ADE7761BARS-RL [ADI]

Energy Metering IC with On-Chip Fault and Missing Neutral Detection; 电能计量IC ,带有片上故障和中性丢失检测
ADE7761BARS-RL
型号: ADE7761BARS-RL
厂家: ADI    ADI
描述:

Energy Metering IC with On-Chip Fault and Missing Neutral Detection
电能计量IC ,带有片上故障和中性丢失检测

模拟IC 信号电路 光电二极管
文件: 总24页 (文件大小:528K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Energy Metering IC with On-Chip Fault and  
Missing Neutral Detection  
ADE7761B  
FEATURES  
GENERAL DESCRIPTION  
High accuracy, active energy measurement IC supports  
IEC 62053-21  
Less than 0.1% error over a dynamic range of 1000 to 1  
Supplies active power on the frequency outputs, F1 and F2  
High frequency output CF is intended for calibration and  
supplies instantaneous active power  
Continuous monitoring of the phase and neutral current  
allows fault detection in 2-wire distribution systems  
Current channel input level best suited for shunt and current  
transformer sensors  
Uses the larger of the two currents (phase or neutral) to bill,  
even during a fault condition  
Continuous monitoring of the voltage and current inputs  
allows missing neutral detection  
Uses one current input (phase or neutral) to bill when  
missing neutral is detected  
Two logic outputs (FAULT and REVP) can be used to indicate  
a potential miswiring, fault, or missing neutral condition  
Direct drive for electromechanical counters and 2-phase  
stepper motors (F1 and F2)  
Proprietary ADCs and DSP provide high accuracy over large  
variations in environmental conditions and time  
Reference 2.5 V 8% (drift 30 ppm/°C typical) with external  
overdrive capability  
The ADE7761B is a high accuracy, fault-tolerant, electrical energy  
measurement IC intended for use with 2-wire distribution systems.  
The part specifications surpass the accuracy requirements as  
quoted in the IEC 62053-21 standard. The only analog circuitry  
used on the ADE7761B is in the ADCs and reference circuit.  
All other signal processing (such as multiplication and filtering)  
is carried out in the digital domain. This approach provides  
superior stability and accuracy over extremes in environmental  
conditions and over time. The ADE7761B incorporates a fault  
detection scheme similar to the ADE7751 by continuously  
monitoring both phase and neutral currents. A fault is indicated  
when the currents differ by more than 6.25%.  
The ADE7761B incorporates a missing neutral detection scheme  
by continuously monitoring the input voltage. When a missing  
neutral condition is detected (no voltage input), the ADE7761B  
continues billing based on the active current signal (see the  
Missing Neutral Mode section). The missing neutral condition  
is indicated when the FAULT pin goes high. The ADE7761B  
supplies average active power information on the low frequency  
outputs, F1 and F2. The CF logic output gives instantaneous  
active power information.  
The ADE7761B includes a power supply monitoring circuit on  
the VDD supply pin. Internal phase matching circuitry ensures  
that the voltage and current channels are matched. An internal  
no-load threshold ensures that the ADE7761B does not exhibit  
any creep when there is no load.  
Single 5 V supply, low power  
FUNCTIONAL BLOCK DIAGRAM  
V
PGA AGND  
FAULT  
15  
DD  
1
13  
8
POWER  
SUPPLY MONITOR  
V
V
V
2
4
1A  
1N  
1B  
ADE7761B  
SIGNAL PROCESSING  
BLOCK  
ADC  
ADC  
ADC  
ADC  
HPF  
A > B  
LPF  
B > A  
A B  
3
7
ZERO-CROSSING  
DETECTION  
MISSING NEUTRAL  
GAIN ADJUST  
MISCAL  
6
5
V
V
2P  
MISSING NEUTRAL  
DETECTION  
2N  
3kΩ  
2.5V  
REFERENCE  
INTERNAL  
OSCILLATOR  
DIGITAL-TO-FREQUENCY CONVERTER  
9
14  
17  
10  
11  
12  
16  
18  
19  
20  
REF  
RCLKIN  
DGND  
SCF S1 S0 REVP CF F2 F1  
IN/OUT  
Figure 1.  
Rev. 0  
Information furnished by Analog Devices is believed to be accurate and reliable. However, no  
responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other  
rights of third parties that may result from its use. Specifications subject to change without notice. No  
license is granted by implication or otherwise under any patent or patent rights of Analog Devices.  
Trademarks and registeredtrademarks arethe property of their respective owners.  
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.  
Tel: 781.329.4700  
Fax: 781.461.3113  
www.analog.com  
©2007 Analog Devices, Inc. All rights reserved.  
 
ADE7761B  
TABLE OF CONTENTS  
Features .............................................................................................. 1  
Analog Inputs ............................................................................. 11  
Internal Oscillator ...................................................................... 12  
Analog-to-Digital Conversion.................................................. 13  
Active Power Calculation.......................................................... 14  
Digital-to-Frequency Conversion............................................ 16  
Transfer Function....................................................................... 16  
Fault Detection ........................................................................... 17  
Missing Neutral Mode............................................................... 18  
Applications Information.............................................................. 21  
Interfacing to a Microcontroller for Energy Measurement.. 21  
Selecting a Frequency for an Energy Meter Application ...... 21  
Negative Power Information..................................................... 22  
Outline Dimensions....................................................................... 23  
Ordering Guide .......................................................................... 23  
General Description......................................................................... 1  
Functional Block Diagram .............................................................. 1  
Revision History ............................................................................... 2  
Specifications..................................................................................... 3  
Timing Characteristics ................................................................ 4  
Absolute Maximum Ratings............................................................ 5  
Performance Issues That May Affect Billing Accuracy........... 5  
ESD Caution.................................................................................. 5  
Pin Configuration and Function Descriptions............................. 6  
Typical Performance Characteristics ............................................. 8  
Test Circuit ........................................................................................ 9  
Terminology .................................................................................... 10  
Theory of Operation ...................................................................... 11  
Power Supply Monitor ............................................................... 11  
REVISION HISTORY  
8/07—Revision 0: Initial Version  
Rev. 0 | Page 2 of 24  
 
ADE7761B  
SPECIFICATIONS  
VDD = 5 V 5%, AGND = DGND = 0 V, on-chip reference, on-chip oscillator, TMIN to TMAX = −40°C to +85°C.  
Table 1.  
Parameter  
Value  
Unit  
Test Conditions/Comments  
ACCURACY1  
Measurement Error2  
0.1  
% of reading, typ  
Over a dynamic range of 1000 to 1  
Phase Error Between Channels  
PF = 0.8 Capacitive  
PF = 0.ꢀ Inductive  
0.0ꢀ  
0.0ꢀ  
Degrees, max  
Degrees, max  
Phase lead 37°  
Phase lag 60°  
AC Power Supply Rejection2  
Output Frequency Variation  
DC Power Supply Rejection2  
Output Frequency Variation  
FAULT DETECTION2, 3  
0.01  
0.01  
%, typ  
%, typ  
V1A = V1B = V2P  
=
100 mV rms  
100 mV rms  
V1A = V1B = V2P  
=
See the Fault Detection section  
Fault Detection Threshold  
Inactive Input ≠ Active Input  
Input Swap Threshold  
Inactive Input ≠ Active Input  
Accuracy Fault Mode Operation  
V1A Active, V1B = AGND  
V1B Active, V1A = AGND  
Fault Detection Delay  
6.2ꢀ  
6.2ꢀ  
%, typ  
V1A or V1B active  
% of larger, typ  
V1A or V1B active  
0.1  
0.1  
3
% of reading, typ  
% of reading, typ  
Seconds, typ  
Over a dynamic range of 1000 to 1  
Over a dynamic range of 1000 to 1  
Swap Delay  
3
Seconds, typ  
MISSING NEUTRAL MODE2, 4  
Missing Neutral Detection Threshold  
V2P − V2N  
See the Missing Neutral Detection section  
ꢀ9.4  
mV peak, min  
Accuracy Missing Neutral Mode  
V1A Active, V1B = V2P = AGND  
V1B Active, V1A = V2P = AGND  
Missing Neutral Detection Delay  
ANALOG INPUTS  
0.1  
0.1  
3
% of reading, typ  
% of reading, typ  
Seconds, typ  
Over a dynamic range of ꢀ00 to 1  
Over a dynamic range of ꢀ00 to 1  
V1A − V1N, V1B − V1N, V2P − V2N  
Differential input  
Differential input MISCAL − V2N  
Maximum Signal Levels  
660  
660  
790  
7
1ꢀ  
4
mV peak, max  
mV peak, max  
kΩ, min  
kHz, typ  
mV, typ  
Input Impedance (DC)  
Bandwidth (−3 dB)  
ADC Offset Error2  
Uncalibrated error, see the Terminology section for details  
External 2.ꢀ V reference  
Gain Error  
%, typ  
Gain Error Match2  
REFERENCE INPUT  
REFIN/OUT Input Voltage Range  
3
%, typ  
External 2.ꢀ V reference  
2.7  
2.3  
3
V, max  
V, min  
kΩ, min  
pF, max  
2.ꢀ V + 8%  
2.ꢀ V − 8%  
Input Impedance  
Input Capacitance  
10  
ON-CHIP REFERENCE  
Reference Error  
Temperature Coefficient  
Current Source  
200  
30  
10  
mV, max  
ppm/°C, typ  
μA, max  
Specification assures that VREF is within 8%  
ON-CHIP OSCILLATOR  
Oscillator Frequency  
Oscillator Frequency Tolerance  
Temperature Coefficient  
4ꢀ0  
12  
30  
kHz  
% of reading, typ  
ppm/°C, typ  
Specification achieved with 2ꢀ ppm/°C max resistor on the  
RCLKIN pin  
Rev. 0 | Page 3 of 24  
 
