EM280  
Multi-channel power analyzer  
Benefits  
Reduced installation time and errors. Equipped with  
detachable terminals for all connections, with possibility  
of requesting pre-wired cables (optional). Connected to  
the 6-channel current transformer block with two cables  
fitted with RJ-11 connectors. For connections in cascade  
of multiple EM280s the voltage reference is required  
once only.  
Compact dimensions. It uses a compact current  
transformer block (TCD06BS or TCD06BX) that performs  
the function of six transformers, observing the standard  
dimensions of the switches for DIN rails.  
Installation flexibility. It can be installed in new or  
existing single- and three-phase systems. Suitable for  
panel or DIN rail mounting .  
Description  
Granular analysis. It provides total measurements or  
single load measurements (up to 2 three-phase loads or  
up to 6 single-phase loads).  
Specific software. The UCS proprietary configuration  
software enables rapid configuration and the display  
of all measurements. The software and subsequent  
updates are free.  
Multi-channel power analyzer for single or three-  
phase systems installable on panels or DIN rails.  
Manages current input up to 32 A via a 6-channel  
current transformer block (TCD06BS with split  
core or TCD06BX with solid core) connected with  
RJ-11 connectors.  
The EM280 is equipped with a LCD display with  
controls to display measurements and configure  
the system, a RS485 port and two pulse outputs  
or two RS485 ports for daisy chain connections.  
Thanks to the SUM function, it also displays total  
load consumption values.  
Tamper-proof. Configuration access can be locked. The  
terminals and display can be sealed.  
Applications  
EM280 is connected directly on output from the switches present in switchboards for simultaneous monitoring  
of multiple single- or three-phase loads in low voltage systems.  
Created for both commercial and industrial environments (e.g. data centers), this device guarantees quick and  
space-saving installations with just a few simple connections.  
Suitable for new installations with little space available (using the transformer block TCD06BX), and for existing  
or new installations where more installation flexibility is required (using transformer block TCD06BS).  
Main functions  
Measurement of energy consumption and main electrical variables of single- or three-phase loads.  
Display of single load measurements and total measurements  
Transmission of data via serial communication.  
Transmission of power consumption via pulse output (optional).  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
1
EM280  
Architecture (example with transformer block TCD06BX)  
Main features  
Up to 2 three-phase loads or 6 single-phase loads managed simultaneously.  
Up to 32 A input current via 6-channel transformer block TCD06BS or TCD06BX.  
Three installation configurations: on DIN rails, mounted on panel of 72 x 72 or 96 x 96 (with optional adapter).  
Single load measurements: V, A, W/VA/var, kWh, kvarh. Total load measurements: W/VA/var, kWh, kvarh.  
Display of electrical variables: 3 digits. Display of energy meters: 7 digits.  
Accuracy: better than a combination of a class 1 meter and a class 0.5 current transformer.  
Easy connection function.  
Up to 20 EM280 connected in cascade.  
RS485 port.  
Optional outputs: additional RS485 port for chain connection or two pulse outputs.  
Self power supply via voltage inputs.  
Detachable terminals and sealable terminal caps.  
Configuration via keypad or UCS configuration software.  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
2
EM280  
Structure  
A
B
C
D
E
F
G
H
I
Area  
A
B
Description  
RJ-11 connector for connection to transformer block.  
Power supply status LED.  
C
Detachable voltage input terminals.  
D
E
Area for mounting on DIN rail or for housing the LCD display in the case of panel mounting.  
LCD display and controls.  
F
G
H
LED that blinks with frequency proportional to active energy consumption, see "LED features".  
Rotary selector to lock configuration.  
RS485 port terminals and pulse outputs.  
