PMA60F-12-TN [COSEL]
AC/DC CONVERTER 12V;型号: | PMA60F-12-TN |
厂家: | COSEL CO., LTD. |
描述: | AC/DC CONVERTER 12V |
文件: | 总11页 (文件大小:2008K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
AC-DC Power Supplies Medical Type
Power
Safety
Approvals
EMI
OCP
OVP
Medical
electric
equipment
World wide
Inrush
current
limiting
Remote
ON/OFF
Factor
Correction
PMA-series
Feature
For medical electric equipment
CE marking
Low Voltage Drective
Internal dual fuses
RoHS Directive
Harmonic attenuator (Complies with IEC61000-3-2)
Universal input (AC85 - 264V)
Efficiency increased with synchronous rectification
technology (PMA60F, PMA100F)
Variety of option
EMS Compliance : EN61204-3, EN61000-6-2
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5 (Common mode Level4, Differential mode Level2)
Safety agency approvals
UL60601-1, C-UL (CSA-C22.2 No.601.1), EN60601-1
EN61000-4-6
EN61000-4-8
EN61000-4-11
EMI
FCC-B, CISPR11-B, CISPR22-B, EN55011-B, EN55022-B,
VCCI-B
5-year warranty (refer to Instruction Manual)
July 01, 2020
PMA-1
Ordering information
AC-DC Power Supplies Medical Type
PM
A
15
F
-O -O
5 6
PMA15F
1
2
3
4
1Series name
2Single output
3Output wattage
4Universal input
5Output voltage
Example recommended EMI/EMC filter
NAM-04-000
R
*5
6Optional
T : Vertical terminal block
T1
:
Horizontal terminal block
N: with Cover
J1: VH(J.S.T.)connector type
Low leakage current type : NAM series
*
A higher current rating EMI/EMC filter
may be recommended in view of the
other devices that could be connected
in parallel with the power supply.
Specification is changed at
option, refer to Instruction
Manual.
Horizontal terminal block
Vertical terminal block Standard type
with Cover
(option : -T1)
(option : -T)
(option : -N)
*Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations.
MODEL
MAX OUTPUT WATTAGE[W]
DC OUTPUT
PMA15F-3R3
9.9
3.3V 3A
PMA15F-5
15
5V 3A
PMA15F-12
15.6
12V 1.3A
PMA15F-15
15
15V 1A
PMA15F-24
16.8
24V 0.7A
SPECIFICATIONS
MODEL
PMA15F-3R3
PMA15F-5
PMA15F-12
PMA15F-15
PMA15F-24
VOLTAGE[V]
AC85 - 264 1f(Refer to the Instruction Manual 1.1 and “Derating”) *3
ACIN 100V 0.30typ (Io=100%)
0.40typ (Io=100%)
0.20typ (Io=100%)
CURRENT[A]
ACIN 200V 0.15typ (Io=100%)
50 / 60 (47 - 440)
ACIN 100V 66typ
FREQUENCY[Hz]
76typ
79typ
76typ
79typ
INPUT
70typ
74typ
74typ
78typ
EFFICIENCY[%]
ACIN 200V 67typ
ACIN 100V 15typ (Io=100%) (At cold start)
ACIN 200V 30typ (Io=100%) (At cold start)
INRUSH CURRENT[A]
LEAKAGE CURRENT[mA]
VOLTAGE[V]
0.05/0.10max (ACIN 100V / 240V 60Hz, Io=100%, According to IEC60601-1)
3.3
5
12
15
24
CURRENT[A]
3.0
3.0
1.3
1.0
0.7
LINE REGULATION[mV]
LOAD REGULATION[mV]
20max
40max
80max
140max
120max
160max
50max
60max
20max
20max
40max
80max
140max
120max
160max
50max
60max
20max
48max
100max
120max
160max
150max
180max
120max
150max
48max
60max
120max
120max
160max
150max
180max
150max
180max
60max
96max
150max
120max
160max
150max
180max
240max
290max
96max
0 to +50C
RIPPLE[mVp-p]
*1
-10 - 0C
0 to +50C
-10 - 0C
RIPPLE NOISE[mVp-p]
*1
OUTPUT
0 to +50C
-10 to +50C
TEMPERATURE REGULATION[mV]
*
2
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
200typ (ACIN 100V, Io=100%) *Start-up time is 700ms typ for less than 1minute of applying input again from turning off the input voltage.