 
ADE7761B  
Parameter  
LOGIC INPUTSꢀ  
Value  
Unit  
Test Conditions/Comments  
PGA, SCF, S1, and S0  
Input High Voltage, VINH  
Input Low Voltage, VINL  
Input Current, IIN  
Input Capacitance, CIN  
LOGIC OUTPUTSꢀ  
CF, REVP, and FAULT  
Output High Voltage, VOH  
Output Low Voltage, VOH  
F1 and F2  
2.4  
0.8  
3
V, min  
VDD = ꢀ V ꢀ%  
VDD = ꢀ V ꢀ%  
Typical 10 nA, VIN = 0 V to VDD  
V, max  
μA, max  
pF, max  
10  
4
1
V, min  
V, max  
VDD = ꢀ V ꢀ%  
VDD = ꢀ V ꢀ%  
Output High Voltage, VOH  
Output Low Voltage, VOH  
POWER SUPPLY  
4
1
V, min  
V, max  
VDD = ꢀ V ꢀ%, ISOURCE = 10 mA  
VDD = ꢀ V ꢀ%, ISINK = 10 mA  
For specified performance  
ꢀ V − ꢀ%  
VDD  
4.7ꢀ  
ꢀ.2ꢀ  
3.6ꢀ  
V, min  
V, max  
mA, max  
ꢀ V + ꢀ%  
IDD  
1 See plots in the Typical Performance Characteristics section.  
2 See the Terminology section for explanation of specifications.  
3 See the Fault Detection section for explanation of fault detection functionality.  
4 See the Missing Neutral Detection section for explanation of missing neutral detection functionality.  
Sample tested during initial release and after any redesign or process change that might affect this parameter.  
TIMING CHARACTERISTICS  
VDD = 5 V 5%, AGND = DGND = 0 V, on-chip reference, on-chip oscillator, TMIN to TMAX = −40°C to +85°C. Sample tested during  
initial release and after any redesign or process change that might affect this parameter. See Figure 2.  
Table 2.  
Parameter  
Value  
Unit  
ms  
Test Conditions/Comments  
1
t1  
120  
F1 and F2 pulse width (logic high)  
t2  
t3  
t4  
See Table 8  
1/2 t2  
90  
sec  
sec  
ms  
Output pulse period (see the Transfer Function section)  
Time between F1 falling edge and F2 falling edge  
CF pulse width (logic high)  
1
tꢀ  
t6  
See Table 8  
CLKIN/4  
sec  
sec  
CF pulse period (see the Transfer Function section)  
Minimum time between F1 pulse and F2 pulse  
1 The pulse widths of F1, F2, and CF are not fixed for higher output frequencies. See the Transfer Function section.  
Timing Diagram  
t1  
F1  
t6  
t2  
t3  
F2  
t4  
t5  
CF  
Figure 2. Timing Diagram for Frequency Outputs  
Rev. 0 | Page 4 of 24  
 
 
 
ADE7761B  
ABSOLUTE MAXIMUM RATINGS  
TA = 25°C, unless otherwise noted.  
PERFORMANCE ISSUES THAT MAY AFFECT  
BILLING ACCURACY  
Table 3.  
Parameter  
Rating  
The ADE7761B provides pulse outputs, CF, F1, and F2, that are  
intended to be used for the billing of active energy. Pulses are  
generated at these outputs in two different situations.  
VDD to AGND  
Analog Input Voltage to AGND  
−0.3 V to +7 V  
−6 V to +6 V  
V
1A, V1B, V1N, V2N, V2P, MISCAL  
Reference Input Voltage to AGND  
Digital Input Voltage to DGND  
Digital Output Voltage to DGND  
Operating Temperature Range  
Industrial  
Storage Temperature Range  
Junction Temperature  
20-Lead SSOP, Power Dissipation  
θJA Thermal Impedance  
Lead Temperature, Soldering  
Vapor Phase (60 sec)  
−0.3 V to VDD + 0.3 V  
−0.3 V to VDD + 0.3 V  
−0.3 V to VDD + 0.3 V  
Case 1  
When the analog input V2P − V2N complies with the conditions  
described in Figure 34, the CF, F1, and F2 frequencies are  
proportional to active power and can be used to bill active energy.  
−40°C to +8ꢀ°C  
−6ꢀ°C to +1ꢀ0°C  
1ꢀ0°C  
4ꢀ0 mW  
112°C/W  
Case 2  
When the analog input V2P − V2N does not comply with the  
conditions described in Figure 34, the ADE7761B does not  
measure active energy but a quantity proportional to kiloampere-  
hours (kAh). This quantity is used to generate pulses on the  
same CF, F1, and F2. This situation is indicated when the  
FAULT pin is high.  
21ꢀ°C  
220°C  
Infrared (1ꢀ sec)  
Analog Devices, Inc., cautions users of the ADE7761B about the  
following:  
Stresses above those listed under Absolute Maximum Ratings  
may cause permanent damage to the device. This is a stress  
rating only; functional operation of the device at these or any  
other conditions above those indicated in the operational  
section of this specification is not implied. Exposure to absolute  
maximum rating conditions for extended periods may affect  
device reliability.  
Billing active energy in Case 1 is consistent with the under-  
standing of the quantity represented by pulses on the CF, F1,  
and F2 outputs (watthour).  
Billing active energy while the ADE7761B is in Case 2 must  
be decided knowing that the entity measured by the ADE7761B  
in this case is ampere-hour and not watthour. Users should  
be aware of this limitation and decide if the ADE7761B is  
appropriate for their application.  
ESD CAUTION  
Rev. 0 | Page ꢀ of 24  
 
ADE7761B  
PIN CONFIGURATION AND FUNCTION DESCRIPTIONS  
1
2
3
4
5
6
7
8
9
V
20  
19  
18  
17  
16  
15  
14  
13  
12  
11  
F1  
DD  
V
V
V
V
F2  
1A  
1B  
1N  
2N  
CF  
DGND  
REVP  
FAULT  
RCLKIN  
PGA  
S0  
ADE7761B  
TOP VIEW  
(Not to Scale)  
V
2P  
MISCAL  
AGND  
REF  
IN/OUT  
SCF 10  
S1  
Figure 3. Pin Configuration (SSOP)  
Table 4. Pin Function Descriptions  
Pin No. Mnemonic Description  
1
VDD  
Power Supply. This pin provides the supply voltage for the digital circuitry in the ADE7761B. The supply voltage  
should be maintained at ꢀ V ꢀ% for specified operation. This pin should be decoupled with a 10 μF capacitor  
in parallel with a ceramic 100 nF capacitor.  
2, 3  
V1A, V1B  
Analog Inputs for Channel V1 (Current Channel). These inputs are fully differential voltage inputs with maximum  
differential input signal levels of 660 mV with respect to V1N for specified operation. The maximum signal level  
at these pins is 1 V with respect to AGND. Both inputs have internal ESD protection circuitry, and an overvoltage  
of 6 V can also be sustained on these inputs without risk of permanent damage.  
4
6
7
V1N  
Negative Input for Differential Voltage Inputs, V1A and V1B. The maximum signal level at this pin is 1 V with respect  
to AGND. The input has internal ESD protection circuitry, and an overvoltage of 6 V can also be sustained on this  
input without risk of permanent damage. The input should be directly connected to the burden resistor and held  
at a fixed potential, that is, AGND. See the Analog Inputs section.  
Negative Input for Differential Voltage Inputs, V2P and MISCAL. The maximum signal level at this pin is 1 V with  
respect to AGND. The input has internal ESD protection circuitry, and an overvoltage of 6 V can also be sustained  
on this input without risk of permanent damage. The input should be held at a fixed potential, that is, AGND. See  
the Analog Inputs section.  
Analog Input for Channel V2 (Voltage Channel). This input is a fully differential voltage input with maximum  
differential input signal levels of 660 mV with respect to V2N for specified operation. The maximum signal level at  
this pin is 1 V with respect to AGND. This input has internal ESD protection circuitry, and an overvoltage of 6 V  
can also be sustained on this input without risk of permanent damage.  
Analog Input for Missing Neutral Calibration. This pin can be used to calibrate the CF, F1, and F2 frequencies in the  
missing neutral condition. This input is a fully differential voltage input with maximum differential input signal  
levels of 660 mV with respect to V2N for specified operation. The maximum signal level at this pin is 1 V with respect  
to AGND. This input has internal ESD protection circuitry, and an overvoltage of 6 V can also be sustained on this  
input without risk of permanent damage.  
V2N  
V2P  
MISCAL  
8
9
AGND  
Analog Ground. This pin provides the ground reference for the analog circuitry in the ADE7761B, that is, ADCs and  
reference. This pin should be tied to the analog ground plane of the PCB. The analog ground plane is the ground  
reference for all analog circuitry such as antialiasing filters and current and voltage transducers. For good noise  
suppression, the analog ground plane should be connected to the digital ground plane only at the DGND pin.  
This pin provides access to the on-chip voltage reference. The on-chip reference has a nominal value of  
2.ꢀ V 8% and a typical temperature coefficient of 30 ppm/°C. An external reference source can also be  
connected at this pin. In either case, this pin should be decoupled to AGND with a 1 ꢁF ceramic capacitor and  
100 nF ceramic capacitor.  
REFIN/OUT  
10  
SCF  
Select Calibration Frequency. This logic input is used to select the frequency on the Calibration Output CF.  
Table 7 shows how the calibration frequencies are selected.  
11, 12  
S1, S0  
These logic inputs are used to select one of four possible frequencies for the digital-to-frequency conversion.  
This offers the designer greater flexibility when designing the energy meter. See the Selecting a Frequency for an  
Energy Meter Application section.  
13  
14  
PGA  
RCLKIN  
This logic input is used to select the gain for the analog inputs, V1A and V1B. The possible gains are 1 and 16.  
To enable the internal oscillator as a clock source on the chip, a precise low temperature drift resistor at  
a nominal value of 6.2 kΩ must be connected from this pin to DGND.  
Rev. 0 | Page 6 of 24  
 
