ADE7761BARS-RL [ADI]
Energy Metering IC with On-Chip Fault and Missing Neutral Detection; 电能计量IC ,带有片上故障和中性丢失检测型号: | ADE7761BARS-RL |
厂家: | ADI |
描述: | Energy Metering IC with On-Chip Fault and Missing Neutral Detection |
文件: | 总24页 (文件大小:528K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Energy Metering IC with On-Chip Fault and
Missing Neutral Detection
ADE7761B
FEATURES
GENERAL DESCRIPTION
High accuracy, active energy measurement IC supports
IEC 62053-21
Less than 0.1% error over a dynamic range of 1000 to 1
Supplies active power on the frequency outputs, F1 and F2
High frequency output CF is intended for calibration and
supplies instantaneous active power
Continuous monitoring of the phase and neutral current
allows fault detection in 2-wire distribution systems
Current channel input level best suited for shunt and current
transformer sensors
Uses the larger of the two currents (phase or neutral) to bill,
even during a fault condition
Continuous monitoring of the voltage and current inputs
allows missing neutral detection
Uses one current input (phase or neutral) to bill when
missing neutral is detected
Two logic outputs (FAULT and REVP) can be used to indicate
a potential miswiring, fault, or missing neutral condition
Direct drive for electromechanical counters and 2-phase
stepper motors (F1 and F2)
Proprietary ADCs and DSP provide high accuracy over large
variations in environmental conditions and time
Reference 2.5 V 8% (drift 30 ppm/°C typical) with external
overdrive capability
The ADE7761B is a high accuracy, fault-tolerant, electrical energy
measurement IC intended for use with 2-wire distribution systems.
The part specifications surpass the accuracy requirements as
quoted in the IEC 62053-21 standard. The only analog circuitry
used on the ADE7761B is in the ADCs and reference circuit.
All other signal processing (such as multiplication and filtering)
is carried out in the digital domain. This approach provides
superior stability and accuracy over extremes in environmental
conditions and over time. The ADE7761B incorporates a fault
detection scheme similar to the ADE7751 by continuously
monitoring both phase and neutral currents. A fault is indicated
when the currents differ by more than 6.25%.
The ADE7761B incorporates a missing neutral detection scheme
by continuously monitoring the input voltage. When a missing
neutral condition is detected (no voltage input), the ADE7761B
continues billing based on the active current signal (see the
Missing Neutral Mode section). The missing neutral condition
is indicated when the FAULT pin goes high. The ADE7761B
supplies average active power information on the low frequency
outputs, F1 and F2. The CF logic output gives instantaneous
active power information.
The ADE7761B includes a power supply monitoring circuit on
the VDD supply pin. Internal phase matching circuitry ensures
that the voltage and current channels are matched. An internal
no-load threshold ensures that the ADE7761B does not exhibit
any creep when there is no load.
Single 5 V supply, low power
FUNCTIONAL BLOCK DIAGRAM
V
PGA AGND
FAULT
15
DD
1
13
8
POWER
SUPPLY MONITOR
V
V
V
2
4
1A
1N
1B
ADE7761B
SIGNAL PROCESSING
BLOCK
ADC
ADC
ADC
ADC
HPF
A > B
LPF
B > A
A ≠ B
3
7
ZERO-CROSSING
DETECTION
MISSING NEUTRAL
GAIN ADJUST
MISCAL
6
5
V
V
2P
MISSING NEUTRAL
DETECTION
2N
3kΩ
2.5V
REFERENCE
INTERNAL
OSCILLATOR
DIGITAL-TO-FREQUENCY CONVERTER
9
14
17
10
11
12
16
18
19
20
REF
RCLKIN
DGND
SCF S1 S0 REVP CF F2 F1
IN/OUT
Figure 1.
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable. However, no
responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other
rights of third parties that may result from its use. Specifications subject to change without notice. No
license is granted by implication or otherwise under any patent or patent rights of Analog Devices.
Trademarks and registeredtrademarks arethe property of their respective owners.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.
Tel: 781.329.4700
Fax: 781.461.3113
www.analog.com
©2007 Analog Devices, Inc. All rights reserved.
ADE7761B
TABLE OF CONTENTS
Features .............................................................................................. 1
Analog Inputs ............................................................................. 11
Internal Oscillator ...................................................................... 12
Analog-to-Digital Conversion.................................................. 13
Active Power Calculation.......................................................... 14
Digital-to-Frequency Conversion............................................ 16
Transfer Function....................................................................... 16
Fault Detection ........................................................................... 17
Missing Neutral Mode............................................................... 18
Applications Information.............................................................. 21
Interfacing to a Microcontroller for Energy Measurement.. 21
Selecting a Frequency for an Energy Meter Application ...... 21
Negative Power Information..................................................... 22
Outline Dimensions....................................................................... 23
Ordering Guide .......................................................................... 23
General Description......................................................................... 1
Functional Block Diagram .............................................................. 1
Revision History ............................................................................... 2
Specifications..................................................................................... 3
Timing Characteristics ................................................................ 4
Absolute Maximum Ratings............................................................ 5
Performance Issues That May Affect Billing Accuracy........... 5
ESD Caution.................................................................................. 5
Pin Configuration and Function Descriptions............................. 6
Typical Performance Characteristics ............................................. 8
Test Circuit ........................................................................................ 9
Terminology .................................................................................... 10
Theory of Operation ...................................................................... 11
Power Supply Monitor ............................................................... 11
REVISION HISTORY
8/07—Revision 0: Initial Version
Rev. 0 | Page 2 of 24
ADE7761B
SPECIFICATIONS
VDD = 5 V 5%, AGND = DGND = 0 V, on-chip reference, on-chip oscillator, TMIN to TMAX = −40°C to +85°C.
Table 1.
Parameter
Value
Unit
Test Conditions/Comments
ACCURACY1
Measurement Error2
0.1
% of reading, typ
Over a dynamic range of 1000 to 1
Phase Error Between Channels
PF = 0.8 Capacitive
PF = 0.ꢀ Inductive
0.0ꢀ
0.0ꢀ
Degrees, max
Degrees, max
Phase lead 37°
Phase lag 60°
AC Power Supply Rejection2
Output Frequency Variation
DC Power Supply Rejection2
Output Frequency Variation
FAULT DETECTION2, 3
0.01
0.01
%, typ
%, typ
V1A = V1B = V2P
=
100 mV rms
100 mV rms
V1A = V1B = V2P
=
See the Fault Detection section
Fault Detection Threshold
Inactive Input ≠ Active Input
Input Swap Threshold
Inactive Input ≠ Active Input
Accuracy Fault Mode Operation
V1A Active, V1B = AGND
V1B Active, V1A = AGND
Fault Detection Delay
6.2ꢀ
6.2ꢀ
%, typ
V1A or V1B active
% of larger, typ
V1A or V1B active
0.1
0.1
3
% of reading, typ
% of reading, typ
Seconds, typ
Over a dynamic range of 1000 to 1
Over a dynamic range of 1000 to 1
Swap Delay
3
Seconds, typ
MISSING NEUTRAL MODE2, 4
Missing Neutral Detection Threshold
V2P − V2N
See the Missing Neutral Detection section
ꢀ9.4
mV peak, min
Accuracy Missing Neutral Mode
V1A Active, V1B = V2P = AGND
V1B Active, V1A = V2P = AGND
Missing Neutral Detection Delay
ANALOG INPUTS
0.1
0.1
3
% of reading, typ
% of reading, typ
Seconds, typ
Over a dynamic range of ꢀ00 to 1
Over a dynamic range of ꢀ00 to 1
V1A − V1N, V1B − V1N, V2P − V2N
Differential input
Differential input MISCAL − V2N
Maximum Signal Levels
660
660
790
7
1ꢀ
4
mV peak, max
mV peak, max
kΩ, min
kHz, typ
mV, typ
Input Impedance (DC)
Bandwidth (−3 dB)
