AC Current Transformer (max 64x20 mm bus-bar)  
Type CTD-4X  
Bus-bar type current transformer  
0.5 class, currents from 150 to 1600 A  
Removable panel fixing clips  
Up to 6 Bus-bar isolated fixing screws  
Double screw terminals (up to 8-wire connections)  
Sealable terminal block covers  
Product Description  
Ordering Key  
CTD-4X 1250 5A XXX  
Cable/Bus-bar type current Rated primary currents from Model  
transformer with DIN-rail/bus- 150 A to 1600 A.  
bar and panel mounting  
facility.  
Primary current  
Secondary current  
Option  
Optional fixing kit:  
CTD-kit  
Type Selection  
Primary current  
Secondary current  
Option  
From 150 to 1600A  
(Refer to Range Table)  
1A  
5A  
XXX: none  
XTX: tropicalization  
Input Specifications  
Operating frequency  
Max. system voltage  
Rated insulation level  
Insulation class  
Short-time current rating  
Ith  
Idyn  
45 to 65 Hz  
0.72 kV  
3 kV/1 min. @ 50 Hz  
E (max 75°C)  
Six plastic caps for  
cable/bus-bar fixing screws  
Special features  
1 A secondary current,  
Tropicalization  
-25°C to: refer to Range Table  
(-13°F to: refer to Range  
Table) (R.H. < 90% non  
condensing @ 40°C)  
-30°C to +70°C (-22°F to  
158°F) (R.H. < 90% non  
condensing @ 40°C)  
Working temperature  
Typical 100 In /1 s  
2.5 Ith  
The short-time thermal  
current Ith is anyway limited  
by the cable/bus-bar size  
Refer to Range Table  
5 (Class: 0.5, 1 and 3)  
Storage temperature  
Approvals  
Connection  
Cable cross section area  
Extended current rating  
Security factor (FS)  
CE, cURus and CSA  
Screw type  
From 1.5 to 6 mm2  
Min/Max screws tightening  
torque relevant to terminal block  
screws: From 1 to 2 Nm  
Max screws tightening torque  
relevant to the cable/bus-bar  
fixing screws: 0,3 Nm  
General Specifications  
Standards  
Housing  
According to EN61869-2  
PA66, self-extinguishing:  
UL 94 V-0  
Mounting  
Standard accessories  
Panel mounting  
Protection degree  
Cable diameter  
Bus-bar size  
Horizontal  
Vertical  
IP00  
IP20 (with sealable terminal  
block covers + wire terminals)  
Two terminal block screws.  
Two cable/bus-bar  
fixing screws.  
Two plastic caps for  
cable/bus-bar fixing screws.  
Two panel mounting fixing  
clips.  
Two sealable terminal block  
covers.  
Max. 51 mm  
Max. 64x20, 51x43 mm  
Max. 51x31 mm  
From 450 to 700 g  
Weight  
Optional accessories  
Extended fixing kit: CTD-kit  
Two panel mounting  
fixing clips.  
Six cable/bus-bar fixing  
screws.  
Output Specifications  
Rated secondary current  
5 A or 1 A  
Specifications are subject to change without notice CTD-4X DS ENG 230518  
1
CTD-4X  
Range Table  
Model CTD-4X from 150A to 700A  
Model CTD-4X from 750A to 1600A  
Extended  
Primary  
Current  
Extended  
Primary  
Current  
Temperature  
Burden (VA)  
CL 0.5 CL 1 CL3  
Temperature  
Burden (VA)  
current rating  
current rating  
CL  
0.5  
CL  
1
CL  
5P5  
A
A
150  
200  
250  
300  
400  
500  
600  
700  
(@60°C/140°F)  
(@60°C/140°F)  
(@60°C/140°F)  
(@60°C/140°F)  
(@60°C/140°F)  
(@60°C/140°F)  
(@60°C/140°F)  
(@60°C/140°F)  
120%  
120%  
120%  
120%  
120%  
120%  
120%  
120%  
2.5  
3.25  
4.5  
4
(5)  
(6)  
2
750  
800  
(@50°C/122°F)  
(@50°C/122°F)  
(@50°C/122°F)  
(@50°C/122°F)  
(@50°C/122°F)  
(@50°C/122°F)  
(@50°C/122°F)  
120%  
120%  
13  
14  
15.5  
16.5  
20  
5
5
6
6
6
8
8
2.5  
3
1000  
1200  
1250  
1500  
1600  
120%  
17.5  
20  
3
100% (+)  
100% (+)  
100% (*)  
100% (*)  
22.5  
22.5  
30  
6
9
3
20  
10  
11  
12.5  
12.5  
13.5  
15  
4
27.5  
27.5  
4
30  
5
(*) A max overload of 120% for 1 min. every 30 min. is allowed.  
(+) A continuous overload of 120% of the range is allowed @ amb.  
temp. 40°C max.  
Benefits  
1
2
3
4
5
6
7
8
9
• Easy and quick mounting on a panel (see  
figure 1).  
Dimensions (mm)  
• Protection of screw terminals using specific  
sealable covers to assure always the best  
safety (see figure 3).  
63  
30  
• Bridging of current transformer output  
without changing the connection of the  
secondary, so to avoid any output  
overvoltage during either the maintenance or  
the installation procedure (see figure 4).  
• Easy output and earth connection (see fig. 5).  
• Screw terminals compatible with any kind of  
wire terminals (see figure 6-7-8-9).  
φ 51  
• Multiple screws provided with isolation cap  
screws to grant a strong and reliable fixing of the  
current transformer to the bus-bar (see figure 10).  
45  
Wiring Diagram  
S1  
S2  
31  
51  
64  
42  
81,2  
90  
L
P1  
P2  
N
2
Specifications are subject to change without notice CTD-4X DS ENG 230518  

相关型号:

CTD-4X12505AXXX

Accessories AC Current Transformer
CARLOGAVAZZI

CTD-55S4001AXTX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI

CTD-55S4001AXXX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI

CTD-55S4005AXTX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI

CTD-55S4005AXXX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI

CTD-6S10001AXTX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI

CTD-6S10001AXXX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI

CTD-6S10005AXTX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI

CTD-6S10005AXXX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI

CTD-8S15001AXTX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI

CTD-8S15001AXXX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI

CTD-8S15005AXTX

Accessories AC Split-Core Current Transformer
CARLOGAVAZZI