ADE7761B  
Pin No. Mnemonic Description  
1ꢀ  
FAULT  
This logic output goes active high when a fault or missing neutral condition occurs. A fault is defined as a  
condition under which the signals on V1A and V1B differ by more than 6.2ꢀ%. A missing neutral condition is  
defined when the chip is powered up with no voltage at the input. The logic output is reset to 0 when a fault or  
missing neutral condition is no longer detected. See the Fault Detection section and the Missing Neutral Mode  
section.  
16  
17  
REVP  
This logic output goes logic high when negative power is detected, that is, when the phase angle between the  
voltage and current signals is greater than 90°. This output is not latched and is reset when positive power is once  
again detected. The output goes high or low at the same time that a pulse is issued on CF.  
Digital Ground. This pin provides the ground reference for the digital circuitry in the ADE7761B, that is, multiplier,  
filters, and digital-to-frequency converters. This pin should be tied to the digital ground plane of the PCB. The  
digital ground plane is the ground reference for all digital circuitry, such as counters (mechanical and digital),  
MCUs, and indicator LEDs. For good noise suppression, the analog ground plane should be connected to the digital  
ground plane only at the DGND pin.  
DGND  
18  
CF  
Calibration Frequency Logic Output. The CF logic output, active high, gives instantaneous active power information.  
This output is used for operational and calibration purposes. See the Digital-to-Frequency Conversion section.  
19, 20  
F2, F1  
Low Frequency Logic Outputs. F1 and F2 supply average active power information. The logic outputs can be  
used to directly drive electromechanical counters and 2-phase stepper motors.  
Rev. 0 | Page 7 of 24  
ADE7761B  
TYPICAL PERFORMANCE CHARACTERISTICS  
1.0  
1.0  
0.8  
PF = 1  
GAIN = 16  
ON-CHIP REFERENCE  
ON-CHIP REFERENCE  
0.8  
0.6  
0.6  
–40°C  
0.4  
0.4  
PF = –0.5  
0.2  
0.2  
+25°C  
0
0
–0.2  
–0.2  
–0.4  
–0.6  
–0.8  
–1.0  
+85°C  
PF = +1  
PF = +0.5  
–0.4  
–0.6  
–0.8  
–1.0  
0.1  
1
10  
100  
0.1  
1
10  
100  
CURRENT (% of Full Scale)  
CURRENT (% of Full Scale)  
Figure 4. Active Power Error As a Percentage of Reading  
with Gain = 1 and Internal Reference  
Figure 7. Active Power Error As a Percentage of Reading  
over Power Factor with Gain = 16 and Internal Reference  
1.0  
1.0  
0.8  
GAIN = 16  
ON-CHIP REFERENCE  
PF = 1  
ON-CHIP REFERENCE  
0.8  
0.6  
0.6  
–40°C; PF = 0.5  
+85°C; PF = 0.5  
0.4  
0.4  
5.25V  
0.2  
0.2  
5.00V  
4.75V  
0
0
–0.2  
–0.4  
–0.6  
–0.8  
–1.0  
–0.2  
–0.4  
–0.6  
–0.8  
–1.0  
+25°C; PF = 1  
+25°C; PF = 0.5  
0.1  
1
10  
100  
0.1  
1
10  
100  
CURRENT (% of Full Scale)  
CURRENT (% of Full Scale)  
Figure 8. Active Power Error As a Percentage of Reading  
over Power Supply with Gain = 1 and Internal Reference  
Figure 5. Active Power Error As a Percentage of Reading  
over Power Factor with Gain = 1 and Internal Reference  
1.0  
0.8  
0.6  
0.4  
0.2  
1.0  
0.8  
PF = 1, GAIN = 16  
ON-CHIP REFERENCE  
ON-CHIP REFERENCE  
–40°C  
0.6  
+25°C  
0.4  
–40°C  
0.2  
+25°C  
+85°C  
0
–0.2  
–0.4  
–0.6  
–0.8  
–1.0  
0
–0.2  
–0.4  
–0.6  
–0.8  
–1.0  
+85°C  
0.1  
1
10  
100  
0.1  
1
10  
100  
CURRENT (% of Full Scale)  
CURRENT (% of Full Scale)  
Figure 6. Active Power Error As a Percentage of Reading  
with Gain = 16 and Internal Reference  
Figure 9. Ampere Hour Error As a Percentage of Reading  
in Missing Neutral Mode with Gain = 1 and Internal Reference  
Rev. 0 | Page 8 of 24  
 
 
 
ADE7761B  
TEST CIRCUIT  
V
V
DD  
+
10µF  
RB  
100nF  
1
PS2501-1  
40A TO 80mA  
I
2k  
18  
CF  
DD  
1kΩ  
1
4
2
V
1A  
19  
20  
16  
F2  
F1  
TO FREQ.  
COUNTER  
33nF  
ADE7761B  
REVP  
2
3
1kΩ  
33nF  
1kΩ  
2kΩ  
3
V
V
V
1B  
1N  
2N  
15  
14  
FAULT  
RB  
6.2kΩ  
RCLKIN  
4
5
RB = 18Ω  
33nF  
10kΩ  
1kΩ  
12  
11  
10  
S0  
S1  
33nF  
SCF  
1MΩ  
1k33nF  
REF  
6
7
9
V
IN/OUT  
2P  
+
220V  
100nF  
10µF  
560kΩ  
MISCAL  
PGA AGND DGND  
13 17  
100k33nF  
8
Figure 10. Test Circuit for Performance Curves  
Rev. 0 | Page 9 of 24  
 
ADE7761B  
TERMINOLOGY  
For the dc PSR measurement, a reading at nominal supplies (5 V)  
is taken. A second reading is obtained with the same input signal  
levels when the power supplies are varied 5%. Any error  
introduced is again expressed as a percentage of reading.  
Measurement Error  
The error associated with the energy measurement made by the  
ADE7761B is defined by  
Percentage Error =  
ADC Offset Error  
Energy Registered by ADE7761B True Energy  
This is the dc offset associated with the analog inputs to the ADCs.  
With the analog inputs connected to AGND, the ADCs still see  
a dc analog input signal. The magnitude of the offset depends on  
the input gain and range selection (see the Typical Performance  
Characteristics section). However, when HPFs are switched on,  
the offset is removed from the current channels and the power  
calculation is not affected by this offset.  
× 100%  
True Energy  
Phase Error Between Channels  
The high-pass filter (HPF) in the current channel has a phase  
lead response. To offset this phase response and equalize the  
phase response among channels, a phase correction network is  
also placed in the current channel. The phase correction network  
ensures a phase match between the current channels and the  
voltage channels to within 0.1° over a range of 45 Hz to  
65 Hz and 0.2° over a range of 40 Hz to 1 kHz.  
Gain Error  
The gain error in the ADE7761B ADCs is defined as the difference  
between the measured output frequency (minus the offset) and  
the ideal output frequency. It is measured with a gain of 1 in  
Channel V1A. The difference is expressed as a percentage of the  
ideal frequency, which is obtained from the transfer function  
(see the Transfer Function section).  
Power Supply Rejection (PSR)  
PSR quantifies the ADE7761B measurement error as a percentage  
of reading when the power supplies are varied. For the ac PSR  
measurement, a reading at nominal supplies (5 V) is taken.  
A second reading is obtained with the same input signal levels  
when an ac signal (175 mV rms/100 Hz) is introduced onto the  
supplies. Any error introduced by this ac signal is expressed as  
a percentage of reading (see the Measurement Error definition).  
Gain Error Match  
The gain error match is defined as the gain error (minus the offset)  
obtained when switching between a gain of 1 or 16. It is expressed  
as a percentage of the output ADC code obtained under a gain of 1.  
Rev. 0 | Page 10 of 24  
 
 
 
