ABC601-1T24-S [BEL]
Universal input voltage range (85 â 305 VAC);型号: | ABC601-1T24-S |
厂家: | BEL FUSE INC. |
描述: | Universal input voltage range (85 â 305 VAC) |
文件: | 总11页 (文件大小:1057K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
The ABC601Series of industrial and medical AC-DCpower supplies
provides up to 600 W of regulated output power through wide input
voltage range 85 – 305 VAC in single outputs of 24, 28, 36 or 48
VDC.
The ABC601 Series comes in two packages, U-frame chassis or
enclosed with a front mounted fan, offering 12 and 5 VSB standby
outputs and a full set of protection features.
The ABC601 Series features a built-in I-share circuit for parallel
operationbetween power units to enhance total power. An optional
OR-ing external circuit can be provided for N+1 redundant
operation.
The ABC601 Series complies with the latest international safety
standards for IT and medical equipment and displays the CE-Mark
for the European Low Voltage Directive (LVD).
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Universal input voltage range (85 – 305 VAC)
Input surge current limiting
800 W peak power (up to 10 s)
High efficiency up to 94%
24, 28, 36 and 48 VDC standard output voltages
Low stand-by consumption (<0.35 W)
Active PFC, EN 61000-3-2 compliant (Class C, >25% load)
Low earth / touch leakage current
Fan speed control circuit
Over temperature, OV, OC and SC protections.
Stand by +5 V, 1.5 A and auxiliary / fan 12 VDC, 1 A outputs
Built-in current share signal for parallel operation
Remote On / Off signal
Power good and remote sense signals
Medical safety approval to IEC 60601-1, 2x MoPP protection grade
BF appliances compatible
•
•
•
•
IEC 60601-1-2 4th edition EMC compliant
IEC 62368-1 standards for Audio Video & IT equipment
LED lighting approval to UL 8750
RoHS 3 compliant (Directive EU 2015/863)
•
•
•
•
•
•
Video Wall Display and SSL Lighting
Industrial Process Control and Automation
Telecommunications
Laboratory / Analysis Equipment
Test and Measurement Equipment
Medical Applications
2
ABC601 Series
INPUTVOLTAGE NOM. OUTPUT MAX. OUTPUT MAX. OUTPUT
MODELNUMBER PACKAGE & COOLING
RANGE
[VAC]
VOLTAGE
[VDC]
POWER
[W]
CURRENT
[A]
DIMENSIONS
Enclosed
Front Mounted Fan
U-Chassis
Convection / Forced Air
Enclosed
Front Mounted Fan
U-Chassis
Convection / Forced Air
Enclosed
Front Mounted Fan
U-Chassis
Convection / Forced Air
Enclosed
107.0 x 206.0 x 41.0 mm
4.21 x 8.11 x 1.6 in
107.0 x 178.5 x 41.0 mm
4.21 x 7.03 x 1.61 in
107.0 x 206.0 x 41.0 mm
4.21 x 8.11 x 1.6 in
107.0 x 178.5 x 41.0 mm
4.21 x 7.03 x 1.61 in
107.0 x 206.0 x 41.0 mm
4.21 x 8.11 x 1.6 in
107.0 x 178.5 x 41.0 mm
4.21 x 7.03 x 1.61 in
107.0 x 206.0 x 41.0 mm
4.21 x 8.11 x 1.6 in
ABC601-1T24-S
ABC601-1T24
ABC601-1T28-S
ABC601-1T28
ABC601-1T36-S
ABC601-1T36
ABC601-1T48-S
ABC601-1T48
85 - 305
85 - 305
85 - 305
85 - 305
85 - 305
85 - 305
85 - 305
85 - 305
24
24
28
28
36
36
48
48
600
600
600
600
600
600
600
600
25
25
21.4
21.4
16.7
16.7
12.5
12.5
Front Mounted Fan
U-Chassis
Convection / Forced Air
107.0 x 178.5 x 41.0 mm
4.21 x 7.03 x 1.61 in
PARAMETER
DESCRIPTION / CONDITION
MIN
85
NOM
100-277
-
MAX
305
300
440
UNIT
VRMS
VDC
AC Input Voltage
DC Input Voltage
Input Frequency
PS starts and operates at 85 VAC at all load conditions
170
47
440 Hz with reduced PFC and output power rating.
Consult factory for details.
50/60
Hz
RMS at 180 VAC, maximum load, 50 / 60 Hz
RMS at 85 VAC, maximum load, 50 / 60 Hz
4.0
8.5
20
Input Current
-
-
A
115 VAC
230 VAC
-
-
-
-
Inrush Current
Fusing
Cold start, 25 °C ambient, full load
A
A
30
High breaking, 10 A, 250 V on each AC lines.
-
-
10
20% rated load
50% rated load
100% rated load
89
93
92
-
-
-
-
-
-
At 115 VAC
Efficiency
%
W
20% rated load
50% rated load
100% rated load
90
94
94
-
-
-
-
-
-
-
-
-
-
-
-
At 230 / 277 VAC
Power on, 115 VAC, no load
5
4
0.35
Input Power Consumption Power on, 230 VAC, no load
Stand by, 115, 230 VAC, no load
Power Factor
THDi
From 50 to 100% of rated load, 230, 115 VAC, 50 / 60 Hz input voltages.
From 50 to 100% rated load, 115, 230, 277 VAC 50 / 60 Hz.
0.90
-
-
-
-
-
20
%
Complies with EN 61000-3-2 at 230 VAC, 50/60 Hz, Class A, D.
Complies with EN 61000-3-2 Class C at 230 VAC, 50/60 Hz, >150 W load.
Complies with EN 61000-3-3 at nominal voltages and full load.
Normal conditions
115 VRMS, 60 Hz
230 VRMS, 50 Hz
Harmonic Current
Fluctuations and Flicker
-
-
-
-
130
240
-
-
-
Earth Leakage Current
µA
264 VRMS, 60 Hz (worst case)
277 VRMS, 60 Hz
400
-
-
264 VRMS, 60 Hz
Touch Leakage Current
Patient Leakage Current
Normal Condition (NC)
-
-
-
-
100
500
µA
µA
Single Fault Condition (SFC)
264 VRMS, 60 Hz
Normal Condition (NC)
-
-
-
-
100
500
Single Fault Condition (SFC)
tech.support@psbel.com
3
ABC601 Series
PARAMETER
DESCRIPTION / CONDITION
MIN
NOM
MAX
UNIT
24
28
36
48
±0.5% set pointaccuracy
V1 Output Voltages
-
-
V
RS+ closed on +V1, RS- closed on V1 RTN, at 20% load.
Convection cooling (Refer to the de-rating curves below)
Forced air cooling Refer to the de-rating curves below)
Peak (less than 10 s, after P_OK high)
400
600
800
25.0
21.4
16.7
12.5
V1 Output Power Rating
V1 Output Current
W
A
V1: 24 VDC
V1: 28 VDC
V1: 36 VDC
V1: 48 VDC
V1 Voltage Adjustment Range
V1 Line Regulation
Manually by potentiometer
-
-
-
-
-
-
±5
±0.1
±2
%V1
%V1
%V1
VAC
VAC
:
:
85 – 305 VRMS
V1 Load-Line-Cross Regulation
85 – 305 VRMS; I1: 0 – 100%
Rated load, Peak-to-peak, 20 MHz BW.
(100 nF ceramic, 10 µF tantalum at load) *
25% load changes at 1 A/µs
24 V at 1000 µF load / IOUT> 2.5 A
28 V at 1000 µF load / IOUT> 2.5 A
36 V at 680 µF load / IOUT> 1.9 A
48 V at 560 µF load / IOUT> 1.25 A
5 VSB at 560 µF load / IOUT> 0.1 A
V1 Ripple and Noise
-
-
1
%V1
Transient Response:
V1, 5VSB
Voltage Deviation
%V1
-
-
±5
%VSB
V1 Start-up Rise Time
V1 Hold-up Time
85<VIN<305, any load conditions.
10
16
-
-
100
-
ms
ms
At nominal VIN, full load **
Two units in parallel at I1 rated load.
V1 Current Sharing Accuracy
Start-up Delay
VS-Logic and I-Share signals connected together.
RS+, RS- signals connected together and to the load
V1 in regulation after de-asserting PS_Inhibit
V1 in regulation after AC is applied (worst case: 85 VAC
45.5
-
54.5
%I1
ms
-
-
-
-
-
-
-
-
-
-
450
2050
1500
10
)
5 VSB in regulation after AC is applied (worst case: 85 VAC
)
%V1
%VSB
Turn-on Overshoot
Minimum Load
10
V1, V2, 5VSB
0
-
-
A
V1: 24 VDC
V1: 28 VDC
V1: 36 VDC
V1: 48 VDC
-
-
-
-
-
-
-
-
16000
15000
12000
8000
Maximum Load Capacitance
µF
V2 Output Voltage
V2 Output Current
5 VSB Output Voltage
V1 at nominal voltage
10.5
12.25
14.00
V
A
V
Convection / forced air cooling
±3% set point accuracy, 20% load.
-
-
-
1
-
5
Front Mounted Fan models (-S)
U-Chassis models
-
-
-
-
1.5
1.2
5 VSB Output Current
A
5 VSB Load, line cross Regulation VAC: 85 – 305 VRMS; ISB: 0 – 100%
-
-
±5
%VSB
North America
Asia-Pacific
Europe, Middle East
+86 755 298 85888
+353 61 225 977
+1 408 785 5200
© 2020 Bel Power Solutions & Protection
BCD.01063_B
4
ABC601 Series
Natural Convection
U-Chassis Models
Vertical Mounting
180 – 305 VAC
Natural Convection
U-Chassis Models
Horizontal Mounting
180 – 305 VAC
Forced Air Cooling
U-Chassis Models
>500 LFM
At 180 – 305 VAC
>600 LFM
At 85 – 180 VAC
Enclosed Front Mounted
Fan Models
85 – 305 VAC
Natural Convection
Any Orientation
85 – 305 VAC
tech.support@psbel.com
5
ABC601 Series
Base signals and controls are accessible from signal connector P204.
SIGNAL
DESCRIPTION / CONDITION
MIN
0
NOM
MAX
1.5
UNIT
+PS_Inhibit
Active high. Input low voltage
-
-
V
V
Input high voltage (IIN = 300 µA)
3.5
5.5
V1 and V2 disabled when PS_Inhibit is pulled high
5VSB not affected by PS_Inhibit
V1 and V2 enabled when PS_Inhibit is open or low
Active low (reverse control, same voltage levels)
Logic level low(<10 mA sinking)
-PS_Inhibit
P_OK *
-
2.4
40
1
-
-
-
-
-
0.7
5.5
350
-
V
Logic level high (100 µA sourcing)
V
Low to high time after V1 in regulation
Power down warning time
ms
ms
ms
5VSB Output
Active and in regulation after a 85 < VAC < 305 is applied
5VSB not affected by PS_Inhibit
-
1500
* When V1 is On, a P_OK low may indicates V1 under voltage condition. When two ABC601 operate in parallel, P_OK low in oneunit
indicates that it is not sharing the expected amount of current (current sharing fault). A 10 kΩ internal pull up to 5VSB is used; do not add
any other external pull up.
AC/DC INPUT OFF-TO-ON AND ON-TO-OFF TIMINGS
5VSB On – V1 On
250 ms ≤ T1 ≤ 550 ms
10 ms ≤ T2 ≤ 100 ms
3 ms ≤ T10 ≤ 40 ms
200 ms ≤ T3 ≤ 350 ms
T4 ≥ 1 ms
V1 rise time
5VSB rise time
V1 On – POWER_OK delay
Power down warning
V1 Off – 5VSB Off
T5 ≥ 0.5 s (V1 load > 25 W)
T6 ≥ 15 ms
AC Off – POWER_OK low
AC_On – 5VSB turn on time
T7 ≤ 1.5 s
North America
Asia-Pacific
+86 755 298 85888
Europe, Middle East
+353 61 225 977
+1 408 785 5200
© 2020 Bel Power Solutions & Protection
BCD.01063_B
6
ABC601 Series
PS_INHIBIT OFF-TO-ON AND ON-TO-OFF TIMINGS
V1 rise time
10 ms ≤ T2 ≤ 100 ms
200 ms ≤ T3 ≤ 350 ms
T4 ≥ 1 ms
V1 On – POWER_OK delay
Power down warning
PS_Inhibit – POWER_OK lowtiming
PS_Inhibit – V1 On delay
T8 ≤ 2 ms
T9 ≤ 450 ms
tech.support@psbel.com
7
ABC601 Series
PARAMETER
Input Under Voltage
Input Fuse
DESCRIPTION / CONDITION
Auto-recovering, hiccup mode.
High breaking, 10 A, 250 V on L and L1.
MIN
58
-
NOM
MAX
75
UNIT
65
-
VAC
A
10
At nominal input voltages
V1: Hiccup mode, auto-recovering (>10 s)
V1: Hiccup mode, auto-recovering (<10 s)
V2: PTC limiting, auto-recovering.
5VSB: Hiccup mode, auto-recovering:
U-Chassis models
108
135
-
-
-
-
132
163
-
%I1Rated
%I1Rated
Over Current
1.3
1.6
-
-
3.6
3.6
A
A
Front Mounted Fan models (-S)
At nominal input voltages
V1: Hiccup mode, auto-recovering.
V2: PTC limiting, auto-recovering.
5VSB: Hiccup mode, auto-recovering.
V1, Power shut down, latch off.
5VSB, Hiccup mode, auto-recovering.
Short Circuit
Over Voltage
-
-
-
120
-
-
-
145
150
%VNOM
Over Temperature (on primary stage)
Over Temperature (on secondary side)
Shut down, latch off.
-
-
-
°C
°C
Hiccup mode, auto-recovering.
-
-
-
Reinforced (2x MoPP).
Production tested at 4242 VDC
Basic (1x MoPP)
5660
4000
2121
1500
-
-
-
-
-
-
-
-
VDC
VAC
VDC
VAC
Isolation: Input-to-Output
Isolation: Input-to-Earth
Isolation: V1/5VSB to V2
Production tested at 2121 VDC
Basic
100
-
-
VAC
Isolation: Output-to-Earth
Means of Protection:
Basic (1x MoPP)
1500
-
-
VAC
2x MoPP (IEC 60601-1 3rd edition) at 100 – 250 VAC, 50/60 Hz up to 4000 m
2x MoPP (IEC 60601-1 3rd edition) at 100 – 277 VAC, 50/60 Hz up to 3000 m
2x MoOP (IEC 60601-1 3rd edition) at 100 – 277 VAC, 440 Hz (50/60 Hz)
1x MoPP (IEC 60601-1 3rd edition) at 100 – 250 VAC, 50/60 Hz up to 4000 m
1x MoPP (IEC 60601-1 3rd edition) at 100 – 277 VAC, 50/60 Hz up to 3000 m
1x MoOP (IEC 60601-1 3rd edition) at 100 – 277 VAC, 440 Hz (50/60 Hz)
1x MoPP (IEC 60601-1 3rd edition) at 100 – 250 VAC, 50/60 Hz up to 4000 m
Primary to secondary
Means of Protection:
Primary to ProtectionEarth
Means of Protection:
1x MoPP (IEC 60601-1 3rd edition) at 100 – 277 VAC, 50/60 Hz up to 3000 m (U-chassis variant only)
1x MoOP (IEC 60601-1 3rd edition) at 100 – 277 VAC, 440 Hz (U-chassis variant only)
Secondary to Protection Earth
Equipment Protection Class
Class I, compatible with BF (Body Floating) ME
PARAMETER
DESCRIPTION / CONDITION
MIN
NOM
MAX
UNIT
Operating Temperature Range No de-rating up to 50°C
Operating Temperature Range
-20
-
50
°C
See derating curves & conditions in the Output Specifications section
-
-40
-
-
-
-
70
°C
with Derating
Storage Temperature
TransportationTemperature
As per IEC/EN 60721-3-1 Class 1K4
As per IEC/EN 60721-3-2 Class 2K4
RH, Non-condensing Operating.
Non-operating
85
°C
90
95
%
%
Humidity
MoPP (100 – 250 VAC, 50/60 Hz)
MoPP (100 – 277 VAC, 50/60 Hz)
MoOP, ITE grade
-
-
-
-
-
-
4000
3000
5000
Operating Altitude
m
Power de-rating above1800 m
EN 60068-2-27
Shock
Operating:
Non-Operating: Half sine, 50 g, 11 ms, 3 axes, 6x each (3 positive and 3 negative).
EN 60068-2-64
Operating:
Half sine, 30 g, 18 ms, 3 axes, 6x each(3 positive and 3 negative).
Sine,10 – 500 Hz, 1 g, 3 axes, 1 oct/min., 60 min.
Vibration
Random, 5 – 500 Hz, 0.02 g2/Hz, 1 gRMS, 3 axes, 30 min.
Non-Operating: 5 – 500 Hz, 2.46 gRMS (0.0122 g2/Hz), 3 axes, 30 min.
Full Load, 40 °C ambient
80% Duty cycle, Telcordia SR-332 Issue 2
MTBF
300000
-
-
-
Hours
Years
Useful Life
Nominal VIN, 80% load, 40 °C ambient (IPC9592)
-
4
North America
Asia-Pacific
+86 755 298 85888
Europe, Middle East
+353 61 225 977
+1 408 785 5200
© 2020 Bel Power Solutions & Protection
BCD.01063_B
8
ABC601 Series
PERFORMANCE
CLASS
PARAMETER
DESCRIPTION / CONDITION
STANDARD
EN 55022 (ITE)
EN 55011 (ISM)
EN 60601-1-2 (Medical)
FCC Part 15
Conducted
115, 230, 277 VRMS, Maximum load
B
EN 55022 (ITE)
EN 55011 (ISM)
EN 60601-1-2 (Medical)
FCC Part 15
Radiated
At 10 m distance
B *
At 20%, 50% and 100% maximum load.
Nominal input voltages
230 VAC input voltage, 50 / 60 Hz
230 VAC 50 / 60 Hz, >150 W load
Line Voltage Fluctuation& Flicker
Harmonic Current Emission
EN 61000-3-3
EN 61000-3-2
EN 61000-3-2
A, D
C
* Performance referred to the enclosed package. Radiated emission relevant to the U-Chassis package, should be assessed at system level.
PARAMETER
DESCRIPTION / CONDITION
STANDARD
EN 60601-1-2, 4th edition
EN 55024
TEST LEVEL
CRITERIA
Reference standard for the medical version
Reference standards for ITE
Reference standard for Industrial/IMS equipment
EN 61000-6-2
15 kV air discharge, 8 kV contact,
ESD
EN 61000-4-2
4
3
A
A
at any point of the system.
10 V/m, 80-1000 MHz, 1 kHz/2 Hz 80% AM.
Dwell time is 3 sec for 2 Hz modulation
Dwell time is 1 sec for 1 kKHz modulation
Radiated Field
EN 61000-4-3
EN 61000-4-4
Electric Fast Transient
Surge
±2 kV on AC power port for 1 minute
3
4
3
A
A
A
±2 kV line to line; ± 4 kV line to earth on AC power port EN 61000-4-5
Conducted RF Immunity
10 VRMS, 0.15-80 MHz, 1 kHz, 80% AM
EN 61000-4-6
Drop-out to 0% for 10 ms
Dip to 40% for 5 cycles (100 ms)
Dip to 70% for 25 cycles (500 ms) EN61000-4-11
Drop-out to 0% for 5 s
EN61000-4-11
EN61000-4-11
A
A
A
B
200 – 277 VAC
100 – 127 VAC
:
:
EN61000-4-11
Dips and Interruptions
Drop-out to 0% for 10 ms
Dip to 40% for 5 cycles (100 ms)
Dip to 70% for 25 cycles (500 ms) EN 61000-4-11
Drop-out to 0% for 5 s
EN 61000-4-11
EN 61000-4-11
A
A (derate to 150 W)
A (derate to 400 W)
B
EN 61000-4-11
CERTIFICATION BODY SAFETY STANDARDS
CATEGORY
Audio Video and Information
Technology Equipment
CSA/UL
CSA C22.2 No. 60950-1, UL 60950-1 and UL 62368-1
CSA C22.2 No.60601-1, ANSI/AAMI ES60601-1 3rd edition + A1
Including Risk Management Assessment
Medical
UL8750, CSA C22.2 No 250.13
Lighting
Audio Video and Information
Technology Equipment.
Medical
IEC IECEE
CB Certification
IEC/EN 60950-1 and IEC/EN 62368-1
IEC/EN 60601-1 3rd edition+A1 Including Risk Management Assessment
Audio Video and Information
Technology Equipment
CE
Directive 2014/35/EU: Electrical Safety: LowVoltage electrical equipment (LVD)
Directive 93/42/CEE: Safety Requirement ofthe Medical Device
Directive 2014/30/EU: Electromagnetic Compatibility (EMC)
Directive EU 2015/863: RoHS 3
Medical
Designed to meet IEC/EN/UL/CSA 61010-1 2nd edition
tech.support@psbel.com
9
ABC601 Series
PARAMETER
DESCRIPTION / CONDITION
820 g (1.8 lb)
1055 g (2.32 lb)
Weight
107.0 x 178.5 x 41.0 mm (4.21 x 7.03 x 1.61 in)
107.0 x 206.0 x 41.0 mm (4.21 x 8.11 x 1.61 in)
Overall Dimensions
Figure 1. Mechanical drawing - U-Chassis Model
North America
Asia-Pacific
Europe, Middle East
+86 755 298 85888
+353 61 225 977
+1 408 785 5200
© 2020 Bel Power Solutions & Protection
BCD.01063_B
10
ABC601 Series
Figure 2. Mechanical drawing – Front Mounted Fan Models (-S)
tech.support@psbel.com
11
ABC601 Series
AC INPUT CONNECTOR – P1
PIN REF.
FUNCTION
Molex 26-62-4051
Mates with
1
3
5
L1
L
Molex 09-93-0500 (housing)
Molex 08-52-0071 (terminal phosphor bronze, tin finishing)
Use 18 AWG minimum wires
PE
DC OUTPUT CONNECTOR – P2
KARSON 520-041-2-1-00
Or equivalent
PIN REF.
1 – 2
FUNCTION
+V1
3 – 4
V1 RTN
SIGNAL CONNECTOR – P3
PIN REF.
FUNCTION
RTN
Molex 90130-1112
Mates with
Molex 90142-0012 (housing)
Molex 90119-0109 (terminal)
Use 22-24 AWG wires
1
2
-V2
3
+5VSB
4
+V2
5
RS-
6
RS+
7
+PS_Inhibit
I-Share
P_OK
8
9
10
11
12
VS_Logic
-PS_Inhibit
RTN
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for useas critical components in life support systems,
equipment used in hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.
North America
Asia-Pacific
Europe, Middle East
+86 755 298 85888
+353 61 225 977
+1 408 785 5200
© 2020 Bel Power Solutions & Protection
BCD.01063_B
相关型号:
©2020 ICPDF网 联系我们和版权申明