ADC Offset Error2
Uncalibrated error, see the Terminology section for details
External 2.ꢀ V reference
Gain Error
%, typ
Gain Error Match2
REFERENCE INPUT
REFIN/OUT Input Voltage Range
3
%, typ
External 2.ꢀ V reference
2.7
2.3
3
V, max
V, min
kΩ, min
pF, max
2.ꢀ V + 8%
2.ꢀ V − 8%
Input Impedance
Input Capacitance
10
ON-CHIP REFERENCE
Reference Error
Temperature Coefficient
Current Source
200
30
10
mV, max
ppm/°C, typ
μA, max
Specification assures that VREF is within 8%
ON-CHIP OSCILLATOR
Oscillator Frequency
Oscillator Frequency Tolerance
Temperature Coefficient
4ꢀ0
12
30
kHz
% of reading, typ
ppm/°C, typ
Specification achieved with 2ꢀ ppm/°C max resistor on the
RCLKIN pin
Rev. 0 | Page 3 of 24
ADE7761B
Parameter
LOGIC INPUTSꢀ
Value
Unit
Test Conditions/Comments
PGA, SCF, S1, and S0
Input High Voltage, VINH
Input Low Voltage, VINL
Input Current, IIN
Input Capacitance, CIN
LOGIC OUTPUTSꢀ
CF, REVP, and FAULT
Output High Voltage, VOH
Output Low Voltage, VOH
F1 and F2
2.4
0.8
3
V, min
VDD = ꢀ V ꢀ%
VDD = ꢀ V ꢀ%
Typical 10 nA, VIN = 0 V to VDD
V, max
μA, max
pF, max
10
4
1
V, min
V, max
VDD = ꢀ V ꢀ%
VDD = ꢀ V ꢀ%
Output High Voltage, VOH
Output Low Voltage, VOH
POWER SUPPLY
4
1
V, min
V, max
VDD = ꢀ V ꢀ%, ISOURCE = 10 mA
VDD = ꢀ V ꢀ%, ISINK = 10 mA
For specified performance
ꢀ V − ꢀ%
VDD
4.7ꢀ
ꢀ.2ꢀ
3.6ꢀ
V, min
V, max
mA, max
ꢀ V + ꢀ%
IDD
1 See plots in the Typical Performance Characteristics section.
2 See the Terminology section for explanation of specifications.
3 See the Fault Detection section for explanation of fault detection functionality.
4 See the Missing Neutral Detection section for explanation of missing neutral detection functionality.
ꢀ Sample tested during initial release and after any redesign or process change that might affect this parameter.
TIMING CHARACTERISTICS
VDD = 5 V 5%, AGND = DGND = 0 V, on-chip reference, on-chip oscillator, TMIN to TMAX = −40°C to +85°C. Sample tested during
initial release and after any redesign or process change that might affect this parameter. See Figure 2.
Table 2.
Parameter
Value
Unit
ms
Test Conditions/Comments
1
t1
120
F1 and F2 pulse width (logic high)
t2
t3
t4
See Table 8
1/2 t2
90
sec
sec
ms
Output pulse period (see the Transfer Function section)
Time between F1 falling edge and F2 falling edge
CF pulse width (logic high)
1
tꢀ
t6
See Table 8
CLKIN/4
sec
sec
CF pulse period (see the Transfer Function section)
Minimum time between F1 pulse and F2 pulse
1 The pulse widths of F1, F2, and CF are not fixed for higher output frequencies. See the Transfer Function section.
Timing Diagram
t1
F1
t6
t2
t3
F2
t4
t5
CF
Figure 2. Timing Diagram for Frequency Outputs
Rev. 0 | Page 4 of 24
ADE7761B
ABSOLUTE MAXIMUM RATINGS
TA = 25°C, unless otherwise noted.
PERFORMANCE ISSUES THAT MAY AFFECT
BILLING ACCURACY
Table 3.
Parameter
Rating
The ADE7761B provides pulse outputs, CF, F1, and F2, that are
intended to be used for the billing of active energy. Pulses are
generated at these outputs in two different situations.
VDD to AGND
Analog Input Voltage to AGND
−0.3 V to +7 V
−6 V to +6 V
V
1A, V1B, V1N, V2N, V2P, MISCAL
Reference Input Voltage to AGND
Digital Input Voltage to DGND
Digital Output Voltage to DGND
Operating Temperature Range
Industrial
Storage Temperature Range
Junction Temperature
20-Lead SSOP, Power Dissipation
θJA Thermal Impedance
Lead Temperature, Soldering
Vapor Phase (60 sec)
−0.3 V to VDD + 0.3 V
−0.3 V to VDD + 0.3 V
−0.3 V to VDD + 0.3 V
Case 1
When the analog input V2P − V2N complies with the conditions
described in Figure 34, the CF, F1, and F2 frequencies are
proportional to active power and can be used to bill active energy.
−40°C to +8ꢀ°C
−6ꢀ°C to +1ꢀ0°C
1ꢀ0°C
4ꢀ0 mW
112°C/W
Case 2
When the analog input V2P − V2N does not comply with the
conditions described in Figure 34, the ADE7761B does not
measure active energy but a quantity proportional to kiloampere-
hours (kAh). This quantity is used to generate pulses on the
same CF, F1, and F2. This situation is indicated when the
FAULT pin is high.
21ꢀ°C
220°C
Infrared (1ꢀ sec)
Analog Devices, Inc., cautions users of the ADE7761B about the
following:
Stresses above those listed under Absolute Maximum Ratings
may cause permanent damage to the device. This is a stress
rating only; functional operation of the device at these or any
other conditions above those indicated in the operational
section of this specification is not implied. Exposure to absolute
maximum rating conditions for extended periods may affect
device reliability.
• Billing active energy in Case 1 is consistent with the under-
standing of the quantity represented by pulses on the CF, F1,
and F2 outputs (watthour).
• Billing active energy while the ADE7761B is in Case 2 must
be decided knowing that the entity measured by the ADE7761B
in this case is ampere-hour and not watthour. Users should
be aware of this limitation and decide if the ADE7761B is
appropriate for their application.
ESD CAUTION
Rev. 0 | Page ꢀ of 24
ADE7761B
PIN CONFIGURATION AND FUNCTION DESCRIPTIONS
1
2
3
4
5
6
7
8
9
V
20
19
18
17
16
15
14
13
12
11
F1
DD
V
V
V
V
F2
1A
1B
1N
2N
CF
DGND
REVP
FAULT
RCLKIN
PGA
S0
ADE7761B
TOP VIEW
(Not to Scale)
V
2P
MISCAL
AGND
REF
IN/OUT
SCF 10
S1
Figure 3. Pin Configuration (SSOP)
Table 4. Pin Function Descriptions
Pin No. Mnemonic Description
1
VDD
Power Supply. This pin provides the supply voltage for the digital circuitry in the ADE7761B. The supply voltage
should be maintained at ꢀ V ꢀ% for specified operation. This pin should be decoupled with a 10 μF capacitor
in parallel with a ceramic 100 nF capacitor.
2, 3
V1A, V1B
Analog Inputs for Channel V1 (Current Channel). These inputs are fully differential voltage inputs with maximum
differential input signal levels of 660 mV with respect to V1N for specified operation. The maximum signal level
at these pins is 1 V with respect to AGND. Both inputs have internal ESD protection circuitry, and an overvoltage
of 6 V can also be sustained on these inputs without risk of permanent damage.
4
ꢀ
6
7
V1N
Negative Input for Differential Voltage Inputs, V1A and V1B. The maximum signal level at this pin is 1 V with respect
to AGND. The input has internal ESD protection circuitry, and an overvoltage of 6 V can also be sustained on this
input without risk of permanent damage. The input should be directly connected to the burden resistor and held
at a fixed potential, that is, AGND. See the Analog Inputs section.
Negative Input for Differential Voltage Inputs, V2P and MISCAL. The maximum signal level at this pin is 1 V with
respect to AGND. The input has internal ESD protection circuitry, and an overvoltage of 6 V can also be sustained
on this input without risk of permanent damage. The input should be held at a fixed potential, that is, AGND. See
the Analog Inputs section.
Analog Input for Channel V2 (Voltage Channel). This input is a fully differential voltage input with maximum
differential input signal levels of 660 mV with respect to V2N for specified operation. The maximum signal level at
this pin is 1 V with respect to AGND. This input has internal ESD protection circuitry, and an overvoltage of 6 V
can also be sustained on this input without risk of permanent damage.
Analog Input for Missing Neutral Calibration. This pin can be used to calibrate the CF, F1, and F2 frequencies in the
missing neutral condition. This input is a fully differential voltage input with maximum differential input signal
levels of 660 mV with respect to V2N for specified operation. The maximum signal level at this pin is 1 V with respect
to AGND. This input has internal ESD protection circuitry, and an overvoltage of 6 V can also be sustained on this
input without risk of permanent damage.
V2N
V2P
MISCAL
8
9
AGND
Analog Ground. This pin provides the ground reference for the analog circuitry in the ADE7761B, that is, ADCs and
reference. This pin should be tied to the analog ground plane of the PCB. The analog ground plane is the ground
reference for all analog circuitry such as antialiasing filters and current and voltage transducers. For good noise
suppression, the analog ground plane should be connected to the digital ground plane only at the DGND pin.
This pin provides access to the on-chip voltage reference. The on-chip reference has a nominal value of
2.ꢀ V 8% and a typical temperature coefficient of 30 ppm/°C. An external reference source can also be
connected at this pin. In either case, this pin should be decoupled to AGND with a 1 ꢁF ceramic capacitor and
100 nF ceramic capacitor.
REFIN/OUT
10
SCF
Select Calibration Frequency. This logic input is used to select the frequency on the Calibration Output CF.
Table 7 shows how the calibration frequencies are selected.
11, 12
S1, S0
These logic inputs are used to select one of four possible frequencies for the digital-to-frequency conversion.
This offers the designer greater flexibility when designing the energy meter. See the Selecting a Frequency for an
Energy Meter Application section.
13
14
PGA
RCLKIN
This logic input is used to select the gain for the analog inputs, V1A and V1B. The possible gains are 1 and 16.
To enable the internal oscillator as a clock source on the chip, a precise low temperature drift resistor at
a nominal value of 6.2 kΩ must be connected from this pin to DGND.
Rev. 0 | Page 6 of 24
ADE7761B
Pin No. Mnemonic Description
1ꢀ
FAULT
This logic output goes active high when a fault or missing neutral condition occurs. A fault is defined as a
condition under which the signals on V1A and V1B differ by more than 6.2ꢀ%. A missing neutral condition is
defined when the chip is powered up with no voltage at the input. The logic output is reset to 0 when a fault or
missing neutral condition is no longer detected. See the Fault Detection section and the Missing Neutral Mode
section.
16
17
REVP
This logic output goes logic high when negative power is detected, that is, when the phase angle between the
voltage and current signals is greater than 90°. This output is not latched and is reset when positive power is once
again detected. The output goes high or low at the same time that a pulse is issued on CF.
Digital Ground. This pin provides the ground reference for the digital circuitry in the ADE7761B, that is, multiplier,
filters, and digital-to-frequency converters. This pin should be tied to the digital ground plane of the PCB. The
digital ground plane is the ground reference for all digital circuitry, such as counters (mechanical and digital),
MCUs, and indicator LEDs. For good noise suppression, the analog ground plane should be connected to the digital
ground plane only at the DGND pin.
DGND
18
CF
Calibration Frequency Logic Output. The CF logic output, active high, gives instantaneous active power information.
This output is used for operational and calibration purposes. See the Digital-to-Frequency Conversion section.
19, 20
F2, F1
Low Frequency Logic Outputs. F1 and F2 supply average active power information. The logic outputs can be
used to directly drive electromechanical counters and 2-phase stepper motors.
Rev. 0 | Page 7 of 24
ADE7761B
TYPICAL PERFORMANCE CHARACTERISTICS
1.0
1.0
0.8
PF = 1
GAIN = 16
ON-CHIP REFERENCE
ON-CHIP REFERENCE
0.8
0.6
0.6
–40°C
0.4
0.4
PF = –0.5
0.2
0.2
+25°C
0
0
–0.2
–0.2
–0.4
–0.6
–0.8
–1.0
+85°C
PF = +1
PF = +0.5
–0.4
–0.6
–0.8
–1.0
0.1
1
10
100
0.1
1
10
100
CURRENT (% of Full Scale)
CURRENT (% of Full Scale)
Figure 4. Active Power Error As a Percentage of Reading
with Gain = 1 and Internal Reference
Figure 7. Active Power Error As a Percentage of Reading
over Power Factor with Gain = 16 and Internal Reference
1.0
1.0
0.8
GAIN = 16
ON-CHIP REFERENCE
PF = 1
ON-CHIP REFERENCE
0.8
0.6
0.6
–40°C; PF = 0.5
+85°C; PF = 0.5
0.4
0.4
5.25V
0.2
0.2
5.00V
4.75V
0
0
–0.2
–0.4
–0.6
–0.8
–1.0
–0.2
–0.4
–0.6
–0.8
–1.0
+25°C; PF = 1
+25°C; PF = 0.5
0.1
1
10
100
0.1
1
10
100
CURRENT (% of Full Scale)
CURRENT (% of Full Scale)
Figure 8. Active Power Error As a Percentage of Reading
over Power Supply with Gain = 1 and Internal Reference
Figure 5. Active Power Error As a Percentage of Reading
over Power Factor with Gain = 1 and Internal Reference
1.0
0.8
0.6
0.4
0.2
1.0
0.8
PF = 1, GAIN = 16
ON-CHIP REFERENCE
ON-CHIP REFERENCE
–40°C
0.6
+25°C
0.4
–40°C
0.2
+25°C
+85°C
0
–0.2
–0.4
–0.6
–0.8
–1.0
0
–0.2
–0.4
–0.6
–0.8
–1.0
+85°C
0.1
1
10
100
0.1
1
10
100
CURRENT (% of Full Scale)
CURRENT (% of Full Scale)
Figure 6. Active Power Error As a Percentage of Reading
with Gain = 16 and Internal Reference
Figure 9. Ampere Hour Error As a Percentage of Reading
in Missing Neutral Mode with Gain = 1 and Internal Reference
Rev. 0 | Page 8 of 24
ADE7761B
TEST CIRCUIT
V
V
DD
+
10µF
RB
100nF
1
PS2501-1
40A TO 80mA
I
2kΩ
18
CF
DD
1kΩ
1
4
2
V
1A
19
20
16
F2
F1
TO FREQ.
COUNTER
33nF
ADE7761B
REVP
2
3
1kΩ
33nF
1kΩ
2kΩ
3
V
V
V
1B
1N
2N
15
14
FAULT
RB
6.2kΩ
RCLKIN
4
5
RB = 18Ω
33nF
10kΩ
1kΩ
12
11
10
S0
S1
33nF
SCF
1MΩ
1kΩ 33nF
REF
6
7
9
V
IN/OUT
2P
+
220V
100nF
10µF
560kΩ
MISCAL
PGA AGND DGND
13 17
100kΩ 33nF
8
Figure 10. Test Circuit for Performance Curves
Rev. 0 | Page 9 of 24
ADE7761B
TERMINOLOGY
For the dc PSR measurement, a reading at nominal supplies (5 V)
is taken. A second reading is obtained with the same input signal
levels when the power supplies are varied 5%. Any error
introduced is again expressed as a percentage of reading.
Measurement Error
The error associated with the energy measurement made by the
ADE7761B is defined by
Percentage Error =
ADC Offset Error
⎛
⎜
⎜
⎝
⎞
⎟
⎟
⎠
Energy Registered by ADE7761B −True Energy
This is the dc offset associated with the analog inputs to the ADCs.
With the analog inputs connected to AGND, the ADCs still see
a dc analog input signal. The magnitude of the offset depends on
the input gain and range selection (see the Typical Performance
Characteristics section). However, when HPFs are switched on,
the offset is removed from the current channels and the power
calculation is not affected by this offset.
× 100%
True Energy
Phase Error Between Channels
The high-pass filter (HPF) in the current channel has a phase
lead response. To offset this phase response and equalize the
phase response among channels, a phase correction network is
also placed in the current channel. The phase correction network
ensures a phase match between the current channels and the
voltage channels to within 0.1° over a range of 45 Hz to
65 Hz and 0.2° over a range of 40 Hz to 1 kHz.
Gain Error
The gain error in the ADE7761B ADCs is defined as the difference
between the measured output frequency (minus the offset) and
the ideal output frequency. It is measured with a gain of 1 in
Channel V1A. The difference is expressed as a percentage of the
ideal frequency, which is obtained from the transfer function
(see the Transfer Function section).
Power Supply Rejection (PSR)
PSR quantifies the ADE7761B measurement error as a percentage
of reading when the power supplies are varied. For the ac PSR
measurement, a reading at nominal supplies (5 V) is taken.
A second reading is obtained with the same input signal levels
when an ac signal (175 mV rms/100 Hz) is introduced onto the
supplies. Any error introduced by this ac signal is expressed as
a percentage of reading (see the Measurement Error definition).
Gain Error Match
The gain error match is defined as the gain error (minus the offset)
obtained when switching between a gain of 1 or 16. It is expressed
as a percentage of the output ADC code obtained under a gain of 1.
Rev. 0 | Page 10 of 24
ADE7761B
THEORY OF OPERATION
V
V
1A
DIFFERENTIAL INPUT A
±660mV MAX PEAK
POWER SUPPLY MONITOR
V
, V
1A 1B
V1
V1
+660mV
GAIN
The ADE7761B continuously monitors the power supply (VDD)
with its on-chip power supply monitor. If the supply is less than
4 V 5%, the ADE7761B goes into an inactive state; that is, no
energy is accumulated, and the CF, F1, and F2 outputs are disabled.
This is useful to ensure correct device operation at power-up
and during power-down. The power supply monitor has built-in
hysteresis and filtering that provide a high degree of immunity
to false triggering due to noisy supplies.