ADE7761B  
THEORY OF OPERATION  
V
V
1A  
DIFFERENTIAL INPUT A  
±660mV MAX PEAK  
POWER SUPPLY MONITOR  
V
, V  
1A 1B  
V1  
V1  
+660mV  
GAIN  
The ADE7761B continuously monitors the power supply (VDD)  
with its on-chip power supply monitor. If the supply is less than  
4 V 5%, the ADE7761B goes into an inactive state; that is, no  
energy is accumulated, and the CF, F1, and F2 outputs are disabled.  
This is useful to ensure correct device operation at power-up  
and during power-down. The power supply monitor has built-in  
hysteresis and filtering that provide a high degree of immunity  
to false triggering due to noisy supplies.  
+ V  
CM  
1N  
COMMON MODE  
V
CM  
±100mV MAX  
V
CM  
AGND  
–660mV  
GAIN  
+ V  
CM  
DIFFERENTIAL INPUT B  
±660mV MAX PEAK  
V
1B  
Figure 12. Maximum Signal Levels, Channel V1  
Channel V2 (Voltage Channel)  
The power supply and decoupling for the part should be such  
that the ripple at VDD does not exceed 5 V 5%, as specified for  
normal operation.  
The output of the line voltage transducer is connected to the  
ADE7761B at this analog input. Channel V2 is a single-ended  
voltage input. The maximum peak differential signal on  
Channel V2 is 660 mV with respect to V2N. Figure 13 shows the  
maximum signal levels that can be connected to Channel V2.  
V
DD  
5V  
4V  
V2  
V
2P  
2N  
+660mV + V  
CM  
V2  
DIFFERENTIAL INPUT  
±660mV MAX PEAK  
0V  
V
V
CM  
TIME  
V
COMMON MODE  
±100mV MAX  
CM  
ADE7761B  
REVP - FAULT - CF -  
F1 - F2 OUTPUTS  
–660mV + V  
CM  
INACTIVE  
ACTIVE  
INACTIVE  
Figure 11. On-Chip, Power Supply Monitoring  
Figure 13. Maximum Signal Levels, Channel V2  
ANALOG INPUTS  
The differential voltage V2P − V2N must be referenced to a  
common mode (usually AGND). The analog inputs of the  
ADE7761B can be driven with common-mode voltages of up  
to 100 mV with respect to AGND. However, the best results  
are achieved using a common mode equal to AGND.  
Channel V1 (Current Channel)  
The voltage outputs from the current transducers are connected  
to the ADE7761B at Channel V1. It has two voltage inputs, V1A  
and V1B. These inputs are fully differential with respect to V1N.  
However, at any one time, only one input is selected to perform  
the power calculation (see the Fault Detection section).  
MISCAL Input  
The input for the power calibration in missing neutral mode  
is connected to the ADE7761B at this analog input. MISCAL  
is a single-ended, voltage input. It is recommended to use a dc  
signal derived from the voltage reference to drive this pin. The  
maximum peak differential signal on MISCAL is 660 mV with  
respect to V2N. Figure 14 shows the maximum signal levels that  
can be connected to the MISCAL pin.  
The maximum peak differential signal on V1A − V1N and V1B − V1N  
is 660 mV. However, Channel V1 has a programmable gain  
amplifier (PGA) with user-selectable gains of 1 and 16 (see  
Table 5). This gain facilitates easy transducer interfacing.  
Table 5. Channel V1 Dynamic Range  
PGA  
Gain  
Maximum Differential Signal (mV)  
0
1
1
16  
660  
41  
MISCAL  
MISCAL  
MISCAL  
+660mV + V  
CM  
DIFFERENTIAL INPUT  
±660mV MAX PEAK  
Figure 12 shows the maximum signal levels on V1A, V1B, and  
V1N. The maximum differential voltage is 660 mV divided by  
the gain selection. The differential voltage signal on the inputs  
must be referenced to a common mode (usually AGND).  
V
2N  
V
CM  
COMMON MODE  
±100mV MAX  
V
CM  
AGND  
Figure 14. Maximum Signal Levels, MISCAL  
The differential voltage, MISCAL − V2N, must be referenced  
to a common mode (usually AGND). The analog inputs of the  
ADE7761B can be driven with common-mode voltages of up to  
100 mV with respect to AGND. However, best results are achieved  
using a common mode equal to AGND.  
Rev. 0 | Page 11 of 24  
 
 
 
 
 
 
ADE7761B  
Typical Connection Diagrams  
Adjusting the level of MISCAL to calibrate the meter in missing  
neutral mode can be done by changing the ratio of RC and  
RD + VR1. When the internal reference is used, the values of RC,  
RD, and VR1 must be chosen to limit the current sourced by  
the internal reference sourcing current to below the specified  
10 μA. Therefore, because VREF internal = 2.5 V, RC + RD +  
VR1 > 600 kΩ.  
Figure 15 shows a typical connection diagram for Channel V1.  
The analog inputs are used to monitor both the phase and  
neutral currents. Because of the large potential difference  
between the phase and neutral, two current transformers (CTs)  
must be used to provide the isolation. Note that both CTs are  
referenced to analog ground (AGND); therefore, the common-  
mode voltage is 0 V. The CT turn ratio and burden resistor (RB)  
are selected to give a peak differential voltage of 660 mV/gain.  
INTERNAL OSCILLATOR  
The nominal internal oscillator frequency is 450 kHz when  
used with the recommended ROSC resistor value of 6.2 kΩ  
between RCLKIN and DGND (see Figure 18).  
V
R
1A  
F
CT  
±660mV  
GAIN  
RB  
RB  
C
F
F
ADE7761B  
IP  
IN  
AGND  
V
V
1N  
1B  
±660mV  
GAIN  
3k  
2.5V  
INTERNAL  
C
REFERENCE  
OSCILLATOR  
CT  
R
F
9
14  
17  
REF  
RCLKIN  
DGND  
IN/OUT  
Figure 15. Typical Connection for Channel V1  
R
OSC  
Figure 16 shows two typical connections for Channel V2.  
The first option uses a potential transformer (PT) to provide  
complete isolation from the main voltage. In the second option,  
the ADE7761B is biased around the neutral wire, and a resistor  
divider is used to provide a voltage signal that is proportional to  
the line voltage. Adjusting the ratio of RA and RB + VR is a  
convenient way to carry out a gain calibration on the meter.  
Figure 18. Internal Oscillator Connection  
The internal oscillator frequency is inversely proportional to the  
value of this resistor. Although the internal oscillator operates  
when used with an ROSC resistor value between 5 kΩ and 12 kΩ,  
it is recommended that a value be chosen within the range of  
the nominal value.  
V
R
2P  
F
C
±660mV  
AGND  
F
F
The output frequencies on CF, F1, and F2 are directly propor-  
tional to the internal oscillator frequency; therefore, Resistor ROSC  
must have a low tolerance and low temperature drift. A low  
tolerance resistor limits the variation of the internal oscillator  
frequency. A small variation of the clock frequency and, conse-  
quently, of the output frequencies from meter to meter contributes  
to a smaller calibration range of the meter.  
V
R
2N  
F
C
1
RA  
C
F
1
1
RB  
V
V
2P  
VR  
R
2N  
F
A low temperature drift resistor directly limits the variation of  
the internal clock frequency over temperature. The stability of  
the meter to external variation is then better ensured by design.  
C
T
1
RB + VR = RF.  
Figure 16. Typical Connections for Channel V2  
Figure 17 shows a typical connection for the MISCAL input.  
The voltage reference input (REFIN/OUT) is used as a dc reference  
to set the MISCAL voltage.  
REF  
IN/OUT  
RC  
C
F
RD  
MISCAL  
VR1  
V
R
2N  
F
C
F
Figure 17. Typical Connection for MISCAL  
Rev. 0 | Page 12 of 24  
 
 
 
 
 
ADE7761B  
ANTIALIAS FILTER (RC)  
DIGITAL FILTER  
ANALOG-TO-DIGITAL CONVERSION  
SAMPLING FREQUENCY  
SHAPED NOISE  
SIGNAL  
NOISE  
The analog-to-digital conversion in the ADE7761B is carried  
out using second-order, Σ-Δ ADCs. Figure 19 shows a first-  
order, Σ-Δ ADC (for simplicity). The converter is made up of  
two parts: the Σ-Δ modulator and the digital low-pass filter.  
MCLK  
0
1
225  
FREQUENCY (kHz)  
450  
ANALOG  
LOW-PASS FILTER  
LATCHED  
COMPAR-  
ATOR  
INTEGRATOR  
DIGITAL  
LOW-PASS FILTER  
HIGH RESOLUTION  
OUTPUT FROM  
DIGITAL LFP  
SIGNAL  
NOISE  
R
V
REF  
1
24  
C
....10100101....  
1-BIT DAC  
0
1
225  
FREQUENCY (kHz)  
450  
Figure 19. First-Order, Σ-Δ ADC  
Figure 20. Noise Reduction Due to Oversampling and  
Noise Shaping in the Analog Modulator  
A Σ-Δ modulator converts the input signal into a continuous  
serial stream of 1s and 0s at a rate determined by the sampling  
clock. In the ADE7761B, the sampling clock is equal to CLKIN.  
The 1-bit DAC in the feedback loop is driven by the serial data  
stream. The DAC output is subtracted from the input signal.  
If the loop gain is high enough, the average value of the DAC  
output (and, therefore, the bit stream) approaches that of the  
input signal level. For any given input value in a single sampling  
interval, the data from the 1-bit ADC is virtually meaningless.  
Only when a large number of samples are averaged is a meaningful  
result obtained. This averaging is carried out in the second part  
of the ADC, the digital low-pass filter. By averaging a large  
number of bits from the modulator, the low-pass filter can  
produce 24-bit data-words that are proportional to the input  
signal level.  
Antialias Filter  
Figure 20 also shows an analog low-pass filter, RC, on input to  
the modulator. This filter is present to prevent aliasing. Aliasing  
is an artifact of all sampled systems, which means that frequency  
components in the input signal to the ADC that are higher than  
half the sampling rate of the ADC appear in the sampled signal  
frequency below half the sampling rate. Figure 21 illustrates  
the effect.  
ANTIALIASING EFFECTS  
SAMPLING  
FREQUENCY  
IMAGE  
FREQUENCIES  
The Σ-Δ converter uses two techniques to achieve high resolution  
from what is essentially a 1-bit conversion technique. The first is  
oversampling, which means that the signal is sampled at a rate  
(frequency) that is many times higher than the bandwidth of  
interest. For example, the sampling rate in the ADE7761B is  
CLKIN (450 kHz) and the band of interest is 40 Hz to 1 kHz.  
Oversampling has the effect of spreading the quantization noise  
(noise due to sampling) over a wider bandwidth. With the noise  
spread more thinly over a wider bandwidth, the quantization  
noise in the band of interest is lowered (see Figure 20).  
0
1
225  
450  
FREQUENCY (kHz)  
Figure 21. ADC and Signal Processing in Current Channel or Voltage Channel  
In Figure 21, frequency components (arrows shown in black)  
above half the sampling frequency (also known as the Nyquist  
frequency), that is, 225 kHz, are imaged or folded back down  
below 225 kHz (arrows shown in gray). This happens with all  
ADCs, no matter what the architecture. In Figure 21, only  
frequencies near the sampling frequency (450 kHz) move into  
the band of interest for metering (40 Hz to 1 kHz). This fact  
allows the use of a very simple low-pass filter to attenuate these  
frequencies (near 250 kHz) and, thereby, prevent distortion in the  
band of interest. A simple RC filter (single pole) with a corner  
frequency of 10 kHz produces an attenuation of approximately  
33 dB at 450 kHz (see Figure 21). This is sufficient to eliminate  
the effects of aliasing.  
However, oversampling alone is not an efficient enough method  
to improve the signal-to-noise ratio (SNR) in the band of interest.  
For example, an oversampling ratio of 4 is required just to increase  
the SNR by only 6 dB (1 bit). To keep the oversampling ratio at  
a reasonable level, it is possible to shape the quantization noise so  
the majority of the noise lies at the higher frequencies. This is what  
happens in the Σ-Δ modulator; the noise is shaped by the inte-  
grator, which has a high-pass type response for the quantization  
noise. The result is that most of the noise is at higher frequencies,  
where it can be removed by the digital low-pass filter. This noise  
shaping is also shown in Figure 20.  
Rev. 0 | Page 13 of 24  
 
 
 
 
ADE7761B  
Power Factor Considerations  
ACTIVE POWER CALCULATION  
The method used to extract the active power information from  
the instantaneous power signal (by low-pass filtering) is still valid  
even when the voltage and current signals are not in phase.  
The ADCs digitize the voltage signals from the current and  
voltage transducers. A high-pass filter in the current channel  
removes any dc component from the current signal. This eliminates  
any inaccuracies in the active power calculation due to offsets in  
the voltage or current signals (see the HPF and Offset Effects  
section).  
Figure 23 displays the unity power factor condition and a  
displacement power factor (DPF = 0.5), that is, current signal  
lagging the voltage by 60°.  
INSTANTANEOUS  
POWER SIGNAL  
INSTANTANEOUS  
ACTIVE POWER SIGNAL  
The active power calculation is derived from the instantaneous  
power signal. The instantaneous power signal is generated by  
a direct multiplication of the current and voltage signals.  
To extract the active power component (dc component), the  
instantaneous power signal is low-pass filtered. Figure 22 illustrates  
the instantaneous active power signal and shows how the active  
power information can be extracted by low-pass filtering the  
instantaneous power signal. This scheme correctly calculates  
active power for nonsinusoidal current and voltage waveforms  
at all power factors. All signal processing is carried out in the  
digital domain for superior stability over temperature and time.  
V × I  
2
0V  
CURRENT  
VOLTAGE  
INSTANTANEOUS  
POWER SIGNAL  
INSTANTANEOUS  
ACTIVE POWER SIGNAL  
DIGITAL-TO-  
FREQUENCY  
V × I  
2
F1  
F2  
× cos(60°)  
0V  
CH1  
CH2  
PGA  
ADC  
ADC  
HPF  
MULTIPLIER  
DIGITAL-TO-  
FREQUENCY  
LPF  
VOLTAGE  
CURRENT  
CF  
60°  
Figure 23. Active Power Calculation over PF  
INSTANTANEOUS  
INSTANTANEOUS  
POWER SIGNAL –p(t)  
ACTIVE POWER SIGNAL  
If one assumes that the voltage and current waveforms are  
sinusoidal, the active power component of the instantaneous  
power signal (dc term) is given by  
V × I  
p(t) = i(t) × v(t)  
WHERE:  
v(t) = V × cos(ωt)  
V × I  
2
i(t) = I × cos(ωt)  
(V × I/2) × cos(60°)  
V × I  
2
p(t) =  
{1 + cos (2ωt)}  
This is the correct active power calculation.  
Nonsinusoidal Voltage and Current  
TIME  
Figure 22. Signal Processing Block Diagram  
The active power calculation method also holds true for  
nonsinusoidal current and voltage waveforms. All voltage  
and current waveforms in practical applications have some  
harmonic content. Using the Fourier transform, instantaneous  
voltage and current waveforms can be expressed in terms of  
their harmonic content.  
The low frequency output of the ADE7761B is generated by  
accumulating this active power information. This low frequency  
inherently means a long accumulation time between output  
pulses. The output frequency is, therefore, proportional to the  
average active power. This average active power information  
can, in turn, be accumulated (for example, by a counter) to  
generate active energy information. Because of its high output  
frequency and, therefore, shorter integration time, the CF  
output is proportional to the instantaneous active power. This is  
useful for system calibration purposes that take place under  
steady load conditions.  
v(t) = V + 2 × V ×sin(hωt + α )  
(1)  
O
h
h
h 0  
where:  
v(t) is the instantaneous voltage.  
VO is the average value.  
Vh is the rms value of Voltage Harmonic h.  
αh is the phase angle of the voltage harmonic.  
Rev. 0 | Page 14 of 24  
 
 
 
 
ADE7761B  
The HPF in Channel V1 has an associated phase response that  
is compensated for on-chip. Figure 25 and Figure 26 show the  
phase error between channels with the compensation network  
activated. The ADE7761B is phase compensated up to 1 kHz as  
shown, which ensures a correct active harmonic power calculation  
even at low power factors.  
(2)  
i(t) = IO + 2 × I ×sin(hωt +β )  
h
h
h 0  
where:  
i(t) is the instantaneous current.  
IO is the dc component.  
Ih is the rms value of Current Harmonic h.  
βh is the phase angle of the current harmonic.  
DC COMPONENT (INCLUDING ERROR TERM)  
IS EXTRACTED BY THE LPF FOR ACTIVE  
POWER CALCULATION  
Using Equation 1 and Equation 2, the Active Power P can be  
expressed in terms of its fundamental active power (P1) and  
harmonic active power (PH).  
V
× I  
1
1
2
P = P1 + PH  
where:  
V
V
× I  
× I  
1
0
P1 = V1 × I1 cos(Φ1)  
Φ1 = α1 − β1  
(3)  
(4)  
0
1
2ω  
FREQUENCY (Rad/s)  
0ω  
and  
Figure 24. Effect of Channel Offsets on the Active Power Calculation  
P = V × I ×cos(Φ )  
H
h
h
h
h=2  
Φh = αh − βh  
0.30  
0.25  
0.20  
0.15  
As can be seen in Equation 4, a harmonic active power component  
is generated for every harmonic provided that the harmonic is  
present in both the voltage and current waveforms. The power  
factor calculation was previously shown to be accurate in the  
case of a pure sinusoid; therefore, the harmonic active power  
must also correctly account for the power factor because it is  
made up of a series of pure sinusoids.  
0.10  
0.05  
0
Note that the input bandwidth of the analog inputs is 7 kHz  
with an internal oscillator frequency of 450 kHz.  
–0.05  
–0.10  
HPF and Offset Effects  
0
100 200 300 400 500 600 700 800 900 1000  
FREQUENCY (Hz)  
Equation 5 shows the effect of offsets on the active power  
calculation. Figure 24 shows the effect of offsets on the active  
power calculation in the frequency domain.  
Figure 25. Phase Error Between Channels (0 Hz to 1 kHz)  
V(t) × I(t) =  
0.30  
0.25  
0.20  
0.15  
0.10  
(5)  
(V0 +V1 × cos(ωt))×(I0 + I1 × cos(ωt)) =  
V1 × I1  
V0 × I1 +  
+V0 × I1 × cos(ωt) +V1 × I0 × cos(ωt)  
2
As shown in Equation 5 and Figure 24, an offset on Channel V1  
and Channel V2 contributes a dc component after multiplication.  
Because this dc component is extracted by the LPF and used to  
generate the active power information, the offsets contribute  
a constant error to the active power calculation. This problem is  
easily avoided in the ADE7761B with the HPF in Channel V1. By  
removing the offset from at least one channel, no error component  
can be generated at dc by the multiplication. Error terms at cos(ωt)  
are removed by the LPF and the digital-to-frequency conversion  
(see the Digital-to-Frequency Conversion section).  
0.05  
0
–0.05  
–0.10  
40  
45  
50  
55  
60  
65  
70  
FREQUENCY (Hz)  
Figure 26. Phase Error Between Channels (40 Hz to 70 Hz)  
Rev. 0 | Page 1ꢀ of 24  
 
 
 