20typ (ACIN 100V, Io=100%)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
2.85 to 3.60
3.30 to 3.40
4.50 to 5.50
5.00 to 5.15
10.00 to 13.20
12.00 to 12.48
13.20 to 18.00
15.00 to 15.60
19.20 to 27.00
24.00 to 24.96
OUTPUT VOLTAGE SETTING[V]
OVERCURRENT PROTECTION Works over 105% of rating and recovers automatically
PROTECTION
CIRCUIT AND
OTHERS
OVERVOLTAGE PROTECTION[V] 4.00 to 5.25
5.75 to 7.00
15.00 to 18.00
20.00 to 25.00
30.00 to 37.00
OPERATING INDICATION
REMOTE ON/OFF
LED (Green)
Not provided
INPUT-OUTPUT
ISOLATION INPUT-FG
OUTPUT-FG
AC4,000V 1minute, Cutoff current = 10mA, DC500V 50MWmin (At Room Temperature)
AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MWmin (At Room Temperature)
AC500V 1minute, Cutoff current = 25mA, DC500V 50MWmin (At Room Temperature)
OPERATING TEMP.,HUMID.AND ALTITUDE -10 to +70C, 20 - 90%RH (Non condensing), 3,000m (10,000 feet) max *3
STORAGE TEMP.,HUMID.AND ALTITUDE -20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000 feet) max
ENVIRONMENT
2
VIBRATION
10 - 55Hz, 19.6m/s (2G), 3minutes period, 60minutes each along X, Y and Z axis
2
IMPACT
196.1m/s (20G), 11ms, once each X, Y and Z axis
AGENCY APPROVALS
CONDUCTED NOISE
HARMONIC ATTENUATOR
CASE SIZE/WEIGHT
COOLING METHOD
UL60601-1, C-UL (CSA-C22.2 No.601.1), EN60601-1
Complies with FCC-B, VCCI-B, CISPR11-B, CISPR22-B, EN55011-B, EN55022-B
SAFETY AND
NOISE
REGULATIONS
*
6
Complies with IEC61000-3-2 (Class A) (Not built-in to active filter *4)
31X78X103mm [1.22X3.07X4.06 inches] (WXHXD) / 230g max (with cover : 265g max)
Convection
OTHERS
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter (equivalent to KEISOKU-GIKEN: RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C.
*3 Refer to “Derating”.
*5 Please contact us about safety approvals for the model with option.
*6 Please contact us about another class.
*
*
*
Parallel operation with other model is not possible.
Derating is required when operated with cover.
A sound may occur from power supply at peak loading.
*4 When two or more units are used, they may not comply with the harmonic attenuator. Please
contact us for details.
July 01, 2020
PMA-2
PMA15F
Block diagram
FUSE
AC250V
2.5A×2
INRUSH
CURRENT
LIMIT
RECTIFIER
AND
FILTER
AC IN
85 264V
NOISE
FILTER
FG
TRANSFORMER
RECTIFIER
AND
CONTROL
INVERTER
DC OUT
FILTER
CURRENT
SENSING
Photocoupler
Photocoupler
CONTROL
OVER VOLTAGE
PROTECTION
External view
¶
External size of option T and T1 is different from standard model and refer to 5 Option of instruction manual for detalis.
18
2.5
[0.71] [0.1]
Point B:C503
CN2
1.5
103
Voltage Adjust
12.2
[0.48]
LED
Cover name plate
[4.06]
Cover (Option)
4
3
2
1
+V
-V
5
3
1
FG
AC(L)
AC(N)
0.5
40.5
46
CN1
[1.81]
[1.59]
Point A:C102
2-M3
Mounting Hole
Name plate
2-M3
Mounting Hole
0.5
75
[2.95]
8.5
[0.33]
¶
Point A,Point B are thermometry points. Please refer to
Instruction Manual 3.
I/O Connector
Mating Connector
Terminal
1123721-1
1318912-1
1123721-1
1318912-1
<PIN CONNECTION>
CN2
Chain
Loose
Chain
Loose
CN1 1-1123724-3 1-1123722-5
CN2 1-1123723-4 1-1123722-4
CN1
Pin No.
¶ Tolerance : 1 [ 0.04]
Input
AC(N)
Pin No.
Output
-V
¶
¶
¶
¶
¶
¶
¶
Weight
:
230g max (with cover : 265g max)
CEM-3 / 1.6mm [0.06inches]
Electric galvanizing steel board
PCB Material/thickness
Chassis material
:
1
2
3
4
5
1, 2
:
(Mfr : Tyco Electronics AMP)
Keep drawing current per pin bellow 5A of CN2.
Dimensions in mm, [ ]=inches
AC(L)
FG
¶
¶
I/O Connector is Mfr.Tyco Electronics AMP
3, 4
+V
Option : -J1 : (J.S.T) connector type
-T : Vertical terminal block type
-T1 : Horizontal terminal block type
Refer to Instruction Manual 5.