I
Plastic protection cover or terminals for voltage connection in cascade.  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
3
EM280  
Features  
General  
Material  
Protection degree  
Noryl, self-extinguishing V-0 (UL 94)  
Front: IP40, Terminals: IP20  
Type: detachable  
Maximum section: 1.5 mm2, Torque: 0.2/0.25 Nm  
Terminals  
Overvoltage category  
Pollution degree  
Cat. III  
2
Noise rejection (CMRR) 100 dB, from 48 to 62 Hz  
Insulation  
Mounting  
Weight  
See "Input and output insulation"  
DIN rail  
Panel 72 x 72, Panel 96 x 96 (with optional adapter)  
400 g (packaging included)  
Fig. 1 DIN rail  
Fig. 2 Panel 72 x 72  
Environmental specifications  
Operating temperature  
Storage temperature  
From -25 to +55 °C/from -13 to +131 °F  
From -30 to +70 °C/from -22 to +158 °F  
NOTE: R.H. < 90 % non-condensing @ 40 °C / 104 °F.  
Input and output insulation  
Voltage input and self  
Current input (TCD06B  
Pulse out-  
puts  
Type  
RS485 port  
Double **  
Double **  
power supply  
output)  
Voltage input and self  
power supply  
Current input (TCD06B  
output)  
-
Reinforced *  
Double **  
Double **  
Reinforced *  
-
Pulse outputs  
RS485 port  
Double **  
Double **  
Double **  
Double **  
-
-
-
-
*By limiting impedance  
**2.5 kV ac 1 min (4 kV pk 1.2/50 µs)+ limiting impedance  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
4
EM280  
Conformity  
2014/35/EU (LVT - Low Voltage)  
Directives  
2014/30/EU (EMC - Electro Magnetic Compatibility)  
2011/65/EU (Electric-electronic equipment hazardous substances)  
Electromagnetic compatibility (EMC) - emissions and immunity: EN62052-11  
Electrical safety: EN61010-1  
Pulse outputs: IEC62053-31, DIN43864  
Standards  
Approvals  
Electrical specifications  
Electrical system and loads  
Single-phase (2-wire)  
Three-phase without neutral (3-wire)  
Three-phase with neutral (4-wire)  
Managed electrical  
system  
Number of loads man-  
Single-phase systems: up to 6 single-phase loads  
aged  
Three-phase systems: up to 2 three-phase loads or up to 6 single-phase loads  
Voltage inputs  
MV5  
MV6  
Voltage connection  
Direct  
Rated voltage L-N (from  
Un min to Un max)  
Rated voltage L-L (from  
Un min to Un max)  
From 160 to 240 V  
From 277 to 415 V  
From 57.7 to 133 V  
From 100 to 230 V  
Voltage tolerance  
-15%, +10%  
Continuous: 1.2 Un max  
For 500 ms: 2 Un max  
Overload  
Input impedance  
Frequency  
1600 kΩ  
From 45 to 65 Hz  
Current inputs  
Current connection  
Primary current  
Rated current (In)  
Via transformer block TCD06BS or TCD06BX  
Automatic setting of primary current of connected TCD06B  
32 A (primary current of TCD06BS or TCD06BX)  
Minimum current (lmin) 0.02 In  
Maximum current (lmax) 1.2 In  
Start-up current (lst)  
0.002 In  
Continuous: 1.2 In  
For 500 ms: 2 In  
Overload  
Input impedance  
< 0.2 VA  
Power supply  
Power supply  
Consumption  
Self powered, between L2 and L3  
2 W, ≤ 4 VA  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
5
EM280  
Measurements  
Method  
Sampling  
TRMS measurements of distorted waveforms  
1600 samples/s @50 Hz  
1900 samples/s @60 Hz  
Available measurements  
Three-phase loads  
Energy  
Active imported  
Reactive imported  
Phase 1  
Phase 2  
Phase 3  
Current  
Phase-phase  
Phase-neutral  
Voltage  
Total load  
Active power  
Average (dmd)  
Maximum dmd  
Total load  
Apparent power  
Reactive power  
Average (dmd)  
Maximum dmd  
Total load  
Single-phase loads  
Energy  
Current  
Voltage  