 
ADE7761B  
The output frequency on CF can be up to 2048 times higher  
than the frequency on F1 and F2. This higher output frequency  
is generated by accumulating the instantaneous active power  
signal over a much shorter time while converting it to a frequency.  
This shorter accumulation period means less averaging of the  
cos(2ωt) component. As a consequence, some of this instantaneous  
power signal passes through the digital-to-frequency conversion.  
This is not a problem in the application.  
DIGITAL-TO-FREQUENCY CONVERSION  
As described in the Active Power Calculation section, the digital  
output of the low-pass filter after multiplication contains the  
active power information. However, because this LPF is not an  
ideal brick wall filter implementation, the output signal also  
contains attenuated components at the line frequency and its  
harmonics, that is, cos(hωt), where h = 1, 2, 3, …, and so on.  
The magnitude response of the filter is given by  
Where CF is used for calibration purposes, the frequency should  
be averaged by the frequency counter, which removes any ripple.  
If CF is being used to measure energy, such as in a microprocessor-  
based application, the CF output should also be averaged to calcu-  
late power. Because the F1 and F2 outputs operate at a much  
lower frequency, much more averaging of the instantaneous active  
power signal is carried out. The result is a greatly attenuated  
sinusoidal content and a virtually ripple-free frequency output.  
1
H( f ) =  
(6)  
1 = ( f /4.5Hz)2  
For a line frequency of 50 Hz, this gives an attenuation of the 2ω  
(100 Hz) component of approximately −26.9 dB. The dominating  
harmonic is at twice the line frequency, cos(2ωt), due to the  
instantaneous power signal.  
Figure 27 shows the instantaneous active power signal output of  
the LPF, which still contains a significant amount of instantaneous  
power information, cos(2ωt). This signal is then passed to the  
digital-to-frequency converter, where it is integrated (accumulated)  
over time to produce an output frequency. This accumulation of  
the signal suppresses or averages out any non-dc components in  
the instantaneous active power signal. The average value of a  
sinusoidal signal is zero. Therefore, the frequency generated by  
the ADE7761B is proportional to the average active power.  
TRANSFER FUNCTION  
Frequency Output F1 and Frequency Output F2  
The ADE7761B calculates the product of two voltage signals  
(on Channel V1 and Channel V2) and then low-pass filters this  
product to extract active power information. This active power  
information is then converted to a frequency. The frequency  
information is output on F1 and F2 in the form of active high  
pulses. The pulse rate at these outputs is relatively low, for  
example, 0.37 Hz maximum for ac signals with S0 = S1 = 0  
(see Table 8). This means that the frequency at these outputs  
is generated from active power information accumulated over  
a relatively long period. The result is an output frequency that  
is proportional to the average active power. The averaging of the  
active power signal is implicit to the digital-to-frequency conver-  
sion. The output frequency or pulse rate is related to the input  
voltage signals by  
F
1
DIGITAL-TO-  
FREQUENCY  
F
F
1
2
V
TIME  
MULTIPLIER  
CF  
DIGITAL-TO-  
FREQUENCY  
LPF  
I
CF  
LPF TO EXTRACT  
ACTIVE POWER  
(DC TERM)  
6.13×Gain×V1rms ×V2rms × f14  
(7)  
F , F Frequency =  
1
2
2
VREF  
where:  
F1, F2 Frequency is the output frequency on F1 and F2 (Hz).  
V1rms is the differential rms voltage signal on Channel V1 (V).  
V2rms is the differential rms voltage signal on Channel V2 (V).  
Gain is 1 or 16, depending on the PGA gain selection made  
using Logic Input PGA.  
TIME  
0
ω
2ω  
FREQUENCY (Rad/s)  
INSTANTANEOUS ACTIVE POWER SIGNAL (FREQUENCY DOMAIN)  
Figure 27. Active Power to Frequency Conversion  
VREF is the reference voltage (2.5 V 8%) (V).  
f1–4 is one of four possible frequencies selected by using Logic  
Input S0 and Logic Input S1 (see Table 6).  
Figure 27 also shows the digital-to-frequency conversion for  
steady load conditions: constant voltage and current. As can be  
seen in Figure 27, the frequency output CF varies over time,  
even under steady load conditions. This frequency variation is  
primarily due to the cos(2ωt) component in the instantaneous  
active power signal.  
Rev. 0 | Page 16 of 24  
 
 
 
 
 
ADE7761B  
Note that if the on-chip reference is used, actual output  
frequencies may vary from device to device due to a reference  
tolerance of 8%.  
Table 6. f1–4 Frequency Selection  
S1  
S0  
f1–4 (Hz)1  
1.72  
f1−4 = OSC/2n2  
OSC/218  
0
0
0
1
3.44  
OSC/217  
6.13 × 0.66 × 0.66 ×1.72Hz  
F , F Frequency =  
= 0.367Hz  
1
2
1
0
6.86  
OSC/216  
OSC/21ꢀ  
2 × 2 × 2.52  
1
1
13.7  
CF Frequency = F1, F2 × 64 = 23.5 Hz  
1 Values are generated using the nominal frequency of 4ꢀ0 kHz.  
2 f1–4 are a binary fraction of the master clock and, therefore, vary with the  
internal oscillator frequency (OSC).  
As can be seen from these two example calculations, the maximum  
output frequency for ac inputs is always half of that for dc input  
signals. Table 8 shows a complete listing of all maximum output  
frequencies for ac signals.  
Frequency Output CF  
The pulse output calibration frequency (CF) is intended for use  
during calibration. The output pulse rate on CF can be up to  
2048 times the pulse rate on F1 and F2. The lower the f1–4  
frequency selected, the higher the CF scaling. Table 7 shows  
how the two frequencies are related, depending on the states of  
Logic Input S0, Logic Input S1, and Logic Input SCF. Because of  
its relatively high pulse rate, the frequency at this logic output is  
proportional to the instantaneous active power. As with F1 and  
F2, the frequency is derived from the output of the low-pass filter  
after multiplication. However, because the output frequency is high,  
this active power information is accumulated over a much shorter  
time. Therefore, less averaging is carried out in the digital-to-  
frequency conversion. With much less averaging of the active  
power signal, the CF output is much more responsive to power  
fluctuations (see Figure 22).  
Table 8. Maximum Output Frequencies on CF, F1, and F2 for  
AC Inputs  
F1, F2 Maximum CF Maximum  
Frequency (Hz), Frequency (Hz),  
CF-to-F1  
Ratio  
SCF S1 S0 1/t2  
1/t5  
1
0
1
0
1
0
1
0
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0.37  
0.37  
0.73  
0.73  
1.47  
1.47  
2.94  
2.94  
46.98  
23.49  
46.98  
23.49  
46.98  
23.49  
46.98  
6013  
128  
64  
64  
32  
32  
16  
16  
2048  
FAULT DETECTION  
Table 7. Relationship Between CF and F1, F2 Frequency  
Outputs  
The ADE7761B incorporates a novel fault detection scheme  
that warns of fault conditions and allows the ADE7761B to  
continue accurate billing during a fault event. The ADE7761B  
does this by continuously monitoring both the phase and neutral  
(return) currents. A fault is indicated when these currents differ  
by more than 6.25%. However, even during a fault, the output  
pulse rate on F1 and F2 is generated using the larger of the two  
currents. Because the ADE7761B looks for a difference between  
the voltage signals on V1A and V1B, it is important that both  
current transducers be closely matched.  
SCF  
S1  
S0  
f1–4 (Hz)  
1.72  
1.72  
3.44  
3.44  
6.86  
6.86  
13.7  
13.7  
CF Frequency Output  
128 × F1, F2  
64 × F1, F2  
64 × F1, F2  
32 × F1, F2  
32 × F1, F2  
16 × F1, F2  
16 × F1, F2  
2048 × F1, F2  
1
0
1
0
1
0
1
0
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
On power-up, the output pulse rate of the ADE7761B is propor-  
tional to the product of the voltage signals on V1A and Channel V2.  
If the difference between V1A and V1B on power-up is greater than  
6.25%, the fault indicator (FAULT) becomes active after about  
1 second. In addition, if V1B is greater than V1A, the ADE7761B  
selects V1B as the input. Fault detection is automatically disabled  
when the voltage signal on Channel V1 is less than 0.3% of the  
full-scale input range. This eliminates false detection of a fault  
due to noise at light loads.  
Example  
In this example, if ac voltages of 660 mV peak are applied to  
Channel V1 and Channel V2, the expected output frequency on  
CF, F1, and F2 is calculated as  
Gain = 1, PGA = 0  
f1–4 = 1.7 Hz, SCF = S1 = S0 = 0  
V1rms = rms of 660 mV peak ac = 0.66/√2 V  
V2rms = rms of 660 mV peak ac = 0.66/√2 V  
VREF = 2.5 V (nominal reference value)  
Rev. 0 | Page 17 of 24  
 
 
 
 
 
 
 
