TCP3500-1048G [BEL]

Compatible with all TCP3500 PSU models;
TCP3500-1048G
型号: TCP3500-1048G
厂家: BEL FUSE INC.    BEL FUSE INC.
描述:

Compatible with all TCP3500 PSU models

文件: 总5页 (文件大小:799K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
The TCR-4-48G power rack can be configured with four TCP3500  
Series units delivering up to 14 kW of output power. It can be  
mounted to a 19 inch rack systems using adaptor mounting brackets.  
Two internal RS485 interfaces are used for control, monitoring and  
diagnostic information that can be supplied to a system controller.  
Water cooling base plate makes the TCR-4-48G suitable for a wide  
variety of Industrial Applications where the liquid cooling is required.  
19” Rack with liquid-cooling Base Plate  
Compatible with all TCP3500 PSU models  
Maximal Configuration up to 4 Units (14 kW)  
3-phase Solid State Relay for power modules AC input driving  
Low Inductance DC output busbars construction  
Two RS485 interfaces (PSU’s Control/Monitor and Digital Control of  
Output Voltage)  
Coolant temperature (water): 0 to 35°C with minimal flow rate 2 l/min.  
(recommended 4 l/min.)  
3.2” Touch Screen Display on front panel with Smart monitoring and  
control menu  
Input and Output water temperature measurement  
Auxiliary output 24 V / 120 W  
USB Interfaces for system monitoring and control via PC and SW GUI  
2
TCR-4-48G  
Figure 1. 19” Rack rear view – AC input connector, DC output busbars, signal connectors and coolant (water) connecting  
NOMINAL  
OUTPUT  
VOLTAGE  
OUTPUT  
VOLTAGE  
RANGE  
Adjustable  
10 50 VDC  
Adjustable  
10 50 VDC  
Adjustable  
20 60 VDC  
Adjustable  
5 30 VDC  
MAX  
OUTPUT  
POWER  
INPUT VOLTAGE  
RANGE  
MAX OUTPUT  
CURRENT  
MODEL  
AVAILABILITY  
180 528 Vrms,  
50/60 Hz  
180 528 Vrms,  
50/60 Hz  
180 528 Vrms,  
50/60 Hz  
180 528 Vrms,  
50/60 Hz  
TCP3500-H048G  
TCP3500-1048G  
TCP3500-H060G  
TCP3500-1024G  
1
48 V  
48 V  
60 V  
24 V  
73 ADC or pulse1  
73 ADC  
3500 W  
3500 W  
3500 W  
3500 W  
Mass production  
Mass production  
Engineering samples  
Consult factory  
65 ADC or pulse1  
145 ADC  
PSU model with pulse load operation capability 0 100 kHz, 0 100% Duty, 0/Iout_max.  
PARAMETER  
DESCRIPTION / CONDITION  
3-phase, 3 wires + PE  
MIN  
NOM  
MAX  
UNIT  
V
Input Voltage  
Input Frequency  
Input Current  
104 - 305 / 180 - 528  
Permitted variation  
47  
63  
Hz  
per Line at 3 x 180 V (line to line)  
Adjustable or fixed (see Model Selection table)  
High Line and Low Line  
56  
Arms  
Output Voltage  
Output Power Rating  
Output Current  
Efficiency  
14  
94  
kW  
%
Fixed or Adjustable (see PSU models above)  
Typical, High Line at load above 40%  
tech.support@psbel.com  
3
TCR-4-48G  
PARAMETER  
DESCRIPTION / CONDITION  
EN55011  
SPECIFICATION  
Class A  
Radiated Emission  
Conducted Emissions  
Electrostatic Discharge  
Radiated Electromagnetic Field  
Electrical Fast Transient (EFT)/Burst  
Surge Immunity  
EN55011  
Class A  
IEC 61000-4-2  
IEC 61000-4-3  
IEC 61000-4-4  
Level 4: ±8 kV contact, ±15 kV air  
10 V/m  
Criterion B  
Criterion B  
Criterion B  
Criterion B  
Level 3: ±2/1 kV  
Level 3: ±1 kV DM, ±2 kV CM  
4.1 GUI (GRAPHIC USER INTERFACE) AND RS485 COMMUNICATION PROTOCOL  
Bel Power Solutions provides a Windows® XP/Vista/Win7 compatible SW User Interface allowing the programming and  
monitoring of the TCP3500 power supplies. The SW Utility can be downloaded from: belpowersolutions.com.  
For detailed information please see Communication Manual (BCA.00129) or contact Bel Power Solutions sales representative.  
Figure 2. SW GUI application screen shot Data logger menu  
North America  
Asia-Pacific  
Europe, Middle East  
+1 408 785 5200  
+86 755 298 85888  
+353 61 225 977  
© 2017 Bel Power Solutions & Protection  
BCD.00903_001  
4
TCR-4-48G  
PARAMETER  
Dimensions (W x D x H)  
Weight  
DESCRIPTION / CONDITION  
See Figure 2  
MIN  
NOM  
MAX  
UNIT  
mm  
482 x 670 x 110  
With 4 PSUs installed  
43  
4
kg  
Cooling  
Liquid cooled (water cooled) base plate with water flow rate  
2
l/min.  
482  
464  
10.5 x 6.5  
80  
73.5  
196  
(4x)  
31  
60  
56  
USB port  
AC input  
---------------------------  
L1+L2+L3  
Cooling water input  
---------------------------  
Threaded hole G1/8"  
or male stud coupling O10mm  
Grounding  
---------------------------  
Threaded stud M6  
SENSE connector  
---------------------------  
24V +/-  
Cooling water output  
---------------------------  
Threaded hole G1/8"  
or male stud coupling O10mm  
670 MAX  
tech.support@psbel.com  
5
TCR-4-48G  
Figure 2. Mechanical Dimensions  
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,  
equipment used in hazardous environments, or nuclear control systems.  
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on  
the date manufactured. Specifications are subject to change without notice.  
North America  
Asia-Pacific  
Europe, Middle East  
+1 408 785 5200  
+86 755 298 85888  
+353 61 225 977  
© 2017 Bel Power Solutions & Protection  
BCD.00903_001  

相关型号:

TCP3500-H048G

Compatible with all TCP3500 PSU models
BEL

TCP3500-H060G

Compatible with all TCP3500 PSU models
BEL

TCP500mA

TCP1.25A,Telecom Circuit Protector
COOPER

TCP70

70 Vdc Telecom fuses
EATON

TCP70-10-R

70Vdc Telecom fuses
COOPER

TCP70-10-R

70 Vdc Telecom fuses
EATON

TCP70-15-R

70Vdc Telecom fuses
COOPER

TCP70-15-R

70 Vdc Telecom fuses
EATON

TCP70-30-R

70Vdc Telecom fuses
COOPER

TCP70-30-R

70 Vdc Telecom fuses
EATON

TCP70-5-R

70Vdc Telecom fuses
COOPER

TCP70-5-R

70 Vdc Telecom fuses
EATON