RM4875 [CANDD]

7.5 AMP Modular Switch Mode Rectifier; 7.5 AMP模块开关模式整流器
RM4875
型号: RM4875
厂家: C&D TECHNOLOGIES    C&D TECHNOLOGIES
描述:

7.5 AMP Modular Switch Mode Rectifier
7.5 AMP模块开关模式整流器

开关
文件: 总4页 (文件大小:168K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Product Data Sheet  
7.5 AMP  
MODULAR SWITCH MODE RECTIFIER  
RM487.5  
FEATURES  
• SWITCH MODE  
• >.99 PFC  
>84% EFFICIENCY  
• AUTOMATIC LOAD SHARING  
• HOT-SWAP CAPABLE  
• COMPACT SIZE  
• SHELF MOUNTED  
• SOFT STARTTURN-ON!  
• TELECOM BULK POWER RATED  
• BELLCORE COMPLIANT  
DESCRIPTION  
The RM487.5 Modular Switch-Mode Rectifier is one of C&D  
Technologies’ family of rectifiers that may be used in  
modular power plants. This unit will function in parallel  
with any rectifier with similar current sharing capacities.  
This compact, versatile and efficient unit is ideal for use in  
advanced telecommunications applications. Its small size  
allows the user to plan economically for system expansion  
at minimum cost and makes it ideal for use in fiber optic,  
microwave and other applications where space is at a  
premium.  
µPROCESSOR INTELLIGENCE ALLOWS  
EXPANSIONTO REMOTE CONTROL FEATURES  
• INFINITE, FULL CURRENT SHORT CIRCUIT  
CAPABLE  
• THD <5%  
AGENCY APPROVALS PENDING  
Internet: http://www.cdpowerelectronics.com  
Power Electronics Division, United States  
3400 E Britannia Drive, Tucson, Arizona 85706  
Phone: 800.547.2537 Fax: 520.770.9369  
Power Electronics Division, Europe  
C&DTechnologies (Power Electronics) Ltd.  
132 Shannon Industrial Estate, Shannon, Co. Clare, Ireland  
Tel:+353.61.474.133  
Fax:+353.61.474.141  
RM4875 4/98 REV A  
Page 1  
Input Specifications  
Parameter  
Operating Range  
Current  
Conditions  
45 - 65 Hz, single phase, no taps required  
Min  
106  
Typ  
Max  
264  
Units  
VAC  
106VAC  
208VAC  
240VAC  
4.6  
2.55  
2.12  
84  
A
A
A
Efficiency  
%
Power Factor Correction (PFC)  
>.99  
MEASUREMENTS OF RM4875  
Module  
Weight  
2.88 lbs.  
2.4”  
Height  
Depth  
Width  
11.0”  
4.75”  
Shelf*  
Weight  
Height  
Depth  
Width  
15.5 lbs.  
3.5with rectifiers mounted in shelf  
12maximum  
23rack mount  
*These measurements are specifically for the AGM25 List 1 up to 8 quantity RM 487.5.  
Please contact factory for other shelf and power plant options.  
GENERAL FEATURES  
Hot Swappable Modules  
Current Limit  
Upon reaching 110% of rated current, the rectifier will  
automatically limit the current down to short circuit  
conditions with no fold back.  
These shelf-mounted modules are easy and safe to install  
or remove while system is operational without affecting  
the overall systems performance.  
Safety  
Parallel Operation and Automatic Load Sharing  
Forced share connection is made via a hard wire. Sharing  
is within 10% of the average current for the load applied.  
UL/CUL Approved: UL 1950/CSA 950.  
File Number: E131694  
Status Indicator  
RFA  
Remote Control  
Equalize  
Front Panel Current Test Jacks  
Normal  
Remote Control Enable Signal  
The rectifiers output voltage control may be changed from  
internal float and equalize pots to external remote control  
though a digital ground signal.  
RM4875 4/98 REV A  
Page 2  
Output Specifications  
Parameter  
Conditions  
Min  
Typ  
Max  
Units  
Voltage Adjustment Range  
float voltage  
equalize voltage  
48  
52  
56  
60  
VDC  
VDC  
Regulation  
0-100% load within  
specified input voltage and frequency range  