ADE7761B  
Fault with Active Input Greater Than Inactive Input  
Calibration Concerns  
If V1A is the active current input (that is, being used for billing),  
and the voltage signal on V1B (inactive input) falls below 93.75%  
of V1A, the fault indicator becomes active. Both analog inputs  
are filtered and averaged to prevent false triggering of this logic  
output. As a consequence of the filtering, there is a time delay of  
approximately 3 sec on the Logic Output FAULT after the fault  
event. The FAULT logic output is independent of any activity on  
the F1 or F2 outputs. Figure 28 shows one condition under  
which FAULT becomes active. Because V1A is the active input  
and it is still greater than V1B, billing is maintained on V1A; that  
is, no swap to the V1B input occurs. V1A remains the active input.  
Typically, when a meter is being calibrated, the voltage and current  
circuits are separated, as shown in Figure 30. This means that  
current passes through only the phase or neutral circuit. Figure 30  
shows current being passed through the phase circuit. This is  
the preferred option because the ADE7761B starts billing on the  
input V1A on power-up. The Phase Circuit CT is connected to  
V1A in Figure 30. Because there is no current in the neutral circuit,  
the FAULT indicator comes on under these conditions. However,  
this does not affect the accuracy of the calibration and can be  
used as a means to test the functionality of the fault detection.  
V
R
1A  
F
IB  
CT  
FAULT  
FILTER  
V
V
1A  
1A  
AND  
RB  
RB  
V
COMPARE  
C
A
1B  
V
F
F
1A  
V
V
TO  
1A  
1B  
AGND  
MULTIPLIER  
0V  
V
V
1N  
V
V
1N  
1B  
IB  
0V  
AGND  
C
B
TEST  
CURRENT  
V
< 93.75% OF V  
1A  
1B  
CT  
R
F
1B  
1
RA  
FAULT  
<0  
C
F
1
1
RB  
V
V
2P  
>0  
VR  
ACTIVE POINT – INACTIVE INPUT  
R
F
2N  
6.25% OF ACTIVE INPUT  
V
C
T
Figure 28. Fault Conditions for Active Input Greater Than Inactive Input  
240V rms  
1
RB + VR = RF.  
Fault with Inactive Input Greater Than Active Input  
Figure 30. Conditions for Calibration of Channel B  
Figure 29 illustrates another fault condition. If the difference  
between V1B, the inactive input, and V1A, the active input (that  
is, being used for billing), becomes greater than 6.25% of V1B,  
the FAULT indicator becomes active and a swap over to the V1B  
input occurs. The Analog Input V1B becomes the active input.  
Again, a time constant of about 3 sec is associated with this swap.  
V1A does not swap back to the active channel until V1A is greater  
than V1B, and the difference between V1A and V1B, in this order,  
becomes greater than 6.25% of V1A. However, the FAULT indi-  
cator becomes inactive as soon as V1A is within 6.25% of V1B. This  
threshold eliminates potential chatter between V1A and V1B.  
If the neutral circuit is chosen for the current circuit in the  
arrangement shown in Figure 30, this may have implications for  
the calibration accuracy. The ADE7761B powers up with the  
V1A input active as normal. However, because there is no current  
in the phase circuit, the signal on V1A is zero. This causes a fault  
to be flagged and the active input to be swapped to V1B (neutral).  
The meter can be calibrated in this mode, but the phase and  
neutral CTs may differ slightly. Because under no-fault conditions  
all billing is carried out using the phase CT, the meter should be  
calibrated using the phase circuit. Of course, both phase and  
neutral circuits can be calibrated.  
FAULT  
FILTER  
AND  
V
V
1A  
1A  
MISSING NEUTRAL MODE  
A
V
COMPARE  
1B  
V
V
TO  
1A  
1B  
The ADE7761B integrates a novel fault detection scheme that  
warns and allows the ADE7761B to continue to bill in case a  
meter is connected to only one wire (see Figure 31). For correct  
operation of the ADE7761B in this mode, the VDD pin of the  
ADE7761B must be maintained within the specified range  
(5 V 5%). The missing neutral detection algorithm is designed  
to work over a line frequency of 45 Hz to 55 Hz.  
MULTIPLIER  
0V  
V
V
1N  
1B  
AGND  
B
V
< 93.75% OF V  
1B  
1A  
FAULT + SWAP  
<0  
>0  
ACTIVE POINT – INACTIVE INPUT  
6.25% OF INACTIVE INPUT  
Figure 29. Fault Conditions for Inactive Input Greater Than Active Input  
Rev. 0 | Page 18 of 24  
 
 
 
 
 
ADE7761B  
V
R
V
1A  
F
Analog Devices cautions users of the ADE7761B about the  
following:  
CT  
IB  
RB  
RB  
C
244V rms  
POWER  
GENERATOR  
F
Billing active energy in Case 1 is consistent with the under-  
standing of the quantity represented by pulses on the CF, F1,  
and F2 outputs (watthour).  
1A  
V
1N  
0V  
C
F
Billing active energy while the ADE7761B is in Case 2 must  
be decided knowing that the entity measured by the ADE7761B  
in this case is ampere-hour and not watthour. Users should  
be aware of this limitation and decide if the ADE7761B is  
appropriate for their application.  
CT  
1
R
V
1B  
F
LOAD  
RA  
C
F
F
1
1
RB  
V
V
2P  
VR  
R
2N  
Missing Neutral Detection  
C
F
The ADE7761B continuously monitors the voltage input and  
detects a missing neutral condition when the voltage input peak  
value is smaller than 9% of the analog full scale or when no zero  
crossings are detected on this input (see Figure 33).  
1
RB + VR = RF.  
Figure 31. Missing Neutral System Diagram  
The ADE7761B detects a missing neutral condition by continu-  
ously monitoring the voltage channel input (V2P − V2N). The  
FAULT pin is held high when a missing neutral condition is  
detected. In this mode, the ADE7761B continues to bill the energy  
based on the signal level on the current channel (see Figure 32).  
The billing rate or frequency outputs can be adjusted by changing  
the dc level on the MISCAL pin.  
V
MISSING  
2P  
NEUTRAL  
FILTER AND  
THRESHOLD  
V2  
ADC  
V
2N  
AGND  
|V2|  
< 9% OF FULL SCALE  
OR  
NO ZERO CROSSING ON V2  
PEAK  
V
V
V
1A  
1N  
1B  
ADC  
V
– V  
2N  
V
– V  
2N  
V – V  
2P 2N  
2P  
2P  
A > B  
HPF  
FS  
FS  
FS  
ADC  
ZERO  
CROSSING  
DETECTION  
B > A  
A B  
9% OF FS  
0V  
0V  
0V  
LPF  
MISSING NEUTRAL  
GAIN ADJUSMTENT  
MISCAL  
ADC  
DIGITAL-TO-  
FREQUENCY  
CONVERTERS  
Figure 33. Missing Neutral Detection  
The ADE7761B leaves the missing neutral mode for normal  
operation when both conditions are no longer valid; that is,  
a voltage peak value of greater than 9% of full scale and zero  
crossing on the voltage channel is detected (see Figure 34).  
F1 F2  
CF  
Figure 32. Energy Calculation in Missing Neutral Mode  
Important Note for Billing of Active Energy  
V
MISSING  
2P  
NEUTRAL  
The ADE7761B provides pulse outputs, CF, F1, and F2, that are  
intended to be used for the billing of active energy. Pulses are  
generated at these outputs in two different situations.  
FILTER AND  
THRESHOLD  
V2  
ADC  
V
2N  
AGND  
Case 1  
|V2|  
PEAK  
> 9% OF FULL SCALE  
AND  
When the analog input V2P − V2N complies with the conditions  
described in Figure 34, the CF, F1, and F2 frequencies are propor-  
tional to active power and can be used to bill active energy.  
ZERO CROSSING ON V2  
V
– V  
2N  
2P  
FS  
Case 2  
+9% OF FS  
–9% OF FS  
When the analog input V2P − V2N does not comply with the  
conditions described in Figure 34, the ADE7761B does not  
measure active energy but a quantity proportional to kAh. This  
quantity is used to generate pulses on the same CF, F1, and F2.  
This situation is indicated when the FAULT pin is high.  
Figure 34. Return to Normal Mode After Missing Neutral Detection  
Rev. 0 | Page 19 of 24  
 
 
 
 
 
