multiple PSU via RS232, RS485 & I2C
• Programmable Output Voltage (0~105%)
• 1200 Watts Output Power
• High Efficiency up to 93%
• 4000VAC I/O Isolation (2 x MOPP)
• Constant Current Limiting
• Global Control via RS232
• Programmable Output Current (0~105%)
• Universal Input Voltage Range: 90~264VAC (127~370VDC)
• Single Outputs Ranging from 12VDC to 60VDC
• Selectable +5V/0.5A or +9V/0.3A Auxiliary Output
• Power OK Signal (Power Good, Logic Low) • Forced Current Sharing at Parallel Operation
• Remote ON/OFF, Remote Sense Functions • ANSI/AAMI ES60601-1, TUV EN60601-1: 2006, IEC60601-1
• Protection: OLP, OVP, OTP, Fan Failure
Medical Approvals
DESCRIPTION
Size:
Weight
The PSME1200 series of medical AC/DC switching power supplies provides 1200 Watts of output power in
a 10.256” x 5.000” x 2.500” enclosed case. This series consists of single output models ranging from 12VDC
to 60VDC with a universal input voltage range of 90~264VAC (127~370VDC). Standard features include
high efficiency up to 93%, programmable output voltage and output current, remote on/off, and power OK
signal. This series also has over temperature, over voltage, and over load protection. These supplies also
feature a low leakage current of less than 300μA (earth) and less than 100µA (patient) at 264VAC and are
designed to withstand 4000VAC input to output isolation (2 x MOPP). All models are RoHS compliant and
have ANSI/AAMI ES60601-1, TUV EN60601-1: 2006, and IEC60601-1 medical approvals.
10.256 x 5.000 x 2.500 inches 5.73 lbs (2.6kg)
(260.50 x 127.00 x 63.50 mm)
MODEL SELECTION TABLE
Model Number Input Voltage (2) Output Voltage Output Current Line Regulation Load Regulation Output Power Ripple & Noise (1) Efficiency
PSME-1200-12
PSME-1200-15
PSME-1200-24
PSME-1200-30
PSME-1200-36
PSME-1200-48
PSME-1200-60
12 VDC
15 VDC
24 VDC
30 VDC
36 VDC
48 VDC
60 VDC
100A
80A
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1200W
1200W
1200W
1200W
1202.4W
1200W
1200W
120mVp-p
150mVp-p
150mVp-p
150mVp-p
150mVp-p
150mVp-p
150mVp-p
89%
90%
91%
92%
92%
93%
93%
50A
90~264 VAC
40A
(127~370 VDC)
33.4A
25A
20A
NOTES
1. Ripple & noise is measured at 20MHz limited bandwidth and using a 12" twisted pair-wire terminated with a 0.1µF & 47µF capacitors in parallel.
2. For voltages near the low end of the input voltage range, see the derating curve for the power supply output rating.
3. When in parallel operation only one unit might operate if the total output load is less than 5% of the rated load condition.
4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
DERATING CURVES
Load vs Ambient Temperature
Load vs Input Voltage
120
120
Ta=25°C
100
90
80
70
60
50
40
100
80
60
40
20
-20
0
10
20
30
40
50
60
70
80
90
264
100
110
120
Ambient Temperature (°C)
Input Voltage (VAC)
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797
website: www.wallindustries.com • e-mail: sales@wallindustries.com
06/05/2014
Page 1 of 7
PSME1200 SERIES
Rev A
Wall Industries, Inc.
1200 Watts, Medical AC/DC Switching Power Supplies
SPECIFICATIONS: PSME1200 SERIES
All specifications are based on 25°C, Nominal Input Voltage, and Maximum Output Current unless otherwise noted.
We reserve the right to change specifications based on technological advances.