+ V
CM
1N
COMMON MODE
V
CM
±100mV MAX
V
CM
AGND
–660mV
GAIN
+ V
CM
DIFFERENTIAL INPUT B
±660mV MAX PEAK
V
1B
Figure 12. Maximum Signal Levels, Channel V1
Channel V2 (Voltage Channel)
The power supply and decoupling for the part should be such
that the ripple at VDD does not exceed 5 V 5%, as specified for
normal operation.
The output of the line voltage transducer is connected to the
ADE7761B at this analog input. Channel V2 is a single-ended
voltage input. The maximum peak differential signal on
Channel V2 is 660 mV with respect to V2N. Figure 13 shows the
maximum signal levels that can be connected to Channel V2.
V
DD
5V
4V
V2
V
2P
2N
+660mV + V
CM
V2
DIFFERENTIAL INPUT
±660mV MAX PEAK
0V
V
V
CM
TIME
V
COMMON MODE
±100mV MAX
CM
ADE7761B
REVP - FAULT - CF -
F1 - F2 OUTPUTS
–660mV + V
CM
INACTIVE
ACTIVE
INACTIVE
Figure 11. On-Chip, Power Supply Monitoring
Figure 13. Maximum Signal Levels, Channel V2
ANALOG INPUTS
The differential voltage V2P − V2N must be referenced to a
common mode (usually AGND). The analog inputs of the
ADE7761B can be driven with common-mode voltages of up
to 100 mV with respect to AGND. However, the best results
are achieved using a common mode equal to AGND.
Channel V1 (Current Channel)
The voltage outputs from the current transducers are connected
to the ADE7761B at Channel V1. It has two voltage inputs, V1A
and V1B. These inputs are fully differential with respect to V1N.
However, at any one time, only one input is selected to perform
the power calculation (see the Fault Detection section).
MISCAL Input
The input for the power calibration in missing neutral mode
is connected to the ADE7761B at this analog input. MISCAL
is a single-ended, voltage input. It is recommended to use a dc
signal derived from the voltage reference to drive this pin. The
maximum peak differential signal on MISCAL is 660 mV with
respect to V2N. Figure 14 shows the maximum signal levels that
can be connected to the MISCAL pin.
The maximum peak differential signal on V1A − V1N and V1B − V1N
is 660 mV. However, Channel V1 has a programmable gain
amplifier (PGA) with user-selectable gains of 1 and 16 (see
Table 5). This gain facilitates easy transducer interfacing.
Table 5. Channel V1 Dynamic Range
PGA
Gain
Maximum Differential Signal (mV)
0
1
1
16
660
41
MISCAL
MISCAL
MISCAL
+660mV + V
CM
DIFFERENTIAL INPUT
±660mV MAX PEAK
Figure 12 shows the maximum signal levels on V1A, V1B, and
V1N. The maximum differential voltage is 660 mV divided by
the gain selection. The differential voltage signal on the inputs
must be referenced to a common mode (usually AGND).
V
2N
V
CM
COMMON MODE
±100mV MAX
V
CM
AGND
Figure 14. Maximum Signal Levels, MISCAL
The differential voltage, MISCAL − V2N, must be referenced
to a common mode (usually AGND). The analog inputs of the
ADE7761B can be driven with common-mode voltages of up to
100 mV with respect to AGND. However, best results are achieved
using a common mode equal to AGND.
Rev. 0 | Page 11 of 24
ADE7761B
Typical Connection Diagrams
Adjusting the level of MISCAL to calibrate the meter in missing
neutral mode can be done by changing the ratio of RC and
RD + VR1. When the internal reference is used, the values of RC,
RD, and VR1 must be chosen to limit the current sourced by
the internal reference sourcing current to below the specified
10 μA. Therefore, because VREF internal = 2.5 V, RC + RD +
VR1 > 600 kΩ.
Figure 15 shows a typical connection diagram for Channel V1.
The analog inputs are used to monitor both the phase and
neutral currents. Because of the large potential difference
between the phase and neutral, two current transformers (CTs)
must be used to provide the isolation. Note that both CTs are
referenced to analog ground (AGND); therefore, the common-
mode voltage is 0 V. The CT turn ratio and burden resistor (RB)
are selected to give a peak differential voltage of 660 mV/gain.
INTERNAL OSCILLATOR
The nominal internal oscillator frequency is 450 kHz when
used with the recommended ROSC resistor value of 6.2 kΩ
between RCLKIN and DGND (see Figure 18).
V
R
1A
F
CT
±660mV
GAIN
RB
RB
C
F
F
ADE7761B
IP
IN
AGND
V
V
1N
1B
±660mV
GAIN
3kΩ
2.5V
INTERNAL
C
REFERENCE
OSCILLATOR
CT
R
F
9
14
17
REF
RCLKIN
DGND
IN/OUT
Figure 15. Typical Connection for Channel V1
R
OSC
Figure 16 shows two typical connections for Channel V2.
The first option uses a potential transformer (PT) to provide
complete isolation from the main voltage. In the second option,
the ADE7761B is biased around the neutral wire, and a resistor
divider is used to provide a voltage signal that is proportional to
the line voltage. Adjusting the ratio of RA and RB + VR is a
convenient way to carry out a gain calibration on the meter.
Figure 18. Internal Oscillator Connection
The internal oscillator frequency is inversely proportional to the
value of this resistor. Although the internal oscillator operates
when used with an ROSC resistor value between 5 kΩ and 12 kΩ,
it is recommended that a value be chosen within the range of
the nominal value.
V
R
2P
F
C
±660mV
AGND
F
F
The output frequencies on CF, F1, and F2 are directly propor-
tional to the internal oscillator frequency; therefore, Resistor ROSC
must have a low tolerance and low temperature drift. A low
tolerance resistor limits the variation of the internal oscillator
frequency. A small variation of the clock frequency and, conse-
quently, of the output frequencies from meter to meter contributes
to a smaller calibration range of the meter.
V
R
2N
F
C
1
RA
C
F
1
1
RB
V
V
2P
VR
R
2N
F
A low temperature drift resistor directly limits the variation of
the internal clock frequency over temperature. The stability of
the meter to external variation is then better ensured by design.
C
T
1
RB + VR = RF.
Figure 16. Typical Connections for Channel V2
Figure 17 shows a typical connection for the MISCAL input.
The voltage reference input (REFIN/OUT) is used as a dc reference
to set the MISCAL voltage.
REF
IN/OUT
RC
C
F
RD
MISCAL
VR1
V
R
2N
F
C
F
Figure 17. Typical Connection for MISCAL
Rev. 0 | Page 12 of 24
ADE7761B
ANTIALIAS FILTER (RC)
DIGITAL FILTER
ANALOG-TO-DIGITAL CONVERSION
SAMPLING FREQUENCY
SHAPED NOISE
SIGNAL
NOISE
The analog-to-digital conversion in the ADE7761B is carried
out using second-order, Σ-Δ ADCs. Figure 19 shows a first-
order, Σ-Δ ADC (for simplicity). The converter is made up of
two parts: the Σ-Δ modulator and the digital low-pass filter.
MCLK
0
1
225
FREQUENCY (kHz)
450
ANALOG
LOW-PASS FILTER
LATCHED
COMPAR-
ATOR
INTEGRATOR
DIGITAL
LOW-PASS FILTER
HIGH RESOLUTION
OUTPUT FROM
DIGITAL LFP
SIGNAL
NOISE
R
V
REF
1
24
C
....10100101....
1-BIT DAC
0
1
225
FREQUENCY (kHz)
450
Figure 19. First-Order, Σ-Δ ADC
Figure 20. Noise Reduction Due to Oversampling and
Noise Shaping in the Analog Modulator
A Σ-Δ modulator converts the input signal into a continuous
serial stream of 1s and 0s at a rate determined by the sampling
clock. In the ADE7761B, the sampling clock is equal to CLKIN.
The 1-bit DAC in the feedback loop is driven by the serial data
stream. The DAC output is subtracted from the input signal.
If the loop gain is high enough, the average value of the DAC
output (and, therefore, the bit stream) approaches that of the
input signal level. For any given input value in a single sampling
interval, the data from the 1-bit ADC is virtually meaningless.
Only when a large number of samples are averaged is a meaningful
result obtained. This averaging is carried out in the second part
of the ADC, the digital low-pass filter. By averaging a large
number of bits from the modulator, the low-pass filter can
produce 24-bit data-words that are proportional to the input
signal level.
Antialias Filter
Figure 20 also shows an analog low-pass filter, RC, on input to
the modulator. This filter is present to prevent aliasing. Aliasing
is an artifact of all sampled systems, which means that frequency
components in the input signal to the ADC that are higher than
half the sampling rate of the ADC appear in the sampled signal
frequency below half the sampling rate. Figure 21 illustrates
the effect.