Active  
Phase  
Phase-neutral  
Total load  
Active power  
Average (dmd)  
Maximum dmd  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
6
EM280  
Measurement accuracy  
EM280  
Current  
From 0.05 In to Imax  
From 0.02 In to 0.05 In  
±(0.5% rdg)  
±(1.0% rdg)  
Phase-phase voltage  
Phase-neutral voltage  
Active power (PF=1)  
From (Un min -10%) to (Un  
max +10%)  
±(0.5% rdg)  
±(1% rdg)  
From (Un min -10%) to (Un  
max +10%)  
From 0.05 In to Imax  
From 0.02 In to 0.05 In  
±(1% rdg)  
±(1.5% rdg)  
Active power (PF=0.5L, 0.8C)  
Reactive power (sinϕ=1)  
From 0.1 In to Imax  
From 0.05 In to 0.1 In  
±(1% rdg)  
±(1.5% rdg)  
From 0.05 In to Imax  
From 0.02 In to 0.05 In  
±(2% rdg)  
±(2.5% rdg)  
Reactive power (sinϕ=0.5 L or C)  
Reactive power (sinϕ=0.25 L o C)  
From 0.1 In to Imax  
From 0.05 In to 0.1 In  
±(2% rdg)  
±(2.5% rdg)  
From 0.1 In to Imax  
±(2.5% rdg)  
Active energy  
Equivalent to class 1 (EN62053-21)  
Reactive energy  
Equivalent to class 2 (EN62053-23)  
Frequency  
From 45 to 65 Hz  
±1 Hz  
EM280+TCD06BX or EM280+TCD06BS  
Current  
From 0.2 In to Imax  
From 0.05 to 0.2 In  
From 0.02 In to 0.05 In  
±(0.75% rdg)  
±(1% rdg)  
±(1.25% rdg)  
Active power (PF=1)  
Reactive power (sinϕ=1)  
From 0.2 In to Imax  
From 0.05 to 0.2 In  
From 0.02 In to 0.05 In  
±(1.25% rdg)  
±(1.5% rdg)  
±(2% rdg)  
From 0.2 In to Imax  
From 0.05 to 0.2 In  
From 0.02 In to 0.05 In  
±(2.25% rdg)  
±(2.5% rdg)  
±(3% rdg)  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
7
EM280  
Display  
Type  
Refresh time  
LCD  
1 s  
2 rows:  
Description  
1st: 7 digits (7 mm)  
2nd: 3 digits (7 mm)  
Electrical variables: 3 digits, min: 0.00, max: 999  
Energy meters: 7 digits, min: 0.0, max: 9 999 999  
Variable readout  
Digital outputs  
Connection type  
Detachable terminals  
Maximum number of  
outputs  
2
Type  
Opto-mosfet  
Pulse output. Each output transmits the consumption of a single three-phase load or the total  
consumption of three single-phase loads.  
Function  
VON: 2.5 V ac/dc, 70 mA max  
VOFF: 40 V ac/dc max  
Features  
Configuration param-  
Pulse weight (from 0.01 to 9.99 kWh per pulse)  
eters  
Pulse duration (40 or 100 ms)  
Configuration mode  
Via keypad or UCS software  
RS485 port  
Protocol  
Modbus RTU  
Devices on the same  
bus  
Max 160 (1/5 unit load)  
Communication type  
Connection type  
Multidrop, bidirectional  
Detachable terminals, 2 wires, maximum distance 1000 m  
Modbus address (from 1 to 247)  
Baud rate (9.6 / 19.2 / 38.4 kbps)  
Parity (None / Even)  
Configuration param-  
eters  
Configuration mode  
Special functions  
Via keypad or UCS software  
Display of total loads connected in relation to energy consumption and power measurements (SUM function)  
Measurements independent from direction of current (Easy connection function)  
Resetting of active energy meters of single and total loads  
Resetting of maximum values within set active and apparent power interval  
Configuration of phase order: 1-2-3-1-2-3 or 3-2-1-3-2-1  
Password protected settings menu  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
8
EM280  
Connection Diagrams  
Note: for three-phase systems without neutral (3 wires) do not consider the connection to neutral N.  
Note: fuses F of 315 mA, if required by local law.  
13 14 15 16  
A1  
13 14 15 16  
A1  
Fig. 3 Three-phase system, one  
Fig. 4 Three-phase system, one  
Fig. 5 Three-phase system, two  
three-phase load.  
three-phase load.  
three-phase loads.  