SPECIFICATION
INPUT SPECIFICATIONS
TEST CONDITIONS
Min
Typ
Max
Unit
AC input voltage range
DC input voltage range
90
127
47
264
370
63
VAC
VDC
Hz
Input Voltage (See Note 2)
Input Frequency
AC Current
At 115VAC and full load
At 230VAC and full load
At 115VAC and cold start
At 230VAC and cold start
At 115VAC and full load
At 230VAC and full load
14.5
6
A
A
30
45
Inrush Current
Power Factor
0.99
0.95
OUTPUT SPECIFICATIONS
Output Voltage
See Table
Voltage Tolerance
Voltage Adjustability
Line Regulation
Load Regulation
Output Power
Includes set-up tolerance, line regulation, and load regulation
Typical adjustment by potentiometer (VR1)
Low Line to High Line
-2.0
-5.0
-1.0
-1.0
+2.0
+5.0
+1.0
+1.0
%
%
%
%
0% to 100% full load
See Table
Output Current
See Table
See Table
Ripple & Noise (20MHz BW)
Hold-up Time
Measured with 0.1µF and 47µF capacitors in parallel
At 230VAC and full load
full load
16
ms
ms
Setup Time
800
100
Rise Time
full load
ms
Temperature Coefficient
PROTECTION
0~50°C
-0.02
+0.02
%/°C
Over Voltage Protection (see page 7) Protection type: latch-style. Recovery after reset AC power ON or inhibit
Variable OVP, 120% 7% Vout
105% rated output power
Over Load Protection
Over Temperature Protection
GENERAL SPECIFICATIONS
Efficiency
Protection type: constant current limit
Protection type: shut down o/p voltage; auto-recovery after temp. goes down
100°C 5°C detect on heatsink of sec. side
See Table
4000
Input to Output 2 x MOPP
Isolation Voltage
Input to FG
Test is done without enclosure
1800
500
100
100
100
VAC
Output to FG
Input to Output 500VDC
Isolation Resistance Input to FG
Output to FG
500VDC
MΩ
µA
500VDC
Earth
Leakage Current
Patient
At 264VAC
At 264VAC
300
100
FUNCTIONS
Auxiliary Power
Selectable +5V/0.5A or +9V/0.3A aux. output
By external switch
Remote ON/OFF Control (see page 4) Isolated from output
Power OK Signal
Sink Current: 20mA max.; Drain Voltage: 40V max.
Open drain signal low when PSU turns on
Output Voltage Trim
Output Current Trim
Parallel Operation (Current Sharing)
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature
Storage Temperature
Operating Humidity
Storage Humidity
0
0
105
105
%Vo
%Io
See page 5
See derating curve
Non-condensing
-20
-40
20
+60
+85
90
°C
°C
% RH
% RH
10
95
Cooling
Load and temperature control fan
Vibration
10~500Hz, 2G 10 min./1 cycle, period for 60 min. each along X, Y, Z axes. Certified IEC60068-2-6-2007; IEC60068-2-64-2008
PHYSICAL SPECIFICATIONS
Weight
5.73 lbs (2.6kg)
Dimensions (W x H x D)
SAFETY & EMC (See Note 4)
Safety Approvals
10.256 x 5.000 x 2.500 inches (260.50 x 127.00 x 63.50 mm)
UL/cUL (ANSI/AAMI ES60601-1; CAN / CSA-C22.2 No.60601-1); NFPA 99; TUV (EN60601-1; IEC60601-1); MOPP approval
EMI (Conduction & Radiation)
Harmonic Current
EN55011
EN61000-3-2; EN61000-3-3
EMS Immunity
EN60601-1-2; IEC61000-4-2, 3, 4, 5, 6, 8, 11
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797
website: www.wallindustries.com • e-mail: sales@wallindustries.com
06/05/2014
Page 2 of 7
PSME1200 SERIES
Rev A
Wall Industries, Inc.
1200 Watts, Medical AC/DC Switching Power Supplies
MECHANICAL DRAWING
10.236 [260.50]
Unit: inches [mm]
2.500 [63.50]
2.264 [57.50]
6.378 [162.00]
4-M4 L=4 both sides
5 N C
11.555 [293.50]
CN5
1.417 [36.00]
7.028 [178.50]
4-M4 L=4 both sides
AC Input Terminal
Control Pin Number Assignment (CN5): JST S24B-PHDSS or Equivalent
Pin
1
Function
ACL
Pin
1
Function
NC
Description
For RS232 Receiver Function
For RS232 Transmission Function
+5V/0.5A or +9V/0.3A Auxiliary Power
Ground
Serial Clock used in the I2C Interface
Serial Data used in the I2C Interface
+5V/0.5A or +9V/0.3A Auxiliary Power
Ground
Pin
13
14
15
16
17
18
19
20
21
22
23
24
Function
EN+
AUX
EN-
Description
Inhibit ON/OFF (+)
+5V/0.5A or +9V/0.3A Auxiliary Power
Inhibit ON/OFF (-)
2
ACN
2
NC
3
3
AUX
GND
SCL
4
GND
PAR
Ground
5
Parallel Operation Current Sharing
AUX Output Set
6
SDA
AUX
GND
VCI
VSET
POK
GND
VS-
7
Power OK
8
Ground
9
V Program
Remote Sense (-)
10
11
12
GND
ACI
Ground
VO-
Negative Output Voltage
Remote Sense (+)
I Program
VS+
GND
Ground
VO+
Positive Output Voltage
LED STATUS
LED
LED Signal
Status
Power OK (Local Mode)
Power OK (Remote Mode)
Power Standby
Solid (Green)
Solid (Orange)
Slow Blink (Green)
Fast Blink (Red)
Solid (Red)
Over Voltage Protection (OVP)
Over Load Protection (OLP)
Over Temperature Protection (OTP)
Fan Failure
Slow Blink (Red)
Intermittent Blink (Red)
Interlace Blink (Red)
Power Failure
* Local mode: Use ACI/VCI to control output current and voltage
* Remote Mode: Use RS232 or I2C command to control output current and voltage
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797
website: www.wallindustries.com • e-mail: sales@wallindustries.com
06/05/2014
Page 3 of 7
PSME1200 SERIES
Rev A
Wall Industries, Inc.
1200 Watts, Medical AC/DC Switching Power Supplies
REMOTE ON/OFF
(1) Using Internal 5V Auxiliary Source
(2) ON/OFF Control by NPN Transistor
(3) Using External Voltage Source
AUX
AUX
AUX
SW
2KΩ
EN+
2KΩ
EN+
2KΩ
EN+
SW
AUX
AUX
AUX
AUX
EN-
EN-
Tr
EN-
Ctrl
GND
GND
GND
GND
OFF Power OFF
ON Power ON
L
Power OFF
Power ON
OFF Power OFF
sw
ON Power ON
sw
Default setting
Ctrl
H
POWER OK SIGNAL
* Place an additional capacitor to have a better performance of auxiliary power operation.
P.OK
Good
Failure
AUX
LOAD
470µF
16V
*
DC / DC
5V/0.5A
or
AUX
VSET
9V/0.3A
* The grounding of “AUX” power should be connected to “GND” port. If “V-“ is connected as
Grounding make sure to short the “GND” and “V-“ ports.
GND
Internal Circuit
Open (Default Setting)
Short to GND
5V
9V
VSET
AUX and P.OK Signal
REMOTE SENSE
1) Remote Sense
2) Local Sense (Default Setting)
+
+
-
+
-
+
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797
website: www.wallindustries.com • e-mail: sales@wallindustries.com
06/05/2014
Page 4 of 7
PSME1200 SERIES
Rev A
Wall Industries, Inc.
1200 Watts, Medical AC/DC Switching Power Supplies
CURRENT SHARING
3) Current Sharing with Remote Sense
+
+
+
+
24
VO+
23
24
23
24
23
24
VO+
23
VS+
VS-
VO+
VO-
VS+
VS-
VO+
VO-
VS+
VS-
VS+
VS-
VO-
VO-
GND
POK
GND
POK
GND
POK
GND
POK
VSET PAR
VSET PAR
VSET PAR
VSET PAR
GND
AUX
GND
GND
GND
SDA
GND
NC
EN-
EN+
ACI
GND
AUX
GND
GND
GND
SDA
GND
NC
EN-
EN+
ACI
GND
AUX
GND
GND
GND
SDA
GND
NC
EN-
EN+
ACI
GND
AUX
GND
GND
GND
SDA
GND
NC
EN-
EN+
ACI
VCI
VCI
VCI
VCI
AUX
SCL
AUX
NC
AUX
SCL
AUX
NC
AUX
SCL
AUX
NC
AUX
SCL
AUX
NC
4) Current Sharing with Local Sensing
+
+
+
+
24
VO+
23
24
23
24
23
24
23
VS+
VS-
VO+
VO-
VS+
VS-
VO+
VO-
VS+
VS-
VO+
VO-
VS+
VS-
VO-
GND
POK
GND
POK
GND
POK
GND
POK
VSET PAR
VSET PAR
VSET PAR
VSET PAR
GND
AUX
GND
GND
GND
SDA
GND
NC
EN-
EN+
ACI
GND
AUX
GND
GND
GND
SDA
GND
NC
EN-
EN+
ACI
GND
AUX
GND
GND
GND
SDA
GND
NC
EN-
EN+
ACI
GND
AUX
GND
GND
GND
SDA
GND
NC
EN-
EN+
ACI
VCI
VCI
VCI
VCI
AUX
SCL
AUX
NC
AUX
SCL
AUX
NC
AUX
SCL
AUX
NC
AUX
SCL
AUX
NC
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797
website: www.wallindustries.com • e-mail: sales@wallindustries.com
06/05/2014
Page 5 of 7
PSME1200 SERIES
Rev A
Wall Industries, Inc.
1200 Watts, Medical AC/DC Switching Power Supplies
INSTALLATION INSTRUCTIONS
1. Mounting Directions
1-1 Recommended Standard Mounting Methods
(a)
(b)
(c)
+
4-M4
L=4mm max.
4-M4
L=4mm max.
4-M4
L=4mm max.
2. Mounting Method
2-1 There are ventilating holes on the front and back side panels. Do not obstruct; allow at least 50mm for airflow
2-2 The maximum allowable penetration for the screw is 4mm. Incomplete threading should not be penetrated.
2-3 Recommended torque of mounting screw: M4 screw: 1.27N • m (13.0kgf • cm)
More than 50mm
More than 50mm
FAN
FAN
Airflow
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797
website: www.wallindustries.com • e-mail: sales@wallindustries.com
06/05/2014
Page 6 of 7
PSME1200 SERIES
Rev A
Wall Industries, Inc.
1200 Watts, Medical AC/DC Switching Power Supplies
CURVES
CMD vs Output Curve
VCI vs OVP Curve
COMPANY INFORMATION
Wall Industries, Inc. has created custom and modified units for over 50 years. Our in-house research and development engineers will provide
a solution that exceeds your performance requirements on-time and on budget. Our ISO9001-2008 certification is just one example of our
commitment to producing a high quality, well-documented product for our customers.
Our past projects demonstrate our commitment to you, our customer. Wall Industries, Inc. has a reputation for working closely with its
customers to ensure each solution meets or exceeds form, fit and function requirements. We will continue to provide ongoing support for
your project above and beyond the design and production phases. Give us a call today to discuss your future projects.
Contact Wall Industries for further information:
Phone:
Toll Free:
Fax:
ꢀ(603)778-2300
ꢀ(888)597-9255
ꢀ(603)778-9797
E-mail:
Web:
Address:
sales@wallindustries.com
www.wallindustries.com
37 Industrial Drive
Exeter, NH 03833
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797
website: www.wallindustries.com • e-mail: sales@wallindustries.com
06/05/2014
Page 7 of 7