Technical data sheet  
22DT-54..  
Duct / Immersion Temperature Sensor  
Active sensor (4...20 mA) for measuring  
temperature in duct applications. In  
combination with a stainless steel or brass  
thermowell can also be used for pipe  
applications. IP65 / NEMA 4X rated  
enclosure.  
Type Overview  
Output signal  
Type  
Probe length  
Probe diameter  
active temperature  
22DT-54H  
22DT-54L  
22DT-54N  
22DT-54P  
22DT-54R  
22DT-54T  
4...20 mA  
4...20 mA  
4...20 mA  
4...20 mA  
4...20 mA  
4...20 mA  
2" [50 mm]  
4" [100 mm]  
6" [150 mm]  
8" [200 mm]  
12" [300 mm]  
18" [450 mm]  
0.24" [6 mm]  
0.24" [6 mm]  
0.24" [6 mm]  
0.24" [6 mm]  
0.24" [6 mm]  
0.24" [6 mm]  
Technical Data  
Electrical Data Power supply DC  
15...24 V, ±10%, 0.5 W  
Electrical connection  
Removable spring loaded terminal block max.  
2.5 mm²  
Cable entry  
Cable gland with strain relief Ø6...8 mm (1/2"  
NPT conduit adapter included)  
Functional Data  
Measuring Data  
Multirange  
8 measuring ranges selectable  
Output signal active note  
Application  
current output: max. 500 Ω load  
air  
water  
Measuring values  
temperature  
Measuring range temperature  
Active sensor: range selectable  
Attention: max. measuring temperature is  
restricted by max. fluid temperature (see  
Safety data)  
Setting  
range [°C]  
range [°F] Factory  
setting  
S0  
S1  
S2  
S3  
S4  
S5  
S6  
S7  
-50...50°C  
-10...120°C  
0...50°C  
-30...130°F  
0...250°F  
40...140°F  
30...480°F  
0...100°F  
0...250°C  
-15...35°C  
0...100°C  
-20...80°C  
0...160°C  
40...240°F  
40...90°F  
0...150°F  
Accuracy temperature active  
±0.9°F @ 70°F [±0.5°C @ 21°C]  
Time constant t (63%) in the air duct  
typical 46 s @ 3 m/s  
typical 210 s @ 0 m/s  
Time constant t (63%) in water pipe  
typical 7 s with thermowell brass  
typical 9 s with thermowell stainless steel  
www.belimo.com  
22DT-54.. • en-us • 2019-08-20 • Subject to change  
1 / 5  
Technical data sheet  
22DT-54..  
Materials Cable gland  
PA6, black  
Housing  
cover: lexan, orange  
base: lexan, orange  
seal: 0467 NBR70, black  
UV resistant  
Safety Data  
Ambient humidity  
max. 95% r.H., non-condensing  
-30...120°F [-35...50°C]  
-60...320°F [-50...160°C]  
max. 160°F [70°C]  
Ambient temperature  
Fluid temperature  
Housing surface temperature  
Protection class IEC/EN  
Protection class UL  
EU Conformity  
III protective extra-low voltage (pelv)  
UL Class 2 Supply  
CE Marking  
Certification IEC/EN  
Certification UL  
IEC/EN 60730-1  
cULus acc. to UL60730-1A/-2-9, CAN/CSA  
E60730-1:02/-2-9  
Degree of protection IEC/EN  
Quality Standard  
IP65  
ISO 9001  
Safety Notes  
This device has been designed for use in stationary heating, ventilation and air-conditioning  
systems and must not be used outside the specified field of application. Unauthorised  
modifications are prohibited. The product must not be used in relation with any equipment  
that in case of a failure may threaten humans, animals or assets.  
Ensure all power is disconnected before installing. Do not connect to live/operating  
equipment.  
Only authorised specialists may carry out installation. All applicable legal or institutional  
installation regulations must be complied during installation.  
The device contains electrical and electronic components and must not be disposed of as  
household refuse. All locally valid regulations and requirements must be observed.  
Remarks  
General Remarks Concerning Sensors When using lengthy connection wires (depending on the cross section used) the measuring  
result might be falsified due to a voltage drop at the common GND-wire (caused by the  
voltage current and the line resistance). In this case, 2 GND-wires must be wired to the  
sensor - one for supply voltage and one for the measuring current.  
Sensing devices with a transducer should always be operated in the middle of the  
measuring range to avoid deviations at the measuring end points. The ambient temperature  
of the transducer electronics should be kept constant. The transducers must be operated at  
a constant supply voltage (±0.2 V). When switching the supply voltage on/off, onsite power  
surges must be avoided.  
Build-up of Self-Heating by Electrical Temperature sensors with electronic components always have a dissipative power which  
Dissipative Power affects the temperature measurement of the ambient air. The dissipation in active  
temperature sensors shows a linear increase with rising operating voltage. This dissipative  
power should be taken into account when measuring temperature. As Belimo transducers  
work with a variable operating voltage, only one operating voltage can be taken into  
consideration, for reasons of production engineering. Transducers 0...10 V / 4...20 mA have  
a standard setting at an operating voltage of DC 24 V. That means, that at this voltage, the  
expected measuring error of the output signal will be the least. For other operating voltages,  
the offset error will be increased by a changing power loss of the sensor electronics. If a re-  
calibration should become necessary later directly on the sensor, this can be done by  
means of a trimming potentiometer on the sensor board.  
www.belimo.com  
22DT-54.. • en-us • 2019-08-20 • Subject to change  
2 / 5  
Technical data sheet  
22DT-54..  
Scope of delivery  
Accessories  
Scope of delivery Description  
Type  
A-22D-A11  
Mounting clip, with screws and adhesive foil  
1/2" NPT conduit adapter  
Optional accessories Description  
Type  
Mounting plate S housing  
A-22D-A09  
A-22P-A51  
A-22G-A01.1  
Cold barrier, Plastic, L 50 mm, for thermowell pocket A-22P-A..  
Connection adapter, M20, for cable 1 x 6 mm, Multipack 10 pcs.  
Optional accessories air Description  
Type  
Mounting flange for sensor probe 6 mm, up to max. 80°C, Plastic  
Mounting flange for sensor probe 6 mm, up to max. 260°C, Brass  
A-22D-A03  
A-22D-A05  
Recommended accessories water Description  
Type  
Thermowell pocket (fabricated) Stainless steel, 2" [50 mm], 1/2" NPT, A-22P-A05  
wrench size 3/4"  
Thermowell pocket (fabricated) Brass, 2" [50 mm], 1/2" NPT, wrench  
size 3/4"  
A-22P-A17  
Thermowell pocket (machined) Stainless steel, 2" [50 mm], 1/2" NPT, A-22P-A36  
wrench size 3/4"  
Thermowell pocket (fabricated) Stainless steel, 4" [100 mm], 1/2" NPT, A-22P-A07  
wrench size 3/4"  
Thermowell pocket (fabricated) Brass, 4" [100 mm], 1/2" NPT, wrench A-22P-A19  
size 3/4"  
Thermowell pocket (machined) Stainless steel, 4" [100 mm], 1/2" NPT, A-22P-A37  
wrench size 3/4"  
Thermowell pocket (fabricated) Stainless steel, 6" [150 mm], 1/2" NPT, A-22P-A09  
wrench size 3/4"  
Thermowell pocket (fabricated) Brass, 6" [150 mm], 1/2" NPT, wrench A-22P-A21  
size 3/4"  
Thermowell pocket (machined) Stainless steel, 6" [150 mm], 1/2" NPT, A-22P-A38  
wrench size 3/4"  
Thermowell pocket (fabricated) Stainless steel, 8" [200 mm], 1/2" NPT, A-22P-A11  
wrench size 3/4"  
Thermowell pocket (fabricated) Brass, 8" [200 mm], 1/2" NPT, wrench A-22P-A23  
size 3/4"  
Thermowell pocket (machined) Stainless steel, 8" [200 mm], 1/2" NPT, A-22P-A39  
wrench size 3/4"  
Thermowell pocket (fabricated) Stainless steel, 12" [300 mm], 1/2" NPT, A-22P-A13  
wrench size 3/4"  
Thermowell pocket (fabricated) Brass, 12" [300 mm], 1/2" NPT, wrench A-22P-A25  
size 3/4"  
Thermowell pocket (fabricated) Stainless steel, 18" [450 mm], 1/2" NPT, A-22P-A15  
wrench size 3/4"  
Thermowell pocket (fabricated) Brass, 18" [450 mm], 1/2" NPT, wrench A-22P-A27  
size 3/4"  
Syringe with thermal paste  
A-22P-A44  
www.belimo.com  
22DT-54.. • en-us • 2019-08-20 • Subject to change  
3 / 5  
Technical data sheet  
22DT-54..  
Wiring Diagram  
The adjustment of the measuring ranges is made by changing the bonding jumpers.  
The output value in the new measuring range is available after 2 seconds.  
Setting  
range [°C]  
range [°F]  
Factory  
setting  
S0  
S1  
S2  
S3  
S4  
S5  
S6  
S7  
-50...50°C  
-10...120°C  
0...50°C  
-30...130°F  
0...250°F  
40...140°F  
30...480°F  
0...100°F  
40...240°F  
40...90°F  
0...150°F  
0...250°C  
-15...35°C  
0...100°C  
-20...80°C  
0...160°C  
www.belimo.com  
22DT-54.. • en-us • 2019-08-20 • Subject to change  
4 / 5  
Technical data sheet  
22DT-54..  
Dimensions  
Dimensions  
L = Probe length  
.
Type  
Probe length  
2" [50 mm]  
Weight  
22DT-54H  
22DT-54L  
22DT-54N  
22DT-54P  
22DT-54R  
22DT-54T  
0.26 lb [0.12 kg]  
0.29 lb [0.13 kg]  
0.29 lb [0.13 kg]  
0.31 lb [0.14 kg]  
4" [100 mm]  
6" [150 mm]  
8" [200 mm]  
12" [300 mm] 0.33 lb [0.15 kg]  
18" [450 mm] 0.35 lb [0.16 kg]  
www.belimo.com  
22DT-54.. • en-us • 2019-08-20 • Subject to change  
5 / 5  

相关型号:

22DT-54P

Duct / Immersion Temperature Sensor
BELIMO

22DT-54R

Duct / Immersion Temperature Sensor
BELIMO

22DT-54T

Duct / Immersion Temperature Sensor
BELIMO

22E05-230

Analog IC
ETC

22E05D

Analog IC
ETC

22E05D230

Analog IC
ETC

22E10A

Analog IC
ETC

22E10A230

Analog IC
ETC

22E15-230

Analog IC
ETC

22E30-230

Analog IC
ETC

22E50-230

Analog IC
ETC

22EXSO-D

DIREKTANLASSER KUNSTSTOFF 0.55KW
ETC