within a 10 - 100% rating  
nominal AC line  
.5  
%
%
Load Current  
Hold-UpTime  
Filtering  
10  
>16  
mS  
Voice band  
<32  
dBrnc  
Wide band noise  
@ 20 MHz  
<250  
mV p-p  
ENVIRONMENTAL  
Temperature  
Operating  
-40  
-40  
-50  
-58  
0
+65  
149  
+85  
185  
95  
°C  
°F  
Storage  
°C  
°F  
Humidity  
Altitude  
non-condensing  
%
0
7000  
2133  
ft.  
0
m
Heat Dissipation  
Audible Noise  
@54V  
264  
Btu/hr  
dBa  
5 ft. from any vertical surface  
<55  
PROTECTION, ALARM AND CONTROL SYSTEMS  
Rectifier Failure Alarm (RFA)  
High Voltage Shutdown (HVSD)  
Problems occurring because of an unacceptable relation-  
ship between the output power and load conditions will  
cause a Rectifier Failure Alarm (RFA).This alarm consists  
of a red LED and a flashing green OK LED. Conditions  
which may lead to an RFA are:  
The units built-in high voltage limit is permanently set at  
60V. When internal shutdown occurs, the unit may be  
restarted by a local switch or by a remote signal.  
Surge Protection  
Low Current - Output current has decreased to below  
5% of its rated value.  
The unit will withstand lightning and input surges of  
6000V/3000A.  
Unit Shutdown - Any shutdown occurrence due to  
overvoltage, external shutdown command, unacceptable  
ambient temperature conditions or low AC input voltage.  
Load Sharing Terminal Pin Out Of Range - The  
terminal pin is out of range.  
Under Voltage Protection  
When input voltage is below 105 VAC, the rectifiers  
operation is automatically power limited.  
Remote ControlTerminal Out Of Range - The remote  
control terminal pins are out of range.  
Line Sag - This condition occurs when the nominal  
voltage decreases below 180V. Normal range is 208-  
240V.  
Fan Malfunction - The fan has stopped operating or is  
not providing the airflow needed to cool the unit.  
Over Temperature - The ambient temperature has  
exceeded 65°C.  
RM4875 4/98 REV A  
Page 3  
Mechanical  
ALL MEASUREMENTS ARE IN INCHES  
2.90  
I+  
EQL  
FLT  
REM  
EQL  
2.400  
NORM  
RFA  
OFF  
I-  
HFM 48-7.5  
10.955  
4.750  
Standard Options are shown, consult factory for other available options.  
The information provided herein is believed to be reliable; however, C&D Technologies assumes no responsibility for inaccuracies or omissions. C&D Technologies assumes no  
responsibility for the use of this information, and all use of such information shall be entirely at the users own risk. Prices and specifications are subject to change without notice. No  
patent rights or licenses to any of the circuits described herein are implied or granted to any third party. C&D Technologies does not authorize or warrant any C&D Technologies product  
for use in life support devices/systems or in aircraft control applications.  
RM4875 4/98 REV A  
Page 4  

相关型号:

RM48L530

16/32 位 RISC 闪存微控制器
TI

RM48L530DPGET

16/32 位 RISC 闪存微控制器 | PGE | 144 | -40 to 105
TI

RM48L530PGE

RISC MICROCONTROLLER
TI

RM48L530PGET

RM48Lx30 16/32-Bit RISC Flash Microcontroller
TI

RM48L530ZWT

暂无描述
TI

RM48L540

16/32 位 RISC 闪存微控制器
TI

RM48L540DPGET

16/32 位 RISC 闪存微控制器 | PGE | 144 | -40 to 105
TI

RM48L540DPGETR

RM48Lx40 16- and 32-Bit RISC Flash Microcontroller
TI

RM48L540DZWTT

16/32-Bit RISC Flash Microcontroller 337-NFBGA -40 to 105
TI

RM48L540PGE

RISC MICROCONTROLLER
TI

RM48L540PGET

RM48Lx40 16/32-Bit RISC Flash Microcontroller
TI

RM48L540ZWT

RM48Lx40 16- and 32-Bit RISC Flash Microcontroller
TI