ANTIALIASING EFFECTS
SAMPLING
FREQUENCY
IMAGE
FREQUENCIES
The Σ-Δ converter uses two techniques to achieve high resolution
from what is essentially a 1-bit conversion technique. The first is
oversampling, which means that the signal is sampled at a rate
(frequency) that is many times higher than the bandwidth of
interest. For example, the sampling rate in the ADE7761B is
CLKIN (450 kHz) and the band of interest is 40 Hz to 1 kHz.
Oversampling has the effect of spreading the quantization noise
(noise due to sampling) over a wider bandwidth. With the noise
spread more thinly over a wider bandwidth, the quantization
noise in the band of interest is lowered (see Figure 20).
0
1
225
450
FREQUENCY (kHz)
Figure 21. ADC and Signal Processing in Current Channel or Voltage Channel
In Figure 21, frequency components (arrows shown in black)
above half the sampling frequency (also known as the Nyquist
frequency), that is, 225 kHz, are imaged or folded back down
below 225 kHz (arrows shown in gray). This happens with all
ADCs, no matter what the architecture. In Figure 21, only
frequencies near the sampling frequency (450 kHz) move into
the band of interest for metering (40 Hz to 1 kHz). This fact
allows the use of a very simple low-pass filter to attenuate these
frequencies (near 250 kHz) and, thereby, prevent distortion in the
band of interest. A simple RC filter (single pole) with a corner
frequency of 10 kHz produces an attenuation of approximately
33 dB at 450 kHz (see Figure 21). This is sufficient to eliminate
the effects of aliasing.
However, oversampling alone is not an efficient enough method
to improve the signal-to-noise ratio (SNR) in the band of interest.
For example, an oversampling ratio of 4 is required just to increase
the SNR by only 6 dB (1 bit). To keep the oversampling ratio at
a reasonable level, it is possible to shape the quantization noise so
the majority of the noise lies at the higher frequencies. This is what
happens in the Σ-Δ modulator; the noise is shaped by the inte-
grator, which has a high-pass type response for the quantization
noise. The result is that most of the noise is at higher frequencies,
where it can be removed by the digital low-pass filter. This noise
shaping is also shown in Figure 20.
Rev. 0 | Page 13 of 24
ADE7761B
Power Factor Considerations
ACTIVE POWER CALCULATION
The method used to extract the active power information from
the instantaneous power signal (by low-pass filtering) is still valid
even when the voltage and current signals are not in phase.
The ADCs digitize the voltage signals from the current and
voltage transducers. A high-pass filter in the current channel
removes any dc component from the current signal. This eliminates
any inaccuracies in the active power calculation due to offsets in
the voltage or current signals (see the HPF and Offset Effects
section).
Figure 23 displays the unity power factor condition and a
displacement power factor (DPF = 0.5), that is, current signal
lagging the voltage by 60°.
INSTANTANEOUS
POWER SIGNAL
INSTANTANEOUS
ACTIVE POWER SIGNAL
The active power calculation is derived from the instantaneous
power signal. The instantaneous power signal is generated by
a direct multiplication of the current and voltage signals.
To extract the active power component (dc component), the
instantaneous power signal is low-pass filtered. Figure 22 illustrates
the instantaneous active power signal and shows how the active
power information can be extracted by low-pass filtering the
instantaneous power signal. This scheme correctly calculates
active power for nonsinusoidal current and voltage waveforms
at all power factors. All signal processing is carried out in the
digital domain for superior stability over temperature and time.
V × I
2
0V
CURRENT
VOLTAGE
INSTANTANEOUS
POWER SIGNAL
INSTANTANEOUS
ACTIVE POWER SIGNAL
DIGITAL-TO-
FREQUENCY
V × I
2
F1
F2
× cos(60°)
0V
CH1
CH2
PGA
ADC
ADC
HPF
MULTIPLIER
DIGITAL-TO-
FREQUENCY
LPF
VOLTAGE
CURRENT
CF
60°
Figure 23. Active Power Calculation over PF
INSTANTANEOUS
INSTANTANEOUS
POWER SIGNAL –p(t)
ACTIVE POWER SIGNAL
If one assumes that the voltage and current waveforms are
sinusoidal, the active power component of the instantaneous
power signal (dc term) is given by
V × I
p(t) = i(t) × v(t)
WHERE:
v(t) = V × cos(ωt)
V × I
2
i(t) = I × cos(ωt)
(V × I/2) × cos(60°)
V × I
2
p(t) =
{1 + cos (2ωt)}
This is the correct active power calculation.
Nonsinusoidal Voltage and Current
TIME
Figure 22. Signal Processing Block Diagram
The active power calculation method also holds true for
nonsinusoidal current and voltage waveforms. All voltage
and current waveforms in practical applications have some
harmonic content. Using the Fourier transform, instantaneous
voltage and current waveforms can be expressed in terms of
their harmonic content.
The low frequency output of the ADE7761B is generated by
accumulating this active power information. This low frequency
inherently means a long accumulation time between output
pulses. The output frequency is, therefore, proportional to the
average active power. This average active power information
can, in turn, be accumulated (for example, by a counter) to
generate active energy information. Because of its high output
frequency and, therefore, shorter integration time, the CF
output is proportional to the instantaneous active power. This is
useful for system calibration purposes that take place under
steady load conditions.
v(t) = V + 2 × ∞ V ×sin(hωt + α )
(1)
∑
O
h
h
h ≠0
where:
v(t) is the instantaneous voltage.
VO is the average value.
Vh is the rms value of Voltage Harmonic h.
αh is the phase angle of the voltage harmonic.
Rev. 0 | Page 14 of 24
ADE7761B
∞
The HPF in Channel V1 has an associated phase response that
is compensated for on-chip. Figure 25 and Figure 26 show the
phase error between channels with the compensation network
activated. The ADE7761B is phase compensated up to 1 kHz as
shown, which ensures a correct active harmonic power calculation
even at low power factors.
(2)
i(t) = IO + 2 × I ×sin(hωt +β )
∑
h
h
h ≠0
where:
i(t) is the instantaneous current.
IO is the dc component.
Ih is the rms value of Current Harmonic h.
βh is the phase angle of the current harmonic.
DC COMPONENT (INCLUDING ERROR TERM)
IS EXTRACTED BY THE LPF FOR ACTIVE
POWER CALCULATION
Using Equation 1 and Equation 2, the Active Power P can be
expressed in terms of its fundamental active power (P1) and
harmonic active power (PH).
V
× I
1
1
2
P = P1 + PH
where:
V
V
× I
× I
1
0
P1 = V1 × I1 cos(Φ1)
Φ1 = α1 − β1
(3)
(4)
0
1
2ω
FREQUENCY (Rad/s)
0ω
and
∞
Figure 24. Effect of Channel Offsets on the Active Power Calculation
P = V × I ×cos(Φ )
∑
H
h
h
h
h=2
Φh = αh − βh
0.30
0.25
0.20
0.15
As can be seen in Equation 4, a harmonic active power component
is generated for every harmonic provided that the harmonic is
present in both the voltage and current waveforms. The power
factor calculation was previously shown to be accurate in the
case of a pure sinusoid; therefore, the harmonic active power
must also correctly account for the power factor because it is
made up of a series of pure sinusoids.
0.10
0.05
0
Note that the input bandwidth of the analog inputs is 7 kHz
with an internal oscillator frequency of 450 kHz.
–0.05
–0.10
HPF and Offset Effects
0
100 200 300 400 500 600 700 800 900 1000
FREQUENCY (Hz)
Equation 5 shows the effect of offsets on the active power
calculation. Figure 24 shows the effect of offsets on the active
power calculation in the frequency domain.
Figure 25. Phase Error Between Channels (0 Hz to 1 kHz)
V(t) × I(t) =
0.30
0.25
0.20
0.15
0.10
(5)
(V0 +V1 × cos(ωt))×(I0 + I1 × cos(ωt)) =
V1 × I1
V0 × I1 +
+V0 × I1 × cos(ωt) +V1 × I0 × cos(ωt)
2
As shown in Equation 5 and Figure 24, an offset on Channel V1
and Channel V2 contributes a dc component after multiplication.
Because this dc component is extracted by the LPF and used to
generate the active power information, the offsets contribute
a constant error to the active power calculation. This problem is
easily avoided in the ADE7761B with the HPF in Channel V1. By
removing the offset from at least one channel, no error component
can be generated at dc by the multiplication. Error terms at cos(ωt)
are removed by the LPF and the digital-to-frequency conversion
(see the Digital-to-Frequency Conversion section).
0.05
0
–0.05
–0.10
40
45
50
55
60
65
70
FREQUENCY (Hz)
Figure 26. Phase Error Between Channels (40 Hz to 70 Hz)
Rev. 0 | Page 1ꢀ of 24
ADE7761B
The output frequency on CF can be up to 2048 times higher
than the frequency on F1 and F2. This higher output frequency
is generated by accumulating the instantaneous active power
signal over a much shorter time while converting it to a frequency.
