Technical data sheet
22ADP-55Q..
Differential Pressure Sensor Air
Differential pressure transmitter with 8
selectable ranges and Modbus funtionality.
NEMA 4X / IP65 rated enclosure. For
monitoring over-, under or the differential
pressure of air and other non-flammable
and non-aggressive gases. Typical
application in HVAC systems for monitoring
air filters, fans V-belts or fire and smoke
control dampers. Options available with
LCD display and Auto-Zero function.
Type Overview
Measuring range
Output signal
Output signal
Additional
Type
Output signal
active volumetric Burst pressure
flow
Display type
pressure
active pressure
features
22ADP-55Q
22ADP-55QA
22ADP-55QB
22ADP-55QL
0...250 Pa / 1
inch WC
Modbus
Modbus
Modbus
Modbus
DC 0...5 V,
DC 0...10 V
DC 0...5 V,
DC 0...10 V
40 kPa /
-
-
160 inch WC
0...250 Pa / 1
inch WC
DC 0...5 V,
DC 0...10 V
DC 0...5 V,
DC 0...10 V
40 kPa /
-
Auto-Zero
Auto-Zero
-
160 inch WC
0...250 Pa / 1
inch WC
DC 0...5 V,
DC 0...10 V
DC 0...5 V,
DC 0...10 V
40 kPa /
LCD
LCD
160 inch WC
0...250 Pa / 1
inch WC
DC 0...5 V,
DC 0...10 V
DC 0...5 V,
DC 0...10 V
40 kPa /
160 inch WC
Technical Data
Electrical Data Power supply DC
Power supply AC
15...24 V, ±10%, 1.4 W
24 V, , ±10%, 2 VA
Electrical connection
Removable spring loaded terminal block max.
2.5 mm²
Cable entry
Cable gland with strain relief 2 x Ø6 mm (1/2"
NPT conduit adapter included)
Functional Data
Sensor Technology
Communicative control
Multirange
piezo measuring element
Modbus RTU
8 measuring ranges selectable
Output signal active note
Output DC 0...5/10 V selectable with switch
voltage output: min. 10 kΩ load
current output: max. 500 Ω load
Display
LCD, 1.14x1.38" [29x35 mm]
with backlight
measured values: Pa, inchWC (configurable)
measured values volumetric flow: m³/h, cfm
(configurable)
Application
air
Response time
adjustable 0.8s or 4.0s
www.belimo.com
22ADP-55Q.. • en-us • 2019-08-20 • Subject to change
1 / 5
Technical data sheet
22ADP-55Q..
Measuring Data Measuring values
differential pressure
Measuring fluid
air and non-aggressive gases
Measuring range settings pressure
Setting range [Pa] range [inch WC] Factory
setting
S0
S1
S2
S3
S4
S5
S6
S7
0...250
0...100
0...1
0...0.4
0...50
0...0.2
0...25
0...0.1
-25...25
-50...50
-100...100
-150...150
-0.1...0.1
-0.2...0.2
-0.4...0.4
-0.6...0.6
Accuracy pressure
±0.004 inch WC (±1 Pa) @ range <1 inch WC
(250 Pa)
Materials
Cable gland
Housing
PA6, black
cover: lexan, orange
base: lexan, orange
seal: 0467 NBR70, black
UV resistant
Safety Data
Ambient humidity
Ambient temperature
Fluid temperature
Protection class IEC/EN
Protection class UL
EU Conformity
max. 95% r.H., non-condensing
15...120°F [-10...50°C]
15...120°F [-10...50°C]
III safety extra-low voltage (selv)
UL Class 2 Supply
CE Marking
Certification IEC/EN
Certification UL
IEC/EN 60730-1 and IEC/EN 60730-2-6
cULus acc. to UL60730-1A/-2-6, CAN/CSA
E60730-1:02
Degree of protection IEC/EN
Degree of protection NEMA/UL
Quality Standard
IP65
NEMA 4X
ISO 9001
Safety Notes
This device has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application. Unauthorised
modifications are prohibited. The product must not be used in relation with any equipment
that in case of a failure may threaten humans, animals or assets.
Ensure all power is disconnected before installing. Do not connect to live/operating
equipment.
Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied during installation.
The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.
www.belimo.com
22ADP-55Q.. • en-us • 2019-08-20 • Subject to change
2 / 5
Technical data sheet
22ADP-55Q..
Remarks
Automated Zero-Point calibration (Auto- Transmitters equipped with the auto-zero calibration are maintenance-free.
Zero)
The auto-zero calibration electronically adjusts the transmitter zero every 10 minutes.The
function eliminates all output signal drift due to thermal, electronic or mechanical effects.
The auto-zero adjustment takes approx. 4 seconds after which the device returns to its
normal measuring mode. During the 4 second adjustment period, the output and display
values will freeze to the latest measured value.
Manual Zero-Point Calibration In normal operation zero-point calibration should be executed every 12 months.
Attention! For executing zero-point calibration the power supply must be connected one
hour before.
• Release both connection tubes from the pressure terminals + and -
• Press the button until the LED lights permanently
• Wait until the LED flashes again and reinstall the connection tubes to the pressure ports
(note + and -)
Scope of delivery
Scope of delivery Description
Mounting plate L housing
Type
A-22D-A10
Duct connector kit, PVC tube 2 m, 2 connection elements (Plastic) for A-22AP-A08
22ADP-..
Cable Gland with strain relief Ø6...8 mm
Dowel
Screws
1/2" NPT conduit adapter, 2 x Ø6 mm
Accessories
Optional accessories Description
Type
Duct connector, Metal, L 1.5", Tube connection 0.2"
Duct connector, Metal, L 4", Tube connection 0.2"
A-22AP-A01
A-22AP-A03
www.belimo.com
22ADP-55Q.. • en-us • 2019-08-20 • Subject to change
3 / 5
Technical data sheet
22ADP-55Q..
Wiring Diagram
① Button
② red: Error
③ yellow: Tx
④ yellow: Rx
⑤ and ⑥ Status LED
*
Factory setting
Pressure unit
Response time
Output signal
P
T
U
Setting
range [Pa]
range [inch WC]
Factory
setting
S0
S1
S2
S3
S4
S5
S6
S7
0...250
0...100
0...1
0...0.4
0...50
0...0.2
0...25
0...0.1
-25...25
-50...50
-100...100
-150...150
-0.1...0.1
-0.2...0.2
-0.4...0.4
-0.6...0.6
Detailed documentation The separate document Sensor Modbus-Register informs about Modbus register,
addressing, parity and bus termination (DIP1: address, DIP2: baud rate, parity, bus
termination)
In addition to the information on the bus, the following analog outputs are available:
AOU1: differential pressure
AOU2: volumetric flow
The volumetric flow is calculated from the differential pressure, the k-factor and the height.
Factory setting for the k-factor is 1.00 and for the height 330 metres above sea level.
The values of the k-factor and the height can be changed via Modbus or BACnet.
Notes Wiring RS485 Connection via safety isolating transformer.
Parallel connection of other devices possible. Observe the performance data.
The wiring of the line for BACnet MS/TP / Modbus RTU is to be carried out in accordance
with applicable RS485 regulations.
Modbus / BACnet: Supply and communication are not galvanically isolated. Connect earth
signal of the devices with one another.
Wiring RS485 (Modbus RTU & BACnet MS/
TP)
www.belimo.com
22ADP-55Q.. • en-us • 2019-08-20 • Subject to change
4 / 5
Technical data sheet
22ADP-55Q..
Dimensions
Dimensions
.
Type
Weight
22ADP-55Q
22ADP-55QA
22ADP-55QB
22ADP-55QL
0.64 lb [0.29 kg]
0.66 lb [0.30 kg]
0.73 lb [0.33 kg]
0.68 lb [0.31 kg]
www.belimo.com
22ADP-55Q.. • en-us • 2019-08-20 • Subject to change
5 / 5