13 14 15 16  
A1  
13 14 15 16  
A1 A2  
Fig. 6 Three-phase system, three  
Fig. 7 Three-phase system, three  
Fig. 8 Three-phase system, six  
single-phase loads.  
single-phase loads.  
single-phase loads.  
15 16  
A1  
15 16  
A1  
15 16  
A1 A2  
Fig. 9 Single-phase system, three  
Fig. 10 Single-phase system,  
Fig. 11 Single-phase system, six  
single-phase loads.  
three single-phase loads.  
single-phase loads.  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
9
EM280  
13 14 15 16  
EM280  
1
2
3
4
9
10 11 12  
13 14 15 16  
EM280  
9
10 11 12  
Fig. 12 Example of connection of  
Fig. 13 Pulse output 1.  
Fig. 14 Pulse output 2.  
multiple EM280s in cascade.  
8
8
8
8
8
6
5
6
5
6
5
6
5
2
1
6
5
2
1
2
1
3
3
3
7
7
7
7
7
Fig. 15 RS485 port.  
Fig. 16 Double RS485 port for  
daisy chain connection.  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
10  
EM280  
References  
Order code  
EM280 72D MV  
3X  
S
(16 total characters)  
Enter the code, replacing the symbol  
with the selected option (e.g.: EM280 72D MV5 3X OS X).  
Code  
Options Description  
E
M
2
8
0
7
2
D
M
V
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5
230 V L-N, 400 V L-L ac, connection via TCD06BS or TCD06BX  
6
120 V L-N, 230 V L-L ac, connection via TCD06BS or TCD06BX  
3
-
-
X
-
-
O S  
2 S  
X
RS485 port and double digital output  
Double RS485 port for daisy chain connection  
Standard configuration  
"Bare" configuration. With respect to the standard configuration, the bare version does NOT include:  
detachable terminals for voltage connections,  
N
detachable terminals for daisy chain connection via RS485 port (only for option 2S).  
Accessories: order codes  
Code  
Options  
Description  
Pre-wired cables for voltage connection  
(one terminal block).  
Replacing the symbol  
available: 30, 60, 90, 150, 200 cm.  
with the cable length. Lengths  
EM270WS V 1T  
Pre-wired cables for voltage connection  
(two terminal blocks).  
Replacing the symbol  
available: 30, 60, 90, 150, 200 cm.  
with the cable length. Lengths  
EM270WS V 2T  
Pre-wired cables for RS485 connection  
(two terminal blocks).  
Replacing the symbol  
available: 60, 90, 120, 180, 230 cm.  
with the cable length. Lengths  
EM270WS S 2T  
EM270WS T V  
EM270WS T C  
EM270WS T S  
20 detachable terminal blocks for voltage  
connections.  
20 plastic protection covers for voltage  
output.  
20 detachable terminal blocks for daisy  
chain connection of RS485 port.  
-
-
-
-
EM200-96 ADAPT-  
Adapter to 96 x 96 panel mounting.  
ER  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
11  
EM280  
Further reading  
Information  
Instruction manual  
Document  
Instruction manual - EM280  
Where to find it  
www.productselection.net  
CARLO GAVAZZI compatible components  
Purpose  
Component name/code key  
Notes  
TCD06BS  
TCD06BX  
Current measurement accessories (mandatory)  
See next chapter  
Available for free download at:  
www.productselection.net  
Configure analyzer via desktop application  
UCS configuration software  
VMU-C EM  
Monitor data from several analyzers  
See relevant datasheet  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
12  
TCD06BS  
Main features  
6 split core current transformers  
Primary current 32 A  
Hole diameter: 8.5 mm  
Distance between hole centers: 17.5 mm  
Connection to the EM280 with two cables with RJ-11  
connectors  
Mounting on panel or DIN rail  
Mechanical lock to prevent accidental opening  
Main functions  
Conversion of current for input to the power analyzer  
EM280.  
Description  
6-channel split core current transformer block for  
power analyzer EM280.  
This manages primary current up to 32 A and  
the value is read automatically by the EM280 to  
eliminate the need for configuration and calibration  
by the user.  
It is equipped with RJ-11 connectors for simple  
connection to the EM280.  