Mounting torque
: 0.6N m (6.3kgf cm) max
- -
Please connect safety ground to the unit in 2-M3 holes.
July 01, 2020
PMA-3
Ordering information
AC-DC Power Supplies Medical Type
PM
A
30
F
-O -O
5 6
PMA30F
1
2
3
4
1Series name
2Single output
3Output wattage
4Universal input
5Output voltage
Example recommended EMI/EMC filter
NAM-04-000
R
*5
6Optional
T : Vertical terminal block
T1
:
Horizontal terminal block
N: with Cover
J1: VH(J.S.T.)connector type
Low leakage current type : NAM series
*
A higher current rating EMI/EMC filter
may be recommended in view of the
other devices that could be connected
in parallel with the power supply.
Specification is changed at
option, refer to Instruction
Manual.
Horizontal terminal block
Vertical terminal block Standard type
with Cover
(option : -T1)
(option : -T)
(option : -N)
*Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations.
MODEL
MAX OUTPUT WATTAGE[W]
DC OUTPUT
PMA30F-3R3
19.8
3.3V 6A
PMA30F-5
30
5V 6A
PMA30F-12
30
12V 2.5A
PMA30F-15
30
15V 2A
PMA30F-24
31.2
24V 1.3A
SPECIFICATIONS
MODEL
PMA30F-3R3
PMA30F-5
PMA30F-12
PMA30F-15
PMA30F-24
VOLTAGE[V]
AC85 - 264 1f(Refer to the Instruction Manual 1.1 and “Derating”) *3
ACIN 100V 0.50typ (Io=100%)
0.70typ (Io=100%)
0.40typ (Io=100%)
CURRENT[A]
ACIN 200V 0.30typ (Io=100%)
50 / 60 (47 - 440)
ACIN 100V 67typ
FREQUENCY[Hz]
INPUT
71typ
74typ
76typ
78typ
77typ
80typ
77typ
80typ
EFFICIENCY[%]
ACIN 200V 69typ
ACIN 100V 15typ (Io=100%) (At cold start)
ACIN 200V 30typ (Io=100%) (At cold start)
INRUSH CURRENT[A]
LEAKAGE CURRENT[mA]
VOLTAGE[V]
0.05 / 0.10max (ACIN 100V / 240V 60Hz, Io=100%, According to IEC60601-1)
3.3
5
12
15
24
CURRENT[A]
6.0
6.0
2.5
2.0
1.3
LINE REGULATION[mV]
LOAD REGULATION[mV]
20max
40max
20max
40max
80max
140max
120max
160max
50max
60max
20max
48max
100max
120max
160max
150max
180max
120max
150max
48max
60max
120max
120max
160max
150max
180max
150max
180max
60max
96max
150max
120max
160max
150max
180max
240max
290max
96max
0 to +50C 80max
-10 - 0C 140max
0 to +50C 120max
-10 - 0C 160max
0 to +50C 50max
RIPPLE[mVp-p]
*1
RIPPLE NOISE[mVp-p]
*1
OUTPUT
TEMPERATURE REGULATION[mV]
-10 to +50
C
60max
20max
*
2
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
200typ (ACIN 100V, Io=100%) *Start-up time is 700ms typ for less than 1minute of applying input again from turning off the input voltage.
20typ (ACIN 100V, Io=100%)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
2.85 to 3.60
3.30 to 3.40
4.50 to 5.50
5.00 to 5.15
10.00 to 13.20
12.00 to 12.48
13.20 to 18.00
15.00 to 15.60
19.20 to 27.00
24.00 to 24.96
OUTPUT VOLTAGE SETTING[V]
OVERCURRENT PROTECTION Works over 105% of rating and recovers automatically
PROTECTION
CIRCUIT AND
OTHERS
OVERVOLTAGE PROTECTION[V] 4.00 to 5.25
5.75 to 7.00
15.00 to 18.00
20.00 to 25.00
30.00 to 37.00
OPERATING INDICATION
REMOTE ON/OFF
LED (Green)
Not provided
INPUT-OUTPUT
ISOLATION INPUT-FG
OUTPUT-FG
AC4,000V 1minute, Cutoff current = 10mA, DC500V 50MWmin (At Room Temperature)
AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MWmin (At Room Temperature)
AC500V 1minute, Cutoff current = 25mA, DC500V 50MWmin (At Room Temperature)
OPERATING TEMP.,HUMID.AND ALTITUDE -10 to +70C, 20 - 90%RH (Non condensing), 3,000m (10,000feet) max *3
STORAGE TEMP.,HUMID.AND ALTITUDE -20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max
ENVIRONMENT
2
VIBRATION
10 - 55Hz, 19.6m/s (2G), 3minutes period, 60minutes each along X, Y and Z axis
2
IMPACT
196.1m/s (20G), 11ms, once each X, Y and Z axis
AGENCY APPROVALS
CONDUCTED NOISE
HARMONIC ATTENUATOR
CASE SIZE/WEIGHT
COOLING METHOD
UL60601-1, C-UL (CSA-C22.2 No.601.1), EN60601-1
Complies with FCC-B, VCCI-B, CISPR11-B, CISPR22-B, EN55011-B, EN55022-B
SAFETY AND
NOISE
REGULATIONS
*
6
Complies with IEC61000-3-2 (Class A) (Not built-in to active filter *4)
31X82X120mm [1.22X3.23X4.72 inches] (WXHXD) / 240g max (with cover : 280g max)
Convection
OTHERS
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter (equivalent to KEISOKU-GIKEN: RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C.
