RM4850 [CANDD]
50 AMP MODULAR SWITCHED MODE RECTIFIER; 50 AMP模块化开关式整流器型号: | RM4850 |
厂家: | C&D TECHNOLOGIES |
描述: | 50 AMP MODULAR SWITCHED MODE RECTIFIER |
文件: | 总4页 (文件大小:251K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Product Data Sheet
50 AMP
MODULAR SWITCHED MODE RECTIFIER
RM4850
FEATURES
•
SWITCHED MODE
• >.99 PFC
>90% EFFICIENCY
• AUTOMATIC LOAD SHARING
•
•
HOT-SWAP CAPABLE
• COMPACT SIZE
•
SHELF MOUNTED
• SOFT STARTTURN-ON
•
•
ESDTO 20,000VOLTS
-40°CTO 65°C FULL OPERATIONWITHOUT DERATING
•
REMOTE EMERGENCY POWER DISCONNECT !
•
•
•
TELECOM BULK POWER RATED!
BELLCORE COMPLIANT
INFINITE, FULL CURRENT SHORT CIRCUIT
CAPABLE!
•
•
•
•
•
BUILT-IN AC & DC DISCONNECTS
FRONT PANEL METER
DESCRIPTION
BATTERY OR BATTERYLESS OPERATION
INTELLIGENT HIGHVOLTAGE SHUTDOWN
GUARANTEED NO SINGLE COMPONENT FAILURE
CAN LEADTO OUTPUT HIGHVOLTAGE!
GUARANTEED SAFE OPERATIONTO 300VAC
The RM4850 Modular Switch-Mode Rectifier is one of C&D
Technologies’family of rectifiers that may be used in modular
power plants. This high power unit will function in parallel
with any rectifier with similar current sharing capacities. This
versatile and efficient rectifier is ideal for use in advanced
telecommunications applications. Its small size allows the
user to plan economically for system expansion at minimum
cost and makes it ideal for use in fiber optic, microwave
and other applications where space is at a premium.
•
•
•
ENVIRONMENTALLY HARDENED!
THD <5%
AGENCY APPROVALS
Internet: http://www.cdpowerelectronics.com
Power Electronics Division, Europe
C&DTechnologies (Power Electronics) Ltd.
132 Shannon Industrial Estate, Shannon, Co. Clare, Ireland
Power Electronics Division, United States
3400 E Britannia Drive, Tucson, Arizona 85706
Phone: 800.547.2537 Fax: 520.770.9369
Tel:+353.61.474.133
Fax:+353.61.474.141
RM4850 4/98 REV A
Page 1
Input Specifications
Parameter
Operating Range
Conditions
45 - 65 Hz, single phase, no taps required
Adjustable
Min
176
0
Typ
Max
264
50
Units
VAC
A
Current
Efficiency
>90
>.99
%
Power Factor Correction (PFC)
MEASUREMENTS OF RM4850
Module
Weight
Height
Depth
25 lbs.
7U (12.25”)
15.25”
5”
Width
Shelf*
Weight
Height
Depth
Width
18 lbs.
7U (12.25”)
15.25”maximum
23” rack mount
* These measurements are specifically for the 200A Power Shelf for up to 4 quantity RM4850
Please contact the factory for other shelf and power plant options.
GENERAL FEATURES
Hot Swappable Modules
Current Limit
The Current Limit is adjustable between 0A to 50A. Upon
exceeding this limit, the rectifier automatically reduces
output voltage.
These shelf-mounted modules are easy and safe to install
or remove while system is operational without affecting
the overall system’s performance.
Safety
Parallel Operation and Automatic Load Sharing
Forced or passive load sharing is available between
modules of the same operating voltages in parallel
applications.
UL/CUL Recognized: UL 1950/CSA 950.
File Number: E181908
Control Inputs
Alarm Outputs
High Voltage Shutdown (HVSD)
Rectifier Fail Alarm
Equalize Occurring
High Voltage Occurring
Temporary Restraint Occurring
Thermal Shutdown Occurring
(RFA)
All control inputs
are initiated with
a ground closure
Restart
Equalize
Temporary Release
(RS)
(EQ)
(TR)
(EQO)
(HVO)
(TRO)
(THSD)
}
24VAC voltage
reference to
ground
Emergency Shutdown
(EMSD)
Open Sense Lead Has Occurred (OS)
Low Current Alarm
}
(LCA)
AC Power Has Failed Alarm
Rectifier Fan Has Failed Alarm
DC Breaker Is Open Alarm
AC Breaker Is Open Alarm
(ACF)
(FF)
(DCBKR)
(ACBKR)
Note:All alarms are “Form A” relay type contacts
RM4850 4/98 REV A
Page 2
Output Specifications
Parameter
Conditions
Min
Typ
Max
Units
Voltage Adjustment Range
float voltage
equalize voltage
48
48
60
60
VDC
VDC
Regulation
0-100% load within
specified input voltage and frequency range
within a 10 - 100% rating
nominal AC line
0.5
10
%
%
Load Current
Hold-UpTime
Filtering
>16
mS
Voice band
<32
dBrnc
Wide band noise
@20 MHz
<250
mV p-p
ENVIRONMENTAL
Temperature
Operating
-40
-40
-50
-58
0
+65
149
+85
185
95
°C
°F
Storage
°C
°F
Humidity
Altitude
non-condensing
%
0
7000
2133
ft.
0
m
Heat Dissipation
Audible Noise
@54V
1025
Btu/hr
dBa
5 ft. from any vertical surface
<55
PROTECTION, ALARM AND CONTROL SYSTEMS
Rectifier Failure Alarm (RFA)
High Voltage Shutdown (HVSD)
Problems occurring because of an unacceptable relation-
ship between the output power and load conditions will
cause a Rectifier Failure Alarm (RFA). Conditions which
may lead to an RFA include:
Low Current - Output current has decreased to below
5% of its rated value.
The unit’s high voltage limit is adjustable up to 60VDC.
Shutdown occurs while voltage is high and the rectifier is
delivering greater than 10% rated current. When internal
shutdown occurs, the unit may be restarted by a local
switch or by a remote signal.
Unit Shutdown - Any shutdown occurrence due to
overvoltage, external shutdown command, unacceptable
ambient temperature conditions or out of bounds AC input
voltage.
Surge Protection
The unit will withstand lightning and input surges of
6000V/3000A.
Fan Malfunction - The fan has stopped operating or is
not providing the airflow needed to cool the unit.
Over Temperature - The ambient temperature has
exceeded 65°C.
Under Voltage Protection
When input voltage is below 176 VAC, the rectifier’s
operation is automatically inhibited.
RM4850 4/98 REV A
Page 3
Mechanical
All measurements are in inches
Standard Options are shown, consult factory for other available options.
The information provided herein is believed to be reliable; however, C&D Technologies assumes no responsibility for inaccuracies or omissions. C&D Technologies assumes
no responsibility for the use of this information, and all use of such information shall be entirely at the user’s own risk. Prices and specifications are subject to change without
notice. No patent rights or licenses to any of the circuits described herein are implied or granted to any third party. C&D Technologies does not authorize or warrant any C&D
Technologies product for use in life support devices/systems or in aircraft control applications.
RM4850 4/98 REV A
Page 4
相关型号:
©2020 ICPDF网 联系我们和版权申明