This shorter accumulation period means less averaging of the
cos(2ωt) component. As a consequence, some of this instantaneous
power signal passes through the digital-to-frequency conversion.
This is not a problem in the application.
DIGITAL-TO-FREQUENCY CONVERSION
As described in the Active Power Calculation section, the digital
output of the low-pass filter after multiplication contains the
active power information. However, because this LPF is not an
ideal brick wall filter implementation, the output signal also
contains attenuated components at the line frequency and its
harmonics, that is, cos(hωt), where h = 1, 2, 3, …, and so on.
The magnitude response of the filter is given by
Where CF is used for calibration purposes, the frequency should
be averaged by the frequency counter, which removes any ripple.
If CF is being used to measure energy, such as in a microprocessor-
based application, the CF output should also be averaged to calcu-
late power. Because the F1 and F2 outputs operate at a much
lower frequency, much more averaging of the instantaneous active
power signal is carried out. The result is a greatly attenuated
sinusoidal content and a virtually ripple-free frequency output.
1
H( f ) =
(6)
1 = ( f /4.5Hz)2
For a line frequency of 50 Hz, this gives an attenuation of the 2ω
(100 Hz) component of approximately −26.9 dB. The dominating
harmonic is at twice the line frequency, cos(2ωt), due to the
instantaneous power signal.
Figure 27 shows the instantaneous active power signal output of
the LPF, which still contains a significant amount of instantaneous
power information, cos(2ωt). This signal is then passed to the
digital-to-frequency converter, where it is integrated (accumulated)
over time to produce an output frequency. This accumulation of
the signal suppresses or averages out any non-dc components in
the instantaneous active power signal. The average value of a
sinusoidal signal is zero. Therefore, the frequency generated by
the ADE7761B is proportional to the average active power.
TRANSFER FUNCTION
Frequency Output F1 and Frequency Output F2
The ADE7761B calculates the product of two voltage signals
(on Channel V1 and Channel V2) and then low-pass filters this
product to extract active power information. This active power
information is then converted to a frequency. The frequency
information is output on F1 and F2 in the form of active high
pulses. The pulse rate at these outputs is relatively low, for
example, 0.37 Hz maximum for ac signals with S0 = S1 = 0
(see Table 8). This means that the frequency at these outputs
is generated from active power information accumulated over
a relatively long period. The result is an output frequency that
is proportional to the average active power. The averaging of the
active power signal is implicit to the digital-to-frequency conver-
sion. The output frequency or pulse rate is related to the input
voltage signals by
F
1
DIGITAL-TO-
FREQUENCY
F
F
1
2
V
TIME
MULTIPLIER
CF
DIGITAL-TO-
FREQUENCY
LPF
I
CF
LPF TO EXTRACT
ACTIVE POWER
(DC TERM)
6.13×Gain×V1rms ×V2rms × f1−4
(7)
F , F Frequency =
1
2
2
VREF
where:
F1, F2 Frequency is the output frequency on F1 and F2 (Hz).
V1rms is the differential rms voltage signal on Channel V1 (V).
V2rms is the differential rms voltage signal on Channel V2 (V).
Gain is 1 or 16, depending on the PGA gain selection made
using Logic Input PGA.
TIME
0
ω
2ω
FREQUENCY (Rad/s)
INSTANTANEOUS ACTIVE POWER SIGNAL (FREQUENCY DOMAIN)
Figure 27. Active Power to Frequency Conversion
VREF is the reference voltage (2.5 V 8%) (V).
f1–4 is one of four possible frequencies selected by using Logic
Input S0 and Logic Input S1 (see Table 6).
Figure 27 also shows the digital-to-frequency conversion for
steady load conditions: constant voltage and current. As can be
seen in Figure 27, the frequency output CF varies over time,
even under steady load conditions. This frequency variation is
primarily due to the cos(2ωt) component in the instantaneous
active power signal.
Rev. 0 | Page 16 of 24
ADE7761B
Note that if the on-chip reference is used, actual output
frequencies may vary from device to device due to a reference
tolerance of 8%.
Table 6. f1–4 Frequency Selection
S1
S0
f1–4 (Hz)1
1.72
f1−4 = OSC/2n2
OSC/218
0
0
0
1
3.44
OSC/217
6.13 × 0.66 × 0.66 ×1.72Hz
F , F Frequency =
= 0.367Hz
1
2
1
0
6.86
OSC/216
OSC/21ꢀ
2 × 2 × 2.52
1
1
13.7
CF Frequency = F1, F2 × 64 = 23.5 Hz
1 Values are generated using the nominal frequency of 4ꢀ0 kHz.
2 f1–4 are a binary fraction of the master clock and, therefore, vary with the
internal oscillator frequency (OSC).
As can be seen from these two example calculations, the maximum
output frequency for ac inputs is always half of that for dc input
signals. Table 8 shows a complete listing of all maximum output
frequencies for ac signals.
Frequency Output CF
The pulse output calibration frequency (CF) is intended for use
during calibration. The output pulse rate on CF can be up to
2048 times the pulse rate on F1 and F2. The lower the f1–4
frequency selected, the higher the CF scaling. Table 7 shows
how the two frequencies are related, depending on the states of
Logic Input S0, Logic Input S1, and Logic Input SCF. Because of
its relatively high pulse rate, the frequency at this logic output is
proportional to the instantaneous active power. As with F1 and
F2, the frequency is derived from the output of the low-pass filter
after multiplication. However, because the output frequency is high,
this active power information is accumulated over a much shorter
time. Therefore, less averaging is carried out in the digital-to-
frequency conversion. With much less averaging of the active
power signal, the CF output is much more responsive to power
fluctuations (see Figure 22).
Table 8. Maximum Output Frequencies on CF, F1, and F2 for
AC Inputs
F1, F2 Maximum CF Maximum
Frequency (Hz), Frequency (Hz),
CF-to-F1
Ratio
SCF S1 S0 1/t2
1/t5
1
0
1
0
1
0
1
0
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0.37
0.37
0.73
0.73
1.47
1.47
2.94
2.94
46.98
23.49
46.98
23.49
46.98
23.49
46.98
6013
128
64
64
32
32
16
16
2048
FAULT DETECTION
Table 7. Relationship Between CF and F1, F2 Frequency
Outputs
The ADE7761B incorporates a novel fault detection scheme
that warns of fault conditions and allows the ADE7761B to
continue accurate billing during a fault event. The ADE7761B
does this by continuously monitoring both the phase and neutral
(return) currents. A fault is indicated when these currents differ
by more than 6.25%. However, even during a fault, the output
pulse rate on F1 and F2 is generated using the larger of the two
currents. Because the ADE7761B looks for a difference between
the voltage signals on V1A and V1B, it is important that both
current transducers be closely matched.
SCF
S1
S0
f1–4 (Hz)
1.72
1.72
3.44
3.44
6.86
6.86
13.7
13.7
CF Frequency Output
128 × F1, F2
64 × F1, F2
64 × F1, F2
32 × F1, F2
32 × F1, F2
16 × F1, F2
16 × F1, F2
2048 × F1, F2
1
0
1
0
1
0
1
0
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
On power-up, the output pulse rate of the ADE7761B is propor-
tional to the product of the voltage signals on V1A and Channel V2.
If the difference between V1A and V1B on power-up is greater than
6.25%, the fault indicator (FAULT) becomes active after about
1 second. In addition, if V1B is greater than V1A, the ADE7761B
selects V1B as the input. Fault detection is automatically disabled
when the voltage signal on Channel V1 is less than 0.3% of the
full-scale input range. This eliminates false detection of a fault
due to noise at light loads.
Example
In this example, if ac voltages of 660 mV peak are applied to
Channel V1 and Channel V2, the expected output frequency on
CF, F1, and F2 is calculated as
Gain = 1, PGA = 0
f1–4 = 1.7 Hz, SCF = S1 = S0 = 0
V1rms = rms of 660 mV peak ac = 0.66/√2 V
V2rms = rms of 660 mV peak ac = 0.66/√2 V
VREF = 2.5 V (nominal reference value)
Rev. 0 | Page 17 of 24
ADE7761B
Fault with Active Input Greater Than Inactive Input
Calibration Concerns
If V1A is the active current input (that is, being used for billing),
and the voltage signal on V1B (inactive input) falls below 93.75%
of V1A, the fault indicator becomes active. Both analog inputs
are filtered and averaged to prevent false triggering of this logic
output. As a consequence of the filtering, there is a time delay of
approximately 3 sec on the Logic Output FAULT after the fault
event. The FAULT logic output is independent of any activity on
the F1 or F2 outputs. Figure 28 shows one condition under
which FAULT becomes active. Because V1A is the active input
and it is still greater than V1B, billing is maintained on V1A; that
is, no swap to the V1B input occurs. V1A remains the active input.
