LPS102-M [ARTESYN]
EN61000-3-2 compliant;型号: | LPS102-M |
厂家: | ARTESYN TECHNOLOGIES |
描述: | EN61000-3-2 compliant 输入元件 |
文件: | 总3页 (文件大小:678K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
POWER
LPS100-M Series
Data Sheet
150 Watts
Total Power: 80 - 150 Watts
Input Voltage: 90 - 264 Vac
120 - 300 Vdc
# of Outputs: Single
SPECIAL FEATURES
Medical and ITE safety approvals,
2X MOPP
Active power factor correction
2” x 4” footprint
Less than 1U high
EN61000-3-2 compliant
Remote sense
Power fail
Electrical Specifications
Input
Adjustable main output
Built-in Class B EMI filter
Overvoltage protection
Overload protection
Input range
Frequency
Inrush current
Efficiency
EMI/RFI
90 - 264 Vac; 120 - 300 Vdc
47 - 63 Hz
Thermal overload protection
Isolated 12 V fan output
LPX100 Enclosure kit available
50 A max., cold start @ 25 °C
88% typical at full load
FCC Class B conducted; CISPR22 Class B conducted;
POE isolation on main output of
LPS109-M
EN55022 Class B conducted; VDE0878PT3 Class B conducted
Safety ground leakage
current
275 μA @ 50/60 Hz, 264 Vac input
SAFETY
Output
TUV
UL
60950, 60601-1
60950, 60601-1
60950, 60601-1
Certificate & report
Mark (LVD)
Maximum power
100 W for convection (80 W for LPS102-M);
150 W with 30 CFM forced air (120 W for LPS102-M)
cULus
CB
Adjustment range
Fan output
10% minimum on the main outputs
12 V @ 1 A isolated, 10%
CE
Hold-up time
10 ms @ 150 W load, 120 Vac input
CQC
Mark
Overload protection
Short circuit protection on all outputs. Case overload
protected @ 110-160% above rating
Overvoltage protection
Logical Control
Power failure
15-35% above nominal output
Open collector logic signal goes high 100-500 msec after main output;
it goes low at least 6 msec before loss of regulation
Remote sense
Compensates for 0.5 V lead drop min. Will operate without remote
sense connected. Reverse connection protected.
LPS100-M Series Data Sheet
Environmental Specifications
Operating temperature
0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C start up
Storage temperature
-40 °C to +85 °C
Electromagnetic susceptibility Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3
Humidity
Operating; non-condensing 10% to 95% RH
Vibration
IEC 60068-2-6 to the levels of IEC721-3-2
MTBF calculated
534,000 hours at full load and 25 °C ambient conditions, 230 V input, Bellcore
Ordering Information
Ripple
P/P (PARD)3
Minimum Maximum Load with
Maximum Load with
30CFM Forced Air
Model Number Output Voltage
Peak Load Regulation2
Load
Convection Cooling
LPS102-M
LPS103-M
LPS104-M
LPS105-M
LPS108-M
LPS109-M
5 V
0 A
0 A
0 A
0 A
0 A
0 A
16 A
8.3 A
6.7 A
4.2A
24 A
12.5 A
10 A
30 A
14 A
11 A
7A
2%
2%
2%
2%
2%
2%
50 mV
120 mV
150 mV
240 mV
480 mV
540 mV
12 V
15 V
24 V
48 V
54 V
6.3 A
3.1 A
2.8 A
2.1A
3.5 A
3.1 A
1.85 A
1. Peak current lasting < 30 seconds with a maximum 10% duty cycle.
2. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3. Peak-to-peak with 20 MHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and load ranges.
4. This product is a Component Power Supply and is only for inclusion by professional installers within other equipment and must not be
operated as a standalone product. EMC compliance to appropriate standards must be verified at the system level. This product is for sale to
OEMs and System Integrators, including through Distribution Channels. It is not intended for sale to End Users.
Pin Assignments
Mating Connectors
Connector
LPS100-M
Molex P/N: 09-50-3031, Pins: 08-52-0072 or
Landwin P/N: 3060S0302, Pins: 3360T011P
AC Input (SK1)
SK1
Pin 1
Pin 3
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Pin 1
Pin 2
Pin 3
Pin 4
Pin 1
Pin 2
Pin 3
Pin 4
Neutral
AC Ground
Molex: 01-90020001
Line
Molex P/N: 09-50-3081, Pins: 08-52-0072or
Landwin P/N: 3060S0802, Pins: 3360T011P
DC Output
(SK2)
SK2
Common
Common
Molex P/N: 35155-0400, Pins: 08-70-0056 or
Landwin P/N: 2640S04A0, Pins: 2543T011P
Remote Sense
(SK203)
Common
Common
Molex P/N: 22-01-1042, Pins: 08-70-0049 or
Landwin: P/N: 2510S04A0, Pins: 2543T011P
Fan: (SK5)
+Vout
+Vout
Artesyn Embedded Technologies Connector Kit #70-841-025,
includes all of the above
+Vout
+Vout
Notes:
1. Specifications subject to change without notice.
2. All dimensions in inches (mm), tolerance is .02ꢀ.
3. Mounting holes M1, M2 should be grounded for EMI purpose
4. Mounting M1 is safety ground connection
5. Specifications are for convection rating at factory settings at 115
Vac input 25 °C unless otherwise stated.
6. This power supply requires mounting on metal standoffs 0.20ꢀ
(5 m) in height.
7. For DC input an external DC safety rated fuse must be used.
8. Warranty: 2 years
SK203
SK5
Common
Power Fail
- Remote Sense
+ Remote Sense
+12 V Fan
+12 V Fan
Fan Return (Isolated)
Fan Return (Isolated)
9. Weight: 0.44 lb. / 0.20 kg
LPS100-M Series Data Sheet
Mechanical Drawing
VR1
Output Voltage
Adjust Pot
SK20 3
SK2
M2
M1
1
4
8
GND
1
4
SK5
1
3
SK1
1
3.72"
(94.6)
Mounting Hole
Ø0.16"[4.0] 4 Places
Max. Screw Head
Diameter .22” (5.6)
4.00"
(101.6)
0.197” (5.0) Minimum
Standoff height
WORLDWIDE OFFICES
Asia (HK)
Americas
Europe (UK)
14/F, Lu Plaza
2900 S.Diablo Way
Tempe, AZ 85282
USA
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
+1 888 412 7832
www.artesyn.com
+852 2176 3333
+44 (0) 1384 842 211
Artesyn Embedded Technologies, Artesyn and the Artesyn Embedded Technologies logo are trademarks and
service marks of Artesyn Embedded Technologies, Inc. All other names and logos referred to are trade names,
trademarks, or registered trademarks of their respective owners. © 2016 Artesyn Embedded Technologies, Inc.
All rights reserved. For full legal terms and conditions, please visit www.artesyn.com/legal.
For more information: www.artesyn.com/power
For support: productsupport.ep@artesyn.com
LPS100-M DS 28Sep2016
相关型号: