MBC1200-1T24-PCF [BEL]
Single 24 VDC / 48 VDC output voltages available;型号: | MBC1200-1T24-PCF |
厂家: | BEL FUSE INC. |
描述: | Single 24 VDC / 48 VDC output voltages available |
文件: | 总14页 (文件大小:1450K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
The MBC1200 / MBE1200 Series of AC-DC power supplies provides a
steady 1200 W of regulated DC power through 180-305 VAC and 1000 W
through 85-137 VAC input voltage ranges in a single output of 24 or 48 VDC,
offering 12 and 5 VSB standby outputs and a full set of protection features.
The MBC1200 / MBE1200 Series is available in three compact 1U height
compatible packages; one, enclosed with a built-in front mounted pair of fans
and two (available only 24 V variant), U-shaped chassis with or without
protective cover, to facilitate system integration.
The MBC1200 / MBE1200 Series supports digital power management over
the Power Management Bus communications protocol. Multiple units may be
connected in parallel for redundancy and / or higher power, enabled with the
internal OR-ing and current sharing functions.
The MBC1200 / MBE1200 Series complies with the latest edition of the
IEC/EN 60601-1 safety standards for medical equipment requiring 2x MoPP
ction grade and displays the CE-Mark for the European Low Voltage
ive (LVD).
Universal input voltage range
90 – 305 VAC, MoOP; 90 – 264 VAC, MoPP
nput inrush current limiting
1200 W rated power
High efficiency up to 94%
Single 24 VDC / 48 VDC output voltages available
Active PFC, EN61000-3-2 compliant (Class C, >25% load)
Low earth / touch leakage current
•
•
•
Fan speed control function
800 LFM airflow for MBC1200 models
Over temperature, OV, OC and SC protections
+12 V, 0.5 A; +5 V, 1 A Stand by outputs
Built-in current sharing and OR-ing for parallel operation and N+1
redundancy
Remote On / Off signal
•
•
•
•
Power good and remote sense signals
Power Management Bus communication protocol supported
Medical safety approval to IEC 60601-1 3rd edition, 2x MoPP rated and
BF appliances compatible
IEC 60601-1-2 4th edition EMC compliant
RoHS 3 compliant (Directive 2015/863/EU)
•
•
X-Ray / CT Scanner
Dental Equipment
Laboratory / Analysis Equipment
Medical Devices / Applications
•
•
•
•
2
MBC1200 / MBE1200 Series
INPUT VOLTAGE
RANGE
NOM. OUTPUT
VOLTAGE
[VDC]
MAX. OUTPUT MAX. OUTPUT
PACKAGE &
COOLING
MODEL NUMBER
POWER
CURRENT
DIMENSIONS
[VAC]
[W]
[A]
U-chassis,
101.6 x 234.0 x 41.0 mm
4.00 x 9.21 x 1.61 in
101.6 x 234.7 x 41.0 mm
4.00 x 9.24 x 1.61 in
101.6 x 264.1 x 41.0 mm
4.00 x 10.4 x 1.61 in
101.6 x 264.1 x 41.0 mm
4.00 x 10.4 x 1.61 in
MBC1200-1T24-UCF
MBC1200-1T24-PCF
MBE1200-1T24
85 - 305
85 - 305
85 - 305
85 - 305
24
24
24
48
1200
1200
1200
1200
50
50
50
25
external air flow
Protective cover,
external air flow
Enclosed,
front mounted fan
Enclosed,
MBE1200-1T48
front mounted fan
PARAMETER
DESCRIPTION / CONDITION
MIN
NOM
MAX
UNIT
PS starts at 85 VAC at all load conditions
Operating input voltage range
MBC1200 / MBE1200 Series is designed to operate with a square or
trapezoidal input voltage wave form (i.e. from UPS)
85
100-277
305
VRMS
AC Input Voltage
Built in fuses safety certified up to 250 VDC. Operating the 1200 W Series
above that limit up to 300 VDC, does require an external fuse protection *
DC Input Voltage
Input Frequency
120
47
-
300
63
VDC
Hz
50/60
At 180 VAC, maximum load, 50 / 60 Hz
At 85 VAC, 1000 W load, 50 / 60 Hz
163 VDC, maximum load
8.0
14.5
9.0
ARMS
Input Current
-
-
A
120 VDC, 1000 W
10.0
At power-on asserted
Cold start, 25 °C ambient, full load
Any point of the AC input sine
Inrush Current
Fusing
230 VAC
277 VAC
-
-
-
-
30
50
A
A
High breaking, 16 / 20 A, 277 VAC (250 VDC) on each AC line.
20% rated load
At 120 VAC
-
-
16 / 20
88
92
92
-
-
-
-
-
-
50% rated load
100% rated load
Efficiency
%
W
20% rated load
50% rated load
100% rated load
90
93
94
-
-
-
-
-
-
7.0
6
4.0
-
-
-
-
-
-
At 230 VAC
At power on, no load, 100-277 VAC range (MBE1200-1T24 / -1T48)
At power on, no load, 100-277 VAC range (MBC1200-1T24-UCF / -PCF)
Stand by, no load, nominal 100-277 VAC range
Input Power Consumption
Power Factor
THDi
Any nominal input line voltage, 50/60 Hz, from 50 to 100% maximum load
From 50 to 100% rated load, 100-277 VAC,50/60 Hz.
0.95
-
-
-
-
-
20
%
Complies with EN 61000-3-2 at 230 VAC, 50/60 Hz, Class A, D.
Complies with EN 61000-3-2 Class C at 230 VAC, 50/60 Hz, >300 W load.
Complies with EN 61000-3-3 at nominal voltages and full load.
Normal conditions
115 VRMS, 60 Hz
230 VRMS, 50 Hz
Harmonic Current
Fluctuations and Flicker
-
-
-
130
240
-
-
-
Earth Leakage Current
µA
264 VRMS, 60 Hz (worst case)
400
264 VRMS, 60 Hz
Normal Condition (NC)
Single Fault Condition (SFC)
264 VRMS, 60 Hz
Normal Condition (NC)
Single Fault Condition (SFC)
Touch Leakage Current
Patient Leakage Current
-
-
-
-
100
500
µA
µA
-
-
-
-
100
500
* Suggested fuse SIBA 5012434.16 and fuse holder SIBA 5105805.1
tech.support@psbel.com
3
MBC1200 / MBE1200 Series
PARAMETER
DESCRIPTION / CONDITION
MIN
NOM
MAX
UNIT
±0.5% set point accuracy
RS+ closed on +V1, RS- closed on V1 RTN, at 6% load.
24
48
V1 Output Voltages
-
-
V
85 – 137 VAC
(120-163 VDC
180 – 305 VAC
(163-300 VDC
85 – 137 VAC
(120-163 VDC
180 – 305 VAC
(163-300 VDC
MBC1200-1T24-UCF / -PCF (800 LFM);
MBE1200-1T24 / MBE1200-1T48
MBC1200-1T24-UCF / -PCF (800 LFM);
MBE1200-1T24 / MBE1200-1T48
MBC1200-1T24-UCF / -PCF; MBE1200-1T24
MBE1200-1T48
1000
)
V1 Output Power Rating
V1 Output Current
W
A
1200
)
41.7
20.8
50
)
MBC1200-1T24-UCF / -PCF; MBE1200-1T24
MBE1200-1T48
)
20
V1 Voltage Adjustment Range
V1 Line Regulation
Manually by push up and down buttons
-
-
-
±5
-
-
%V1
%V1
%V1
VAC
:
:
85 – 305 VRMS
±0.1
±2
V1 Load-Line-Cross Regulation
VAC
85 – 305 VRMS; I1: 0 – 100%
-
Rated load, Peak-to-peak, 20 MHz BW.
(100 nF ceramic, 10 µF tantalum at load)
25% load changes at 1 A/µs
24 V at 1000 µF load / IOUT > 2.5 A
48 V at 560 µF load / IOUT > 1.25 A
12 VSB, 5 VSB at 0-2200 µF load
V1 Ripple and Noise
-
-
1
%V1
Transient Response:
V1, 12VSB, 5VSB
Voltage Deviation
%V1
%VSB
-
-
±5
V1 Start-up Rise Time
V1 Hold-up Time
85<VIN<305, any load conditions.
10
10
-
-
150
-
ms
ms
At nominal VIN, full load
SEMI F47-0706 compliant at ≥208 VAC
50% sag (104 V)
30% sag (145 V)
20% sag (166 V)
200
500
1000
-
-
-
-
-
-
Parallel operation up to four units.
Two units in parallel at I1 rated load.
I-Share signals connected together.
V1 Current Sharing Accuracy
40
-
60
%I1
RS+, RS- signals connected together and to the load.
Max load at start up 1200 W, operating 2000 W, 180 ÷305 VAC
.
.
Max load at start up 1000 W, operating 1667 W, 85 ÷ 137 VAC
V1 Remote Sense
Start-up Delay
RS+ and RS- power path voltage loss compensation
-
-
0.36
V
V1 in regulation after de-asserting PS_Inhibit
V1 in regulation after AC is applied
-
-
-
-
1700
2200
(worst case: 85 VAC
)
ms
5VSB in regulation after AC is applied
-
-
500
(worst case: 85 VAC
)
-
-
-
-
10
10
%V1
%VSB
Turn-on Overshoot
Minimum Load
V1, 12VSB, 5VSB
0
-
-
A
V1: 24 VDC
V1: 48 VDC
V1: 24 VDC
V1: 48 VDC
-
-
-
-
16000
8000
75
Maximum Load Capacitance
µF
V1 Over Current Protection
A
37.5
12 VSB Output Voltage
12 VSB Output Current
12 VSB Ripple & Noise
12 VSB Line Cross Regulation
5 VSB Output Voltage
5 VSB Output Current
5 VSB Ripple & Noise
VSB output voltage is referred to the same V1 output voltage return
All models up to 70 °C
-
-
12
-
-
0.5
120
±5
-
V
A
Peak-to-peak
mV
%VSB
V
VAC: 85 – 305 VRMS; ISB: 0 – 100%
VSB output voltage is referred to the same V1 output voltage return
All models up to 70 °C
-
-
-
-
5
-
1
A
Peak-to-peak
50
±5
mV
%VSB
5 VSB Load, line cross Regulation VAC: 85 – 305 VRMS; ISB: 0 – 100%
-
-
North America
Asia-Pacific
Europe, Middle East
+1 408 785 5200
+86 755 298 85888
+353 61 225 977
© 2020 Bel Power Solutions & Protection
BCD.01054_B
4
MBC1200 / MBE1200 Series
Front Fan (Models MBE1200-1T24 / MBE1200-1T48)
Any orientation, V1 nominal
U-Chassis and Perforated Cover
Forced Air Cooling (Models MBC1200-1T24-UCF / -PCF)
Air flow from top, V1 nominal
U-Chassis and Perforated Cover
Forced Air Cooling (Models MBC1200-1T24-UCF / -PCF)
Air flow from AC side, V1 nominal
tech.support@psbel.com
5
MBC1200 / MBE1200 Series
The MBC1200 / MBE1200 Series does support communication according to the Power Management Bus 1.2 protocol via SDA,
SCL and #SMBALERT signals as defined in the SMBus Specification version 2.0.
The power supply shall not load the SMBus if it has no input power (SCL & SDA lines should go to High-Z).
The pull-up resistors (2.2 kΩ) for these signals shall be external to the power supply and referenced to an external +3.3 V bus
voltage.
The DSP circuits inside the power supply are powered by the standby output.
The Power Management Bus is active whatever input power is applied to the power supply or a parallel redundant power supply in
the system, provided that their 12VSB are connected in parallel.
Maximum speed of SMBus is 100 kHz.
The ADDR0 and ADDR1 signals, are inputs to the power supply that control the Power Management Bus address assigned to the
power supply.
On the system side, the ADDR0 and ADDR1 signals will either be connected to return through a 1 kΩ pull-down resistor or
connected to +3.3 V external bus voltage through a 1 kΩ pull-up resistor.
The address shall be derived from the logic of this pin as indicated on Outline Drawing and Connections section.
The power supply is a slave only on SMBus device.
For a comprehensive description of MBC1200 / MBE1200 Series Power Management Bus management, do refer to the application
note, “MBC1200 / MBE1200 Series Power Management Bus Mgt”. Examples of 1200 W Series parameters available through
communication bus are:
•
•
•
•
•
•
•
•
•
Input voltage status
Output voltages +V1 measured value
Output current on +V1 measured value
Current sharing status
Thermal health measured value
Fan health status
Power-On / Working hours
Product information
Status information
Failures shall be reported by Power Management Bus for all failure types:
•
•
•
Fan fault
Protections failure (OV, OC, OT)
Voltages out of specification
North America
Asia-Pacific
Europe, Middle East
+1 408 785 5200
+86 755 298 85888
+353 61 225 977
© 2020 Bel Power Solutions & Protection
BCD.01054_B
6
MBC1200 / MBE1200 Series
Base signals and controls are accessible from signal connector P204.
SIGNAL
DESCRIPTION / CONDITION
MIN
NOM
MAX
UNIT
Input low voltage (IIN= 0 µA)
0
2.5
-
-
0.8
5.5
V
Input high voltage (IIN= 500 µA at 5.5 V)
V1 disabled when PS_Inhibit is pulled high
V1 enabled when PS_Inhibit is floating or low
5VSB and 12VSB not affected by PS_Inhibit
Input low voltage (IIN= -800 µA at 0 V)
Input high voltage (IIN= -200 µA at 2.5 V)
(IIN= 700 µA at 5.5 V)
+PS_Inhibit
(Active High)
0
2.5
-
-
0.8
5.5
V
-PS_Inhibit
(Active Low)
V1 disabled when -PS_Inhibit is pulled low
V1 enabled when -PS_Inhibit is floating or high
5VSB and 12VSB not affected by -PS_Inhibit
Logic level low (<10 mA sinking)
-
-
-
-
-
0.7
3.45
350
-
V
Power_OK *
(PS_OK)
Logic level high (200 µA sourcing)
Low to high time after V1 in regulation
Power down warning time
2.4
150
2
ms
The I_SHARE signals shall be daisy chained among power supplies operating in parallel.
On a single power supply operating it provides current measurement on V1 output.
I_Share
On multiple power supplies operating in parallel, it provides current measurement on master V1output.
These are signals which support Power Management Bus communication protocol as specified in the application
note MBC1200 / MBE1200 Series Power Management Bus Mgt.
SDA, SCL, #SMBALERT,
ADDR0, ADDR1
Mainly intended for internal use, these RX and TX signals - available at the output signal connector
P204 - may be used to access some DSP functions (monitoring, threshold settings, debug functions).
These signals work as an UART Rx/Tx port and can also work as a RS-232 Rx/Tx port by building in the
“RS-232 LINE DRIVERS/RECEIVERS” IC
RSVD RX, RSVD TX
Active and in regulation after an 85<VAC<305 is applied
Not affected by PS_Inhibit. Available on P204, pin#4
Active and in regulation after an 85<VAC<305 is applied
Not affected by PS_Inhibit. Available on P204, pin#16
-
-
500
ms
ms
5VSB Output **
-
-
500
12VSB Output ***
* When V1 is On, a P_OK low may indicates V1 under voltage condition. When two 1200 W models operate in parallel, P_OK low in one unit
indicates that it is not sharing the expected amount of current (current sharing fault). A 3.3 kΩ internal pull up to a 3.3 V internal reference
voltage is used; do not add any other external pull up.
** The 5VSB outputs of two or more 1200 W models operating in parallel, cannot be connected in parallel in turn, since doing so results in
power supplies damage.
*** The 12VSB outputs of two or more 1200 W models operating in parallel can be connected in parallel in turn, taking into account that the
maximum available power will not be higher of a single operating power supply one.
tech.support@psbel.com
7
MBC1200 / MBE1200 Series
AC/DC INPUT OFF-TO-ON AND ON-TO-OFF TIMINGS
12VSB/5VSB On to V1 On
V1 rise time
250 ms ≤ T1 ≤ 1700 ms
10 ms ≤ T2 ≤ 150 ms
3 ms ≤ T10 ≤ 150 ms
150 ms ≤ T3 ≤ 350 ms
T4 ≥ 2 ms
12VSB/5VSB rise time
V1 On – POWER_OK delay
Power down warning
V1 Off to 12VSB/5VSB Off
AC Off to POWER_OK low
AC_On to 12VSB/5VSB On
T5 ≥ 0.5 s (V1 load > 25 W)
T6 ≥ 8 ms
T7 ≤ 500 ms
PS_INHIBIT OFF-TO-ON AND ON-TO-OFF TIMINGS
10 ms ≤ T2 ≤ 150 ms
V1 rise time
V1 On – POWER_OK delay
Turn-Off warning
150 ms ≤ T3 ≤ 350 ms
T11 ≥ 1 ms
PS_Inhibit – POWER_OK low delay
PS_Inhibit – V1 On delay
T8 ≤ 3 ms
T9 ≤ 1700 ms
North America
+1 408 785 5200
Asia-Pacific
+86 755 298 85888
Europe, Middle East
+353 61 225 977
© 2020 Bel Power Solutions & Protection
BCD.01054_B
8
MBC1200 / MBE1200 Series
PARAMETER
DESCRIPTION / CONDITION
MIN
NOM
MAX
UNIT
Input Under Voltage
Auto-recovering, hiccup mode.
58
75
82
VAC
High breaking, 16 / 20 A, 277 VAC (250 VDC
on each AC lines.
)
Input Fuse
-
-
16/20
A
At nominal input voltages
V1: Hiccup mode, auto-recovering
5VSB: Auto-recovering
12VSB: Hiccup mode, auto-recovering
At nominal input voltages
-
-
-
-
-
-
150
-
-
%I1Rated
Over Current
A
A
V1: Hiccup mode or latch
5VSB: Auto-recovery
12VSB: Hiccup mode, auto-recovering.
V1, Power shut down, latch off.
12VSB, Hiccup mode, auto-recovering.
Short Circuit
Over Voltage
-
-
-
116
-
-
-
145
150
%VNOM
°C
Over Temperature
(ambient)
Over Temperature
Hiccup mode, auto-recovering.
Hiccup mode, auto-recovering.
70
-
-
-
-
-
°C
(on secondary side)
Relevant to the MBE1200-1T24 / MBE1200-1T48 models.
The DSP monitors the signals (frequency generator) provided by both fans. If one fan fails, the DSP asserts
maximum speed the other fan and provides an alarm indication through Power Management Bus.
If both fans fail, the DSP provides an alarm indication through LED and through Power Management Bus and
after 20 s, does shut down V1.
Fan Fault Protection
PS INHIBIT or AC/DC input have to be cycled to resume operations, after removed the fault.
5660
4000
2642
1865
-
-
-
-
-
-
-
-
VDC
VAC
VDC
VAC
Isolation: Primary-to-Secondary
Reinforced
Basic
Isolation: Input-to-Earth
Isolation: Output-to-Earth
Production tested at 2642 VDC
Basic
1500
-
-
VAC
Means of Protection:
Primary to secondary
Means of Protection:
Input to Protection Earth
Means of Protection:
Output to Protection Earth
2x MoPP (IEC 60601-1 3rd edition) at 90 – 264 VAC, 50/60 Hz (120-300 VDC) up to 4000 m
2x MoOP (IEC 60601-1 3rd edition) at 90 – 305 VAC, 50/60 Hz (120-300 VDC) up to 4000 m
1x MoPP (IEC 60601-1 3rd edition) at 90 – 264 VAC, 50/60 Hz (120-300 VDC) up to 4000 m
1x MoOP (IEC 60601-1 3rd edition) at 90 – 305 VAC, 50/60 Hz (120-300 VDC) up to 4000 m
1x MoPP (IEC 60601-1 3rd edition) at 100 – 250 VAC, 50/60 Hz up to 4000 m
Equipment Protection Class
Class I, compatible with BF (Body Floating) ME (Medical Equipment)
PARAMETER
DESCRIPTION / CONDITION
MIN
NOM
MAX
UNIT
No derating up to 60 °C (MBE1200) and up to 55 °C (MBC1200)
See derating curves above
-20
-
60
Operating Temperature Range
°C
MBC1200 / MBE1200 Series starts at -40 °C upon warm up delay
See derating curves and conditions in the Output Specifications
section
As per IEC/EN 60721-3-1 Class 1K4
As per IEC/EN 60721-3-2 Class 2K4
RH, Non-condensing Operating.
Operating Temperature Range
with Derating
Storage Temperature
Transportation Temperature
-
-40
-
-
-
-
70
85
°C
°C
90
95
%
%
Humidity
Non-operating
MoPP (90 – 264 VAC, 50/60 Hz, 120 – 300 VDC
MoOP (90 – 305 VAC, 50/60 Hz)
Power derating above 1800 m
EN 60068-2-27
)
-
-
-
-
4000
4000
Operating Altitude
m
Shock
Operating:
Non-Operating: Half sine, 50 g, 11 ms, 3 axes, 6x each (3 positive and 3 negative).
EN 60068-2-64
Operating:
Half sine, 30 g, 18 ms, 3 axes, 6x each (3 positive and 3 negative).
Sine,10 – 500 Hz, 1 g, 3 axes, 1 oct/min., 60 min.
Vibration
Random, 5 – 500 Hz, 0.02 g2/Hz, 1 gRMS, 3 axes, 30 min.
Non-Operating: 5 – 500 Hz, 2.46 gRMS (0.0122 g2/Hz), 3 axes, 30 min.
tech.support@psbel.com
9
MBC1200 / MBE1200 Series
Full load, 25 °C ambient, 100% duty cycle,
Full load, 40 °C ambient, 75% duty cycle
Telcordia SR-332 Issue 2
700000
600000
-
-
-
-
Hours
MTBF
Useful Life
Nominal VIN, 80% load, 40 °C ambient (IPC9592)
-
7
-
Years
PERFORMANCE
CLASS
PARAMETER
DESCRIPTION / CONDITION
STANDARD
Conducted
Radiated
115, 230 VRMS, Maximum load
EN 60601-1-2 (Medical)
EN 60601-1-2 (Medical)
B
B *
At 20%, 50% and 100% maximum load
Nominal input voltages
230 VAC input voltage, 50 / 60 Hz
230 VAC 50 / 60 Hz, >300 W load
Line Voltage Fluctuation & Flicker
Harmonic Current Emission
EN 61000-3-3
EN 61000-3-2
EN 61000-3-2
A, D
C
* Performance referred to the enclosed package with additional HF chokes on input, output power and signal cables.
Radiated emission relevant to the UCF and PCF package variants, should be assessed at system level.
PARAMETER
DESCRIPTION / CONDITION
STANDARD
TEST LEVEL
CRITERIA
Reference standard for the medical version
EN 60601-1-2, 4th Edition
15 kV air discharge, 8 kV contact,
at any point of the system.
ESD
EN 61000-4-2
4
A
Radiated Field
10 V/m, 20 – 2700 MHz, 1 kHz, 80% AM
EN 61000-4-3
EN 61000-4-4
3
3
4
3
A
A
A
A
Electric Fast Transient
Surge
±2 kV on AC power port for 1 minute
±2 kV line to line; ± 4 kV line to earth on AC power port EN 61000-4-5
Conducted RF Immunity
10 VRMS, 0,15 – 80 MHz, 1 kHz, 80% AM
EN 61000-4-6
Drop-out to 0% for 10 ms
EN61000-4-11
EN61000-4-11
EN61000-4-11
EN61000-4-11
A *
200 – 264 VAC
:
:
Dip to 40% for 5 cycles (100 ms)
Dip to 70% for 25 cycles (500 ms)
Drop-out to 0% for 5 s
A (derate to 900 W)
A
B
Dips and Interruptions
Drop-out to 0% for 10 ms
EN 61000-4-11
EN 61000-4-11
EN 61000-4-11
EN 61000-4-11
A *
100 – 127 VAC
Dip to 40% for 5 cycles (100 ms)
Dip to 70% for 25 cycles (500 ms)
Drop-out to 0% for 5 s
A (derate to 400 W)
A (derate to 700 W)
B
* Performance referred to +5VSB, +12VSB and V1 (PS_OK goes to low level after 8 ms as per timing described at page 8
CERTIFICATION BODY
SAFETY STANDARDS
CATEGORY
CSA / UL
CSA C22.2 No.60601-1, ANSI/AAMI ES60601-1 3rd Edition + A1
IEC/EN 60601-1 3rd edition+A1
Medical
Medical
Medical
Directive 93/42/CEE: Safety Requirement of the Medical Device
Directive 2014/30/EU: Electromagnetic Compatibility (EMC)
Directive 2015/863/EU: RoHS 3
Meets all essential requirements of the standard IEC/EN/UL/CSA 61010-1 2nd edition
North America
Asia-Pacific
Europe, Middle East
+1 408 785 5200
+86 755 298 85888
+353 61 225 977
© 2020 Bel Power Solutions & Protection
BCD.01054_B
10
MBC1200 / MBE1200 Series
CONNECTIONS
CONNECTOR
REFERENCE
FUNCTION
Line 1
AC Input Connections
P1: AMTEK TB25C-B02P-13-00A-L
M4 GROUND STUD
1
2
3
Line 2
Protection Earth
DC Input Connections
Signal Connector
P200, P201, P202, P203:
BRASS M4 THREADED TERMINALS
(tight to 0.8-1 Nm,
24 V Optional
+V1
24 / 48 V
P200
P201
P202
P203
+V1
+V1
-
max. deep screws 7 mm)
V1 RTN
V1 RTN
V1 RTN
-
P204:
MOLEX 501876-1640
1
RMT (-)
2
RMT (+)
3
I-SHARE
+5VSB
4
5
PS_INHIBIT
PS_OK
6
7
SCL
8
SDA
9
#SMBALERT
ADDR0
10
11
12
13
14
15
16
-PS_INHIBIT
ADDR1
RSVD_RX (OUT)
RSVD_TX (OUT)
RTN
+12VSB
Additional Control Functions
SW600
SW601
DL600
V1_ADJ (UP)
V1_ADJ (DOWN)
Bi-colour LED
Off
No AC/DC input power provided
Blinking Green
Input power good, standby active,
V1 inhibited
Steady Green
V1 Active
Steady or Blinking red
Power Supply Fault
PARAMETER
DESCRIPTION / CONDITION
1150 g (2.53 lb) – MBC1200-1T24-UCF
1250 g (2.75 lb) – MBC1200-1T24-PCF
Weight
1550 g (3.42 lb) – MBE1200-1T24 / MBE1200-1T48
101.6 x 234.0 x 41.0 mm (4.00 x 9.21 x 1.61 in) – MBC1200-1T24-UCF
101.6 x 234.7 x 41.0 mm (4.00 x 9.24 x 1.61 in) – MBC1200-1T24-PCF
Overall Dimensions
101.6 X 264.1 x 41.0 mm (4.00 x 10.4 x 1.61 in) – MBE1200-1T24 / MBE1200-1T48
tech.support@psbel.com
11
MBC1200 / MBE1200 Series
Figure 1. Mechanical Drawing - MBC1200-1T24-UCF Model
Figure 2. Front View - MBC1200-1T24-UCF Model
Figure 6. Rear View - MBC1200-1T24-UCF Model
North America
Asia-Pacific
Europe, Middle East
+1 408 785 5200
+86 755 298 85888
+353 61 225 977
© 2020 Bel Power Solutions & Protection
BCD.01054_B
12
MBC1200 / MBE1200 Series
Figure 4. Mechanical Drawing - MBC1200-1T24-PCF Model
Figure 5. Front View - MBC1200-1T24-PCF Model
Figure 6. Rear View - MBC1200-1T24-PCF Model
tech.support@psbel.com
13
MBC1200 / MBE1200 Series
Figure 7. Mechanical Drawing - MBE1200-1T24 / MBE1200-1T48 Models
Figure 9. Rear View - MBE1200-1T24 / MBE1200-1T48 Models
Figure 8. Front View - MBE1200-1T24 / MBE1200-1T48 Models
North America
Asia-Pacific
Europe, Middle East
+1 408 785 5200
+86 755 298 85888
+353 61 225 977
© 2020 Bel Power Solutions & Protection
BCD.01054_B
14
MBC1200 / MBE1200 Series
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,
equipment used in hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on lMBEls, may change depending on
the date manufactured. Specifications are subject to change without notice.
tech.support@psbel.com
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明