*3 Refer to “Derating”.
*5 Please contact us about safety approvals for the model with option.
*6 Please contact us about another class.
*
*
*
Parallel operation with other model is not possible.
Derating is required when operated with cover.
A sound may occur from power supply at peak loading.
*4 When two or more units are used, they may not comply with the harmonic attenuator. Please
contact us for details.
July 01, 2020
PMA-4
PMA30F
Block diagram
FUSE
AC250V
3.15A×2
INRUSH
CURRENT
LIMIT
RECTIFIER
AND
FILTER
AC IN
85 264V
NOISE
FILTER
FG
TRANSFORMER
RECTIFIER
AND
CONTROL
INVERTER
DC OUT
FILTER
CURRENT
SENSING
Photocoupler
Photocoupler
CONTROL
OVER VOLTAGE
PROTECTION
External view
¶
External size of option T and T1 is different from standard model and refer to 5 Option of instruction manual for detalis.
17
2.5
Point B:C503
[0.67] [0.1]
1.5
120
11.2
LED
Cover name plate
Cover (Option)
Voltage Adjust
[4.72]
[0.44]
CN2
4
3
2
1
+V
-V
5
3
1
FG
AC(L)
AC(N)
2-M3
Mounting Hole
0.5
[3.03]
77
4
CN1
[0.16]
Point A:C102
Name plate
2-M3
Mounting Hole
0.5
88
[3.46]
11
[0.43]
¶
Point A,Point B are thermometry points. Please refer to
Instruction Manual 3.
I/O Connector
Mating Connector
Terminal
1123721-1
1318912-1
1123721-1
1318912-1
<PIN CONNECTION>
CN2
Chain
Loose
Chain
Loose
CN1 1-1123724-3 1-1123722-5
CN2 1-1123723-4 1-1123722-4
CN1
Pin No.
¶ Tolerance : 1 [ 0.04]
¶
¶
¶
¶
¶
¶
¶
Weight
PCB Material/thickness
Chassis material Aluminum
Keep drawing current per pin bellow 5A of CN2.
Dimensions in mm, [ ]=inches
:
240g max (with cover : 280g max)
Input
AC(N)
Pin No.
Output
-V
:
CEM-3 / 1.6mm [0.06inches]
1
2
3
4
5
1, 2
:
(Mfr : Tyco Electronics AMP)
AC(L)
FG
¶
¶
I/O Connector is Mfr.Tyco Electronics AMP
3, 4
+V
Option : -J1 : (J.S.T) connector type
-T : Vertical terminal block type
-T1 : Horizontal terminal block type
Refer to Instruction Manual 5.
Mounting torque
: 0.49N m (5kgf cm) max
- -
Please connect safety ground to the unit in 2-M3 holes.
July 01, 2020
PMA-5
Ordering information
AC-DC Power Supplies Medical Type
PM
A
60
F
-O -O
5 6
PMA60F
1
2
3
4
1Series name
2Single output
3Output wattage
4Universal input
5Output voltage
Example recommended EMI/EMC filter
NAM-04-000
R
*5
6Optional
T : Vertical terminal block
T1
:
Horizontal terminal block
N: with Cover
J1: VH(J.S.T.)connector type
R: with Remote ON/OFF
Low leakage current type : NAM series
*
A higher current rating EMI/EMC filter
may be recommended in view of the
other devices that could be connected
in parallel with the power supply.
Specification is changed at
option, refer to Instruction
Manual.
Horizontal terminal block
Vertical terminal block Standard type
with Cover
(option : -T1)
(option : -T)
(option : -N)
*Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations.