Typically, when a meter is being calibrated, the voltage and current
circuits are separated, as shown in Figure 30. This means that
current passes through only the phase or neutral circuit. Figure 30
shows current being passed through the phase circuit. This is
the preferred option because the ADE7761B starts billing on the
input V1A on power-up. The Phase Circuit CT is connected to
V1A in Figure 30. Because there is no current in the neutral circuit,
the FAULT indicator comes on under these conditions. However,
this does not affect the accuracy of the calibration and can be
used as a means to test the functionality of the fault detection.
V
R
1A
F
IB
CT
FAULT
FILTER
V
V
1A
1A
AND
RB
RB
V
COMPARE
C
A
1B
V
F
F
1A
V
V
TO
1A
1B
AGND
MULTIPLIER
0V
V
V
1N
V
V
1N
1B
IB
0V
AGND
C
B
TEST
CURRENT
V
< 93.75% OF V
1A
1B
CT
R
F
1B
1
RA
FAULT
<0
C
F
1
1
RB
V
V
2P
>0
VR
ACTIVE POINT – INACTIVE INPUT
R
F
2N
6.25% OF ACTIVE INPUT
V
C
T
Figure 28. Fault Conditions for Active Input Greater Than Inactive Input
240V rms
1
RB + VR = RF.
Fault with Inactive Input Greater Than Active Input
Figure 30. Conditions for Calibration of Channel B
Figure 29 illustrates another fault condition. If the difference
between V1B, the inactive input, and V1A, the active input (that
is, being used for billing), becomes greater than 6.25% of V1B,
the FAULT indicator becomes active and a swap over to the V1B
input occurs. The Analog Input V1B becomes the active input.
Again, a time constant of about 3 sec is associated with this swap.
V1A does not swap back to the active channel until V1A is greater
than V1B, and the difference between V1A and V1B, in this order,
becomes greater than 6.25% of V1A. However, the FAULT indi-
cator becomes inactive as soon as V1A is within 6.25% of V1B. This
threshold eliminates potential chatter between V1A and V1B.
If the neutral circuit is chosen for the current circuit in the
arrangement shown in Figure 30, this may have implications for
the calibration accuracy. The ADE7761B powers up with the
V1A input active as normal. However, because there is no current
in the phase circuit, the signal on V1A is zero. This causes a fault
to be flagged and the active input to be swapped to V1B (neutral).
The meter can be calibrated in this mode, but the phase and
neutral CTs may differ slightly. Because under no-fault conditions
all billing is carried out using the phase CT, the meter should be
calibrated using the phase circuit. Of course, both phase and
neutral circuits can be calibrated.
FAULT
FILTER
AND
V
V
1A
1A
MISSING NEUTRAL MODE
A
V
COMPARE
1B
V
V
TO
1A
1B
The ADE7761B integrates a novel fault detection scheme that
warns and allows the ADE7761B to continue to bill in case a
meter is connected to only one wire (see Figure 31). For correct
operation of the ADE7761B in this mode, the VDD pin of the
ADE7761B must be maintained within the specified range
(5 V 5%). The missing neutral detection algorithm is designed
to work over a line frequency of 45 Hz to 55 Hz.
MULTIPLIER
0V
V
V
1N
1B
AGND
B
V
< 93.75% OF V
1B
1A
FAULT + SWAP
<0
>0
ACTIVE POINT – INACTIVE INPUT
6.25% OF INACTIVE INPUT
Figure 29. Fault Conditions for Inactive Input Greater Than Active Input
Rev. 0 | Page 18 of 24
ADE7761B
V
R
V
1A
F
Analog Devices cautions users of the ADE7761B about the
following:
CT
IB
RB
RB
C
244V rms
POWER
GENERATOR
F
• Billing active energy in Case 1 is consistent with the under-
standing of the quantity represented by pulses on the CF, F1,
and F2 outputs (watthour).
1A
V
1N
0V
C
F
• Billing active energy while the ADE7761B is in Case 2 must
be decided knowing that the entity measured by the ADE7761B
in this case is ampere-hour and not watthour. Users should
be aware of this limitation and decide if the ADE7761B is
appropriate for their application.
CT
1
R
V
1B
F
LOAD
RA
C
F
F
1
1
RB
V
V
2P
VR
R
2N
Missing Neutral Detection
C
F
The ADE7761B continuously monitors the voltage input and
detects a missing neutral condition when the voltage input peak
value is smaller than 9% of the analog full scale or when no zero
crossings are detected on this input (see Figure 33).
1
RB + VR = RF.
Figure 31. Missing Neutral System Diagram
The ADE7761B detects a missing neutral condition by continu-
ously monitoring the voltage channel input (V2P − V2N). The
FAULT pin is held high when a missing neutral condition is
detected. In this mode, the ADE7761B continues to bill the energy
based on the signal level on the current channel (see Figure 32).
The billing rate or frequency outputs can be adjusted by changing
the dc level on the MISCAL pin.
V
MISSING
2P
NEUTRAL
FILTER AND
THRESHOLD
V2
ADC
V
2N
AGND
|V2|
< 9% OF FULL SCALE
OR
NO ZERO CROSSING ON V2
PEAK
V
V
V
1A
1N
1B
ADC
V
– V
2N
V
– V
2N
V – V
2P 2N
2P
2P
A > B
HPF
FS
FS
FS
ADC
ZERO
CROSSING
DETECTION
B > A
A ≠ B
9% OF FS
0V
0V
0V
LPF
MISSING NEUTRAL
GAIN ADJUSMTENT
MISCAL
ADC
DIGITAL-TO-
FREQUENCY
CONVERTERS
Figure 33. Missing Neutral Detection
The ADE7761B leaves the missing neutral mode for normal
operation when both conditions are no longer valid; that is,
a voltage peak value of greater than 9% of full scale and zero
crossing on the voltage channel is detected (see Figure 34).
F1 F2
CF
Figure 32. Energy Calculation in Missing Neutral Mode
Important Note for Billing of Active Energy
V
MISSING
2P
NEUTRAL
The ADE7761B provides pulse outputs, CF, F1, and F2, that are
intended to be used for the billing of active energy. Pulses are
generated at these outputs in two different situations.
FILTER AND
THRESHOLD
V2
ADC
V
2N
AGND
Case 1
|V2|
PEAK
> 9% OF FULL SCALE
AND
When the analog input V2P − V2N complies with the conditions
described in Figure 34, the CF, F1, and F2 frequencies are propor-
tional to active power and can be used to bill active energy.
ZERO CROSSING ON V2
V
– V
2N
2P
FS
Case 2
+9% OF FS
–9% OF FS
When the analog input V2P − V2N does not comply with the
conditions described in Figure 34, the ADE7761B does not
measure active energy but a quantity proportional to kAh. This
quantity is used to generate pulses on the same CF, F1, and F2.
This situation is indicated when the FAULT pin is high.
Figure 34. Return to Normal Mode After Missing Neutral Detection
Rev. 0 | Page 19 of 24
ADE7761B
Missing Neutral Gain Calibration
Example
When the ADE7761B is in missing neutral mode, the energy is
billed based on the active current input signal level. The frequency
outputs in this mode can be calibrated with the MISCAL analog
input pin. In this mode, applying a dc voltage of 330 mV on
MISCAL is equivalent to applying, in normal mode, a pure sine
wave on the voltage input with a peak value of 330 mV. The
MISCAL input can vary from 0 V to 660 mV (see the Analog
Inputs section). When set to 0 V, the frequency outputs are
close to zero. When set to 660 mV dc, the frequency outputs are
twice that when MISCAL is at 330 mV dc. In other words,
Equation 7 can be used in missing neutral mode by replacing
V2rms by MISCALrms /√2.
In normal mode, ac voltages of 330 mV peak are applied to
Channel V1 and Channel V2, and then the expected output
frequency on F1 and F2 is calculated as follows:
Gain =1; PGA =0
F1–4 = 1.7 Hz, SCF = S1 = S0 = 0
V1 = rms of 330 mV peak ac = 0.33/√2 V
V2 = rms of 330 mV peak ac = 0.33/√2 V
VREF = 2.5 V (nominal reference value)
6.13× 0.33× 0.33×1.7Hz
F , F2 Frequency =
= 0.0917Hz
1
2 × 2 × 2.52
F , F Frequency =
1
2
CF Frequency = F1, F2 Frequency × 64 = 5.87 Hz
(8)
6.13×Gain×V1rms × MISCALrms / 2 × f1−4
In missing neutral mode, the ac voltage of 330 mV peak is
applied to Channel V1, no signal is connected on Channel V2,
and a 330 mV dc input is applied to MISCAL. With the ADE7761B
in the same configuration as the previous example, the expected
output frequencies on CF, F1, and F2 are
2
VREF
where:
F1, F2 Frequency is the output frequency on F1 and F2 (Hz).
Gain is 1 or 16, depending on the PGA gain selection made
using Logic Input PGA.
6.13× 0.33× 0.33/ 2 ×1.7Hz
F1 , F2 Frequency =
= 0.0917Hz
V1rms is the differential rms voltage signal on Channel V1 (V).
MISCALrms is the differential rms voltage signal on the MISCAL
pin (V).
2 × 2.52
CF Frequency = F1, F2 Frequency × 64 = 5.87 Hz
VREF is the reference voltage (2.5 V 8%) (V).
f1-4 is one of four possible frequencies selected by using Logic
Input S0 and Logic Input S1 (see Table 6).
Rev. 0 | Page 20 of 24
ADE7761B
APPLICATIONS INFORMATION
INTERFACING TO A MICROCONTROLLER FOR
ENERGY MEASUREMENT
SELECTING A FREQUENCY FOR AN ENERGY
METER APPLICATION
The easiest way to interface the ADE7761B to a microcontroller
is to use the CF high frequency output with the output frequency
scaling set to 2048 × F1, F2. This is done by setting SCF = 0
and S0 = S1 = 1 (see Table 8). With full-scale ac signals on the
analog inputs, the output frequency on CF is approximately
5.5 kHz. Figure 35 illustrates one scheme that could be used to
digitize the output frequency and carry out the necessary
averaging mentioned in the Frequency Output CF section.
As shown in Table 6, the user can select one of four frequencies.
This frequency selection determines the maximum frequency
on F1 and F2. These outputs are intended to be used to drive
the energy register (electromechanical or other). Because only
four different output frequencies can be selected, the available
frequency selection was optimized for a meter constant of
100 impulses/kWh with a maximum current of between 10 A
and 120 A. Table 9 shows the output frequency for several
maximum currents (IMAX) with a line voltage of 240 V. In all
cases, the meter constant is 100 impulses/kWh.
CF
FREQUENCY
RIPPLE
Table 9. F1 and F2 Frequency at 100 Impulses/kWh
AVERAGE
FREQUENCY
±10%
IMAX (A)
12.ꢀ
2ꢀ
F1 and F2 (Hz)
0.083
0.166
0.266
0.4
40
TIME
60
MCU
80
0.ꢀ33
0.8
ADE7761B
COUNTER
120
CF
1
The f1–4 frequencies allow complete coverage of this range of
output frequencies on F1 and F2. When designing an energy
meter, the nominal design voltage on Channel V2 (voltage)
should be set to half-scale to allow for calibration of the meter
constant. The current channel should also be no more than half-
scale when the meter sees maximum load, which accommodates
overcurrent signals and signals with high crest factors. Table 10
shows the output frequency on F1 and F2 when both analog
inputs are half-scale. The frequencies listed in Table 10 align
well with those listed in Table 9 for maximum load.
UP/DOWN
REVP
2
FAULT
LOGIC
1
REVP MUST BE USED IF THE METER IS BIDIRECTIONAL OR
DIRECTION OF ENERGY FLOW IS NEEDED.
FAULT MUST BE USED TO RECORD ENERGY IN FAULT CONDITION.
2
Figure 35. Interfacing the ADE7761B to an MCU
As shown in Figure 35, the frequency output CF is connected to
an MCU counter or port that counts the number of pulses in a
given integration time, determined by an MCU internal timer.
The average power, proportional to the average frequency, is
Table 10. F1 and F2 Frequency with Half-Scale AC Inputs
Frequency on F1 and F2, Channel V1 and
S0 S1 f1–4 (Hz) Channel V2, Half-Scale AC Inputs (Hz)
Counter
Average Frequency = Average Active Power =
Timer
The energy consumed during an integration period is
Counter
0
0
1
1
0
1
0
1
1.72
3.44
6.86
13.ꢀ
0.092
0.183
0.337
0.734
Energy = Average Power ×Time =
×Time = Counter
Time
When selecting a suitable f1–4 frequency for a meter design, the
frequency output at IMAX (maximum load) with a meter constant
of 100 impulses/kWh should be compared with Column 4 of
Table 10. The frequency that is closest in Table 10 determines
the best choice of frequency (f1-4). For example, if a meter with
a maximum current of 40 A is being designed, the output
frequency on F1 and F2 with a meter constant of 100 impulses
per kWh is 0.266 Hz at 40 A and 240 V (see Table 9).
For the purpose of calibration, this integration time could be
10 sec to 20 sec to accumulate enough pulses to ensure correct
averaging of the frequency. In normal operation, the integration
time could be reduced to 1 sec or 2 sec, depending on, for
example, the required update rate of a display. With shorter
integration times on the MCU, the amount of energy in each
update may still have a small amount of ripple, even under
steady load conditions. However, over a minute or more, the
measured energy has no ripple.
Looking at Table 10, the closest frequency to 0.266 Hz
in Column 4 is 0.183 Hz. Therefore, F2 (3.4 Hz; see Table 6)
is selected for this design.
Rev. 0 | Page 21 of 24
ADE7761B
Frequency Outputs
For example, with an energy meter with a meter constant of
100 impulses per kWh on F1, F2 using SCF = 1, S1 = 0, and
S0 = 1, the maximum output frequency at F1 or F2 is 0.68 Hz
and 43.52 Hz on CF. The minimum output frequency at F1
or F2 is 0.0045% of 0.68 Hz or 3.06 × 10–5 Hz. This is 1.96 ×
10–3 Hz at CF (64 × F1 Hz).
Figure 2 is a timing diagram for the various frequency outputs.
The high frequency CF output is intended for communication
and calibration purposes. CF produces a 90 ms wide, active high
pulse (t4) at a frequency that is proportional to active power. The
CF output frequencies are given in Table 8. As with F1 and F2,
if the period of CF (t5) falls below 180 ms, the CF pulse width is set
to half the period. For example, if the CF frequency is 20 Hz,
the CF pulse width is 25 ms.
In this example, the no-load threshold is equivalent to 1.1 W of
load or a startup current of 4.6 mA at 240 V. Compare this value
to the IEC 62053-21 specification, which states that the meter must
start up with a load equal to or less than 0.4% of IB. For a 5 A (IB)
meter, 0.4% of IB is equivalent to 20 mA.
No-Load Threshold
The ADE7761B includes a no-load threshold and start-up current
feature that eliminate creep effects in the meter. The ADE7761B
is designed to issue a minimum output frequency. Any load
generating a frequency lower than this minimum frequency
does not cause a pulse to be issued on F1, F2, or CF. The minimum
output frequency is given as 0.0045% of the full-scale output
frequency (see Table 8 for maximum output frequencies for
ac signals).
Note that the no-load threshold is not enabled when using the
high CF frequency mode: SCF = 0, S1 = S0 = 1.
NEGATIVE POWER INFORMATION
The ADE7761B detects when the current and voltage channels
have a phase shift greater than 90°. This mechanism can detect
a wrong connection of the meter or the generation of negative
power. The REVP pin output goes active high when negative
power is detected and active low when positive power is detected.
The REVP pin output changes state as a pulse is issued on CF.
Rev. 0 | Page 22 of 24
ADE7761B
OUTLINE DIMENSIONS
7.50
7.20
6.90
11
20
5.60
5.30
5.00
8.20
7.80
7.40
1
10
0.25
0.09
1.85
1.75
1.65
2.00 MAX
8°
4°
0°
0.95
0.75
0.55
0.38
0.22
0.05 MIN
SEATING
PLANE
COPLANARITY
0.10
0.65 BSC
COMPLIANT TO JEDEC STANDARDS MO-150-AE
Figure 36. 20-Lead Shrink Small Outline Package [SSOP]
(RS-20)
Dimensions shown in millimeters
ORDERING GUIDE
Model
ADE7761BARS
ADE7761BARS-RL
ADE7761BARSZ1
ADE7761BARSZ-RL1
ADE7761BARS-REF
Temperature Range
–40°C to +8ꢀ°C
–40°C to +8ꢀ°C
–40°C to +8ꢀ°C
–40°C to +8ꢀ°C
Package Description
Package Option
20-Lead Shrink Small Outline Package (SSOP)
20-Lead Shrink Small Outline Package (SSOP)
20-Lead Shrink Small Outline Package (SSOP)
20-Lead Shrink Small Outline Package (SSOP)
Reference Board
RS-20
RS-20
RS-20
RS-20
1 Z = RoHS Compliant Part.
Rev. 0 | Page 23 of 24
ADE7761B
NOTES
©2007 Analog Devices, Inc. All rights reserved. Trademarks and
registered trademarks are the property of their respective owners.
D06797-0-8/07(0)
Rev. 0 | Page 24 of 24
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明