3
					LDC480 Series  
					LDC480-24 / LDC480-36  
					LDC480-48 / LDC480-72  
					LDC480-24 / LDC480-36  
					LDC480-48 / LDC480-72  
					≤ 1.5%  
					≤ 0.5%  
					≤ 150 mVpp  
					≤ 50 mVpp  
					Load Regulation  
					Ripple & Noise1  
					Hold up Time  
					≥ 25 ms  
					Overload, short circuit, with constant current or hiccup mode (user settable)  
					Thermal protection  
					Input undervoltage lockout  
					Output overvoltage  
					Protections  
					LDC480-24  
					LDC480-36  
					LDC480-48  
					LDC480-72  
					≥ 33 VDC  
					≥ 45 VDC  
					≥ 68 VDC  
					≥ 100 VDC  
					Output Over Voltage Protection  
					Status Signals  
					DC OK - green LED  
					OVERLOAD - red LED  
					DC OK - dry contact (NO, 24 VDC / 1 A)  
					Possible for power or redundancy (with external ORing module)  
					P (models) - include internal ORing circuit  
					LDC480-24 / LDC480-36  
					LDC480-48 / LDC480-72  
					LDC480-24 / LDC480-36  
					LDC480-48 / LDC480-72  
					Parallel Connection2  
					Efficiency  
					> 93%  
					> 94%  
					< 36.5 W  
					< 31 W  
					Dissipated Power  
					1
					Ripple and Noise are measured with 20 MHz bandwidth, probe terminated with a 0.1μF MKP parallel capacitor.  
					Pay attention, set the current limitation mode jumper on C.C. mode when connecting more units in parallel.  
					2
					NOTE: Power rating, losses, efficiency, ripple, thermal behaviour and start-up may change outside of the nominal rated input range.  
					Contact factory for details.  
					UL certified up to 50°C at 120 VAC or  
					Operating Temperature  
					Storage Temperature  
					Derating  
					- 40° to + 70°C  
					- 40° to + 80°C  
					- 7.6 W / °C over 50°C at 120 VAC  
					- 7.2 W / °C over 60°C at 240 VAC  
					up to 60°C at 240 VAC (Start-up type tested: - 40°C)3  
					Humidity  
					Non condensing  
					5 - 95% RH  
					Life Time Expectancy  
					At 25°C ambient, full load  
					167953 h (19.1 years)  
					Overvoltage Category  
					Pollution Degree  
					III (EN50178)  
					2 (IEC60664-1)  
					Protection Class  
					Class I  
					Input to Output  
					Input to Ground  
					Output to Ground  
					UL508 (certified)  
					EN60950 (reference)  
					EN50178 (reference)  
					EN55011 (CISPR11)  
					EN55022 (CISPR22)  
					EN61000-3-2  
					EN61000-4-2  
					EN61000-4-3  
					EN61000-4-4  
					EN61000-4-5  
					4.2 kVDC  
					2.2 kVDC  
					0.75 kVDC  
					Isolation Voltage  
					Safety Standards & Approvals  
					Class B  
					Class B  
					Class A  
					Level 3  
					Level 3  
					Level 3  
					Level 4  
					Level 2  
					Emission  
					EMC Standards  
					Immunity  
					EN61000-4-11  
					Protection Degree  
					Vibration Sinusoidal  
					EN60529  
					IP20  
					5-17.8 Hz: ±1.6 mm;  
					IEC 60068-2-6  
					17.8-500 Hz: 2 g 2Hours / axis (X,Y,Z)  
					30 g 6 ms, 20 g 11 ms; 3 bumps / direction,  
					18 bumps total  
					Shock  
					IEC 60068-2-27  
					3
					Possible with load derating.  
					North America  
					Asia-Pacific  
					Europe, Middle East  
					+1 408 785 5200  
					+86 755 298 85888  
					+353 61 225 977  
					© 2016 Bel Power Solutions & Protection  
					BCD.00757_AB