SERIES: VMS-20 DESCRIPTION: AC-DC POWER SUPPLY  
FEATURES  
• up to 21.6 W continuous power  
• compact size  
• universal input (90 ~ 264 Vac)  
• single output from 3.3 to 24 V  
• no load power < 0.3W  
• over voltage and short circuit protections  
• full medical safety approvals  
• efficiency up to 85%  
RoHS  
output  
voltage  
output  
current  
max  
(A)  
output  
power  
max  
(W)  
ripple and  
noise1  
max  
(mVp-p)  
efciency  
MODEL  
typ  
(%)  
(Vdc)  
3.3  
5
VMS-20-3.3  
VMS-20-5  
VMS-20-9  
VMS-20-12  
VMS-20-15  
VMS-20-24  
4.0  
4.0  
2.3  
1.7  
1.4  
0.9  
13.2  
20.0  
20.7  
20.4  
21.0  
21.6  
50  
50  
75  
80  
81  
83  
84  
85  
9
90  
12  
15  
24  
100  
100  
100  
Notes:  
1. Measured at 20MHz, with 0.1uF ceramic and 10uF electrolytic capacitors  
PART NUMBER KEY  
VMS-20 - XX  
Base Number  
Output Voltage  
cui.com  
date 10/26/2011 page 2 of 4  
CUI Inc SERIES: VMS-20 DESCRIPTION: AC-DC POWER SUPPLY  
INPUT  
parameter  
voltage  
conditions/description  
min  
90  
typ  
max  
264  
63  
units  
Vac  
Hz  
frequency  
47  
input current  
inrush current  
0.5  
40  
A
at 230 Vac, cold start at 25 °C  
A
OUTPUT  
parameter  
conditions/description  
low line to high line, full load  
10% to 100% full load  
115 Vac  
min  
typ  
max  
±0.5  
±1  
units  
%
line regulation  
load regulation  
hold-up time  
%
10  
ms  
switching frequency  
100  
KHz  
PROTECTIONS  
parameter  
conditions/description  
min  
typ  
typ  
max  
units  
over voltage protection  
short circuit protection  
115  
140  
%
continuous  
SAFETY & COMPLIANCE  
parameter  
conditions/description  
input to output  
min  
max  
units  
isolation voltage  
safety approvals  
EMI/EMC  
5,656  
Vdc  
UL60601-1, IEC60601-1, EN60601-1  
EN60601-1/EN61204-3/EN55022/CISPR Class B, EN55024  
leakage current  
RoHS compliant  
MTBF  
0.1  
mA  
hrs  
yes  
MIL-HDBK-217F, GB  
400,000  
ENVIRONMENTAL  
parameter  
conditions/description  
min  
-25  
-40  
typ  
typ  
max  
70  
units  
°C  
operating temperature  
storage temperature  
operating humidity  
see derating curve  
85  
°C  
non-condensing  
93  
%
MECHANICAL  
parameter  
conditions/description  
min  
max  
units  
inch  
g
dimensions  
2.38 x 1.60 x 0.80 (60.5 x 40.6 x 20.4 mm)  
weight  
50  
cooling method  
free air convection  
(see derating curves below)  
cui.com  
date 10/26/2011 page 3 of 4  
CUI Inc SERIES: VMS-20 DESCRIPTION: AC-DC POWER SUPPLY  
DERATING CURVES  
output power vs. ambient temperature  
100  
80  
(Natural Convection)  
60  
40  
20  
-30  
-20  
0
10  
20  
30  
40  
50  
60  
70  
Ambient Temperature (°C)  
MECHANICAL DRAWING  
units: mm[in]  
TOLERANCE: mm: X.X = ±0.5 ; X.XX = ±0.25  
inch: X.XX = ±0.02 ; X.XXX = ±0.01  
60.5 2.38  
54.00 2.126  
-Vo  
ACN  
ACL  
40.6 1.60  
30.32 1.194  
20.32 0.800  
+Vo  
10.32 0.406  
3.06 0.120  
2.82 0.111  
20.40 0.803  
MAX  
17.00 0.669  
2.00 0.079  
3.40 0.134  
MAX  
1.80 0.071  
1.00 0.039  
3.80 0.150  
cui.com  
date 10/26/2011 page 4 of 4  
CUI Inc SERIES: VMS-20 DESCRIPTION: AC-DC POWER SUPPLY  
REVISION HISTORY  
rev.  
description  
initial release  
date  
1.0  
10/26/2011  
The revision history provided is for informational purposes only and is believed to be accurate.  
Headquarters  
20050 SW 112th Ave.  
Tualatin, OR 97062  
800.275.4899  
Fax 503.612.2383  
cui.com  
techsupport@cui.com  
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.  
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is  
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.  
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical  
component is any component of a life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to  
affect its safety or effectiveness.  

相关型号:

VMS-20-15

AC-DC POWER SUPPLY
CUI

VMS-20-24

AC-DC POWER SUPPLY
CUI

VMS-20-3.3

AC-DC POWER SUPPLY
CUI

VMS-20-5

AC-DC POWER SUPPLY
CUI

VMS-20-9

AC-DC POWER SUPPLY
CUI

VMS-200

AC-DC POWER SUPPLY
CUI

VMS-200-12

Chassis Mount Power Supply, 12 Vdc, 16.67 A, 200 W
CUI

VMS-200-12-CNF

Chassis Mount Power Supply, 12 Vdc, 16.67 A, 200 W
CUI

VMS-200-24

Chassis Mount Power Supply, 24 Vdc, 8.33 A, 200 W
CUI

VMS-200-24-CNF

Chassis Mount Power Supply, 24 Vdc, 8.33 A, 200 W
CUI

VMS-200-48

Chassis Mount Power Supply, 48 Vdc, 4.17 A, 200 W
CUI

VMS-200-48-CNF

Chassis Mount Power Supply, 48 Vdc, 4.17 A, 200 W
CUI