 
ADE7761B  
Missing Neutral Gain Calibration  
Example  
When the ADE7761B is in missing neutral mode, the energy is  
billed based on the active current input signal level. The frequency  
outputs in this mode can be calibrated with the MISCAL analog  
input pin. In this mode, applying a dc voltage of 330 mV on  
MISCAL is equivalent to applying, in normal mode, a pure sine  
wave on the voltage input with a peak value of 330 mV. The  
MISCAL input can vary from 0 V to 660 mV (see the Analog  
Inputs section). When set to 0 V, the frequency outputs are  
close to zero. When set to 660 mV dc, the frequency outputs are  
twice that when MISCAL is at 330 mV dc. In other words,  
Equation 7 can be used in missing neutral mode by replacing  
V2rms by MISCALrms /√2.  
In normal mode, ac voltages of 330 mV peak are applied to  
Channel V1 and Channel V2, and then the expected output  
frequency on F1 and F2 is calculated as follows:  
Gain =1; PGA =0  
F1–4 = 1.7 Hz, SCF = S1 = S0 = 0  
V1 = rms of 330 mV peak ac = 0.33/√2 V  
V2 = rms of 330 mV peak ac = 0.33/√2 V  
VREF = 2.5 V (nominal reference value)  
6.13× 0.33× 0.33×1.7Hz  
F , F2 Frequency =  
= 0.0917Hz  
1
2 × 2 × 2.52  
F , F Frequency =  
1
2
CF Frequency = F1, F2 Frequency × 64 = 5.87 Hz  
(8)  
6.13×Gain×V1rms × MISCALrms / 2 × f14  
In missing neutral mode, the ac voltage of 330 mV peak is  
applied to Channel V1, no signal is connected on Channel V2,  
and a 330 mV dc input is applied to MISCAL. With the ADE7761B  
in the same configuration as the previous example, the expected  
output frequencies on CF, F1, and F2 are  
2
VREF  
where:  
F1, F2 Frequency is the output frequency on F1 and F2 (Hz).  
Gain is 1 or 16, depending on the PGA gain selection made  
using Logic Input PGA.  
6.13× 0.33× 0.33/ 2 ×1.7Hz  
F1 , F2 Frequency =  
= 0.0917Hz  
V1rms is the differential rms voltage signal on Channel V1 (V).  
MISCALrms is the differential rms voltage signal on the MISCAL  
pin (V).  
2 × 2.52  
CF Frequency = F1, F2 Frequency × 64 = 5.87 Hz  
VREF is the reference voltage (2.5 V 8%) (V).  
f1-4 is one of four possible frequencies selected by using Logic  
Input S0 and Logic Input S1 (see Table 6).  
Rev. 0 | Page 20 of 24  
ADE7761B  
APPLICATIONS INFORMATION  
INTERFACING TO A MICROCONTROLLER FOR  
ENERGY MEASUREMENT  
SELECTING A FREQUENCY FOR AN ENERGY  
METER APPLICATION  
The easiest way to interface the ADE7761B to a microcontroller  
is to use the CF high frequency output with the output frequency  
scaling set to 2048 × F1, F2. This is done by setting SCF = 0  
and S0 = S1 = 1 (see Table 8). With full-scale ac signals on the  
analog inputs, the output frequency on CF is approximately  
5.5 kHz. Figure 35 illustrates one scheme that could be used to  
digitize the output frequency and carry out the necessary  
averaging mentioned in the Frequency Output CF section.  
As shown in Table 6, the user can select one of four frequencies.  
This frequency selection determines the maximum frequency  
on F1 and F2. These outputs are intended to be used to drive  
the energy register (electromechanical or other). Because only  
four different output frequencies can be selected, the available  
frequency selection was optimized for a meter constant of  
100 impulses/kWh with a maximum current of between 10 A  
and 120 A. Table 9 shows the output frequency for several  
maximum currents (IMAX) with a line voltage of 240 V. In all  
cases, the meter constant is 100 impulses/kWh.  
CF  
FREQUENCY  
RIPPLE  
Table 9. F1 and F2 Frequency at 100 Impulses/kWh  
AVERAGE  
FREQUENCY  
±10%  
IMAX (A)  
12.ꢀ  
2ꢀ  
F1 and F2 (Hz)  
0.083  
0.166  
0.266  
0.4  
40  
TIME  
60  
MCU  
80  
0.ꢀ33  
0.8  
ADE7761B  
COUNTER  
120  
CF  
1
The f1–4 frequencies allow complete coverage of this range of  
output frequencies on F1 and F2. When designing an energy  
meter, the nominal design voltage on Channel V2 (voltage)  
should be set to half-scale to allow for calibration of the meter  
constant. The current channel should also be no more than half-  
scale when the meter sees maximum load, which accommodates  
overcurrent signals and signals with high crest factors. Table 10  
shows the output frequency on F1 and F2 when both analog  
inputs are half-scale. The frequencies listed in Table 10 align  
well with those listed in Table 9 for maximum load.  
UP/DOWN  
REVP  
2
FAULT  
LOGIC  
1
REVP MUST BE USED IF THE METER IS BIDIRECTIONAL OR  
DIRECTION OF ENERGY FLOW IS NEEDED.  
FAULT MUST BE USED TO RECORD ENERGY IN FAULT CONDITION.  
2
Figure 35. Interfacing the ADE7761B to an MCU  
As shown in Figure 35, the frequency output CF is connected to  
an MCU counter or port that counts the number of pulses in a  
given integration time, determined by an MCU internal timer.  
The average power, proportional to the average frequency, is  
Table 10. F1 and F2 Frequency with Half-Scale AC Inputs  
Frequency on F1 and F2, Channel V1 and  
S0 S1 f1–4 (Hz) Channel V2, Half-Scale AC Inputs (Hz)  
Counter  
Average Frequency = Average Active Power =  
Timer  
The energy consumed during an integration period is  
Counter  
0
0
1
1
0
1
0
1
1.72  
3.44  
6.86  
13.ꢀ  
0.092  
0.183  
0.337  
0.734  
Energy = Average Power ×Time =  
×Time = Counter  
Time  
When selecting a suitable f1–4 frequency for a meter design, the  
frequency output at IMAX (maximum load) with a meter constant  
of 100 impulses/kWh should be compared with Column 4 of  
Table 10. The frequency that is closest in Table 10 determines  
the best choice of frequency (f1-4). For example, if a meter with  
a maximum current of 40 A is being designed, the output  
frequency on F1 and F2 with a meter constant of 100 impulses  
per kWh is 0.266 Hz at 40 A and 240 V (see Table 9).  
For the purpose of calibration, this integration time could be  
10 sec to 20 sec to accumulate enough pulses to ensure correct  
averaging of the frequency. In normal operation, the integration  
time could be reduced to 1 sec or 2 sec, depending on, for  
example, the required update rate of a display. With shorter  
integration times on the MCU, the amount of energy in each  
update may still have a small amount of ripple, even under  
steady load conditions. However, over a minute or more, the  
measured energy has no ripple.  
Looking at Table 10, the closest frequency to 0.266 Hz  
in Column 4 is 0.183 Hz. Therefore, F2 (3.4 Hz; see Table 6)  
is selected for this design.  
Rev. 0 | Page 21 of 24  
 
 
 
 
 
 
ADE7761B  
Frequency Outputs  
For example, with an energy meter with a meter constant of  
100 impulses per kWh on F1, F2 using SCF = 1, S1 = 0, and  
S0 = 1, the maximum output frequency at F1 or F2 is 0.68 Hz  
and 43.52 Hz on CF. The minimum output frequency at F1  
or F2 is 0.0045% of 0.68 Hz or 3.06 × 10–5 Hz. This is 1.96 ×  
10–3 Hz at CF (64 × F1 Hz).  
Figure 2 is a timing diagram for the various frequency outputs.  
The high frequency CF output is intended for communication  
and calibration purposes. CF produces a 90 ms wide, active high  
pulse (t4) at a frequency that is proportional to active power. The  
CF output frequencies are given in Table 8. As with F1 and F2,  
if the period of CF (t5) falls below 180 ms, the CF pulse width is set  
to half the period. For example, if the CF frequency is 20 Hz,  
the CF pulse width is 25 ms.  
In this example, the no-load threshold is equivalent to 1.1 W of  
load or a startup current of 4.6 mA at 240 V. Compare this value  
to the IEC 62053-21 specification, which states that the meter must  
start up with a load equal to or less than 0.4% of IB. For a 5 A (IB)  
meter, 0.4% of IB is equivalent to 20 mA.  
No-Load Threshold  
The ADE7761B includes a no-load threshold and start-up current  
feature that eliminate creep effects in the meter. The ADE7761B  
is designed to issue a minimum output frequency. Any load  
generating a frequency lower than this minimum frequency  
does not cause a pulse to be issued on F1, F2, or CF. The minimum  
output frequency is given as 0.0045% of the full-scale output  
frequency (see Table 8 for maximum output frequencies for  
ac signals).  
Note that the no-load threshold is not enabled when using the  
high CF frequency mode: SCF = 0, S1 = S0 = 1.  
NEGATIVE POWER INFORMATION  
The ADE7761B detects when the current and voltage channels  
have a phase shift greater than 90°. This mechanism can detect  
a wrong connection of the meter or the generation of negative  
power. The REVP pin output goes active high when negative  
power is detected and active low when positive power is detected.  
The REVP pin output changes state as a pulse is issued on CF.  
Rev. 0 | Page 22 of 24  
 
ADE7761B  
OUTLINE DIMENSIONS  
7.50  
7.20  
6.90  
11  
20  
5.60  
5.30  
5.00  
8.20  
7.80  
7.40  
1
10  
0.25  
0.09  
1.85  
1.75  
1.65  
2.00 MAX  
8°  
4°  
0°  
0.95  
0.75  
0.55  
0.38  
0.22  
0.05 MIN  
SEATING  
PLANE  
COPLANARITY  
0.10  
0.65 BSC  
COMPLIANT TO JEDEC STANDARDS MO-150-AE  
Figure 36. 20-Lead Shrink Small Outline Package [SSOP]  
(RS-20)  
Dimensions shown in millimeters  
ORDERING GUIDE  
Model  
ADE7761BARS  
ADE7761BARS-RL  
ADE7761BARSZ1  
ADE7761BARSZ-RL1  
ADE7761BARS-REF  
Temperature Range  
–40°C to +8ꢀ°C  
–40°C to +8ꢀ°C  
–40°C to +8ꢀ°C  
–40°C to +8ꢀ°C  
Package Description  
Package Option  
20-Lead Shrink Small Outline Package (SSOP)  
20-Lead Shrink Small Outline Package (SSOP)  
20-Lead Shrink Small Outline Package (SSOP)  
20-Lead Shrink Small Outline Package (SSOP)  
Reference Board  
RS-20  
RS-20  
RS-20  
RS-20  
1 Z = RoHS Compliant Part.  
Rev. 0 | Page 23 of 24  
 
 
ADE7761B  
NOTES  
©2007 Analog Devices, Inc. All rights reserved. Trademarks and  
registered trademarks are the property of their respective owners.  
D06797-0-8/07(0)  
Rev. 0 | Page 24 of 24  
 
 
 
 

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY