RM4850 [CANDD]

50 AMP MODULAR SWITCHED MODE RECTIFIER; 50 AMP模块化开关式整流器
RM4850
型号: RM4850
厂家: C&D TECHNOLOGIES    C&D TECHNOLOGIES
描述:

50 AMP MODULAR SWITCHED MODE RECTIFIER
50 AMP模块化开关式整流器

开关
文件: 总4页 (文件大小:251K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Product Data Sheet  
50 AMP  
MODULAR SWITCHED MODE RECTIFIER  
RM4850  
FEATURES  
SWITCHED MODE  
• >.99 PFC  
>90% EFFICIENCY  
• AUTOMATIC LOAD SHARING  
HOT-SWAP CAPABLE  
• COMPACT SIZE  
SHELF MOUNTED  
• SOFT STARTTURN-ON  
ESDTO 20,000VOLTS  
-40°CTO 65°C FULL OPERATIONWITHOUT DERATING  
REMOTE EMERGENCY POWER DISCONNECT !  
TELECOM BULK POWER RATED!  
BELLCORE COMPLIANT  
INFINITE, FULL CURRENT SHORT CIRCUIT  
CAPABLE!  
BUILT-IN AC & DC DISCONNECTS  
FRONT PANEL METER  
DESCRIPTION  
BATTERY OR BATTERYLESS OPERATION  
INTELLIGENT HIGHVOLTAGE SHUTDOWN  
GUARANTEED NO SINGLE COMPONENT FAILURE  
CAN LEADTO OUTPUT HIGHVOLTAGE!  
GUARANTEED SAFE OPERATIONTO 300VAC  
The RM4850 Modular Switch-Mode Rectifier is one of C&D  
Technologiesfamily of rectifiers that may be used in modular  
power plants. This high power unit will function in parallel  
with any rectifier with similar current sharing capacities. This  
versatile and efficient rectifier is ideal for use in advanced  
telecommunications applications. Its small size allows the  
user to plan economically for system expansion at minimum  
cost and makes it ideal for use in fiber optic, microwave  
and other applications where space is at a premium.  
ENVIRONMENTALLY HARDENED!  
THD <5%  
AGENCY APPROVALS  
Internet: http://www.cdpowerelectronics.com  
Power Electronics Division, Europe  
C&DTechnologies (Power Electronics) Ltd.  
132 Shannon Industrial Estate, Shannon, Co. Clare, Ireland  
Power Electronics Division, United States  
3400 E Britannia Drive, Tucson, Arizona 85706  
Phone: 800.547.2537 Fax: 520.770.9369  
Tel:+353.61.474.133  
Fax:+353.61.474.141  
RM4850 4/98 REV A  
Page 1  
Input Specifications  
Parameter  
Operating Range  
Conditions  
45 - 65 Hz, single phase, no taps required  
Adjustable  
Min  
176  
0
Typ  
Max  
264  
50  
Units  
VAC  
A
Current  
Efficiency  
>90  
>.99  
%
Power Factor Correction (PFC)  
MEASUREMENTS OF RM4850  
Module  
Weight  
Height  
Depth  
25 lbs.  
7U (12.25)  
15.25”  
5”  
Width  
Shelf*  
Weight  
Height  
Depth  
Width  
18 lbs.  
7U (12.25)  
15.25maximum  
23rack mount  
* These measurements are specifically for the 200A Power Shelf for up to 4 quantity RM4850  
Please contact the factory for other shelf and power plant options.  
GENERAL FEATURES  
Hot Swappable Modules  
Current Limit  
The Current Limit is adjustable between 0A to 50A. Upon  
exceeding this limit, the rectifier automatically reduces  
output voltage.  
These shelf-mounted modules are easy and safe to install  
or remove while system is operational without affecting  
the overall systems performance.  
Safety  
Parallel Operation and Automatic Load Sharing  
Forced or passive load sharing is available between  
modules of the same operating voltages in parallel  
applications.  
UL/CUL Recognized: UL 1950/CSA 950.  
File Number: E181908  
Control Inputs  
Alarm Outputs  
High Voltage Shutdown (HVSD)  
Rectifier Fail Alarm  
Equalize Occurring  
High Voltage Occurring  
Temporary Restraint Occurring  
Thermal Shutdown Occurring  
(RFA)  
All control inputs  
are initiated with  
a ground closure  
Restart  
Equalize  
Temporary Release  
(RS)  
(EQ)  
(TR)  
(EQO)  
(HVO)  
(TRO)  
(THSD)  
}
24VAC voltage  
reference to  
ground  
Emergency Shutdown  
(EMSD)  
Open Sense Lead Has Occurred (OS)  
Low Current Alarm  
}
(LCA)  
AC Power Has Failed Alarm  
Rectifier Fan Has Failed Alarm  
DC Breaker Is Open Alarm  
AC Breaker Is Open Alarm  
(ACF)  
(FF)  
(DCBKR)  
(ACBKR)  
Note:All alarms are Form Arelay type contacts  
RM4850 4/98 REV A  
Page 2  
Output Specifications  
Parameter  
Conditions  
Min  
Typ  
Max  
Units  
Voltage Adjustment Range  
float voltage  
equalize voltage  
48  
48  
60  
60  
VDC  
VDC  
Regulation  
0-100% load within  
specified input voltage and frequency range  
within a 10 - 100% rating  
nominal AC line  
0.5  
10  
%
%
Load Current  
Hold-UpTime  
Filtering  
>16  
mS  
Voice band  
<32  
dBrnc  
Wide band noise  
@20 MHz  
<250  
mV p-p  
ENVIRONMENTAL  
Temperature  
Operating  
-40  
-40  
-50  
-58  
0
+65  
149  
+85  
185  
95  
°C  
°F  
Storage  
°C  
°F  
Humidity  
Altitude  
non-condensing  
%
0
7000  
2133  
ft.  
0
m
Heat Dissipation  
Audible Noise  
@54V  
1025  
Btu/hr  
dBa  
5 ft. from any vertical surface  
<55  
PROTECTION, ALARM AND CONTROL SYSTEMS  
Rectifier Failure Alarm (RFA)  
High Voltage Shutdown (HVSD)  
Problems occurring because of an unacceptable relation-  
ship between the output power and load conditions will  
cause a Rectifier Failure Alarm (RFA). Conditions which  
may lead to an RFA include:  
Low Current - Output current has decreased to below  
5% of its rated value.  
The units high voltage limit is adjustable up to 60VDC.  
Shutdown occurs while voltage is high and the rectifier is  
delivering greater than 10% rated current. When internal  
shutdown occurs, the unit may be restarted by a local  
switch or by a remote signal.  
Unit Shutdown - Any shutdown occurrence due to  
overvoltage, external shutdown command, unacceptable  
ambient temperature conditions or out of bounds AC input  
voltage.  
Surge Protection  
The unit will withstand lightning and input surges of  
6000V/3000A.  
Fan Malfunction - The fan has stopped operating or is  
not providing the airflow needed to cool the unit.  
Over Temperature - The ambient temperature has  
exceeded 65°C.  
Under Voltage Protection  
When input voltage is below 176 VAC, the rectifiers  
operation is automatically inhibited.  
RM4850 4/98 REV A  
Page 3  
Mechanical  
All measurements are in inches  
Standard Options are shown, consult factory for other available options.  
The information provided herein is believed to be reliable; however, C&D Technologies assumes no responsibility for inaccuracies or omissions. C&D Technologies assumes  
no responsibility for the use of this information, and all use of such information shall be entirely at the users own risk. Prices and specifications are subject to change without  
notice. No patent rights or licenses to any of the circuits described herein are implied or granted to any third party. C&D Technologies does not authorize or warrant any C&D  
Technologies product for use in life support devices/systems or in aircraft control applications.  
RM4850 4/98 REV A  
Page 4  

相关型号:

RM48600L2RGR

ULTRA-R2 48X600 GRAY RUBBER MAT
ETC

RM4875

7.5 AMP Modular Switch Mode Rectifier
CANDD

RM48L530

16/32 位 RISC 闪存微控制器
TI

RM48L530DPGET

16/32 位 RISC 闪存微控制器 | PGE | 144 | -40 to 105
TI

RM48L530PGE

RISC MICROCONTROLLER
TI

RM48L530PGET

RM48Lx30 16/32-Bit RISC Flash Microcontroller
TI

RM48L530ZWT

暂无描述
TI

RM48L540

16/32 位 RISC 闪存微控制器
TI

RM48L540DPGET

16/32 位 RISC 闪存微控制器 | PGE | 144 | -40 to 105
TI

RM48L540DPGETR

RM48Lx40 16- and 32-Bit RISC Flash Microcontroller
TI

RM48L540DZWTT

16/32-Bit RISC Flash Microcontroller 337-NFBGA -40 to 105
TI

RM48L540PGE

RISC MICROCONTROLLER
TI