Structure  
A
A
B
B
Area  
A
Description  
Mechanical lock to prevent accidental opening  
B
Cables with RJ-11 connectors for connection to the EM280  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
13  
TCD06BS  
Features  
General  
Material  
Frianyl C3 H V0 GY7035/TA  
Protection degree  
Terminals  
Front: IP50  
RJ-11 connector  
Overvoltage category  
Pollution degree  
Insulation  
Cat. III  
2
60s 1500 V ac (RJ connectors to housing)  
Panel mounting, by means of four removable hooks  
DIN rail  
350 g (packaging included)  
Mounting  
Weight  
17,5  
117,5  
59,0  
Environmental specifications  
Operating temperature  
Storage temperature  
From -25 to +55 °C/from -13 to +131 °F  
From -30 to +70 °C/from -22 to +158 °F  
Electrical specifications  
Primary current (In)  
32 A  
Maximum current (con-  
tinuous)  
1.2 In  
Maximum system volt-  
age  
0.72 kV ac  
Frequency  
Accuracy  
From 45 to 65 Hz  
0.5%  
Phase error  
<4°  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
14  
TCD06BS  
Connection Diagrams  
Fig. 17 Current connection  
Fig. 18 RJ11 connections  
References  
Order code  
TCD06BS 32  
CM X  
Enter the code, replacing the symbol  
with the length of the cable with RJ11 connectors (2 or 3 digits).  
Lengths available: 80, 150, 200 cm.  
Further reading  
Information  
Instruction manual  
Document  
Instruction manual - TCD06BS  
Where to find it  
www.productselection.net  
CARLO GAVAZZI compatible components  
Purpose  
Component name/code key  
EM280  
Notes  
Measure and display consumption of connected  
loads  
See relevant datasheet  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
15  
TCD06BX  
Main features  
6 solid core current transformers  
Primary current 32 A  
Hole diameter: 8.5 mm  
Distance between hole centers: 17.5 mm  
Connection to the EM280 with two cables with RJ-11  
connectors  
Mounting on panel or DIN rail  
Main functions  
Conversion of current for input to the power analyzer  
EM280.  
Description  
6-channel solid core current transformer block for  
power analyzer EM280.  
This manages primary current up to 32 A and  
the value is read automatically by the EM280 to  
eliminate the need for configuration and calibration  
by the user.  
It is equipped with RJ-11 connectors for simple  
connection to the EM280.  
Structure  
Area  
A
Description  
Cables with RJ-11 connectors for connection to the EM280  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
16  
TCD06BX  
Features  
General  
Material  
Frianyl C3 H V0 GY7035/TA  
Protection degree  
Terminals  
Front: IP50  
RJ-11 connector  
Overvoltage category  
Pollution degree  
Insulation  
Mounting  
Weight  
Cat. III  
2
60s 1500 V ac (RJ connectors to housing)  
Panel mounting, by means of four removable hooks  
350 g (packaging included)  
17,50  
117,50  
Environmental specifications  
Operating temperature  
Storage temperature  
From -25 to +55 °C/from -13 to +131 °F  
From -30 to +70 °C/from -22 to +158 °F  
Electrical specifications  
Primary current (In)  
32 A  
Maximum current (con-  
tinuous)  
1.2 In  
Maximum system volt-  
age  
0.72 kV ac  
Frequency  
Accuracy  
From 45 to 65 Hz  
0.5%  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
17  
TCD06BX  
Connection Diagrams  
Fig. 19 Current connection  
Fig. 20 RJ11 connections  
References  
Order code  
TCD06BX 32  
CM X  
Enter the code, replacing the symbol  
with the length of the cable with RJ11 connectors (2 or 3 digits).  
Lengths available: 80, 150, 200 cm.  
Further reading  
Information  
Instruction manual  
Document  
Instruction manual - TCD06BX  
Where to find it  
www.productselection.net  
CARLO GAVAZZI compatible components  
Purpose  
Component name/code key  
EM280  
Notes  
Measure and display consumption of connected  
loads  
See relevant datasheet  
COPYRIGHT ©2017  
Content subject to change. Download the PDF: www.productselection.net  
01/02/2018 EM280 DS ENG  
Carlo Gavazzi Controls S.p.A.  
18  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY