MBS400 [BEL]

400 W rated power (440 W peak up to 10 s);
MBS400
型号: MBS400
厂家: BEL FUSE INC.    BEL FUSE INC.
描述:

400 W rated power (440 W peak up to 10 s)

文件: 总9页 (文件大小:725K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
The ABS/MBS400 Series of AC-DC power supplies provides up to  
400 W of regulated output power through wide input voltage range  
90 264 VAC in single outputs of 12, 24, 36 or 48 VDC.  
The ABS/MBS400 Series comes in a 83.0 x 212.0 x 42.0 mm form  
factor, offering 12 and 5 VSB standby outputs and a full set of  
protection features. Available control signals include Power Good  
(Power_OK), remote On/off (PS_ON) and remote sense (+RS).  
The sealed and full potted package allows an IP67 ingress  
protection index and can be installed in contact with thermo-  
conductive part of the system to transfer heat by conduction.  
The ABS400/MBS Series complies with the latest international  
safety standards for IT and medical equipment, offering 2x MoPP  
protection grade and displays the CE-Mark for the European Low  
Voltage Directive (LVD).  
Universal input voltage range (90 264 VAC)  
Input surge current limiting  
400 W rated power (440 W peak up to 10 s)  
High efficiency up to 94%  
Low stand-by consumption (<0.5 W)  
12, 24, 36 and 48 V standard output voltages  
Active PFC, EN61000-3-2 compliant (Class C, >25% load).  
Low earth / touch leakage current  
Over temperature protection, OV, OC and SC protections  
Stand by +5 V, 2 A and auxiliary / fan 12 VDC, 1 A outputs.  
Remote On / Off signal  
Power good and remote sense signals  
Sealed, potted package IP67 rated, fits 1U applications  
Medical safety approval to IEC 60601-1 3rd edition, 2x MoPP rated  
and BF appliances compatible.  
IT safety approval to UL/IEC 60950-1  
Medical version compatible with 4000 m altitude operation  
Optional heatsink accessory available (HSKIT-400-XBS)  
Suitable for harsh environments  
Video Wall Display & Entertainment  
Industrial Process Control  
Telecommunications  
Laboratory Equipment  
Test & Measurement Equipment  
Medical Applications  
2
ABS/MBS400 Series  
INPUT VOLTAGE NOM. OUTPUT MAX. OUTPUT  
MAX. OUTPUT  
CURRENT  
[A]  
MODEL NUMBER PACKAGE & COOLING  
RANGE  
[VAC]  
VOLTAGE  
[VDC]  
POWER  
[W]  
DIMENSIONS  
ABS400-1012  
MBS400-1012  
ABS400-1024  
MBS400-1024  
ABS400-1036  
MBS400-1036  
ABS400-1048  
MBS400-1048  
HSKIT-400-XBS  
33.3  
16.7  
11.1  
8.3  
Sealed Chassis  
Convection / Conduction  
90 - 264  
90 - 264  
90 - 264  
90 - 264  
12  
24  
36  
48  
400  
400  
400  
400  
Dimensions without  
heatsink:  
83.0 x 212.0 x 42.0 mm  
3.27 x 8.34 x 1.65 in  
Sealed Chassis  
Convection / Conduction  
Sealed Chassis  
Convection / Conduction  
Dimensions with  
heatsink:  
83.0 x 212.0 x 70.1 mm  
3.27 x 8.34 x 2.76 in  
Sealed Chassis  
Convection / Conduction  
- Heatsink accessory (optional) Mounting kit includes 4x screws, M4x10, and the thermally conductive graphite sheet  
PARAMETER  
AC Input Voltage  
DC Input Voltage  
Input Frequency  
DESCRIPTION / CONDITION  
MIN  
90  
NOM  
100-240  
-
MAX  
264  
UNIT  
VRMS  
VDC  
PS starts and operates at 90 VAC at all load conditions  
170  
47  
270  
50/60  
440  
Hz  
RMS at 180 VAC, maximum load, 50 / 60 Hz  
RMS at 90 VAC, maximum load, 50 / 60 Hz  
2.5  
5.0  
Input Current  
-
-
A
Inrush Current  
Fusing  
265 VAC, 25 °C ambient, cold start.  
20  
6.3  
-
A
A
2x Time Lag 6.3 A, 250 V on both L and N  
-
-
-
-
-
-
20% rated load  
100 % load  
90  
92  
90  
94  
At 115 VAC  
-
Efficiency  
%
20% full load  
-
At 230 VAC  
50 100 % full load  
-
Power on, 115-230 VRMS, no load  
Stand by, 115-230 VRMS, no load  
-
-
1
0.4  
1.5  
0.5  
Input Power Consumption  
Power Factor  
W
-
At full rated load, 115 VAC, 60 Hz and 230 VAC, 50 Hz input voltages  
0.95  
-
-
Harmonic Current  
Fluctuations and Flicker  
Complies with EN-61000-3-2 Class C at 230 VAC 50 Hz, load >50 W.  
Complies with EN-61000-3-3 at nominal voltages and full load.  
Normal conditions, 240 VRMS, 60 Hz.  
Leakage Current  
300  
µA  
tech.support@psbel.com  
3
ABS/MBS400 Series  
PARAMETER  
DESCRIPTION / CONDITION  
MIN  
NOM  
MAX  
UNIT  
-
-
-
-
-
-
-
12  
24  
36  
48  
-
-
-
-
-
-
V1 Output Voltage  
±0.5% set point accuracy on all outputs  
V
W
A
-
All models, convection cooling  
All models, conduction cooling / heat sink  
All models, peak power (10 s)  
350  
400  
440  
33.3  
16.7  
11.1  
8.3  
29.2  
14.6  
9.7  
7.3  
V1 Output Power Rating  
V1 Output Current  
V1: 12 VDC  
V1: 24 VDC  
V1: 36 VDC  
V1: 48 VDC  
V1: 12 VDC  
V1: 24 VDC  
V1: 36 VDC  
V1: 48 VDC  
* Conduction (with heatsink)  
** Convection (without heatsink)  
A
V1 Voltage Adjustment Range  
V1 Load-Line-Cross Regulation  
V1 Line Regulation  
±5  
-
-
-
-
-
-
%V1  
V1 Load: 0 33.3 A (12 V)  
0 16.7 A (24 V)  
0 11.1 A (36 V)  
0 8.3 A (48 V)  
V2 Load: 0 1 A  
5VSB Load: 0 2 A  
VAC: 90 264 VRMS  
VAC: 90 264 VRMS  
±2  
%V1  
%V1  
-
±0.1  
±5  
25% load changes at 1 A/µs  
12 V at 2200 µF Load / IOUT> 0.5 A  
24 V at 1000 µF Load / IOUT> 0.5 A  
36 V at 820 µF Load / IOUT> 0.5 A  
48 V at 560 µF Load / IOUT> 0.5 A  
5VSB at 560 µF Load / IOUT> 0.1 A  
Transient Response  
(Voltage Deviation)  
V1, 5VSB  
%V1  
%5VSB  
-
All models, Peak-to-peak, 20 MHz BW.  
100 nF ceramic and 10µF tantalum to the load.  
V1 Ripple & Noise  
Start-up Rise Time  
-
-
-
1
%V1  
ms  
90<VIN<264, any load conditions.  
5
85  
V1 in regulation after PS_ON is asserted  
V1 in regulation after AC is applied  
5VSB in regulation after AC is applied  
200  
750  
500  
Start-up Delay  
-
-
-
ms  
10  
10  
10  
16  
20  
35  
%V1  
%V2  
%VSB  
Turn-on Overshoot  
At 500 mA output current, V1 in regulation within 50 ms.  
-
At nominal VIN, 400 W, for all outputs  
At nominal VIN, 365 W, for all outputs  
At nominal VIN, 200 W, for all outputs  
-
-
-
-
-
-
Hold-up Time  
ms  
A
Minimum Load ***  
All models; V1, V2 and 5VSB  
0
-
-
12 V  
24 V  
36 V  
48 V  
-
-
-
-
-
-
-
-
33000  
16000  
10000  
7000  
At nominal VIN, 25 °C ambient  
Maximum Load Capacitance  
µF  
Temperature Drift  
V2 Output Voltage  
-1.2  
11.25  
-
-
12.5  
-
+1.2  
mV/°C  
V
All versions.  
Load on V2: from 5 to 1000 mA  
Load on V1: from 0.1 to 16.7 A  
13.75  
V2 Output Current  
V2 Ripple  
All models, convection/forced air cooling  
Peak-to-Peak measured at 20 MHz Bandwidth.  
All models (3% set point accuracy)  
1
240  
-
A
mV  
V
5VSB Output Voltage  
-
5
All models, convection cooling  
All models, conduction cooling / heat sink  
-
-
-
-
1.5  
2
5VSB Output Current  
A
North America  
Asia-Pacific  
Europe, Middle East  
+1 408 785 5200  
+86 755 298 85888  
+353 61 225 977  
© 2020 Bel Power Solutions & Protection  
BCD.01062_A  
4
ABS/MBS400 Series  
V1 Load: 0 33.3 A (12 V)  
0 16.7 A (24 V)  
0 11.1 A (36 V)  
0 8.3 A (48 V)  
5VSB Load-Line-Cross  
Regulation  
VAC: 90 264 VRMS  
-
-
±5  
%5VSB  
V2 Load: 0 1 A  
5VSB Load: 0 2 A  
Peak-to-Peak measured at 20 MHz Bandwidth.  
5VSB Ripple  
50  
mV  
* The combined output power of V1, V2 and 5VSB for all models, when conduction cooled or convection cooled with heat sink  
mounted, must not exceed 400 W up to 50 °C, and 300 at 70 °C ambient temperature.  
** The combined output power of V1, V2 and 5 VSB for all models, when convection cooled and VIN 180 VRMS, must not exceed  
350 W up to 50 °C, and 240 W at 70 °C ambient temperature. See de-rating curves below.  
*** When the load on the main output is less than 100 mA, V2 output voltage might regulate below its minimum value.  
Contact Bel for details.  
Sealed Box without Heatsink  
Sealed Box without Heatsink  
Figure 2. Power Derating Curves  
tech.support@psbel.com  
5
ABS/MBS400 Series  
Base signals and controls are accessible from signal connector P204.  
SIGNAL  
PS_ON  
DESCRIPTION / CONDITION  
Active low, +5 V TTL signal compatible. Input low voltage  
Input high voltage (IIN = 200 µA)  
MIN  
0
NOM  
MAX  
2.0  
-
UNIT  
-
-
V
V
3.0  
V1 and V2 disabled when PS_ON is open  
5VSB not affected by PS_ON  
V1 and V2 enabled with PS_ON connected to RTN  
+5 V TTL compatible  
P_OK  
Logic level low (<10 mA sinking)  
-
2.4  
0.05  
1
-
-
-
-
-
0.7  
5
V
V
Logic level high (100 µA sourcing)  
Low to high time after V1 in regulation  
Power down warning time  
0.1  
-
s
ms  
ms  
Active and in regulation after a 90<VAC<264 is applied  
5VSB not affected by PS_ON  
5VSB output  
-
200  
Above waveforms are expected with AC Input ON/OFF:  
Standby on - Main outputs on  
Main output Rise Time  
50 ms T1 250 ms  
5 ms T2 110 ms  
4 ms T10 20 ms  
25 ms T3 100 ms  
T4 1 ms  
5 VSB rise time  
Main outputs On P_OK delay  
Power down warning 1  
Main Output off Standby off 2  
Hold-up time (AC off P_OK low)  
AC_ON - Standby turn on time  
T5 1.2 s  
T6 15 ms (115/ 230 VAC)  
T7 500 ms  
North America  
Asia-Pacific  
Europe, Middle East  
+1 408 785 5200  
+86 755 298 85888  
+353 61 225 977  
© 2020 Bel Power Solutions & Protection  
BCD.01062_A  
6
ABS/MBS400 Series  
Above waveforms are expected with PS_ON Signal ON/OFF state change:  
Main Output Rise Time  
5 ms T2 110 ms  
25 ms T3 100 ms  
Main Outputs on P_OK delay  
Power down warning 1  
1 ms T4 5 ms  
T8 1 ms  
PS_ON - Main Output (off) Timing  
PS_ON - Main Output (on) Timing  
T9 200 ms  
1 T4 parameter measurement setup will assume at least 10% of the maximum load on each output.  
2 T5 parameter measurement setup will assume 50% of the maximum load on 5VSB  
.
PARAMETER  
Input Under Voltage  
Input Fuse  
DESCRIPTION / CONDITION  
Auto-recovering, hiccup mode.  
2x Time Lag 6.3 A, 250 V on L and N  
MIN  
60  
-
NOM  
MAX  
-
UNIT  
VAC  
A
75  
-
6.3  
At nominal input voltages.  
V1: Hiccup mode. auto-recovering.  
V2: PTC limiting, auto-recovering.  
5VSB: Hiccup mode, auto-recovering.  
At nominal input voltages.  
V1: Hiccup mode. auto-recovering.  
V2: PTC limiting, auto-recovering.  
5VSB: Hiccup mode, auto-recovering.  
12V  
Over Current  
110  
-
-
-
155  
-
%I1MAX  
Short Circuit  
Over Voltage  
24V  
48V  
110  
-
136  
%VNOM  
5VSB  
Shut down, latch-off.  
Over Temperature (on primary stage)  
Over Temperature (on secondary side)  
Shut down, latch off.  
-
-
-
-
-
-
Hiccup mode, auto-recovering.  
5660  
4000  
-
-
-
-
VDC  
VAC  
Isolation Primary to Secondary  
Reinforced (2x MoPP)  
Isolation Input to Earth  
Isolation V1 to V2  
Basic (1x MoPP)  
Functional  
1500  
100  
VAC  
VDC  
VAC  
-
-
-
-
Isolation Output to Earth  
Basic (1x MoPP)  
1500  
tech.support@psbel.com  
7
ABS/MBS400 Series  
PARAMETER  
DESCRIPTION / CONDITION  
PS starts up at -30 °C  
See graphs above for output power de-rating against TAmb and VIn.  
MIN  
-20  
-40  
-
NOM  
MAX  
70  
UNIT  
Operating Temperature Range  
Storage Temperature Range  
Humidity  
-
-
-
-
°C  
85  
°C  
RH, Non-condensing Operating  
Non-operating  
90  
95  
%
%
Operating Altitude  
-
4000  
m
EN 60068-2-27  
Shock  
Operating: Half sine, 30 g, 18 ms, 3 axes, 6x each (3 positive and 3 negative).  
Non-Operating: Half sine, 50 g, 11 ms, 3 axes, 6x each (3 positive and 3 negative).  
EN 60068-2-64  
Operating: Sine,10 500 Hz, 1 g, 3 axes, 1 oct/min., 60 min.  
Random, 5 500 Hz, 0.02 g2/Hz, 1 gRMS, 3 axes, 30 min.  
Non-Operating: 5 500 Hz, 2.46 gRMS (0.0122 g2/Hz), 3 axes, 30 min.  
Vibration  
MTBF  
Full Load, 120 VAC, 50 °C ambient 70% Duty cycle, Telcordia Issue 1 400000  
-
-
Hours  
Convection with or without heat sink and conduction providing an  
adequate thermal path between the unit and the external  
environment.  
Cooling  
Case hot spot temperature, Tc, should not exceed 90 °C in any  
working condition.  
Useful Life  
Low line range, 200 W, 40 °C ambient, natural convention.  
-
4
-
Years  
PERFORMANCE  
CLASS  
PARAMETER  
DESCRIPTION / CONDITION  
STANDARD  
115 VRMS, 230 VRMS. Maximum load.  
4 dB minimum margin  
EN 55022 (ITE)  
EN 55011 (ISM)  
Conducted  
B
EN 60601-1-2 (Medical)  
At 10 m distance  
EN 55022 (ITE)  
EN 55011 (ISM)  
Radiated  
B
EN 60601-1-2 (Medical)  
Line Voltage Fluctuation and  
Flicker  
At 20%, 50% and 100% maximum load.  
Nominal input voltages.  
EN 61000-3-3  
Nominal input voltages.  
Output load > 50 W.  
Harmonic Current Emission  
EN 61000-3-2  
C
North America  
+1 408 785 5200  
Asia-Pacific  
+86 755 298 85888  
Europe, Middle East  
+353 61 225 977  
© 2020 Bel Power Solutions & Protection  
BCD.01062_A  
8
ABS/MBS400 Series  
PARAMETER  
DESCRIPTION / CONDITION  
STANDARD  
TEST LEVEL  
CRITERIA  
Reference standard for the medical version  
EN 60601-1-2  
15 kV air discharge, 8 kV contact,  
at any point of the system.  
3 V/m, 80-1000 MHz, 1 KHz/2 Hz 80% AM.  
Dwell time is 3 sec for 2 Hz modulation  
Dwell time is 1 sec for 1KHz modulation  
±2 kV on AC power port for 1 minute;  
±1 kV on signal/control lines  
ESD  
EN 61000-4-2  
EN 61000-4-3  
EN 61000-4-4  
4
3
3
A
A
A
Radiated Field  
Electric Fast Transient  
± 2kV line to line;  
± 4 KV line to earth;  
on AC power port; ±0.5 kV for outdoor cables  
A
B
Surge  
EN 61000-4-5  
EN 61000-4-6  
3
3
Conducted RF Immunity  
3 VRMS, 0,15-80 MHz, 1 KHz/2 Hz 80% AM  
A
Dip to 30% for 5 cycle (10 ms)  
Dip to 40% for 5 cycles (100 ms)  
Dip to 70% for 25 cycles (500 ms)  
Drop-out to 5% for 10 ms  
EN61000-4-11  
EN61000-4-11  
EN61000-4-11  
EN61000-4-11  
EN61000-4-11  
A
B
B
B
B
Dips and Interruptions  
Interrupts > 95% for 5 s  
CERTIFICATION BODY SAFETY STANDARDS  
CATEGORY  
CSA C22.2 No. 60950-1, UL 60950-1; 2007, 2nd edition  
CSA C22.2 No.601.1, ANSI/AAMI ES60601-1 3rd edition  
IEC/EN 60950-1 2nd edition  
Information Technology Equipment  
Medical  
Information Technology Equipment  
CSA/UL  
IEC IECEE  
CB Certification  
IEC/EN 60601-1 3rd edition  
Low Voltage Directive (LDV) 2006/95/EC  
Low Voltage Directive (LDV) 2007/47/EC MDD  
Medical  
Information Technology Equipment  
Medical  
CE  
CONNECTIONS  
AC Input  
WIRES GAUGE AND LENGTH  
ASSIGNMENT  
Live (L)  
COLOUR/PIN  
Brown  
3x 18 AWG, black external insulation, 300 V, 105°C,  
UL2517 cord, 310 ± 10 mm extension from grommet.  
Neutral (N)  
Blue  
Protective Earth (PE)  
Green Yellow  
Red  
12 V version:  
3x (2x) +V1 Output (+V1)  
6 x 14 AWG, Style 1015, 600 V, 105°C, 260±10 mm  
24, 48 V versions:  
4x 14 AWG, Style 1015, 600 V, 105°C, 260±10 mm  
DC Output  
3x (2x) V1 Return (RTN)  
Black  
+5 V Stand-by Output (+5VSB  
Output Power Good (P_OK)  
- Fan Voltage (-V2)  
)
Red / 1  
Auxiliary Voltages  
Control Signals  
Green / 2  
Brown / 3  
Grey / 4  
Yellow / 5  
Blue / 6  
Wires: 8x 22 AWG, black external insulation, 300 V,  
105°C, UL2517 cord, 220 ± 10 mm extension from  
grommet to connector.  
Remote On/Off (PS_ON)  
Housed by Connector: Molex 90142-0008  
Terminals: Molex 90119-0109 (Tin plating)  
+ Terminal Remote Sense (+RS)  
Stand-by/Signals Return (RTN)  
+ Fan Voltage (+V2)  
Mates with Molex 90130-1106 or equivalent.  
Terminals: Tin plating termination  
White / 7  
Black / 8  
Stand-by/Signals Return (RTN)  
tech.support@psbel.com  
9
ABS/MBS400 Series  
PARAMETER  
DESCRIPTION / CONDITION  
1300 g (2.87 lb) without heatsink  
1665 g (3.67 lb) with heatsink  
Weight  
83.0 x 212.0 x 42.0 mm (3.27 x 8.34 x 1.65 in) - without heatsink  
83.0 x 212.0 x 70.1 mm (3.27 x 8.34 x 2.76 in) - with heatsink  
Overall Dimensions  
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,  
equipment used in hazardous environments, or nuclear control systems.  
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the  
date manufactured. Specifications are subject to change without notice.  
North America  
Asia-Pacific  
Europe, Middle East  
+1 408 785 5200  
+86 755 298 85888  
+353 61 225 977  
© 2020 Bel Power Solutions & Protection  
BCD.01062_A  

相关型号:

MBS400-1012

Universal input voltage range (90 – 264 VAC)
BEL

MBS400-1024

Universal input voltage range (90 – 264 VAC)
BEL

MBS400-1036

Universal input voltage range (90 – 264 VAC)
BEL

MBS400-1048

Universal input voltage range (90 – 264 VAC)
BEL

MBS40A100KI

Micro Power Resistors
ETC

MBS4991

Silicon Bidirectional Switches(Diode Thyristors)
MOTOROLA

MBS4991-18

Silicon Bilateral Switch, 10V, TO-92
MOTOROLA

MBS4991-5

10V, SILICON BILATERAL SWITCH, TO-92
MOTOROLA

MBS4992

Silicon Bidirectional Switches(Diode Thyristors)
MOTOROLA

MBS4992-18

9V, SILICON BILATERAL SWITCH, TO-92
MOTOROLA

MBS4992-5

Silicon Bilateral Switch, 9V, TO-92
MOTOROLA

MBS4993

Silicon Bidirectional Switches(Diode Thyristors)
MOTOROLA