MODEL
MAX OUTPUT WATTAGE[W]
DC OUTPUT
PMA60F-3R3
39.6
3.3V 12A
PMA60F-5
60
5V 12A
PMA60F-12
60
12V 5A
PMA60F-15
60
15V 4A
PMA60F-24
60
24V 2.5A
SPECIFICATIONS
MODEL
PMA60F-3R3
PMA60F-5
PMA60F-12
PMA60F-15
PMA60F-24
VOLTAGE[V]
AC85 - 264 1f(Refer to the Instruction Manual 1.1)
ACIN 100V 0.7typ (Io=100%)
ACIN 200V 0.4typ (Io=100%)
50 / 60 (47 - 63)
0.8typ (Io=100%)
0.5typ (Io=100%)
CURRENT[A]
FREQUENCY[Hz]
ACIN 100V 77typ
80typ
83typ
80typ
82typ
81typ
83typ
81typ
83typ
EFFICIENCY[%]
INPUT
ACIN 200V 78typ
ACIN 100V 0.98typ
ACIN 200V 0.85typ
POWER FACTOR
(Io=100%)
0.90typ
ACIN 100V 15typ (Io=100%) (At cold start)
ACIN 200V 30typ (Io=100%) (At cold start)
INRUSH CURRENT[A]
LEAKAGE CURRENT[mA]
VOLTAGE[V]
0.09 / 0.18max (ACIN 100V / 240V 60Hz, Io=100%, According to IEC60601-1)
3.3
5
12
15
24
CURRENT[A]
12.0
12.0
5.0
4.0
2.5
LINE REGULATION[mV]
LOAD REGULATION[mV]
20max
40max
20max
40max
80max
140max
120max
160max
50max
60max
20max
48max
100max
120max
160max
150max
180max
120max
150max
48max
60max
120max
120max
160max
150max
180max
150max
180max
60max
96max
150max
120max
160max
150max
180max
240max
290max
96max
0 to +50C 80max
-10 - 0C 140max
0 to +50C 120max
-10 - 0C 160max
0 to +50C 50max
RIPPLE[mVp-p]
*1
RIPPLE NOISE[mVp-p]
*1
OUTPUT
TEMPERATURE REGULATION[mV]
-10 to +50
C
60max
20max
*
2
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
250typ (ACIN 100V, Io=100%)
20typ (ACIN 100V, Io=100%)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
2.85 to 3.60
3.30 to 3.40
4.50 to 5.50
5.00 to 5.15
10.00 to 13.20
12.00 to 12.48
13.20 to 18.00
15.00 to 15.60
19.20 to 27.00
24.00 to 24.96
OUTPUT VOLTAGE SETTING[V]
OVERCURRENT PROTECTION Works over 105% of rating and recovers automatically
PROTECTION
CIRCUIT AND
OTHERS
OVERVOLTAGE PROTECTION[V] 4.00 to 5.25
5.75 to 7.00
15.00 to 18.00
20.00 to 25.00
30.00 to 37.00
OPERATING INDICATION
REMOTE ON/OFF
INPUT-OUTPUT RC
LED (Green)
Optional (Required external power source)
AC4,000V 1minute, Cutoff current = 10mA, DC500V 50MWmin (At Room Temperature)
AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MWmin (At Room Temperature)
AC500V 1minute, Cutoff current = 25mA, DC500V 50MWmin (At Room Temperature)
.
*
*
3
3
ISOLATION INPUT-FG
.
OUTPUT RC-FG
OPERATING TEMP.,HUMID.AND ALTITUDE -10 to +70C, 20 - 90%RH (Non condensing), 3,000m (10,000feet) max *4
STORAGE TEMP.,HUMID.AND ALTITUDE -20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max
ENVIRONMENT
2
VIBRATION
10 - 55Hz, 19.6m/s (2G), 3minutes period, 60minutes each along X, Y and Z axis
2
IMPACT
196.1m/s (20G), 11ms, once each X, Y and Z axis
AGENCY APPROVALS
CONDUCTED NOISE
HARMONIC ATTENUATOR
CASE SIZE/WEIGHT
COOLING METHOD
UL60601-1, C-UL (CSA-C22.2 No.601.1), EN60601-1
Complies with FCC-B, VCCI-B, CISPR11-B, CISPR22-B, EN55011-B, EN55022-B
Complies with IEC61000-3-2 *6
32X82X135mm [1.26X3.23X5.31 inches] (WXHXD) / 350g max (with cover : 395g max)
Convection
SAFETY AND
NOISE
REGULATIONS
OTHERS
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter (equivalent to KEISOKU-GIKEN: RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C.
*3 Applicable when Remote ON/OFF (optional) is added. RC is insulated with input, output and FG.
*4 Refer to “Derating”.
*6 Please contact us about class C.
*
*
*
Parallel operation with other model is not possible.
Derating is required when operated with cover.
A sound may occur from power supply at peak loading.
*5 Please contact us about safety approvals for the model with option.
July 01, 2020
PMA-6
PMA60F
Block diagram
FUSE
250V3.15A×2
INRUSH
CURRENT
LIMIT
NOISE
FILTER
RECTIFIER
AC IN 85 264V
FG
CURRENT
SENSING
OPTION
RC
EXTERNAL
SOURCE
E
BOOSTER
INDUCTOR
CURRENT
SENSING
RECTIFIER
AND
FILTER
CONTROL
INVERTER
CONTROL
OVER VOLTAGE
PROTECTION
INVERTER
CONTROL
RECTIFIER
AND
FILTER
TRANSFORMER
DC OUT
External view
¶
External size of option T and T1 is different from standard model and refer to 5 Option of instruction manual for detalis.
CN3
Connector for Remote ON/OFF(option)
17 2.5
[0.67] [0.1]
Point A:C118
Point B:C505
135
[5.31]
1.5
11.2
Voltage Adjust
LED
[0.44]
Cover name plate
Cover (Option)
1 2
CN2
CN1
6
5
4
3
2
1
+V
-V
5
3
1
FG
AC(L)
AC(N)
2-M3
Mounting Hole
0.5
94
4
[3.7]
[0.16]
Connector type
Name plate
2-M3
Mounting Hole
CN3 Option (Mfr:J.S.T)
PIN No.
1
2
Contents
RC(+)
RC(-)
Barrier strip type
Model B2B-XH-A
Mating Connector (Terminal)
XHP-2
0.5
105.5
[4.15]
9
[0.35]
¶
Point A,Point B are thermometry points. Please refer to
Instruction Manual 3.
BXH-001T-P0.6
<PIN CONNECTION>
CN2
I/O Connector
Mating Connector
Terminal
1123721-1
1318912-1
1123721-1
1318912-1
or SXH-001T-P0.6
Chain
Loose
Chain
Loose
CN1
Pin No.
CN1 1-1123724-3 1-1123722-5
CN2 1-1123723-6 1-1123722-6
¶ Tolerance : 1 [ 0.04]
Input
AC(N)
Pin No.
Output
-V
¶
¶
¶
¶
¶
¶
¶
Weight
:
350g max (with cover : 395g max)
CEM-3 / 1.6mm [0.06inches]
Aluminum
PCB Material/thickness
Chassis material
:
1
1 - 3
:
2
3
4
5
(Mfr : Tyco Electronics AMP)
Keep drawing current per pin bellow 5A of CN2.
Dimensions in mm, [ ]=inches
: 0.49N m (5kgf cm) max
- -
Please connect safety ground to the unit in 2-M3 holes.
AC(L)
FG
¶
¶
I/O Connector is Mfr.Tyco Electronics AMP
4 - 6
+V
Option : -J1 : (J.S.T) connector type
-T : Vertical terminal block type
-T1 : Horizontal terminal block type
Refer to Instruction Manual 5.
Mounting torque
July 01, 2020
PMA-7
Ordering information
AC-DC Power Supplies Medical Type
PM
A
100
F
-O -O
5 6
PMA100F
1
2
3
4
1Series name
2Single output
3Output wattage
4Universal input
5Output voltage
Example recommended EMI/EMC filter
NAM-06-000
R
*5
6Optional
T : Vertical terminal block
T1
:
Horizontal terminal block
N: with Cover
J1: VH(J.S.T.)connector type
R: with Remote ON/OFF
Low leakage current type : NAM series
*
A higher current rating EMI/EMC filter
may be recommended in view of the
other devices that could be connected
in parallel with the power supply.
Specification is changed at
option, refer to Instruction
Manual.
Horizontal terminal block
Vertical terminal block Standard type
with Cover
(option : -T1)
(option : -T)
(option : -N)
*Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations.
MODEL
MAX OUTPUT WATTAGE[W]
DC OUTPUT
PMA100F-3R3
66
3.3V 20A
PMA100F-5
100
5V 20A
PMA100F-12
102
12V 8.5A
PMA100F-24
108
24V 4.5A
PMA100F-48
100.8
48V 2.1A
SPECIFICATIONS
MODEL
PMA100F-3R3
PMA100F-5
PMA100F-12
PMA100F-24
PMA100F-48
VOLTAGE[V]
AC85 - 264 1f(Refer to the Instruction Manual 1.1)
ACIN 100V 0.9typ (Io=100%)
ACIN 200V 0.5typ (Io=100%)
50 / 60 (47 - 63)
1.3typ (Io=100%)
0.7typ (Io=100%)
CURRENT[A]
FREQUENCY[Hz]
ACIN 100V 77typ
81typ
83typ
82typ
83typ
84typ
86typ
84typ
86typ
EFFICIENCY[%]
INPUT
ACIN 200V 78typ
ACIN 100V 0.98typ
ACIN 200V 0.85typ
POWER FACTOR
(Io=100%)
0.90typ
ACIN 100V 20typ (Io=100%) (At cold start)
ACIN 200V 40typ (Io=100%) (At cold start)
INRUSH CURRENT[A]
LEAKAGE CURRENT[mA]
VOLTAGE[V]
0.09 / 0.18max (ACIN 100V / 240V 60Hz, Io=100%, According to IEC60601-1)
3.3
5
12
24
48
CURRENT[A]
20.0
20.0
8.5
4.5
2.1
LINE REGULATION[mV]
LOAD REGULATION[mV]
20max
40max
20max
40max
80max
140max
120max
160max
50max
60max
20max
48max
100max
120max
160max
150max
180max
120max
150max
48max
96max
150max
120max
160max
150max
180max
240max
290max
96max
192max
240max
150max
200max
250max
300max
480max
600max
192max
0 to +50C 80max
-10 - 0C 140max
0 to +50C 120max
-10 - 0C 160max
0 to +50C 50max
RIPPLE[mVp-p]
*1
RIPPLE NOISE[mVp-p]
*1
OUTPUT
TEMPERATURE REGULATION[mV]
-10 to +50
C
60max
20max
*
2
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
250typ (ACIN 100V, Io=100%)
20typ (ACIN 100V, Io=100%)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
2.85 to 3.60
3.30 to 3.40
4.50 to 5.50
5.00 to 5.15
10.00 to 13.20
12.00 to 12.48
19.20 to 27.00
24.00 to 24.96
39.00 to 53.00
48.00 to 49.92
OUTPUT VOLTAGE SETTING[V]
OVERCURRENT PROTECTION Works over 105% of rating and recovers automatically
PROTECTION
CIRCUIT AND
OTHERS
OVERVOLTAGE PROTECTION[V] 4.00 to 5.25
5.75 to 7.00
15.00 to 18.00
30.00 to 37.00
58.00 to 65.00
OPERATING INDICATION
REMOTE ON/OFF
INPUT-OUTPUT RC
LED (Green)
Optional (Required external power source)
AC4,000V 1minute, Cutoff current = 10mA, DC500V 50MWmin (At Room Temperature)
AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MWmin (At Room Temperature)
AC500V 1minute, Cutoff current = 25mA, DC500V 50MWmin (At Room Temperature)
.
*
*
3
3
ISOLATION INPUT-FG
.
OUTPUT RC-FG
OPERATING TEMP.,HUMID.AND ALTITUDE -10 to +70C, 20 - 90%RH (Non condensing), 3,000m (10,000feet) max *4
STORAGE TEMP.,HUMID.AND ALTITUDE -20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max
ENVIRONMENT
2
VIBRATION
10 - 55Hz, 19.6m/s (2G), 3minutes period, 60minutes each along X, Y and Z axis
2
IMPACT
196.1m/s (20G), 11ms, once each X, Y and Z axis
AGENCY APPROVALS
CONDUCTED NOISE
HARMONIC ATTENUATOR
CASE SIZE/WEIGHT
COOLING METHOD
UL60601-1, C-UL (CSA-C22.2 No.601.1), EN60601-1
Complies with FCC-B, VCCI-B, CISPR11-B, CISPR22-B, EN55011-B, EN55022-B
SAFETY AND
NOISE
REGULATIONS
*6
Complies with IEC61000-3-2
34X93X168mm [1.34X3.66X6.61 inches] (WXHXD) / 560g max (with cover : 625g max)
Convection
OTHERS
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter (equivalent to KEISOKU-GIKEN: RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C.
*3 Applicable when Remote ON/OFF (optional) is added. RC is insulated with input, output and FG.
*4 Refer to “Derating”.
*6 Please contact us about class C.
*
*
*
Parallel operation with other model is not possible.
Derating is required when operated with cover.
A sound may occur from power supply at peak loading.
*5 Please contact us about safety approvals for the model with option.
July 01, 2020
PMA-8
PMA100F
Block diagram
FUSE
250V3.15A×2
INRUSH
CURRENT
LIMIT
NOISE
FILTER
RECTIFIER
AC IN 85 264V
FG
CURRENT
SENSING
OPTION
RC
EXTERNAL
SOURCE
E
BOOSTER
INDUCTOR
CURRENT
SENSING
RECTIFIER
CONTROL
INVERTER
CONTROL
AND
FILTER
OVER VOLTAGE
PROTECTION
INVERTER
CONTROL
RECTIFIER
AND
FILTER
TRANSFORMER
DC OUT
External view
¶
External size of option T and T1 is different from standard model and refer to 5 Option of instruction manual for detalis.
CN3
17.5 2.5
[0.69] [0.1]
Connector for Remote ON/OFF(option)
Point B:C505
Point A:C118
1.5
11.7
168
LED
[0.46]
[6.61]
Voltage Adjust
Cover name plate
1
2
Cover (Option)
CN2
CN1
8
7
6
5
4
3
2
1
+V
-V
5
3
1
FG
AC(L)
AC(N)
2-M3
Mounting Hole
0.5
[3.07]
58.5
78
[2.3]
Connector type
2-M3
Mounting Hole
Name plate
CN3 Option (Mfr:J.S.T)
PIN No.
1
2
Contents
RC(+)
RC(-)
Barrier strip type
Model B2B-XH-A
Mating Connector (Terminal)
XHP-2
0.5
139.5
[5.49]
9
[0.35]
¶
Point A,Point B are thermometry points. Please refer to
Instruction Manual 3.
BXH-001T-P0.6
I/O Connector
Mating Connector
Terminal
1123721-1
1318912-1
1123721-1
1318912-1
<PIN CONNECTION>
CN2
or SXH-001T-P0.6
Chain
Loose
Chain
Loose
CN1 1-1123724-3 1-1123722-5
CN2 1-1123723-8 1-1123722-8
CN1
Pin No.
¶ Tolerance : 1 [ 0.04]
Input
AC(N)
Pin No.
Output
-V
¶
¶
¶
¶
¶
¶
¶
Weight
:
560g max (with cover : 625g max)
CEM-3 / 1.6mm [0.06inches]
Aluminum
PCB Material/thickness
Chassis material
:
1
2
3
4
5
1 - 4
(Mfr : Tyco Electronics AMP)
:
Keep drawing current per pin bellow 5A of CN2.
Dimensions in mm, [ ]=inches
: 0.49N m (5kgf cm) max
- -
Please connect safety ground to the unit in 2-M3 holes.
AC(L)
FG
¶
¶
I/O Connector is Mfr.Tyco Electronics AMP
5 - 8
+V
Option : -J1 : (J.S.T) connector type
-T : Vertical terminal block type
-T1 : Horizontal terminal block type
Refer to Instruction Manual 5.
Mounting torque
July 01, 2020
PMA-9
PMA-series
Assembling and Installation Method
Installation method
Chassis of
MA series
Do not insert a screw more than 6mm from the outside of a power supply to keep
¡
Chassis of
customer system
enough insulation distance between the screw and internal components.
A
B
C
Mounting Screw
6mm max
Normal position
If you use two or more power supplies side by side, please keep a sufficient distance between them to allow enough air ventilation.
¡
¡
Ambient temperature around each power supply should not exceed the temperature range shown in “Derating”.
Derating
PMA15F,PMA30F Input voltage Derating Curve
¿
[%]
100
80
8590
[AC V]
Ambient temperature Derating Curve (Reference value)
100
¿
2
80
1
60
1Convection
2
Forced air (0.5m3 / min)
40
20
0
-10
0
10
20
30 [20] 40 [30] 50 [40] 60 [50] 70 [60] 80 [70]
40 [30] 50 [40] 60 [50] 70 [60]
[25] [35] [45] [55]
A
B
C
35
45
55
65
Inside
is with case cover
[ ]
Ambient temperature [C]
In the hatched area, the specification of Ripple, Ripple Noise is different from other area.
The ambient temperature should be measured 5 to 10 cm away from the power supply so that it won’t be influenced by the heat from the
power supply. Please consult us for more details.
¡
¡
Make sure the temperature at point A and point B is less than the temperatures shown in Instruction Manual 3.
¡
Instruction Manual
◆ It is neccessary to read the “Instruction Manual” and “Before using our product” before you use our product.
Instruction Manual
https://en.cosel.co.jp/product/powersupply/PMA/
Before using our product https://en.cosel.co.jp/technical/caution/index.html
PMA
NOTICE
July 01, 2020
PMA-10
PMA-series
Basic Characteristics Data
Series/Parallel
Switching
frequency
[kHz]
Input
current
[A]
Inrush
current
protection
PCB/Pattern
operation availability *2
Model
PMA15F
PMA30F
PMA60F
PMA100F
Circuit method
Flyback converter
Flyback converter
Single Double
Series
Parallel
sided sided operation operation
Material
*1
100
100
0.4
0.7
0.8
1.3
Thermistor
Thermistor
Thermistor
Thermistor
CEM-3
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
CEM-3
CEM-3
CEM-3
Active filter
Forward converter
Active filter
60 - 550
120
60 - 550
120
Forward converter
*1 The value of input current is at ACIN 100V and rated load.
*2 Refer to Instruction Manual 2.
July 01, 2020
PMA-11
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明